Electronics Line EL-4703 Installation Instructions Manual

2-WAY WIRELESS SUPERVISED
PHOTOELECTRIC SMOKE DETECTOR
Model: EL-4703
Wireless Supervisor Photoelectric Smoke Detector
2
GENERAL DESCRIPTION
Electronics Line's smoke detector is single station, photoelectric smoke detector with a built-in supervised wireless transmitter. When sufficient smoke is detected, or the test feature is operated, the detector will sound its alarm horn and the transmitter will send an ALARM message. The Alarm output in the receiver will remain activated until the alarm condition clears. The smoke alarm base lock discourages unauthorized removal of the smoke alarm by requiring a screwdriver to remove the alarm from the base. The smoke alarm provides the following signals to the control panel:
Alarm Alarm restore Low battery Tamper Supervision
WARNINGS:
This smoke detector is designed for use in a single residential unit only, which means that it should be used inside a single family home or apartment. It is not meant to be used in lobbies, hallways, basements, or another apartment in multi-family buildings, unless there are already working detectors in each family unit. Smoke detectors, placed in common areas outside of the individual living unit, such as on porches or in hallways, may not provide early warning to residents. In multi-family buildings, each family living unit should set up its own detectors. This detector is not to be used in non-residential buildings. Warehouses, industrial or commercial buildings, and special purpose non-residential buildings require special fire detection and alarm systems. This detector alone is not a suitable substitute for complete fire detection systems for places where many people live or work, such as hotels or motels. The same is true of dormitories, hospitals; nursing homes or group homes of any kind, even if they were once single - family homes. Please refer NFPA 101, the Life Safety Code, NFPA71, 72A, 72B, 72C, 72D, and 72E for smoke detector requirements for fire protection in buildings not defined as “households”.
Wireless Supervisor Photoelectric Smoke Detector
3
EN
SELECTING A LOCATION
Smoke detectors should be installed in accordance with the NFPA Standard 74 (National Fire Protection Association, Batterymarch Park, Quincy, MA 02169). For complete coverage in residential units, smoke detectors should be installed in all rooms, halls, storage areas, basements, and attics in each family living unit. Minimum coverage is one detector on each floor and one in each sleeping area and attics in each family living unit. Minimum coverage is one detector on each floor and one in each sleeping area.
Install a smoke detector in the hallway
outside every separate bedroom area, as shown in Figure 1. Two detectors are required in homes with two bedroom areas, as shown in Figure 2.
Install a smoke detector on every floor
of a multi-floor home or apartment, as shown in Figure 3.
Install a minimum of two detectors in
any household.
Install a smoke detector inside every
bedroom.
Install smoke detectors at both ends of
a bedroom hallway if the hallway is more than 40 feet (12 meters) long.
Install a smoke detector inside every
room where one sleeps with the door partly or completely closed, since smoke could be blocked by the closed door and a hallway alarm may not wake up the sleeper if the door is closed.
Install basement detectors at the bottom
of the basement stairwell.
Install second-floor detectors at the top
of the first-to-second floor stairwell.
Be sure no door or other obstruction
blocks the path of smoke to the detector.
Install additional detectors in your living
room, dining room, family room, attic, utility and storage rooms.
Install smoke detectors as close to the
center of the ceiling as possible. If this is not practical, put the detector on the ceiling, no closer than 4 inches (10 cm) from any wall or corner, as shown in Figure 4.
Figure 1: Locations for placing smoke
detectors for single residence with only
one sleeping area
Figure 2: Locations for placing smoke
detectors for single-floor residence with
more than one sleeping area
Wireless Supervisor Photoelectric Smoke Detector
4
If ceiling mounting is not possible and
wall mounting is permitted by your local and state codes, put wall-mounted detectors between 4 and 6 inches (10 ~ 15 cm) from the ceiling, also see Figure
4.
If some of your rooms have sloped,
peaked, or gabled ceilings, try to mount detectors 3 feet (0.9 meter) measured horizontally from the highest point of the ceiling as shown in Figure 5.
CAUTION: (As required by the California State Fire Marshall)
Early warning fire detection is best achieved by the
installation of fire detection equipment in all rooms and areas of the household as follows: (1) A smoke detector installed in each separate sleeping area (in the vicinity, but outside of the bedrooms), and (2) Heat or smoke detectors in the living rooms, dining rooms, bedrooms, kitchens, hallways, attics, furnace rooms, closets, utility and, storage rooms, basements and attached garages.” For your information, NFPA Standard 74, Section 2-4 reads as follows: “2-4.1.1 Smoke detectors shall be installed outside of each separate sleeping area in the immediate vicinity of the bedrooms and on each additional story of the family living unit including basements and excluding crawl spaces and unfinished attics. The provisions of 2-4.1.1 represent the minimum number of detectors required by this standard. It is recommended that the householder consider the use of additional smoke detectors for increased protection for those areas separated by a door from the areas protected by the required smoke detectors under 2-4.1.1 above. The recommended additional areas are living room, dining room, bedroom(s), kitchen, attic (finished or unfinished), furnace rooms, utility room, basement, integral or attached garage, and hallways not included in 2-4.1.1 above. However, the use of additional detectors remains the option of the householder.” We recommend complete coverage and use of additional smoke detectors.
Figure 3: Location for placing smoke
detectors for a multi-floor residence
Figure 4: Recommended best and
acceptable locations to mount
smoke detectors
Figure 5: Recommended location to
mount smoke detectors in rooms with
sloped, gabled, or peaked ceiling
Loading...
+ 8 hidden pages