Eliwell IC 912, IC 912p, IC 912r, IC 912v-i User Manual

USER INTERFACE
The user has a display and four keys for controlling status and programming of the instrument.
KEYS AND MENUS
UP key Scrolls through the menu
items Increases the values
DOWN key Scrolls through the menu items
Decreases the values
fnc key ESC function (exit)
set key Accesses the setpoint
Accesses the menus Confirms the commands
At start-up the instrument performs a Lamp Test; for few seconds the display and the leds blink, in order to verify their integrity and correct operation. The instru­ment has two main menus: the “Machine Status” and “Programming” menu.
ACCESSING AND USING MENUS
Resources are arranged in a menu, which can be accessed by pressing and quickly releasing the “set” key (“Machine Status” menu) or by holding down the “set” key for more than 5 seconds (“Programming” menu). To access the contents of each folder, indi­cated by the relevant label, just press the “set” key once. You can now scroll through the contents of each folder, modify it or use its func­tions. If you do not use the keyboard for over 15 seconds (time-out) or if you press the “fnc” key once, the last value shown on the display is confirmed and you return to the previous screen mask.
MACHINE STATUS MENU
To access the “Machine Status” menu Press and quickly release the “set” key. The label “SP1” appears.
By using the “UP” and “DOWN” keys you can scroll through the other folders in the menu:
-SP1: Setpoint 1 setting folder.
Setpoint Setting
Access the “Machine Status” menu by pressing and quickly releasing the “set” key. The label of the “SP1” folder appears. To display the Setpoint 1 value press the “set” key again. The value appears on the display. To change the Setpoint 1 value, use the “UP” and “DOWN” keys within 15 sec­onds. If the parameter is LOC = y the Setpoint cannot be changed.
PROGRAMMING MENU
To enter the “Programming” menu, press the “set” key for more than 5 seconds. If specified, the access PASSWORD will be requested, (parameter “PA1”), and the label of the first folder will follow. To scroll through the other folders, use the “UP” and “DOWN” keys; To enter the folder, press “set”. The label of the first visible parameter appears. To scroll through the other parameters, use the “UP” and “DOWN” keys; to change the parameter, press and release “set”, then set the desired value using the “UP” and “DOWN” keys, and confirm with the “set” key to move to the next parameter. PLEASE NOTE: It is strongly recommended to switch off and switch on again the con­troller anytime parameters have been changed to prevent malfunctioning on configuration and/or ongoing timings.
PASSWORD
The password “PA1” allows access to level 1 parameters. In the standard configura­tion passwords are not present. To enable them and assign them the desired value, access the “Programming” menu, within the folder with the “diS” label. If passwords are enabled, you will see it at the entrance of the “Program­ming” menu.
COPY CARD
The Copy Card is an accessory connected to the TTL serial port which allows pro­gramming quickly the instrument parame­ters (upload and download parameter’s map). The operation is performed as fol­lows:
Format
This command allows copy card formatting, an operation necessary in case of first use or to copy maps with different models. Warning: if the copy card has been pro­grammed, using the “Fr” the data entered are erased. This operation cannot be can­celled.
Upload
This operation loads the programming parameters from the instrument.
Download
This operation downloads to the instru­ment the programming parameters. The operations are performed accessing the folder identified by the “FPr” label and selecting, according to the case, “UL”, “dL” or “Fr” commands; the operation is con­firmed by pressing the “set” key. If the operation is successful an “y” is displayed, on the contrary, if it fails a “n” will be dis­played.
Download “from reset (instrumennt OFF”
Connect the coy card with the instrument OFF (not under voltage). When the instrument is switched on the programming parameters will be down­loaded into the instrument (this operation takes about 8 secods); after the lamp-test the diplay will show for about 5 seconds:
• label dLY if copy operation successful
• label DLn if not
PLEASE NOTE:
• after the download operation the instru­ment will immediately work with the new parameters map setting
KEYBOARD LOCKING
The instrument includes a facility for dis­abling the keyboard, by programming the “LOC” parameter (see folder with “diS” label). If the keyboard is locked, you can still access the programming menu by pressing the “set” key. The Setpoint can also be viewed.
IC 912/P/R/V-I
electronic controller with single output
fnc
set
LED
Position Related Function Status
OUT1 relay 1 (OUT1) ON when the regulator is started up; blinking in case of delay,
protection or blocked enabling
Alarm ON when the alarm is enabled;
DIAGNOSTICS
The alarm condition is always signalled by the led of the alarm icon The alarm signal (referred to analogue input) is shown as E1 on the instrument display, by a faulty regulator probe for model 4…20mA, or by reading a value out of the bound limits, for all models . When the analogue input detects an error condition:
• the code E1 is displayed
• the regulator is activated as indicated by the "On1" and "OF1" parameters if pro­grammed for the duty cycle or:
INSTALLATION
The instrument is designed for panel mounting. Make a hole of 29x71 mm, insert the instrument and fix it using the brackets provided. Do not mount the instrument in humid and/or dirty places; it is suitable for use in ordinary polluted places. Ventilate the place in proximity to the instrument colling slits.
ELECTRICAL WIRING
Attention! Never work on electrical con­nections when the machine is switched on. The instrument is equipped with screw ter­minal boards for connection of electrical cables with a diameter of 2.5 mm
2
(one conductor only per terminal for power connections). For the capacity of the terminals, see the label on the instrument. The relay contacts are voltage free. Do not exceed the maximum current allowed; in case of higher loads, use an appropriate contactor. Make sure the power supply voltage complies with the one required by the instrument. In 12V versions the power supply must be provided by a security transformer with the protection of a delayed 250 mA fuse. Probes have no connection polarity and can be extended using a regular bipolar cable (note that the extension of the probes affects the EMC electromagnetic compatibility of the instrument: pay extreme attention to wiring). Probe cables, power supply cables and the TTL serial cables should be distant from power cables.
CONDITIONS OF USE
PERMITTED USE
For safety reasons the instrument must be installed and used according to the instruction provided and in particular, under normal conditions, parts bearing dangerous voltage levels must not be accessible. The device must be adequately protected from water and dust as per the application and must also only be accessible via the use of tools (with the exception of the frontlet). The device is ideally suited for use on household appliances and/or similar refrig­eration equipment and has been tested with regard to the aspects concerning European reference standards on safety. It is classified as follows:
• according to its manufacture: as an auto­matic electronic control device to be incorporated by independent mounting;
• according to its automatic operating fea­tures: as a 1 B-type operated control type;
• as a Class A device in relation to the cat­egory and structure of the software
UNPERMITTED USE
Any other use other than that permitted is de facto prohibited. It should be noted that the relay contacts provided are of a practical type and therefore subject to fault. Any protection devices required by product standards or dictated by common sense due to obvious safety reasons should be applied externally.
LIABILITY AND RESIDUAL RISKS
Invensys Controls Italy S.r.L. shall not be liable for any damages deriving from:
- installation/use other than that pre­scribed and, in particular, that which does not comply with safety standards anticipat­ed by regulations and/or those given here­in;
- use on boards which do not guarantee adequate protection against electric shock, water or dust under the conditions of assembly applied;
- use on boards which allow access to dan­gerous parts without the use of tools;
- tampering with and/or alteration of the products;
DISCLAIMER
This manual and its contents remain the sole property of Invensys Controls Italy s.r.l., and shall not be reproduced or dis­tributed without authorization. Although great care has been exercised in the preparation of this document, Invensys Controls Italy s.r.l., its employees or its vendors, cannot accept any liability what­soever connected with its use. Invensys Controls Italy s.r.l. reserves the right to make any changes or improvements with­out prior notice.
TECHNICAL DATA
Frontal panel protection: IP65. Casing: plastic body in resin type PC+ABS UL94 V-0, inspection window in polycarbonate, buttons in thermoplastic resin. Dimensions: frontal panel 74x32 mm, depth 59 mm (without wirings). Installation: on panel, with drilling tem­plate 71x29 mm (+0.2/–0.1 mm). Use temperature: –5…55 °C. Storage temperature.: –30…85 °C. Use environment humidity: 10…90 % RH (not condensing). Storage environment humidity: 10…90% RH (not condensing). Viewing range:
-99…100 (ndt = n), -99.9…100.0 (ndt = y),
-999…1000 (ndt = int) without decimal point (selectable through parameter on 3 digit & 1/2 + mark display. Serial: TTL for connection to Copy Card. Analogue input (see table): one V-I (0-1V, 0-5V, 0-10V; 0…20mA, 4…20mA) (program­mable by parameter). Digital output: 1 SPDT output on 8(3)A 1/2 hp configurable. (for relay capabilities see label on the instrument) Measuring range: from –999 to 1000. Accuracy: 0.5% better than end scale + 1 digit. Resolution: 1 or 0,1 digit depending on parameter’s settings Consumption:
• model 230V: 3 VA max.
• model 12V: 1,5 VA max. Power supply: 12 Va/c ±10% or 230Va
±10% 50/60 Hz.
Warning: check the power supply specified on the instrument label; for relay and power supply capacities, contact the Sales Office).
IC 912/P/R/V-I 2/4
On1
0 0 >0 >0
OF1
0 >0 0 >0
regulator output
OFF OFF ON D.C.
Model
IC 912/P IC 912/R IC 912/V-I PLEASE NOTE: For EWPA and EWHS probe connec­tions please refer to relative instruction sheets