Eliwell ID 961 LX, ID 961 A User Manual

USER INTERFACE
The user has a display and four keys for controlling status and programming of the instrument.
KEYS AND MENUS
UP key Scrolls through the menu
items Increases the values Activates manual def. function
DOWN key Scrolls through the menu items
Decreases the values Programmable by parameter
fnc key ESC function (exit)
Programmable by parameter
set key Accesses the setpoint
Accesses the menus Confirms the commands Displaying the alarms (if present)
At start-up the instrument performs a Lamp Test; for few seconds the display and the leds blink, in order to verify their integrity and correct operation. The instru­ment has two main menus: the “Machine Status” and “Programming” menu.
ACCESSING AND USING MENUS
Resources are arranged in a menu, which can be accessed by pressing and quickly releasing the “set” key (“Machine Status” menu) or by holding down the “set” key for more than 5 seconds (“Programming” menu). To access the contents of each folder, indi­cated by the relevant label, just press the “set” key once. You can now scroll through the contents of each folder, modify it or use its func­tions. If you do not use the keyboard for over 15 seconds (time-out) or if you press the “fnc” key once, the last value shown on the display is confirmed and you return to the previous screen mask.
MACHINE STATUS MENU
To access the “Machine Status” menu Press and quickly release the “set” key. If alarms are not present, the label “SEt” appears. By using the “UP” and “DOWN” keys you can scroll through the other fold­ers in the menu:
-AL: alarm folder (if present);
-Pb1: probe 1 value folder;
-SEt: Setpoint setting folder.
Set Setting
Access the “Machine Status” menu by pressing and quickly releasing the “set” key. The label of the “SEt” folder appears. To display the Setpoint value press the “set” key again. The value appears on the display. To change the Setpoint value, use the “UP” and “DOWN” keys within 15 seconds. If the parameter is LOC = y the Setpoint cannot be changed.
Alarm on
If alarm condition exists, when accessing The “Machine Status” menu the “AL” fold­er label appears (see the “Diagnostics” section).
Displaying Probes
By pressing the “set” key when the appro­priate label appears, the value of the probe associated to it is displayed.
PROGRAMMING MENU
1) Level 1 P
arameters
To access the “Programming” menu, press the “set” key for more than 5 seconds. If specified, the level 1 access PASSWORD will be requested (see parameter “PA1”) and (if the password is correct) the label of the first folder will follow. If the pass­word is wrong, the display will show the PA1 label again.
To scroll other folders, use the “UP” and “DOWN” keys; the folders contain only
the level 1 parameters. NOTE: At this point level 2 parameters are NOT visible, even if they aren’t protected by password.
2) Level 2 P
arameters
In the Programming Menu go into the “CnF” folder, scroll all the parameter until you reach the PA2 label. By pressing and releasing the “set” button you will enter to level 2 parameters and the label of the first folder in the programming menu will follow. The level 2 parameters may be protected by a second password (see “PA2” parame­ter inside “diS” folder, not to be confused with PA2 label inside “CnF” folder. If specified, level 2 parameters are hidden to user; accessing the “CnF” folder the level 2 access PASSWORD will be request­ed and (if the correct password is entered) the label of the first folder in the pro­gramming menu will follow.
NOTE: At this point you will see only level 2 parameters.
Level 1 parameters will NOT be visible; to reach them you shall exit the Programming Menu and re-entry the Programming Menu section (see step 1). To enter the folder, press “set”. The label of the first visible parameter appears. To scroll through the other parameters, use the “UP” and “DOWN” keys; to change the parameter, press and release “set”, then set the desired value using the “UP” and “DOWN” keys, and confirm with the “set” key. Move to the next parameter. PLEASE NOTE: It is suggested to switch­off and switch-on again the instrument everytime it is changed the configuration of the parameters: this prevents malfunc­tioning on regulation and delay time occuring.
PASSWORD
The passwords “PA1” and “PA2” allow access respectively to level 1 and level 2 parameters. In the standard configuration passwords are not present. To enable them (value 0) and assign them the desired value, access the “Programming” menu, within the folder with the “diS” label. If passwords are enabled, they will be requested:
- PA1 at the entrance of the “Programming” menu (see the “Programming Menu“ section);
- PA2 within the folder with the “Cnf” label containing level 1 parameters.
ID 961 LX/A
electronic controllers for refrigerating units
fnc
set
LED
Position Related Function Status
Compressor or relay 1 ON when the compressor is started up; blinking in case of delay,
protection or blocked enabling
Defrost ON when defrosting; blinking in case of manual
enabling
Alarm ON when the alarm is enabled; blinking when the alarm is silenced
MANUAL ACTIVATION OF THE DEFROSTING CYCLE
To manually activate the defrosting cycle, press the “UP” key for 5 seconds. If defrosting conditions are not present, (for example the evaporator probe temperature is higher than defrost stop temperature), the display will blink three (3) times, in order to indicate that the operation will not be performed.
COPY CARD
The Copy Card is an accessory connected to the TTL serial port which allows pro­gramming quickly the instrument parame­ters. The operation is performed as fol­lows:
FrFormat
This command allows copy card formatting, an operation recommended in case of first use. Warning: if the copy card has been pro­grammed, using the “Fr” the data entered are erased. This operation cannot be can­celled.
UL-Upload
This operation loads the programming parameters from the instrument.
dL-Download
This operation downloads to the instru­ment the programming parameters.
NOTE:
• UPLOAD: instrument --> Copy Card
• DOWNLOAD: Copy Card --> instru­ment.
The operations are performed accessing the folder identified by the “FPr” label and selecting, according to the case, “UL”, “dL” or “Fr” commands; the operation is con­firmed by pressing the “set” key. If the operation is successful an “y” is displayed, on the contrary, if it fails a “n” will be dis­played.
TELEVIS SYSTEM
The link with the Televis system can go through the serial port TTL (the BUS ADAPTER 100 TTL RS-485 interface module must be used). In order to configure the instrument for this purpose you must access the folder identified by the “Add” label and use the parameters “dEA” and “FAA”.
KEYBOARD LOCKING
The instrument includes a facility for dis­abling the keyboard, by programming the “Loc” parameter (see folder with “diS” label). If the keyboard is locked, you can still access the programming menu by pressing the “set” key. The Setpoint can also be viewed.
DIAGNOSTICS
The alarm condition is always signalled by the buzzer (if present) and by the led of
the alarm icon The alarm signal produced by a faulty
thermostat probe (referred to probe 1) is shown as E1 on the instrument display
When the sensor detects an error condi­tion:
• the code E1 is displayed
• the compressor is activated as indicated by the "On" and "Off" parameters if pro­grammed for the duty cycle or:
Other signalling alarm are not shown on the instrument display, but from the “Machine Status” menu within the “AL” folder.
MINIMUM AND MAXIMUM TEMPERA­TURE ALARMS
Regulation of the minimum and maximum temperature alarms refers to the thermo­stat probe. The temperature limits defined by the “HAL” (maximum temperature alarm) and “LAL” parameters (minimum temperature alarm) are in absolute temperature value. When an alarm status occurs, if no alarm exclusion phases are underway (see alarm exclusion parameters), the alarm set icon is lit up and the buzzer, and/or the relay configured as an alarm, is activated. The occurrence of this alarm does not in any­way effect the control activities in progress. This alarm status can be viewed in the “AL” folder with AH1-AL1 labels.
INSTALLATION
The instrument is designed for panel mounting. Make a hole of 29x71 mm, insert the instrument and fix it using the brackets provided. Do not mount the instrument in humid and/or dirty places; it is suitable for use in ordinary polluted places. Ventilate the place in proximity to the instrument colling slits.
ELECTRICAL WIRING
Attention! Never work on electrical connections when the machine is switched on.
The instrument is equipped with screw ter­minal boards for connection of electrical cables with a diameter of 2.5 mm
2
(one conductor only per terminal for power connections). For the capacity of the terminals, see the label on the instrument. The relay contacts are voltage free. Do not exceed the maximum current allowed; in case of higher loads, use an appropriate contactor. Make sure the power supply voltage complies with the one required by the instrument. In 12V versions the power supply must be provided by a security transformer with the protection of a delayed 250 mA fuse. Probes have no connection polarity and can be extended using a regular bipolar cable (note that the extension of the probes affects the EMC electromagnetic compatibility of the instrument: pay extreme attention to wiring). Probe cables, power supply cables and the TTL serial cables should be distant from power cables.
ID 961 LX/A 2/6
DISPLAY
E1
If simultaneous they will appear on display with 2 seconds alternation
ERROR
Thermostat probe fault
Probe Error table
Ont
0 0 >0 >0
Oft
0 >0 0 >0
Compressor output
OFF OFF ON dc
DISPLAY
AH1
AL1
EA oPd To silence alarms press any key. If silenced the LEDs will blink Alarms are in absolute value or related to Setpoint and (considered as the distance from the Setpoint itself) depending on Att parameter.
ALARM
High temperature alarm (referred to the thermostat probe or probe 1) Low temperature alarm (referred to the thermostat probe or probe 1) Esternal alarm Open door alarm
CONDITIONS OF USE
PERMITTED USE
For safety reasons the instrument must be installed and used according to the instruction provided and in particular, under normal conditions, parts bearing dangerous voltage levels must not be accessible. The device must be adequately protected from water and dust as per the application and must also only be accessible via the use of tools (with the exception of the frontlet). The device is ideally suited for use on household appliances and/or similar refrig­eration equipment and has been tested with regard to the aspects concerning European reference standards on safety. It is classified as follows:
• according to its manufacture: as an auto­matic electronic control device to be incorporated by independent mounting;
• according to its automatic operating fea­tures: as a 1 B-type operated control type;
• as a Class A device in relation to the cat­egory and structure of the software
UNPERMITTED USE
Any other use other than that permitted is de facto prohibited. It should be noted that the relay contacts provided are of a practical type and therefore subject to fault. Any protection devices required by product standards or dictated by common sense due to obvious safety reasons should be applied externally.
LIABILITY AND RESIDUAL RISKS
Invensys Controls Italy S.r.L. shall not be liable for any damages deriving from:
- installation/use other than that pre­scribed and, in particular, that which does not comply with safety standards anticipat­ed by regulations and/or those given here­in;
- use on boards which do not guarantee adequate protection against electric shock, water or dust under the conditions of assembly applied;
- use on boards which allow access to dan­gerous parts without the use of tools;
- tampering with and/or alteration of the products;
DISCLAIMER
This manual and its contents remain the sole property of Invensys Controls Italy s.r.l., and shall not be reproduced or dis­tributed without authorization. Although great care has been exercised in the preparation of this document, Invensys Controls Italy s.r.l., its employees or its vendors, cannot accept any liability what­soever connected with its use. Invensys Controls Italy s.r.l. reserves the right to make any changes or improvements with­out prior notice.
TECHNICAL DATA
Frontal panel protection: IP65. Casing: plastic body in resin type PC+ABS UL94 V-0, inspection window in polycarbonate, buttons in thermoplastic resin. Dimensions: frontal panel 74x32 mm, depth 60 mm. Installation: on panel, with drilling tem­plate 71x29 mm (+0.2/–0.1 mm). Use temperature: –5…55 °C. Storage temperature.: –30…85 °C. Use environment humidity: 10…90 % RH (not condensing). Storage environment humidity: 10…90% RH (not condensing). Viewing range: –50…110 (NTC); –55…140 (PTC) °C without decimal point (selectable through parameter on 3 digit &
1
/2+ mark
display. Analog inputs: one PTC or NTC input (selectable through parameter). Digital input : 1 configurable low voltage digital input Serial: TTL for connection to Copy Card or Televis system. Digital outputs:
• (A) SPDT 8(3)A (1/2 Hp) 250Va
• (B) SPST 8(3)A (1/2 Hp) 250Va Measuring range: from –55 to 140 °C. Accuracy: 0.5% better than end scale + 1 digit. Resolution: 1 or 0.1 °C. Consumption:
• 12 Va/c model 1,5 VA max.
• 230 Va model 3 VA max. Power supply: 12 Va/c ±10% or 230Va ±10%.
Warning: check the power supply specified on the instrument label; for relay and power supply capacities, contact the Sales Office).
ID 961 LX/A 3/6
PLEASE NOTE: The technical data included in this document, related to measurement (range, accuracy, resolu­tion, etc.) refer to the instrument itself, and not to its equipment such as, for example, sensors. This means, for example, that sensor(s) error(s) shall be added to the instru­ment’s one.
OFt
Off
On
OUT
Ont Ont
Ont, OFt parameters programmed for Duty Cycle
When the sensor detects an error condition:
• the code E1 is displayed
• the regulator is activated as indicated by the "Ont" and "OFt" parameters if pro­grammed for the duty cycle or:
Ont
0 0 >0 >0
OFt
0 >0 0 >0
Output compressor
OFF OFF ON
dc
Duty Cycle Diagram
ID 961 LX/A 4/6
PAR.
diF
HSE LSE OSP
Cit
CAt
dOd
dAd
Ont
OFt
dOn
dOF
dbi
OdO
dit
dt1
dt2
dCt
dOH
dEt
dPO
tcd
Cod
Att
AFd HAL
LAL
PAO
dAO OAO
tdO tAO EAL
dEA
FAA
LOC
DESCRIPTION COMPRESSOR REGULATOR (folder with “CP” label)
diFferential. Relay compressor tripping differential. The compressor stops on reaching the Setpoint value (as indicated by the adjustment probe), and restarts at temperature value equal to the Setpoint plus the value of the differential. Note: the value 0 cannot be assumed. Higher SEt. Maximum possible setpoint value. Lower SEt. Minimum possible setpoint value. Offset Setpoint: temperature value to be added algebraically to the setpoint in the case of reduced set enabled (Economy function). It can be activated through digital input or by a key configured for such use.Offset SetPoint Compressor min on time. Minimum compressor activation time before any possible dis­abling. If set at 0 it is not active Compressor mAx on time. Maximum compressor activation time before any possible dis­abling. If set at 0 it is not active digital (input) Open door. Digital input user shut off. y = yes; n = no. Valid for parameter “H11” = ±4 (door switch). digital (input) Activation delay. Delay time of digital input activation.
COMPRESSOR PROTECTIVE DEVICE (folder with “CP” label)
On time (compressor). Compressor activation time in the event of faulty probe. If set to “1” with Oft at “0” the compressor is always on, while at Oft >0 it functions always in duty cycle mode. OFF time (compressor). Compressor in disabled state time in the event of a faulty probe. If set to “1” with Ont at “0” the compressor is always off, while at Ont >0 it functions always in duty cycle mode. delay (at) On compressor. Delay time in activating the compressor relay after switch-on of instrument delay (after power) OFF. Delay after switch off; the indicated time must elapse between switch-off of the compressor relay and the successive switch-on. delay between power-on. Delay between switch-ons; the indicated time must elapse between two successive switch-ons of the compressor. delay Output (from power) On. Delay time in activating the outputs after switch-on of the instrument or after a power failure.
DEFROSTING REGULATOR (folder with “dEF” label)
defrost interval time. Interval between the start of two successive defrosting operations. U.M. Hours (default) /min/sec depending on dt1 parameter defrost time 1. Measure unit for defrosting intervals (“dit” parameter). 0 = “dit” parameter in hours; 1 = “dit” parameter in minutes; 2 = “dit” parameter in seconds. defrost time 2. Measure unit for defrosting duration (“dEt” parameter). 0 = “dEt” parameter in hours; 1 = “dEt” parameter in minutes; 2 = “dEt” parameter in seconds. defrost Counting type. Selection of count mode for the defrosting interval. 0 = compressor operating hours (DIGIFROST® method); 1 = Real Time – appliance operating time; 2 = compressor stop. defrost Offset Hour. Start-of-defrosting delay time from start up of instrument. defrost Endurance time. Defrosting time-out; determines duration of defrosting. U.M. minutes (default) /hours/sec depending on dt2 parameter defrost (at) Power On. Determines if at the start-up the instrument must enter defrosting (if the temperature measured by the evaporator allows this operation). y = yes, starts defrost at start-up; n = no, doesn’t start defrost. time compressor for defrost. Minimum time for compressor On or OFF before defrost. If >0 (positive value) the compressor will be ON for tcd minutes; If<0 (negative value) the compressor will be OFF for tcd minutes. If =0 parameter is disregarded Compressor off (before defrost). Time for compressor OFF in proximity of the defrost cycle. If a defrost cycle is set within the programmed time for this parameter, the com­pressor is not started up.
ALARMS (folder with “AL” label)
Alarm type. Parameter “HAL” and “LAL” modes, as temperature absolute values or as dif­ferential compared to the Setpoint. 0 = absolute value; 1 = relative value. Alarm Fan differential. Alarm differential. Higher ALarm. Maximum temperature alarm. Temperature value (with regard to Setpoint) which if exceeded in an upward direction triggers the activation of the alarm signal. Lower ALarm. Minimum temperature alarm. Temperature value (with regard to Setpoint), which if exceeded in a downward direction, triggers the activation of the alarm signal. Power-on Alarm Override. Alarm exclusion time after instrument switch on, after a power failure. defrost Alarm Override. Alarm exclusion time after defrost. Output (door) Alarm Override. Delay time for temperature alarm signalling after disabling of digital input (or door closure). Time-out Door Open. Alarm signalling delay time for gate open. temperature Alarm Override. Temperature alarm signal delay time. External Alarm Lock. External alarm for regulators stop. Allows the blocking of compres­sor, defrosting and fan regulators if the digital input (configured as external alarm) is activated. n = not block; y = block.
COMUNICATION (folder with label “Add”)
dEvice Address. Device address: indicates the appliance address to the management pro­tocol FAmily Address. Family address: indicates the appliance family to the management proto­col
DISPLAY (folder with “diS” label)
Keyboard locking. However, you can enter parameter programming modify them along with the status of this parameter in order to allow keyboard locking. y = yes; n = no
Tab. 1 Parameter Table
DEFAULT
2.0
99.0
-50.0 0
0
0
n
0
0
1
0
0
0
0
6h
0
1
1
0
30min
n
0
0
0
2.0
50.0
-50.0
0
0 0
0 0 n
0
0
n
RANGE
0.1...30.0
LSE..302
-55.0...HSE
-30.0...30.0
0...250
0...250
n/y
0…255
0...250
0...250
0...250
0...250
0...250
0...250
0...250
0/1/2
0/1/2
0/1/2
0...59
1...250
n/y
-31...31
0…60
0/1
1.0...50.0
LAL...150.0
-50.0...HAL
0...10
0..999 0…10
0…250
0...250 n/y
0...14
0...14
n/y
VALUE* LEVEL**
1
1 1
2
2
2
2
2
1
1
1
1
1
1
1
2
2
1
1
1
1
2
2
2
1 1
1
1
1
2
2
1
2
1
1
1
U.M.
°C/°F
°C/°F °C/°F °C/°F
min
min
flag
Min.
min
min
sec
min
min
min
hours
(/min/sec)
flag
flag
flag
min min
(/h/sec)
flag
min
min
flag
°C/°F °C/°F
°C/°F
hours
min
hours
min min flag
num
num
flag
**NOTE: At level 1 the folders will show only level 1 parameters. At level 2 the folders will show only level 2 parameters.
ID 961 LX/A 5/6
PAR.
PA1
PA2***
ndt CA1
CA
LdL HdL ddL
dro
ddd
H00(!)(1) H02 H11(!)(2)
H21(!)
H22(!)
H25(!)(3)
H31(!)
H32(!)
H33(!)
reL tAb
UL dL Fr
(1) the default value is 1 (NTC input, see the label on the instrument). (2)
WARNING! positive or negative values change polarity;
Positive values: active input for on contact; negative values: active input for off contact. (3) Parameter visible in models with optional buzzer. (5) If alarms are related to the Setpoint, HAL parameter should be set to positive values and LAL should be set to negative values (6) Referred only to low and high temperature alarms
* VALUE column: to be filled manually, with customized settings (if different from the default value). ** LEVEL column: indicates the level of visibility of parameters accessible by PASSWORD (see the related paragraph) *** PA2 is visible (it will be required, if necessary) at level 1 and can be set (editable) at level 2
(!) WARNING!
• If one or more of these parameters highlighted with (!) are modified, the controlller must be switched off and switched on again to ensure correct operation.
• It is strongly recommended, anyway to switch off and switch on again the controller anytime parameters have been changed to prevent malfunctioning on configuration and/or ongoing timings
DESCRIPTION
PAssword 1. When enabled (value other than 0) it constitutes the access key for level 1 parameters. PAssword 2. When enabled (value other than 0) it constitutes the access key for level 2 parameters. number display type. View with decimal point. y = yes; n = no CAlibration 1.Calibration 1. Positive or negative temperature value added to the value read by probe 1, based on “CA” parameter settings. CAlibration Intervention. Intervention on view offset, thermostat offset or both. 0 = modifies the temperature displayed only; 1 = adds to the temperature used by regulators, not to the temperature displayed, which stays unchanged. 2 = adds to the temperature displayed that is also used by regulators. Low display Label. Minimum value the instrument is able to display. High display Label. Maximum value the instrument is able to display. defrost display Lock. Viewing mode during defrosting. 0 = shows the temperature read by the thermostat probe; 1 = locks the reading on the temperature value read by thermostat probe when defrosting starts, and until the next time the Setpoint value is reached; 2 = displays the label “deF” during defrosting, and until the next time the Setpoint value is reached. display read-out. Select °C or °F for displaying the temperature read by the probe. 0 = °C, 1 = °F. PLEASE NOTE: the switch between °C and °F DO NOT modify set-
point, differential, etc. (for example set=10°C become 10°F).
Selection of the value type to be shown on the display. 0 = Setpoint; 1 = probe 1; 2 = not used
CONFIGURATION (folder with “CnF” label)
Probe type selection, PTC or NTC. 0 = PTC; 1 = NTC. Time to enable keys, if these are configured for a specific function. Configurability digital inputs/polarity. 0 = disabled; ± 1 = defrosting; ± 2 = reduced set; ± 3 = not used; ± 4 = door switch; ± 5 = external alarm. Configurability digital output 1. (B) 0 = disabled; 1 = compressor; 2 = defrosting; 3 = fans; 4 = alarm; (default) 5 = auxiliary. Configurability digital output 2. (A) Same as H21 NOTA: 1 = compressor; (default)
NOTE: PARAMETER VISIBLE ONLY IN MODELS WITH BUZZER
Configurability buzzer output. 0 = disabled; 4= enabled; 1-3,5= not used Configurability UP key 0 = disabled; 1 = defrosting; (default) 2 = not used; 3 = reduced set (economy). Configurability DOWN key 0 = disabled; (default) 1 = defrosting; 2 = not used; 3 = reduced set (economy). Configurability FNC key 0 = disabled; (default) 1 = defrosting; 2 = not used; 3 = reduced set (economy). reLease firmware. Device version: read only parameter. tAble of parameters. Reserved: read only parameter.
COPY CARD (folder with “Fpr”label)
Up load. Programming parameter transfer from instrument to Copy Card. Down load. Programming parameter transfer from Copy Card to instrument Format. Erasing all data in the copy card.
NOTA BENE: using “Fr” parameter (copy card formatting) the data within the copy card will be lost permenently. The operation cannot be cancelled.
DEFAULT
0
0
y 0
2
-55.0
140.0 1
0
0
0 5 0
4
1
4
1
0
0
/ /
/ / /
RANGE
0...250
0...255
n/y
-12.0...12.0
0/1/2
-55.0...302
-55.0..302 0/1/2
0/1
0/1/2
0/1
0...15
-5...5
0...5
0...5
0...5
0...3
0...3
0...3
/ /
/ / /
VALUE* LEVEL**
1
2
1 1
2
2 2
1
1
2
1
2 2
2
2
2
2
2
2
1 1
1 1
2
U.M.
number
number
flag
°C/°F
num
°C/°F °C/°F
flag
flag
num
flag
sec
flag
flag
flag
flag
num
num
num
/ /
/ / /
label PA2 Inside CnF folder it is possible to reach all level 2 parameters from label PA2 by pressing the “set” button SEE 2) level 2 Parameters paragraph
ID 961 LX/A 6/6
Invensys Controls Italy s.r.l
via dell'Industria, 15 Zona Industriale Paludi 32010 Pieve d'Alpago (BL) ITALY Telephone +39 0437 986111 Facsimile +39 0437 989066 Internet http:/www.climate-eu.invensys.com
7/2003 eng cod. 9IS22089
TERMINALS
1 - 2 N.C. compressor relay (A) 1 - 3 N.O. compressor relay (A) 4 - 5 N.O. alarm relay (B) 6 - 7 Power supply • 12 Va/c model, 1,5 VA max.
• 230 Va model, 3 VA max. 8 - 9 Probe 1 input (thermostat) 8 - 10 Digital input A TTL input for Copy Card and connection to
Televis system
NOTE: Default user settings
Wiring diagram
1 2 3 4 5
6 7 8 9
10 11
ID 961 LX/A - 12 V
A
(A) (B)
1 2 3 4 5 6 7
8 9
10 11
ID 961 LX/A - 230 V
A
(A)
(B)
Loading...