Elite Industrial Mfg. DISCONNECT SWITCH & FUSE FOR CONVERTERS EQUIPPED WITH “SA” PACKAGES Selection Guide

MODEL
MAX
START HP
TOTAL
RUN HP
CONVERTER
DISCONNECT
FUSE
CONVERTER
DISCONNECT
FUSE
M,P010
5
10
60
60
30
30
M,P015
7.5
15
100
75
60
40
M,P020
10
20
100
100
60
60
M,P030
15
30
200
150
100
75
M,P040
20
40
200
200
100
100
M,P050
25
50
400
250
200
125
M,P060
30
60
NA
NA
200
150
M,P075
40
70
NA
NA
200
175
M,P100
50
90
NA
NA
400
250
M,P125
60
100
NA
NA
400
300
ELITE INDUSTRIAL MFG. LLC
TOLL FREE: 1-877-706-3830
FOR CONVERTERS EQUIPPED WITH “SA” PACKAGES
240VAC 480VAC
NOTES:
The above chart should be used for all converters equipped with the “SA” package. This information will help you determine the service disconnect and the appropriate fuse size to supply adequate protection for the phase converter.
Sizes above are based upon the converters total running potential, not actual running load. This table does not replace or supersede any requirements of local, state, or national electric codes. Use only dual element time delay fuses to protect the phase converter. Do not connect any control loads to T3. No load output voltage on T2 to T3 will exceed lines L1 and L2 by 12-15%. Voltages will be reduced when load is applied. National Electric Code (NEC) requires single phase cable and branch circuit to be rated for 250% of three phase load current. Consult factory for additional information.