Elektro-Automatik Rittal TS8 42U Installation Manual

Installation Guide
Cabinet
ELR Rack 42U: 33 130 326
EN
Technical specications
Type: Rittal TS8 42U Dim (WxHxD): 600mm x approx. 2000mm x 1000mm Model: front and rear doors, no wheels AC input connection: L1+L2+L3+N+PE AC input voltage: 230 V AC, +/-10%, 50/60 Hz AC input current: max. 330 A
Feature overview
• Prepared to be equipped with 8x ELR 9750-66
• Prepared to be equipped with 1x PSI 8000 2U
• Share bus wiring
• ENS 2 automatic isolation unit installed
Shipping & Scope of delivery
The cabinet is shipped in disassembled state. Before you start to assemble the cabinet, please verify all contents of the shipped parts to be intact and in correct amount.
For later assembly on location, following items are to be included:
1x precongured cabinet 42U with side panels and doors
8x ELR 9750-66 electronic load device 1x PSI 8000 2U power supply device 1x Share bus cable 7x CAT5 Ethernet cable 0.5 m for master-slave 1x Set of front mounting screws for the devices 2x DC copper bar 1x Set if DC copper bar mounting bolts/nuts/washers 1x Set of lifting eyes for cabinet transportation 4x Plastic DC covers (numbered 1-4)
Read before use
Attention!
Always connect sources with correct polarity! The electronic loads do not have protection against false polarity and can even be damaged in switched-off state.
The ENS2 unit, together with the contactors, switches the N conductor - do not use conductor N1 to connect the cabinet to AC supply!
When connecting DC sources to the ELR units which can withstand up to 750 V, never connect the PSI 8000 power supply unit in parallel!
Installation
Cabinet
The cabinet comes without wheels and can be moved to the installation location on the Euro palette it was delivered with or by using the included lift eyes (to be mounted on top) and a crane.
The AC input connection is done using screw terminals which are accessible from the rear side and mounted to the right side. Also see Figure 3 on page 6. The terminals to connect the AC supply for the cabinet to are labelled L1, L2, L3, N and PE.
AC supply specication:
• three-phase (120° phase angle)
• 230 V AC (L-N), max. 330 A (~ max. 110 A per phase)
• 50 / 60 Hz For additional safety, every unit has a circuit breaker, which
is accessible on the front of the cabinet and labelled with sticker to assign it to a certain unit.
Wiring to AC supply and external fusing has to be done according to general standards. We recommend to use NH fuses of 125 A rating or 160 A (max.) and wiring with cross section of 25 mm² per conductor.
Installation Guide 33130326
ELR units
The separately delivered ELR 9000 units are inserted to the cabinets and mounted with the front mounting screws. The arrangement is intended to be like shown in Figure 9 on page 9. With this, the master unit, which is labelled as “Master” is in the approximate vertical middle and easy to access. The AC supply connectors of the ELR units are
precongured and just need to be plugged.
Power supply unit
The separately delivered power supply unit is inserted to the cabinet into the 2U high position according to Figure 9 on page 9. The AC supply connector is precongured
and just needs to be plugged. There is no further wiring
installed in the cabinet for this unit.
Date: 14.01.2016
3
DC input copper bars
The DC input copper bars are tied inside the cabinet. It is recommended to install them only after all ELR units are correctly placed and mounted on the front.
The copper bars are intended to be mounted to the DC
input terminals of the ELR units, as shown in the gure to
the right. The M6 screw set (bolt, nut, washer) are included.
DC input connection to source
The connection to the DC source is recommended to be made as last step of installation. The lower end of the copper bars will have three drillings each for M8 screw con­nection of appropriate cables. M8 screw sets are included.
The DC cable cross section has be selected according to the maximum current the DC loads can take, in this case 8x 66 A = 528 A.
The traverse below the DC copper bars holder can be used as strain relief for the DC input cables.
Master-slave (MS)
The master-slave connection between the up to eight units of ELR 9000 (the power supply can not be included in the master-slave) can be installed by simply plugging the included CAT5 0.5 m cables into the MS sockets, as printed on the rear of the ELR units. Also see Figure 5 on page 7.
EN
Attention!
The master-slave bus is RS485. Do not connect Eth­ernet network here!
The MS must not be wired to have full functionality of the ELR units. It is only required to in case you want to have the units be one big 84 kW system.
Share bus
The Share bus connection, which is required for correct parallel operation of the ELR units, is recommended to be
installed. Use the included and precongured Share bus
cable (green plugs, red/blue wires) to connect all units. Also see Figure 5 on page 7.
DC cover
The plastic DC covers are intended to cover the DC copper bars and prevent touching the dangerous voltage there. They are mounted on several hexagon bolts. Due to the arrangement of ELR units 1 thru 8, from top to bottom, the covers can not be mounted to arbitrary position and are thus numbered 1-4. Mount them, as depicted in Figure 2 on page 5, from top (1) to bottom (4).
Operation
Handling of the electronic loads
See separate manual for ELR 9000 series.
Handling of the power supply
See separate manual for PSI 8000 2U series.
Handling of the ENS 2 unit
See separate manual for ENS 2.
© 2006, Elektro-Automatik GmbH & Co. KG
Master-slave (MS)
The cabinet is wired for MS operation by default. The MS wiring is done on the master-slave bus connectors
of all ELR units that shall be included in the MS. For the master it doesn‘t matter if there is only 1 slave or 7.
Master-slave handling, setup and operation is described the ELR 9000 series manual.
Irrtümer und Änderungen vorbehalten
4
Date: 14.01.2016
Installation Guide
33130326
Loading...
+ 8 hidden pages