Electro EVOLUTION Installation & Operating Manual

Page 1
EVOLUTION Pool Heater
Installation & Operating Manual
Page 2
1
www.elecro.co.uk
ENGLISH
Important Notes!
To ensure your new heater will give years of trouble free service please
carefully read the following instructions. Incorrect installation will a ect your warranty.
Do not discard this manual, please retain for future reference.
Product Overview
Fig 1.
Page 3
www.elecro.co.uk
2
Positioning
Your heater should be horizontally or vertically sited allowing su cient space for pipe connections and wiring, it should be screw  xed securely to a  rm base or wall.
NOTE: See  gure 2 for details of the foot arrangement when securing to the wall or  oor.
The heater should be installed at a low point in the  ltration system. It should be positioned downstream (after) of the  lter and upstream (before) of any dosing or other water treatment plant. (see  g.3)
NOTE : If the  ow direction is reversed (explained later in this booklet) the heater must remain sited after the  lter.
Factory set  oor
mount ‘Foot position’
To reset for wall
mount option,
undo the bolts and
re-assemble in the
vertical position as
shown.
Floor mount ‘Foot position’
Wall mount ‘Foot position’
Fig 2.
ENGLISH
Page 4
3
www.elecro.co.uk
ENGLISH
Flow switch
at top
For vertical wall
mounting water
must always enter
at the bottom
Fig 3.
Fig 4.
Page 5
www.elecro.co.uk
4
Pipe Work
It is essential that the pipe work connecting to and from the heater has a minimum bore (internal diameter) of 1¼” (32mm). To assist correct air purging and to ensure the heater remains completely full of water during operation, the return pipe which carries the water back to the pool must incorporate a safety loop or ‘kick-up’ in the pipe as close as possible to the heater (see  g 4)
NOTE: When coupling to a  exible pipe a safety loop can simply be created by routing the pipe up and over an obstacle. Remember to use pipe clips to securely fasten all hose connections.
Weather Protection
The heater must be installed within a dry weather proof enclosure.
Caution! If the heater is not used during winter months it must be drained to prevent frost damage.
Electrical Connection
The heater must be installed in accordance with the country / regional requirements & regulations. In any event the work must be carried out by a quali ed electrician, who will provide a certi cate of conformity upon completion of the work. The power supply must be  tted with a RCD. If required your electrician may replace the supplied cable entry gland with a larger size to secure the cable powering the heater, this will not a ect your warranty if carried out by a quali ed electrician.
Cable section: This should be calculated at 5-amp / mm for distances up to 20 metres (these sections are indicative and should be checked and adapted if necessary for cable lengths over 20 metres.
ENGLISH
Remove Access Cover to make the electrical
connections
(Quali ed electricians only)
Fig 5.
Page 6
5
www.elecro.co.uk
Power Requirements
Flow Requirements
Your heater is factory set to accept input water  ow entering on the left and exiting on the right, this can be reversed by rotating the  ow switch 180 degrees (ie:½ turn, see  g 6)
WARNING! The  ow switch paddle can be damaged when reversing the  ow direction if it is lifted by more than 5mm from its housing and turned with force. If the  ow switch has been rotated it is important to ensure that it is  nally locked in the correct orientation perpendicular (at right angles) to the  ow of water.
ENGLISH
Power
Output
Voltage
(V)
Amp
2 - kW 230 9
3 - kW 230 13
4.5 - kW 230 20
6 - kW 230 27
9 - kW 230 40
12 - kW 230 53
15 - kW 230 66
18 - kW 230 79
3 Phase
Power
Output
400 V Star / 230 V Delta
Amp
6 - kW 400 / 230V 9 / 15
9 - kW 400 / 230V 13 / 23
12 - kW 400 / 230V 18 / 31
15 - kW 400 / 230V 22 / 38
18 - kW 400 / 230V 26 / 46
24 - kW 400 35
To reverse  ow: Loosen cap
and rotate Flow switch by
180 degrees as shown.
Always ensure the arrow
marked on the plastic  ow
switch body is in the same
direction as the water  ow
Factory set  ow
Optional reverse
 o w
Flow
Fig 6.
Page 7
www.elecro.co.uk
6
The  ow rate of water into the heater must not exceed 17,000 litres per hour (3,740 UK gallons/hour) A higher  ow rate will require the installation of a bypass to prevent damage to the heater elements. The heater will not operate unless the following minimum  ow rates are achieved ie:
1,000 litres / hour (220 UK gallons/hour) for 2 ~ 6-kW heaters and 4,000 litres / hour (880 UK gallons/hour) for 9 ~ 24-kW heaters.
Water Quality
The water quality MUST be within the following limits: PH 6.8 - 8.0 TA (Total alkalinity) 80—140ppm (parts per million) Chloride Content MAX: 150 mg/litre Free Chlorine: 2.0 mg/litre Total Bromine: Max 4.5 mg/litre TDS (Total Dissolved Solids) / Calcium hardness 200— 1,000ppm Stainless Steel heaters are NOT suitable for use on saline (salt) water pools. ONLY heaters with titanium heating elements are suitable for use on saline (salt) pools.
Water chemistry is complicated if in doubt seek expert advise.
Operating Instructions
Upon completion of the installation, run the water-circulating pump to purge the system & heater of air (i.e. Remove any trapped air in the system & heater). TIP: You can encourage air out of the heater  ow tube by gently elevating the exit port of the heater when the pump is running. On initial power up of the heater the amber light should illuminate.
The heater will only switch ‘On’ (red light indicator illuminated) and the amber light switching ‘O ’ when the following criteria are met ie:
Water circulating pump is ‘On’ delivering in excess of the minimum  ow
rate of water (see  ow requirement information)
Temperature set point dial is set to a higher value than that of the water
ENGLISH
Page 8
7
www.elecro.co.uk
Q: How long will it take to heat my pool?
A: Assuming no heat losses, and a heater sized in the ratio 1.5-kW
per 1,000 UK gallons of water (4,545-litres): it will take 2 days of continuous running to raise the temperature of a pool from tap temperature to swimming temperature. Heat loss will slow the heating process, particularly during periods of cold weather, hence the higher the water temperature is to be maintained above average ambient air temperature, the slower the heating process will become.
The only in uencing factors are the level of insulation and the location of the pool with regard to wind shelter.
Useful advice: To reduce running costs and speed up the heating process; Insulate the pool wherever possible. A  oating solar cover is an essential minimum to retain heat.
Quick Function Test
Observe the main electricity meter when the heater is on (ie: red light ‘On’) and then observe it again when the heater is in the standby mode (ie: amber light ‘On’) The test should show that the meter is recording more electricity being used by the heater when the red light is ‘On’. It is impossible for an electric heater to waste energy, if it is drawing power then that power will be turned into heat that will be transferred to the water.
Accurate Function Test
If a more accurate test is required to con rm that your heater is delivering the speci ed heat output, two electricity meter readings will need to be taken from the properties main electricity meter, with an exact one hour interval (ie: take one meter reading and then a second reading exactly one hour later) then by subtracting the  rst reading from the second reading the number of units (kilo watts kW) consumed can be calculated. Note that your heater is also rated in kW hours.
The pool pump and heater will need to be running continuously during the test (ie: with the heater red light ’On’) To avoid inaccurate results when performing this test, it is important to refrain from using other high
ENGLISH
Page 9
www.elecro.co.uk
8
current consuming appliances in the property (such as tumble dryer, showers, cookers etc). A large domestic pool pump of 1 horsepower will draw less than 1kW in a one hour period. The conclusion of the test should prove that for example a 6kW heater and a ½ horsepower pump will draw between 6.3-kW ~ 6.5-kW in one hour. It is impossible for an electric heater to waste energy, if it is drawing power then that power will be turned into heat that will be transferred to the water.
Trouble Shooting
HEATER WILL NOT SWITCH FROM STANDBY (AMBER LIGHT ) TO ON (RED LIGHT)
In most cases this will be the result of one of the following points not being met.
Possible cause 1: The set point temperature has been achieved. To con rm increase the set point value by turning the temperature set point dial to a value greater than the current water temperature.
Possible cause 2: The ‘thermal safety cut out’ has tripped.
Remedy: Remove button cover and press red button to re-set (see  g 7) If a positive click is felt, the cause of the tripping must be investigated and could be caused by a debris build-up or air pocket trapped inside the  ow tube of the heater.
ENGLISH
Fig 7.
Page 10
9
www.elecro.co.uk
Possible cause 3: Insu cient  ow.
If using a cartridge  lter: Con rm this by running the system with the cartridge removed from your pump &  lter unit, this will supply the heater with the maximum  ow rate your unit is capable of. If the heater then switches ’On’ (ie: red light ’On’) a blocked cartridge can be con rmed to be the cause. The cartridge should be cleaned or replaced.
If using a sand  lter: Check the pressure indicator on your sand  lter and back wash if necessary.
NOTE: In some cases the thermal safety cut-out tripping and a low  ow rate can be linked ie: when a  lter becomes choked air can be drawn into the  ltration system and become trapped inside the heater so causing the thermostat to trip.
NO LIGHT APPEARS ON THE HEATER WHEN IT IS SWITCHED ’ON’
Possible cause: Power failure external to the heater
Remedy : Check any fuses, RCD or other switch components installed in the supply cable. Note: the heater is not  tted with a fuse.
THE FLOW TUBE DOES NOT FEEL WARM
Due to the high e ciency of your electric heater no warmth should be detectable from the  ow tube of the heater. The most likely causes of the  ow tube feeling warm are:-
Possible cause 1: The heater has been positioned in direct sunlight. Possible cause 2: An air pocket is trapped inside the heater particularly if
the tank feels warmer at the highest point of the tank (as air rises)
THE WATER ENTERING MY POOL DOES NOT FEEL MUCH WARMER
The temperature gain of the water after it has passed through the heater will be directly proportional to the volume of water being pumped in relationship to the power output of the heater.
For example: A 6-kW heater, when connected to a 4,000 litre / hour
pump, will produce a lift in temperature of approximately 1.2 °C (almost
undetectable to the human hand) however, as the water being heated is re-circulated from a single body of water, the time required to heat it remains una ected by the volume of  ow. A popular misconception is that slowing down the  ow rate will speed up the heating process.
ENGLISH
Page 11
www.elecro.co.uk
10
RoHS Compliance Statement
Elecro Engineering Limited certify that our Electric Swimming Pool Heater Range complies in accordance with RoHS Directive 2002/95/EC on the restriction of hazardous substances.
Waste of Electrical / Electronic Equipment
This product complies with EU directive 2002/96/EC
Do Not dispose of this product as unsorted municipal waste.
This symbol on the product or on it’s packaging indicates that this product should not be treated as household waste. Instead it should be handed over to the applicable collection point for the recycling of electrical and electronic equipment.
By ensuring this product is disposed of correctly you will help prevent potential negative consequences for the environment and human health, which could otherwise be caused by inappropriate waste handling of this product. The recycling of materials will help to conserve natural resources.
For more information please contact your local Civic o ce, your household waste disposal service or the retailer where you purchased the product.
ENGLISH
Page 12
11
www.elecro.co.uk
Guarantee
Your heater is guaranteed from the date of purchase against faulty workmanship and materials ie: 2 years guarantee for incoloy heating element products and 3 years guarantee for titanium heating element products.
The manufacturer will replace or repair, at it’s discretion, any faulty units or components returned to the company for inspection. Proof of purchase may be required.
The manufacturer will not be liable in cases of incorrect installation of the heater, inapropriate use or neglect of the heater.
CE Declaration Of Conformity
The manufacturer declares that the herewith products or ranges
ELECTRIC SWIMMING POOL HEATER RANGE
Are in conformity with the provisions:
of the ELECTROMAGNETIC COMPATIBILITY directive 89/336/EEC, as
amended 93/068/EEC. Controlled by AEMC Measures laboratory—
technical report no P96045T
The harmonised standards have been applied: EN 55014—EN 55104
EN 55011 EN 55022 CEI 801-4
CEI 801-2 CEI 801-3
of the LOW VOLTAGE directive 73/23/EEC.
The harmonised standards have been applied
EN 60335-2-35
Product Overview
ENGLISH
Page 13
www.elecro.co.uk
73
Page 14
11 Gunnels Wood Park | Stevenage | Hertfordshire | SG1 2BH | United Kingdom
t: +44 (0) 1438 749 474 | f: +44 (0) 1438 361 329 | e: info@elecro.co.uk
www.elecro.co.uk
© Copyright 2011 Z-INS-ANA-POOL
Loading...