eLine Technology SOLAR User Manual

Renogy Charge Controller Model No. PWM10CC
1
30 AMP PWM CHARGE CONTROLLER MANUAL
Technical Information (12/24V Auto Mode)
24V
Rated Solar Input
Related Load
25% Current Overload
1 minute
Load Disconnect
22.2V
Load Reconnect
25.2V
Equalization Voltage (30 minutes)
29.2V
Boost Voltage (30 minutes)
28.8V
Float Voltage
27.2V
Temperature Compensation (mV/C)
-60mV/C
Terminals
For wire sizes up to 6mm2
Temperature
-35°C to + 55°C
Battery type
Lead Acid batteries, including AGM and Flooded
Table 1. Charge controller technical information
Quick Start Instructions
This section provides a brief overview of how to begin using your solar charge controller. It is recommended that each user review the entire manual to ensure the best possible performance as well as maximize years of worry-free service. It is highly recommended that the connections be made in the following steps provided:
1. Mount the charge controller onto a clean, vertical flat surface. It is very important to allow enough space both above and below the charge controller to ensure maximum air flow.
2. After proper mounting is established, connect the battery to the charge controller terminals. Be careful not to switch the polarities of the battery and do not allow the bare wires to touch the metal casing of the charge controller.
3. Connect the solar (PV array) with the MC4 adapter kit cables. The green LED indicator will light up if there is enough sunlight.
4. Optional: Connect the load if you have a 12VDC application. If the red LED indicator light turns on, the battery capacity is low and needs to be charged before completing the system installation.
eLineTechnology.com
Charge Controller Specifications
30A 30A 30A 30A
11.1V
Renogy Charge Controller Model No. PWM10CC
2
5. After all connections are made, power ON the charge controller by pressing the SET button.
6. To test the system for proper connections, press the SET button on the charge controller until you see the number 17 (see description below).
7. Make sure the solar module(s) voltage and current do not exceed the ratings of the charge controller.
Lighting Control Options
1. Press the SET button for about 5 seconds and select the desired lighting control option. The LED will come on, which will indicate that you have selected an option.
2. The controller requires about 10 minutes of continuous transition values before it starts working properly. These constraints avoid false transitions due to lighting or shading.
3. A brief description of the work mode:
Number
LCD Display
Description of Work Mode
0
Dusk-to-Dawn, light id on all night
1
Light turns on 1 hour after sundown
2
Light turns on 2 hour after sundown
3
Light turns on 3 hour after sundown
4
Light turns on 4 hour after sundown
5
Light turns on 5 hour after sundown
6
Light turns on 6 hour after sundown
7
Light turns on 7 hour after sundown
8
Light turns on 8 hour after sundown
9
Light turns on 9 hour after sundown
10
Light turns on 10 hour after sundown
11
Light turns on 11 hour after sundown
12
Light turns on 12 hour after sundown
13
Light turns on 13 hour after sundown
14
Light turns on 14 hour after sundown
15
Light turns on 15 hour after sundown
16
Turn on/off light mode
17
Test mode; lights turns on after no sunlight detected or lights turn off after sunlight detected.
Table 2. Lighting control options
eLineTechnology.com
Loading...
+ 2 hidden pages