Eliwell IC 915, IC 915 LX User Manual

BUTTONS AND MENUS ACCESSING AND USING MENUS
The resources are arranged in a menu that can be accessed by pressing and quickly releasing the “set” button (Machine Status menu) or holding down the “set” button for more than 5 seconds (Programming menu). To access the contents of each folder indi­cated by the relevant label, just press the “set” button once. You can now scroll through the contents of each folder, modify it or use its func­tions. If you do not use the keyboard for over 15 seconds (time-out) or if you press the “fnc” button once, the last value shown on the display is confirmed and you are taken back to the previous screen mask.
MACHINE STATUS MENU (See Machine Status Menu Diagram)
To access the Machine Status menu, press the “set” button and quickly release it. The “SP1” label appears. (If alarms are active, with the exception of faulty probes/probe errors, the “AL” label appears). By using the “UP” and “DOWN” buttons you can scroll through the other folders in the menu: the folders are indicated below in the order they appear:
-SP1: Set point 1 setting folder or
-AL: alarm folder (if alarms present, with exception of faulty probes/probe errors);
-SP2: Set point 2 setting folder.
-Pb1: probe 1 value folder;
-Pb2: probe 2 value folder;
The folders are present according to the presence and configuration of the associated resource.
Alarm on
If an alarm condition exists when the Machine Status menu is accessed, the “AL” folder label appears (see “Diagnostics” section).
USER INTERFACE
The user has a display and four buttons for controlling instrument status and pro­gramming.
IC 915 (LX)
electronic controller with 2 set points and differential set point adjustment
cod. 9IS23071
rel. 12/04
GB
Alarm
•ON for active
alarm;
•blinking when
a silenced alarm
is still present
out2
Relay 2 (OUT2)
ON for relay on
(energized);blin
king for protec-
tion delay or
enabling
blocked
out1
Relay 1 (OUT1)
ON for relay on
(energized);blin
king for protec-
tion delay or
enabling
blocked
Soft Start
ON when Set
point is being
set
(and Set point
setting)
blinking when
Soft Start func-
tion is on
Set-point/
Reduced set
point
•ON to modify
Set-Point;
•blinking when
reduced set
point is entered
set
f nc
IC915LX
out 2
out 1
AL
SP1
SP2
set
alarms
value SP1
value SP2
set
set
set
change
SP1(2) value
show alarms
is present
press and release
(quickly/single press)
if alarm(s)
present
Pb1
Pb2
value Pb1
value Pb2
set
set
is present
MACHINE STATUS MENU DIAGRAM
LEDs
out2 out1
Scrolls through the menu items UP button Increases the values Parameter programmable (par. H31)
DOWN button Scrolls through the menu items Decreases the values Parameter programmable (par. H32)
fnc button ESC function (quit)
Parameter programmable (par. H33)
Set point button 1-Accesses Machine Status Menu
(SET POINTS, ACTIVE ALARMS, PROBE READING) and labels/values; 1-Accesses Programming Menu (PARAMETERS, COPY C ARD) and relative labels/values; 3-Confirms commands
fnc
set
*FNC FUNCTION FOLDER The FnC folder (last folder visible from the Programming Menu, level 1) con­tains the following functions. They are activated using the “set” button
If the unit is switched off, the function labels go back to their default status.
ADVANCED FUNCTIONS
DIFFERENTIAL AND SET POINT OFF
DIFFERENTIAL AND SET POINT OFF--
SET ADJUSTMENT (see relevant para
SET ADJUSTMENT (see relevant para--
graph)
graph) SOFT START Note: The SOFT START function is but­ton, D.I. or function selectable.
The Soft Start controller can be used to set the temperature gradient required to reach a specific set point in a specific peri­od of time. This function automatically gives you a progressive increase of the control set point from the Ta value (ambient tempera­ture at start-up) to the value actually dis­played. This means that a rise in tempera­ture can be immediately stopped and the risk of overshooting reduced. (continued on pg. 4)
IC 915 LX 2/10
Function
Soft Start Reduced set point Controls blocked Periodic Cycle Aux Stand-by Maintenance request
NOTE: In this case the UnP label is displayed (flashing)
**default
Function label INACTIVE
SoF** SP** boF coF AoF oF AtF**
Function label ACTIVE
Son OSP bon** con Aon on** Atn
USING COPY CARD
The Copy Card is an accessory connect­ed to the TTL serial port used for quick programming of the unit parameters (upload and download parameter map to one or more units of the same type). Operations are described below:
Fr-Format
This command is used to format the copy card. This is necessary if:
•it is used for the first time,
•it is used with models that are incom­patible,
•after use with a specific model if another model needs to be connected. Warning: when the copy card has been programmed using the “Fr” parameter all the data entered is cancelled. This operation cannot be undone.
UL-Upload
This operation uploads the programming parameters from the instrument.
dL-Download
This operation downloads the program­ming parameters to the instrument.
NOTE:
• UPLOAD: instrument —> Copy Card
• DOWNLOAD: Copy Card —> instru­ment.
The operations are performed by access­ing the folder identified by the “FPr” label and selecting the “UL”, “dL” or “Fr” commands. The operation is confirmed by pressing the “set” button. If the oper­ation is successful, a “y” is displayed whereas if it is unsuccessful an “n” will be displayed.
Download “from reset”
Connect the copy card with the instru
­ment OFF. When the instrument is switched on the programming parame­ters will be downloaded into the copy card; when the lamp test has been com­pleted, the following appear on the dis­play for about 5 seconds:
• label dLY if copy operation is success­ful
• label DLn if operation fails PLEASE NOTE:
• after downloading the instrument will work with the parameter map settings that have just been downloaded.
HOW TO LOCK THE KEYBOARD
Keyboard operating can be locked by pro­gramming the “LOC” parameter (see folder with “diS” table). If the keyboard is locked you can only access the Programming MENU (see) Functions CANNOT be activated with but­tons (to silence alarms, for example) .
HOW TO SET THE SET POINTS Setting Setpoint 1 (Setpoint 2)
Go to the “Machine Status” menu, press the “set” button and quickly release it. The “SP1” folder label appears. (To set Set point 2 press the “UP“ and “DOWN“ buttons until “SP2” appears). To display the Set point 1 (2) value, press the “set” but­ton again. The Set point value appears on the display. To change the Set point 1 (2) value, press the “UP” and “DOWN” buttons within 15 seconds. If parameter LOC = y the Set points cannot be changed.
HOW TO DISPLAY THE TEMPERATURE READ BY PROBE(S)
If you press the “set” button when the corresponding label appears, the value of the probe associated with it is displayed.
ALARM PRESENT?
If an alarm condition exists when the Machine Status menu is accessed, the “AL” folder label appears. which will include the alarm codes. (see section on “Diagnostics”).
IC 915 LX 3/10
PROGRAMMING MENU (See Programming Menu Diagram)
1) Displaying level 1 parameters
To access the Programming menu, hold the “set” button for more than 5 seconds.
Level 1 parameters can be protected by a PASSWORD* (defined by parameter DIS/PA1) If the PASSWORD is enabled, the label “PA1” will appear when you access the Programming Menu; press the “set” button and the value “0” will appear; enter the password using the “UP”/”DOWN” buttons and press the “set” button again. This allows you to access the level 1 parameters. The first folder that appears is “CP”. Use the “UP” and “DOWN” buttons to scroll through the other folders; the
folders will only display level 1 para­meters. NOTE: at this point level 2 parameters are NOT visible even if NOT password­protected.
2) Displaying level 2 parameters
Go to the “CnF” folder in the Programming Menu and scroll down the parameters until you reach the PA2 label. By pressing and releasing the “set” but­ton you will enter the level 2 parameters and the “CP” label of the first folder in
the programming menu will appear.
The level 2 parameters can be protected by a second PASSWORD* (defined by parameter DIS/PA2) (NOTE: not to be confused with the PA2 label in the “CnF” folder). If the PASSWORD is enabled, the label “PA2” will appear in CnF/PA2 when you access the Programming Menu; press the “set” button and the value “0” will appear; enter the password using the “UP”/”DOWN” buttons and press the “set” button again. This allows you to access the level 2 parameters. The first folder that appears is “CP”.
NOTE: At this level the folders will only display all the level 2 parame­ters.Therefore level 1 parameters will
only be visible if you quit the Programming Menu and repeat proce­dure 1).
NOTE: It is strongly recommended that the unit is switched off and on again each time parameter configuration is changed in order to prevent malfunc­tioning of the configuration and/or ongoing timings (compulsory for selec-
tion of probe type and count parame­ters).
*PASSWORD
Passwords “PA1” and “PA2” allow level 1 and level 2 parameters to be accessed. There are no passwords in the standard configuration. To enable them (value ≠0) and assign them the desired value, access the Programming menu in the “diS” fold­er. If passwords are enabled, they will be requested:
- PA1 when entering the Programming menu (see the “Programming Menu“ sec­tion);
- PA2 in the “Cnf” folder containing the level 1 parameters.
AL
level 1 par
set
set
PA1≠0
set
set PA1 value
Add
diS
CnF
Fpr
set
level 1 par
level 1 par
level 1 par
level 1 par
set
set
set
PA2
level 2 par
level 2 par
level 2 par
level 2 par
level 2 par
level 2 par
level 2 par
rE1/2
SFt
cLc
AL
set
set
set
set
diS
CnF
Fpr
set
set
set
set
set
PA2≠0
set
set PA2 value
level 2
level 1
change
par value
scroll
parameters
FnC
functions
set
scroll
functions
activate/disactivate
function
set
press for 5 sec
rE1
rE2
set
level 1 par
level 1 par
set
if folder
present
PROGRAMMING MENU DIAGRAM
TECHNICAL DATA
Front protection: IP65. Casing: PC+ABS UL94 V-0 resin plastic body, polycarbonate front, thermoplastic resin buttons. Dimensions: front panel 74x32 mm, depth 59 mm (terminals excluded). Mounting: on panel, with drilling template 71x29 mm (+0.2/-0.1 mm). Operating temperature: -5…55 °C. Storage temperature: -30…85 °C. Usage ambient humidity: 10…90 % RH (non-condensing). Storage ambient humidity: 10…90% RH (non-condensing). Display range:
• NTC probe: –50…110°C (–58…230°F);
• PTC probe: –55…150°C (–67…150.00°C) on display 3 1/2 digits + sign.
Analogue inputs: two PTC or NTC inputs (H00 parameter-selectable). Digital input: 1 voltage-free parameter­configurable digital input. Serial: TTL for connection to Copy Card and Televis System. Digital outputs: 1 output on SPDT relay 8(3)A 1/2 hp 250Va, 1 output on SPST relay 8(3)A 1/2 hp 250Va configurable (for relay capacity, see instrument label). Buzzer output: only in certain models. Measurement range: from -55 a 150 °C. Accuracy: better than 0.5% of bottom scale + 1 digit. Resolution: 1°C or 0.1°C (displayed with decimal point). Consumption:
• 230V model: 3 VA max.;
• 12/24V model: 1.5 VA max. Power supply: 12/24 Va/c ±10% or 230Va ±10% 50/60 Hz.
Warning: check the power supply speci­fied on the instrument label; for informa­tion on relay capacity and power supplies contact the Sales Office.
(continued from pg 2) The Soft Start parameters are displayed in the “SOFT START” folder (with label “SFt”)
PERIODIC CYCLE Note: The PERIODIC CYCLE function is button, D.I. or function selectable.
This function can be associated with relay outputs (by setting parameters H21, H22 =4) and can be used for Duty Cycle adjust­ment with the ranges defined by the para­meters Con and CoF (see Periodic Cycle
Diagram on page 9). AUX (Auxiliary Controller)
The digital input can be configured as aux­iliary (parameter H11=5): if this is the case, the controller 1(2) command must be set as aux (auxiliary) using parameters H21(22). This function can be used to activate the relay if it was de-energized or energize it if this was not the case. The status is stored so that the unit operates correctly in the event of a black-out unless parameter H11=5 (aux); if this is the case, the relay reflects the status of the digital input. Parameter H13 can be used to establish the priority/polarity between keyboard, relay and Digital Input activation.
NOTE: The meaning of the Digital Input (D.I.) must not change: for example, by activating the relay from the D.I. and deactivating using the keyboard, the relay does not change status if the D.I. is repositioned since it has been deacti­vated by the keyboard
MECHANICAL ASSEMBLY
The unit has been designed to be panel­mounted: Drill a 29x71 mm hole, insert the keyboard and fix it in place with the special brackets provided. Do not install the keyboard in excessively humid and/or dirty locations. It is suitable for use in locations with normal pollution levels. Always make sure that the area near the cooling slits of the device is adequately ventilated.
ELECTRICAL WIRING
Warning! Always switch off machine before working on electrical connec­tions.
The instrument has screw terminals for connecting electrical cables with a diame­ter of 2,5 mm
2
max. (only one conductor per terminal for power connections). for terminal capacity, see the label on the instrument. The relay contacts are voltage free. Do not exceed the maximum current allowed. For higher loads, use a suitable contactor. Make sure that the power voltage com­plies with the device voltage. The sensor has no connection polarity and can be extended using an ordinary bipolar cable (note that extending the probe may affect the electromagnetic compatibility (EMC) of the instrument: special care must be used when wiring).
Probe cables, power supply cables and the TTL serial cable should be kept separate from power cables.
IC 915 LX 4/10
NOTE: The technical characteristics in this document concerning mea­surements (range, accuracy, resolu­tion, etc.) refer to the instrument in the strictest sense and not to any accessories provided such as probes, for example. This means that an error intro­duced by the probe is added to any error that is in the instrument.
RS232 (to PC)
RS485
BusAdapter
PCInterface
TTL
PC with
Televis package
230V
N
L
230V
N
L
The Televis remote control systems can be connected using the TTL serial port (the TTL- RS 485 BUS ADAPTER 130 or 150 interface module must be used). To configure the instrument to do this, you need to access the folder with the “Add” label and use the “dEA” and “FAA” parameters.
TELEVIS SYSTEM
BUSAdapter130/150
TTL - RS-485 serial interface on DIN rail for connecting device and a RS-485 network designed for connection to Televis monitoring system.
PCInterface1100 RS-232/RS-485 serial interface for con­necting a PC and a series of instru­ments in an RS-485 network. The device needs the BlueCard activation module supplied with the Eliwell soft­ware package licence to be plugged in.
DIFFERENTIAL ADJUSTMENT
DIFFERENTIAL ADJUSTMENT
For this type of adjustment, set:
•folder CnF, parameter H42=y indicating the presence of probe Pb2;
•folder CnF, parameter H03=1 indicating the type of adjustment (=1, adjustment according to Pb1-Pb2 difference compared with set point; On the basis of these settings, the new adjustment value is calculated according to the difference between the values read by the two probes “diff”=Pb1-Pb2. If the difference is positive (Pb1> Pb2) or negative (Pb2>Pb1) but lower or equal to the value of the set point (SP1>”diff”, or SP1=”diff”) the output set “for heating” will be activated. If the difference is positive (Pb1> Pb2) but higher than the value of the set point (SP1>”diff”) the output set “for cooling” will be activated.
-->Adjustment varies according to parame­ter H01 that determines the link between the outputs. See diagram on right.
SETPOINT=OFFSET ADJUSTMENT
SETPOINT=OFFSET ADJUSTMENT
compared with Pb2.
compared with Pb2.
For this type of adjustment, set:
•folder CnF, parameter H42=y indicating the presence of probe Pb2;
•folder CnF, parameter H03=2 indicating the type of adjustment (H03=2, adjust­ment of set point calculated as offset from probe Pb2; On the basis of these settings, the new adjustment value “SE= effective set point” is calculated according to the sum of the set point offset (see parameter SP1) and the value read by probe Pb2 within the
new setting limits defined by parame­ters LLS and HLS.
The control input is always determined by Pb1.
-->Adjustment varies according to parame­ter H01 that determines the link between the outputs. See diagram on right.
IC 915 LX 5/10
DIFFERENTIAL and SET POINT OFFSET ADJUSTMENT
HC1
H* H*
-
H* maximum set point controller with differential dF1 negative C** minimum set point controller with differential dF2 positive
NOTE:
•for 1 and 2 examples with HC1=H e HC2=C;
•for 3 HC1 and HC2 settings are ignored
HC2
C** C**
-
H01
0 1 2
type of regulation
independent set points dependent set points Neutral Area (or window)
SP1
SP1-dF1
dF1
Off
On
SP2+dF2
SP2
dF2
Off
On
HC1=H
H01=in
HC2=C
differential adjustment diagrams
SP1
SP1-dF1
dF1
Off
On
SP1+SP2+dF2
SP1+SP2
dF2
Off
On
HC1=H
H01=di
HC2=C
SP1-db2+dF2
SP1-db2
dF2
Off
On
SP1+db1
SP1+db1-dF1
dF1
On
OUTPUT 2
OUTPUT 1
SP1
db2
db1
independent outputs. The two outputs regulate as though they are completely indepen­dent
dependent outputs. The set point 2 SP2 regulates accord­ing to SP1
outputs with Neutral Zone adjustment
(or window).
NOTE: if dF1 and dF2 are both =0 the outputs are deactivat­ed when SP1 is reached
1
2
3
SP1
+pb2
SP1
+pb2
-dF1
dF1
Off
On
SP2
+pb2
+dF2
SP2
+pb2
dF2
Off
On
HC1=H
HC2=C
Setpoint=offset adjustment compared with Pb2 diagrams.
SP1
+pb2
SP1+pb2
-dF1
dF1
Off
On
SP1
+pb2
+SP2 +dF2
SP1
+pb2
+SP2
dF2
Off
On
HC1=H
HC2=C
SP1
+pb2
-db2+dF2
SP1
+pb2
-db2
dF2
Off
On
SP1+pb2 +db1
SP1+pb2 +db1-dF1
dF1
On
OUTPUT 2
OUTPUT 1
SP1
+pb2
db2
db1
independent outputs. The two outputs are adjusted as if they were completely independent­except for the
Pb2 analogue
input for both
dependent outputs. The set point 2 SP2 is adjusted according to SP1 and Pb2
outputs with Neutral Zone adjustment
(or window).
NOTE: if dF1 and dF2 are both =0 the outputs are deactivat­ed when SP1 is reached
1
2
3
H01=0
H01=1
H01=2
H01=0
H01=1
H01=2
IC 915 LX 6/10
The alarm condition is always signalled by a buzzer (if present) and the alarm
icon
LED. The alarm signals from the
• control probe that measures values out­side the nominal reading range
• control probe faulty/shorted/open probe appears directly on the instrument display as E1. Note: to prevent false alarms, the error condition must persist for more than 10 seconds. An error condition in probe 1 (regulation) leads to:
• E1 code appears on display
• the controller being activated as indicat­ed by the “On1(On2)” and “OF1(OF2)” parameters if programmed for the duty cycle or... (see DUTY CYCLE diagram)
MAXIMUM AND MINIMUM TEMPERA­TURE ALARM (SEE PAR. H04)
If an alarm condition occurs and alarm exclusion times are not in progress (see alarm exclusion parameters), the alarm icon lights up permanently and the relay that is configured as an alarm is activated. This type of alarm does not affect the regulating in progress. Alarms are considered as absolute (default) values or as values related to the
Set point (the distance from the Set point itself) and based on the Att parameter. If the alarms are relative (Att=1), the para­meter HA1(2) is set to positive values and LA1(2) to negative values. This alarm condition can be viewed in the folder “AL” with labels “AH1-AL1”.
EXTERNAL ALARM
The device can also control an external alarm, i.e. from a digital input. If the digi­tal input is enabled, the alarm control is activated by programming and remains enabled until the next time the digital input is deactivated. The alarm is signalled by turning on the fixed alarm icon, acti­vating the relay configured as alarm and deactivating compressor, defrost and fan controls (if specified by the “H11=5” para­meter). This alarm condition can be dis­played in the “AL” folder using the “EA”
label. The relay can be silenced; even if the alarm icon starts blinking, the con­trollers remain locked until the next time the digital input is deactivated.
OPEN DOOR ALARM
If a door is open, the Open Door alarm is signalled in response to a delay defined by the tdO parameter. The alarm is signalled by the flashing alarm icon. This alarm condition can be viewed in the “AL” folder with the label “Opd”.
DIAGNOSTICS
DISPLAY
E1 E2
If simultaneous, they will be shown on the display alternately every 2 seconds
FAULT
Faulty probe 1 (thermostat control) Faulty probe 2 (evaporator)
Table of faulty probes
DISPLAY
AH1**
AL1**
EA Opd Press any button to silence the alarm. The LED will start to blink.
ALARM
High temperature alarm (referring to probe Pb1/Pb2 based on par. H04) Low temperature alarm (referring to probe Pb1/Pb2 based on par. H04) External alarm Door Open Alarm
Alarm table
Minimum temperature alarm
Maximum temperature alarm
LAL
AFd
HAL
AFd
1
set+ LAL
AFd
Off
set+HAL
AFd
set
2
Temperature lower than or equal to LA1(2) (LA1(2) with sign)
Temperature lower than or equal to set point +LA1(2) positive only)
Temperature greater than or equal to set point +HA1(2) (HA1(2) positive only)
Temperature greater than or equal to HA1(2) (HA1(2) with sign)
Maximum temperature alarm back swing
Minimum temperature alarm back swing
Temperature greater than or equal to LA1(2)+AFd Temperature greater than or equal to set point + LA1(2) + AFd
set point -|LA1(2)|+AFd
Temperature lower than or equal to set point+HAL-AFd
Temperature lower than or equal to HA1(2)-AFd
Temperature expressed as an absolute value (par “Att0) Abs(olute)
Temperature expressed in relation to set point (par “Att”=0) reL(ative)
if Att=reL(ative) LA1(2) must be negative: therefore set point+LAL<set point because set point+(-|LA1(2)|)=set-|LA1(2)|
ALARM DIAGRAM HIGH AND LOW TEMPERATURE
OF1(2)
Off
On
OUT
On1(2) On1(2)
An error condition in probe 1 (regulation) leads to:
• E1 code appears on display
• activation of controller as indicated by the “On1(On2)” and “OF1(OF2)” parameters if programmed for the duty cycle
Ont
0 0 >0 >0
OFt
0 >0 0 >0
Compressor output
OFF OFF ON dc
DUTY CYCLE DIAGRAM
On1(2) OF1(2) parameters programmed for Duty Cycle
**VALUE H04 = 0 —> Pb1-Pb2; = 1 —> Pb1;
= 2 —> Pb2; = 3 —> Pb1 and Pb2.
PAR.
HC1
OS1 db1 dF1
HS1
LS1
HA1 LA1
dn1
do1
di1
dE1
On1
OF1
HC2
OS2 db2 dF2
HS2
LS2
HA2 LA2
dn2 do2
di2
dE2
On2
OF2
dSi
dSt
Unt SEn
Sdi
Con CoF
7/10
DESCRIPTION
CONTROLLER 1 (folder with “rE1” label)
Regulating mode. If set to H, the controller operates in heating mode. If set to C, the controller operates in cooling mode.
Offset Set point 1 Regulation band 1 See ON-OFF regulation diagram Relay 1 intervention differential. The load will stop when Set point 1 is reached (as indicated by the control probe) and will restart at a tem­perature equal to Set point 1 plus (or minus depending on HC1) the value of the differential. See ON-OFF reg. diagram
Maximum value for set point 1. By default, it will be set to the maxi­mum value that the probe can reach. Minimum value for set point 1. By default, it will be set to the mini­mum value that the probe can reach. Maximum alarm OUT 1 See Max/Min. Alarm diagram. Minimum alarm OUT 1 See Max/Min. Alarm diagram.
CONTROLLER 1 PROTECTIONS (folder with “rE1” label)
Start-up delay. The specified time must elapse between the controller relay start-up request and actual start-up. Delay after shut-down. The specified time must elapse between shut­down of controller relay and a subsequent start-up.
Delay between start-ups. The specified time must elapse between two subsequent start-ups of the controller. Shut-down delay. The specified time must elapse between the con­troller relay shut-down request and actual shut-down.
NOTE: for parameters dn1, do1, di1, dE1 0= not active
Controller start-up time if probe is faulty. If set to “1” with Oft at “0” the controller is always on whereas if Oft >0 it operates in duty cycle mode.
See Duty Cycle diagram
Controller shut-down time if probe is faulty. If set to “1” with Oft at “0” the controller is always off whereas if Oft >0 it operates in duty cycle mode.
See Duty Cycle diagram CONTROLLER 2 (folder with “rE2” label)
Regulating mode. If set to H, the controller operates in heating mode. If set to C, the controller operates in cooling mode.
Offset Set point 2 Regulation band 2 See ON-OFF regulation diagram Relay 2 intervention differential. The load will stop when the Set point is reached (as indicated by the control probe) and will restart at a temperature equal to Set point 2 plus (or minus depending on HC2) the value of the differential. See ON-OFF reg. diagram
Maximum value for set point 2. By default, it will be set to the maxi­mum value that the probe can reach. Minimum value for set point 2. By default, it will be set to the mini­mum value that the probe can reach. Maximum alarm OUT 2 SEE ALARM DIAGRAM HIGH AND LOW T. minimum alarm OUT 2 SEE ALARM DIAGRAM HIGH AND LOW T.
CONTROLLER 2 PROTECTIONS (folder with “rE2” label)
Delay in start-up of controller 2. See dn1 Delay after shut-down. The specified time must elapse between shut­down of controller 2 relay and a subsequent start-up.
Delay between start-ups. The specified time must elapse between two subsequent start-ups of controller 2. Delay in shut-down of controller 2. The specified time must elapse between the controller relay shut-down request and actual shut-down.
NOTE: for parameters dn2, do2, di2, dE2 0= not active
Controller start-up time if probe is faulty. If set to “1” with Oft at “0” the controller is always on whereas if Oft >0 it operates in duty cycle mode.
See Duty Cycle diagram
Controller shut-down time if probe is faulty. If set to “1” with Oft at “0” the controller is always off whereas if Oft >0 it operates in duty cycle mode. See Duty Cycle diagram
SOFT START (folder with “SFt” label)
dynamic Step increment (Step Value). Value (in degrees)of each of subsequent increases (dynamic) of adjustment point. 0=disables SOFT START function. dynamic Step time (Step Duration). Time between two subsequent increases (dynamic) of set point Unit of measurement (hours, minutes, seconds) Enabled outputs. Establishes which outputs the function must be enabled on: 0 = disabled; 1 = OUT 1; 2 = OUT 2; 3 = OUT 1 & 2; Function reinsertion threshold. Establishes the threshold beyond which the SOFT START function is automatically re-inserted
PERIODIC CYCLE (folder with “cLc” label)
Output ON time. Output OFF time.
Tab. 1 Table of parameters
DEFAULT*
C
0 1 1
140
-50
140
-50
1
0
0
0
0
1
C
0 1 1
140
-50
140
-50
1 0
0
0
0
1
0
0
1 1
0
0 0
RANGE
H/C
-30.0...30.0
0...30.0
0.0...30.0
LS1..HdL
LdL..HS1
LA1…350.0
-99.9…HA1
0...250
0...250
0...250
0...250
0...250
0...250
H/C
-30.0...30.0
0...30.0
0.0...30.0
LS2..HdL
LdL..HS2
LA2…350.0
-99.9…HA2
0...250
0...250
0...250
0...250
0...250
0...250
0…25.0
(0...twenty-five.0)
0…250
0/1/2
0/1/2/3
0…30.0
0…250 0…250
VALUE**
U.M.
flag
°C/°F °C/°F °C/°F
°C/°F
°C/°F
°C/°F °C/°F
°C/°F
sec
min
min
sec
min
min
flag °C/°F °C/°F
°C/°F
°C/°F
°C/°F °C/°F
sec
min
min
sec
min
min
°C/°F
H/m/sec
H/m/sec
num
°C/°F
min
min
LEVEL***
1
2
1 1
1
1
1 1
1
1
1
1
1
1
1
2
1 1
1
1
1 1
1 1
1
1
1
1
2
2
2 2
2
2 2
IC 915 LX
SP1: Control SetPoint 1, range LS1...HS1 SP2: Control SetPoint 2, range LS2...HS2
***NOTE: At level 1 the folders will only display all the level 1 parameters. At level 2 the folders will only display all the level 2 parameters.
rE1
re2
SFt
CLc
PAR.
Att
AFd PAO (!)
(2)
SAO
tAO (2)
AOP
dEA (!)
FAA (!)
LOC
PA1
PA2****
ndt
CA1
CA2
CAI
LdL HdL LLS HLS dro
ddd
H00(1)(!) H01
H02
H03
H04
H05 H06
H08
H10
IC 915 LX 8/10
DESCRIPTION
ALARMS (folder with “AL” label)
Alarm type. Parameter “HAL” and “LAL” modes, as absolute tempera­ture values or as differential compared to the Set point. 0 = absolute value; 1 = relative value. Alarm Fan differential. Alarm differential. Power-on Alarm Override. Alarm exclusion time after instrument start-up following a power fail­ure. Set point Alarm Override. Alarm exclusion time after reaching set point. 0 = disabled. If >0, an alarm will be generated if the set point is not reached after the time (in hours) set by this parameter.
temperature Alarm Override. Temperature alarm signal delay time.
Alarm Output Polarity. Polarity of alarm output. 0 = alarm active and output disabled; 1 = alarm active and output enabled.
COMMUNICATION (folder with “Add” label)
dEvice Address. dEA = device address in family (valid values from 0 to
14) FAmily Address. FAA = device family (valid values from 0 to 14) The pair of values FAA and dEA represents the device network address and is indicated as “FF.DD” (where FF=FAA and DD=dEA).
DISPLAY (folder with “diS” label)
Keyboard locked (set point and buttons). However, you can still access the parameter programming menu and modify parameters including the status of this parameter to allow keyboard unlocking. y = yes; n = no. Password 1. When enabled (value is not 0) it represents the access button to level 1 parameters. Password 2. When enabled (value is not 0) it represents the access button to level 2 parameters. number display type. Display with decimal point. y = yes; n = no. Calibration 1. Positive or negative temperature value that is added to the value read by control probe (probe 1) before being displayed or used for control. Calibration 1. Positive or negative temperature value that is added to the value read by control probe (probe 2) before being displayed or used for control. CAlibration Intervention. Intervention of offset on display, thermostat control or both. 0 = only modifies the temperature displayed; 1 = adds to the temperature used by controllers, not the tempera­ture displayed that remains unchanged; 2 = adds to temperature displayed that is also used by controllers.
Low display Label. Minimum value the instrument is able to display. High display Label. Maximum value the instrument is able to display. Low Limit Setpoint. Minimum value the instrument is able to display. High Limit Setpoint. Maximum value the instrument is able to display. Select °C or °F to display temperature read by probe.
N. B.: switching from °C to °F DOES NOT modify set points, dif­ferentials, etc. (for example set point=10°C becomes 10°F).
Selection of the value type to be displayed. 0 = Set point; 1 = probe 1 (Pb1); 2 = probe 2 (Pb2);
CONFIGURATION (folder with “CnF” label)
For selection of probe type, PTC or NTC. Output link. 0 = independent; 1 = dependent; 2 = Neutral Zone (or window) Button activation time if buttons are configured for a second func­tion. For the ESC, Up and DOWN buttons configured for a second func­tion (defrost, aux, etc) the time for rapid enabling is set. Aux is an exception and has a set time of 1 second Adjustment type SEE
DIFFERENTIAL AND SETPOINT OFFSET
ADJUSTMENT
0 = standard adjustment; 1 = adjustment according to difference between Pb1-Pb2 and set point; 2 = set point adjustment calculated as offset from probe Pb2 Setting value on basis of which temperature alarms will be signalled SEE ALARM DIAGRAM HIGH AND LOW TEMP.: 0 = Pb1-Pb2; 1 = Pb1; 2 = Pb2; 3 = Pb1 e Pb2. Window filter. -2=very fast; -1=fast; 0=normal; 1=slow; 2=very slow button/aux input/door switch light active when instrument is off (but powered) Stand-by operating mode.. 0= only display switched off; 1= display on and controllers locked; 2= display off and controllers locked;
Output delay from power-on. Attention! If = 0 is not active; if ≠ 0 the output will not be activated before this time has expired
DEFAULT*
Abs
2 0
0
0
nc/no
0
0
n
0
0
n
0
0
2
-50 140
-50 140
°C
1
PtC/ntC*
0
5
0
1
0 y
2
0
RANGE
Abs/reL
1.0…50.0 0…10
0…10
0…250
nc/no
0…14
0…14
n/y
0...250
0...250
n/y
-30.0...30.0
-30.0...30.0
0/1/2
-67.0…HdL LdL…302 LdL…HLS LLS…HdL
°C/°F
0/1/2
PtC/ntC
0/1/2
0...15
0/1/2
0/1/2/3
-2/+1/0/1/2 n/y
0/1/2
0...250
VALUE**
U.M.
flag
°C/°F hours
hours
min
flag
num
num
flag
num
num
flag
°C/°F
°C/°F
num
°C/°F °C/°F °C/°F °C/°F
flag
num
flag
num
sec
°C/°F
num
num
flag
num
min
LEVEL***
1
2
1
1
1
2
1
1
1
1
2
1
1
1
2
2 2
1 1 1
2
1 1
2
1
1
2 2
2
1
***NOTE: At level 1 the folders will only display all the level 1 parameters. At level 2 the folders will only display all the level 2 parameters.
AL
Add
diS
CnF
IC 915 LX 9/10
PAR.
H11
H13
H14 H21 (!)
H22 (!)
H31 (!)
H32 (!)
H33 (!)
H42 rEL tAb
UL
dL
Fr
N.B.: if “Fr” parameter (copy card formatting) is used, the data entered in the card will be permanently lost. This operation cannot be undone. After the operation with the Copy Card the controller must be switched off and then switched back on
(1) Check the NTC/PTC default probe type installed (see label) (2) Refers exclusively to high and low temperature alarms * DEFAULT column: for parameters HC1, HS1, LS1, DF1, H00 the default value depends on the model. ** VALUE column: to be compiled manually with any custom settings (if different from default value). *** LEVEL column: indicates the visibility level of parameters accessed using a PASSWORD (see relevant para­graph) **** PA2 is visible (or will be requested, if specified) at level 1 in the CnF folder
and can be set (modified) at
level 2 in the diS folder
(!) WARNING!
• If one or more parameters marked with (!) are modified, the controller must be switched off after the modifica­tion and then switched back on
NOTE: We strongly recommend that you switch the instrument off and on again each time parameter configuration is changed in order to prevent malfunctioning of the configuration and/or ongoing timings.
DESCRIPTION
Configuration of digital inputs 0 = disabled; 1 = SOFT START; 2 = Set point Offset; 3 = outputs shut down; 4 = periodic cycle; 5 = auxiliary output; 6 = stand-by 7 = maintenance request 8 = external alarm 9 = external alarm to lock controllers Polarity and priority Digital Input no= normally open/ nc= normally closed / noP= normally open with polarity / ncP= normally closed with polarity
Enabling delay Digital Input Configurability digital output 1 (OUT1) 0 = disabled; 1 = on-off 2 = not used; 3 = alarm; 4 = cyclic 5 = aux/light 6 = stand-by Configurability digital output 2. (OUT2) Same as H21. UP button configurability. 0 = disabled; 1 = SOFT START; 2 = Set point Offset; 3 = outputs shut down; 4 = periodic cycle; 5 = auxiliary output (aux); 6 = stand-by; 7 = maintenance request DOWN button configurability. Same as H31. ESC button configurability. Same as H31. Presence of probe 2. n= not present; y= present. Device version. Read only parameter. Reserved. Read only parameter.
COPY CARD (folder with “Fpr” label)
UpLoad: transfer of programming parameters from instrument to Copy Card. downLoad: transfer of programming parameters from Copy Card to instrument. Format. Cancels all data entered in the copy card.
DEFAULT*
0
no
0 1
1
0
0
0
y
/
/
/ / /
RANGE
0…9
no/nc/noP/ncP
0…250
0…6
0…6
0…7
0…7
0…7
n/y
/
/
/ / /
VALUE* LEVEL***
2
2
2 2
2
2
2
2
2
1 1
1 1 1
U.M.
num
num
min
num
num
num
num
num
flag
/ /
/ / /
FUNCTIONS (folder with “FnC” label)The FnC folder (last folder visible from the Programming Menu) contains several functions that are acti­vated using the “set” button SEE FUNCTIONS paragraph
label PA2 In the CnF folder you can access all level 2 parameters from label PA2 by pressing the “set” button SEE paragraph 2) Displaying level 2 parameters
(°) The mathematical conversion for temperature is °F=(9/5)* °C+32. For example: 32°F=0°C; 50°F=10°C. dro parameter: when changing from °C to °F or vice versa the mathematical conversion is NOT performed and the values are NOT modified.
All the temperature values set will therefore need reviewing. e.g. with a set point set at 10°C, the set point will become 10°F and not 50°F when changing the value to °F (according to conversion table)
***NOTE: At level 1 the folders will only display all the level 1 parameters. At level 2 the folders will only display all the level 2 parameters.
Cof
Off
On
OUT
Con Con
Periodic Cycle Diagram
CnF
Fpr
IC 915 LX 10/10
Wiring Diagram
TERMINALS (12V and 230V versions)
1 - 2 N.O. controller relay 1 (OUT1) 1 - 3 N.C. controller relay 1 (OUT1) 4 - 5 N.O. controller relay 2 (OUT2) 6 - 7 Power supply 1.5 VA max. (12V version)
Power supply 3 VA max. (230V version) 8 - 10 Probe input 1 (control*) Pb1 8 - 9 Probe input 2 (control**) Pb2 8 - 11 Digital Input (D.I.) A TTL input for Copy Card and connection to
TelevisSystem
NOTE:
* used for differential adjustment ** used for offset and set point differential adjustment
• Default load settings
• for relay capacity, see instrument label. The diagram only shows 12 and 230V power supplies and 8(3)A 250V capacity relays
IC 915 LX - 12 V
A
6 7
1 2 3 4 5
D.I.
OUT1 OUT2
10
8 9
11
Supply
Pb2
Pb1
IC 915 LX - 230 V
A
6 7
1 2 3 4 5
D.I.
OUT1 OUT2
10
8 9
11
Supply
Pb2
Pb1
Eliwell & Controlli s.r.l.
Via dell'Industria, 15 Zona Industriale Paludi 32010 Pieve d'Alpago (BL) ITALY Telephone +39 0437 986111 Facsimile +39 0437 989066 Internet http://www.eliwell.it
Technical Customer Support:
Email: techsuppeliwell@invensys.com Telephone +39 0437 986300
Climate Controls Europe An Invensys Company
12/2004 eng cod. 9IS23071
CONDITIONS OF USE
PERMITTED USE
For safety reasons the instrument must be installed and used in accordance with the instructions sup­plied. Users must not be able to access parts with danger­ous voltage levels under normal operating conditions. The device must be suitably protected from water and dust according to the specific application and only be accessible using special tools (except for the front keypad). The device is ideally suited for household use and/or similar use in the refrigeration sector and has been tested with regard to safety in accordance with the European harmonized reference standards. It is classi­fied as follows:
• as an automatic electronic control device to be independently mounted as regards its construction;
• as a 1 B type operated control device as regards its automatic operating features;
• as a Class A device as regards the category and structure of the software.
UNPERMITTED USE
The use of the unit for applications other than those described above is forbidden. It should be noted that the relay contacts supplied with the device are functional and therefore exposed to potential faults. Any protection devices required to comply with product requirements or dictated by common sense due to obvious safety reasons should be installed externally.
RESPONSIBILITY AND RESIDUAL RISKS Eliwell & Controlli s.r.l. shall not be liable for any dam-
ages deriving from:
- installation/use other than that prescribed and, in particular, which does not comply with the safety stan­dards specified in the regulations and/or those given herein;
- use on equipment that does not guarantee adequate protection against electric shock, water or dust when assembled.
- use on equipment that allows dangerous parts to be accessed without the use of tools;
- tampering with and/or alteration of the product;
- use on equipment that does not comply with the standards and regulations in force.
DISCLAIMER This document is the exclusive property of Eliwell & Controlli s.r.l. and cannot be reproduced and circu­lated unless expressly authorized by Eliwell & Controlli s.r.l.. Although Eliwell & Controlli s.r.l. has taken all possi­ble measures to guarantee the accuracy of this docu­ment, it declines any responsibility for any damage arising out of its use. The same applies to any person or company involved in preparing and writing this manual. Eliwell & Controlli s.r.l. reserves the right to make any changes or improvements without prior notice and at any time.
CONDITIONS OF USE Permitted Use For safety reasons the instrument must be installed and used in accordance with the instructions supplied. Users must not be able to access parts with dangerous voltage levels under normal operating conditions. The device must be suitably protected from water and dust according to the specific application and only be accessible using special tools (except for the front key­pad). The device is ideally suited for household use and/or sim­ilar use in the refrigeration sector and has been tested with regard to safety in accordance with the European harmonized reference standards. It is classified as follows:
• as an automatic electronic control device to be inde­pendently mounted as regards its construction;
• as a 1 B type operated control device as regards its automatic operating features;
• as a Class A device as regards the category and struc­ture of the software. Unpermitted use The use of the unit for applications other than those described is forbidden. It should be noted that the relay contacts supplied with the device are functional and therefore exposed to potential faults. Any protection devices required to comply with product requirements or dictated by common sense due to obvi­ous safety reasons should be installed externally.
Loading...