Electro-Sensors, Inc. RatemeterfTachometer . TR400-C
Wiring:
AC Power Supply: Line TB1-1, Neutral TB1-2
The TR400-C Standard uses 115 Vac 6 VA at 60/50 Hz
with 230 Vac available as an option. External fusing must be
provided by the customer. The recommended fuse is 1/16
amp slow-blow.
Line
(1)
Neutral (L2)
NC
TB1
01
0'
03
04
05
06
=
=
TB2
01
0'
03
04
05
06
07
08
Maximum
Contact Ratings
SA 250 Vac
SA 30 Vdc
Pulse
Generator
Relay
Output 1
o Relay
Output 2
Common
+12V
Single Channel A
Relay Outputs:
Output 1- TB3 and Output 2- TB3 the TR400-C offers 2 Form
C Relays. These relays are rated 250 Vac 5 A, and 30 Vdc 5
A resistive load.
Programming the Relay Outputs:
Relay Output Functions:
Each relay output has a set point value (Variables 07 and 10).
This value is compared to the displayed value on the front
panel and any action required is performed on the outputs.
Underspeed: De-energizes the output when the displayed
value is below the set point value.
Relay Programming Variables:
--------
Output 1
Set Point Value Variable 07
Output 2
Variable 10
Output Value: Enter the value at which the set point will de-
energize. There is a 1 % hysteresis for the value at which the
output will re-energize (i.e. Underspeed Set Point at 100 rpm
output will reset at 101 'pm, if On Time has expired).
Variable 02-PPR: Enter the pulses per revolution of the
sensor on the monitored shaft. Note: Electro-Sensors Model
907 Sensor with a Model 255 Disc will provide 8 PPR.
Sensor Connections:
Sensor Switches in Bottom Stat
~D
l t BBBBBB
OFFON 123456
=
Sensor Input Configuration Switches:
Input Channel A TB2-7
Input Type NPN
Switches On 5
Switches Oft 4, 6
Terminal Description Sensor
906-907
----------------------------
Supply Red
A Signal Black
Common Clear
TB2-6
TB2-7
TB2-5
A Signal Input:
TB2-7 A Signal Input:
These inputs require a frequency input relative to speed.
Devices such as Hall-Effect Sensors, encoders or magnetic
pickups can all be used. Power for sensors is provided across
TB2-6 (+12 Vdc) and TB2-5 (common). The maximum power
draw available is 100 mA at an unregulated 12 Vdc. Wiring to
these inputs should be shielded cable with the shield tied to
TB2-5 only. Never use shielded æble wiih extra conductors.
Extra conductors act as antennas picking up electrical noise.
This is one of the most common reasons for electrical noise
on the frequency input signals. The default switch selection
settngs comply with Electro-Sensors Inc. sensors.
Diagnostics:
The relays may be tested by pressing the "." decimal place
button and holding it for 4 seconds. The relays will turn off as
long as the button is held. Releasing the button will reinitialize
the relays and include the start delay (Variable 6).
~,