DISCONNECT SWITCH & FUSE SELECTION
CHART FOR STANDARD PACKAGES ONLY.
240VAC 480VAC
NOTES:
The above chart should be used for our basic model phase converters only. This information will help you determine the
recommended size of the Main breaker / Disconnect, Phase Converter Disconnect for on/off operation, and the appropriate fuse size to
supply adequate protection for the phase converter.
Sizes above are based upon the converters total running potential, not actual running load. This table does not replace or supersede
any requirements of local, state, or national electric codes. Use only dual element time delay fuses to protect the phase converter. Do
not connect any control loads to T3. No load output voltage on T2 to T3 will exceed lines L1 and L2 by 12-15%. Voltages will be
reduced when load is applied. National Electric Code (NEC) requires single phase cable and branch circuit to be rated for 250% of
three phase load current. Consult factory for additional information.
.