Eliwell EM300, EM300LX User Manual

USER INTERFACE
The user has a display and four buttons for controlling instrument status and pro­gramming.
BUTTONS AND MENUS ACCESSING
AND USING MENUS
The resources are arranged in a menu that can be accessed by pressing and quickly releasing the “set” button (Machine Status menu) or holding down the “set” button for more than 5 seconds (Programming menu). To access the contents of each folder indicated by the relevant label, just press the “set” button once. You can now scroll through the contents of each folder, modify it or use its functions. If you do not use the keyboard for over 15 seconds (time-out) or if you press the “fnc” button once, the last value shown on the display is confirmed and you return to the previ­ous screen mask.
MACHINE STATUS MENU (See Machine Status Menu Diagram)
To access the Machine Status menu, press the “set” button and quickly release it (The “SP1” label appears.
V/I
V/I
MODELS
MODELS
ONL
ONLY)Y)
(If alarms are active, with the exception of faulty probes/probe errors, the “AL” label appears). By using the “UP” and “DOWN” buttons you can scroll through the other folders in the menu: the folders are indi­cated below in the order they appear:
-AL: alarm folder
LXLXMODELS
MODELS
ONL
ONLYY
NOTE: The AL folder appears if high or low temperature alarms are present.
Alarm (IF PRESENT)
•ON for active alarm;
•blinking for silenced
alarm that is still present
LLEEDDSS AANNDD KKEEYYPPAADD
decimal point: associated with displaying decimal point
•ON if enabled-decimal point present (see ndt parameter);
•OFF if disabled-decimal
point NOT present (see
ndt parameter);
for NTC/PTC
or Pt100-TC
input
for V/I input
(current-
voltage std
signals)
bar for
V/I input
(pressure)
%RH for
V/I input
(humidity)
EM300(LX)
electronic digital indicator
code 9IS43049
rel. 6/06
GB
UP Button Scrolls through the menu items
Increases the values
DOWN button Scrolls through the menu items
Decreases the values
fnc button ESC function (quit)
Set point button 1-Accesses Machine Status Menu
(ACTIVE ALARMS, PROBE READ­ING) and related labels/values; 1-Accesses Programming Menu (PARAMETERS, COPY C ARD (LX models)) and related labels/val­ues; 3-Confirms commands
fnc
set
ALARM PRESENT?
If an alarm condition exists when the “Machine Status” menu is accessed, the “AL” folder label appears with the alarm codes. (see section on “Diagnostics”).
if alarm(s)
present
AL
set
alarms
set
scroll alarms
press and release
(single press)
MACHINE STATUS MENU DIAGRAM
HOW TO LOCK THE KEYBOARD
Keyboard operating can be locked by pro­gramming the “Loc” parameter (see folder with “diS” table). If the keyboard is locked you can only access the Programming MENU (see) Functions CANNOT be activat­ed with buttons (to silence alarms, for example).
TELEVIS SYSTEM (LX MODELS ONLY)
The Televis remote control systems can be connected using the TTL serial port. The TTL- RS 485 interface module must be used:
• 130 or 150 BUS ADAPTER.
• 350 BUS ADAPTER for EM300(LX) with V/I. Pt100/TC input.
To configure the instrument to do this, you need to access the folder with the “Add” label and use the “dEA” and “FAA” para­meters.
ONLY MODELS LX
AL
Add
dIS
CnF
set
level 1 par
level 1 par
level 1 par
level 1 par
set
set
set
set
PA1≠0
set
set PA1 value
Fpr
level 1 par
set
level 1
change
par value
scroll 
parameters
press for 5 sec
ONLY MODELS LX
ONLY MODELS LX
rE1
input VI
PROGRAMMING MENU
DIAGRAM
230V
PC with
Televis package
N
L
only use 350 Bus Adapter for model with V/I, Pt100/TC input
EM300(LX) 2/6
USING COPY CARD (LX MODELS ONLY)
The Copy Card is an accessory connected to the TTL serial port used for quick programming of the unit parameters (upload and download parameter map to one or more units of the same type). Operations are described below:
Fr-Format
This command is used to format the copy card. This is necessary if
•it is used for the first time,
•it is used with models that are incompatible,
•after use with a specific model, another model must be connected. Warning: when the copy card has been programmed using the “Fr” parameter all the data entered is can­celled. This operation cannot be undone.
UL-Upload
This operation unloads the programming para­meters from the instrument.
dL-Download
This operation downloads the programming parameters to the instrument.
NOTE:
• UPLOAD: instrument —> Copy Card
• DOWNLOAD: Copy Card —> instrument.
The operations are performed by accessing the folder identified by the “FPr” label and selecting the “UL”, “dL” or “Fr” commands. The operation is confirmed by pressing the “set” button. If the
operation is successful, a “y” is displayed where­as if it is unsuccessful an “n” will be displayed.
Download “from reset”
Connect the copy card with the instrument OFF. When the instrument is switched on the pro­gramming parameters will be downloaded into the copy card; when the lamp test has been completed, the following appear on the display for about 5 seconds:
• label dLY if copy operation is successful
• label DLn if operation fails PLEASE NOTE:
• after downloading the instrument will work with the parameter map settings that have just been downloaded.
PROGRAMMING MENU (See Programming Menu Diagram)
1) Displaying level 1 parameters
To access the Programming menu, hold the “set” button for more than 5 seconds.
Level 1 parameters can be protected by a PASSWORD* (defined by parameter DIS/PA1) If the PASSWORD is enabled, the label “PA1” will appear when you access the Programming Menu; press the “set” button and the value “0” will appear; enter the password using the “UP”/”DOWN” but­tons and press the “set” button again. This
allows you to access the level 1 parame­ters. Use the “UP” and “DOWN” buttons to scroll through the other folders; the
folders will only display level 1 parame­ters. PLEASE NOTE: It is strongly recommended
that the unit is switched off and on again each time parameter configuration is changed in order to prevent malfunction­ing of the configuration and/or ongoing timings (compulsory for selection of
probe type and count parameters).
*PASSWORD
The “PA1” password allows level 1 and level 2 parameters to be accessed. This password is not present in the standard configuration. To enable it (value 0) and assign it the desired value, access the Programming menu in the “diS” folder. If the password is enabled, it will be requested when entering the “Programming” menu.
The alarm condition is always signalled by a
buzzer (if present) and the alarm icon LED
(IF PRESENT)
The alarm signal from the
• control probe that measures values outside the nominal reading range
• control probe faulty/shorted/open probe for 4…20 mA* model appears directly on the instru­ment display as E1. Note: to prevent false alarms, the error condition must persist for more than 10 seconds. An error condition in probe 1 (regulation) leads to:
• E1 code appearing on display
PLEASE NOTE: In case of wrong connection of the 3rd wire (Pt100 sensor) in “AL” folder it will appear the label “Pt3”. For few seconds the display will shows a uncor­rect temperature.
MAXIMUM AND MINIMUM TEMPERATURE ALARM
If an alarm condition occurs and alarm exclu­sion times are not in progress (see alarm exclu­sion parameters), the fixed alarm icon comes on.
DIAGNOSTICS
DISPLAY
E1
*faulty/shorted/open probe for 4…20 mA model; the other probes, if shorted, will measure the 0V or 0mA value)
FAULT
Probe 1 (control) faulty*
Table of faulty probes
DISPLAY
AH1
AL1
Press any button to silence the alarm. The LED will start to blink.
ALARM
High temperature alarm (referring to thermostat control probe or probe 1) Low temperature alarm (referring to thermostat control probe or probe 1)
Alarm table
Alarms are considered as absolute values This alarm condition can be viewed in the “AL” folder with labels “AH1-AL1”.
The maximum temperature alarm occurs when the probe temperature is:
•higher than or equal to HAL/HA1
The minimum temperature alarm occurs when the probe temperature is lower than or equal to LAL/LA1
The maximum temperature alarm back swing occurs when the probe temperature is:
• higher than or equal to HAL/HA1 - AFd
Minimum temperature alarm back swing occurs when the probe temperature is:
•higher than or equal to LAL/LA1 + AFd
LAL/LA1
AFd
HAL/HA1
AFd
Max/Min. Alarm Diagram (minimum and maximum temperature)
UPLOAD
DOWNLOAD
Loading...
+ 4 hidden pages