USER INTERFACE
How to modify the SetPoint
• Press and release the SET key. The upper display will show SEt, the lower display will indicate the
current SetPoint value
• Press and release the SET key once more. The upper display will show SEt blinking
• Use the UP & DOWN keys to adjust the Setpoint value
• Press the ESC key several times (or keep it pressed) to return to the normal display
How to read the probe value
• Press and release the SET key. The upper display will show SEt, the lower display will indicate the
current SetPoint value
• Press and release the DOWN key. If the RTC clock is present, the time will be shown in the lower display
• Press and release the DOWN key once more. The upper display will show Pb1, the lower display will
indicate the value read by the room probe
• Press and release the DOWN key once more to read the value of probe Pb2 and Pb3 if configured
• Press the ESC key to return to the normal display.
How to modify the User Parameters
The ‘User’ parameters are the most useful ones. This document describes them in the Parameter
Table section.
1) Press and hold the SET key for 3 seconds until the display shows USr
2) Press and release the SET key again. The upper display will show the first parameter, the lower display
will indicate the current parameter value
3) Using the UP & DOWN keys, find the parameter that you wish to modify
4) Press and release the SET key again. The upper display will show the name of the blinking parameter
5) Use the UP & DOWN keys to adjust the parameter value.
6) Press and release SET to save the parameter value
7) Return to step 3) or press ESC several times to return to the normal display
USER PARAMETERS TABLE
This section describes the most commonly used parameters, which are always visible (the access password PA1 is not enabled by default).
For a description of all other parameters, see the user manual.
NOTE: the user parameters are NOT divided into sub-folders and are always visible. The same parameters are also visible in the respective fold-
ers ‘Compressor’, ‘Fans’, etc. (indicated also here to make the groupings clearer) in the password-protected Installer parameters menu.
PAR. DESCRIPTION M.U. RANGE DEFAULT
SEt Temperature control SEtpoint °C/°F -58.0...302 0.0
COMPRESSOR (CPr)
diF
Activation differential
N.B.: diF cannot be equal to 0.
°C/°F 0 ... 30.0 2.0
HSE
Maximum value that can be assigned to the setpoint.
NOTE: The two setpoints are interdependent: HSE cannot be less than LSE and vice-versa.
°C/°F LSE ... HdL 50.0
LSE
Minimum value that can be assigned to the setpoint.
NOTE: The two setpoints are interdependent: LSE cannot be greater than HSE and vice
versa.
°C/°F LdL ... HSE -50.0
OSP
Temperature value to be added algebraically to the Setpoint if reduced set enabled (Economy function).
Enabling can take place via key, function or digital input configured specifically for this purpose.
°C/°F
-30.0 ...
30.0
0.0
Cit
Minimum activation time of compressor before possible deactivation.
If Cit = 0 not active.
min 0 ... 255 0
CAt
Maximum activation time of compressor before possible deactivation.
If CAt = 0 not active.
min 0 ... 255 0
Ont
Controller switch-on time in the event of faulty probe.
- if Ont = 1 and OFt = 0, the compressor stays on permanently (ON),
- if Ont > 0 and OFt > 0, it operates in Duty Cycle mode.
min 0 ... 255 10
OFt
Controller switch-off time in the event of faulty probe.
- if OFt = 1 and Ont = 0, the compressor stays off permanently (OFF),
- if Ont > 0 and OFt > 0, it operates in Duty Cycle mode
min 0 ... 255 10