TYPE SLA
Type SLA is identical to standard UL listed liquidtight flexible steel conduit, but is augmented with a tinned copper shielding
braid located over the inner steel core and under its protective PVC jacket. The braid offers a minimum of 90% coverage.
Please see the Shielding Effectiveness chart on page 21.
APPLICATION:
This conduit is intended for
installation in accordance with
Article 350 of the NEC (ANSI / NFPA-70).
EMI/RFI Shielded
Suitable as an equipment grounding
conductor per Article 250.118(7).
Suitable for use in hazardous
locations: Class I, Div. 2 and Classes II
and III.
PVC jacket is resistant to a wide
variety of oils, acids, alkaline and
ultraviolet light.
Accepts standard metallic
liquidtight ttings.
Listed File #E29278. Conforms
to UL360 for liquidtight flexible
steel conduit.
RoHS and WEEE Compliant.
STANDARD COLORS:
Black. Other colors and jacketing
materials available upon request.
WORKING TXEMPERATURES:
-20°C to 60°C
METAL USED: Steel
PLASTIC USED: PVC
See the Chemical Resistance
Guide on our website.
For a low-smoke, low-flame spread,
zero-halogen version, ask for
Squarelock with Filler (Sizes 3/8" – 1-1/4")
HFSLA™.
Trade
Size (In.) Type
3/8 SLA-10 2.0 29 100 78901 500 78903 1000 78904
1/2 SLA-11 3.0 32 100 78911 500 78913 1000 78914
3/4 SLA-12 4.2 53 100 78921 500 78924 - -
1 SLA-13 5.5 82 100 78932 400 78934 - -
1-1/4 SLA-14 7.0 102 50 78942 200 78944 - -
1-1/2 SLA-15 4.5 124 50 78952 150 78954 - -
2 SLA-16 6.0 145 50 78962 100 78964 - -
See page 37 for Dimensions.
Inside Bend
Radius (In.)
Weight
(Lbs.)/100 Ft.
Carton Footage Reel Footage
Length Part # Length Part # Length Part #
Halogen-Free (HF) Series
For a low-smoke, low-flame spread,
zero-halogen version, ask for HFSLA,
HFEMS™ or HFEMCS™. It's ideal for
field installation in confined, public
areas such as subways, tunnels, etc.
There are many situations and
areas where PVC is not allowed for
electrical construction. The jacketing
material used in the Halogen-Free
Series virtually eliminates the release
of acidic gases found in PVC products.
COMBUSTION & FLAMMABILITY PROPERITES TEST VALUE
HFSLA / HFEMS / HFEMCS
Vertical Burn (Material) UL94 V-O rating; no aming drips
Vertical Burn (Conduit) UL360 Pass; no aming drips
Oxygen Index % D2863 28.5
Flame Spread Index ASTM E162 20; no aming drips
Flame Propagation ASTM C542 (NFPA-130) Pass; no aming drips
Smoke Generation (Flaming) ASTM E662 (NFPA-258) Ds 50@1.5 min / Ds 102@4.0 min
Smoke Generation (Non- aming) ASTM E662 (NFPA-258) Ds 5@1.5 min / Ds 26@4.0 min
Toxic Gas Generation Bombardier SMP 800-C Pass
Toxicity Index NES 713 3.9
Test data is based on controlled laboratory conditions and does not necessarily reflec t performance in actual fire conditions.
Additi onal product i nformation available up on requ est.
22
www.electriflex.com
Colored Conduit
for Custom Installations
The use of colored
Type LA conduit saves
time and money in
maintenance and repair
situations, and provides
a visible warning to use
caution in and around
specific areas. They
can provide for quick
identification of circuits,
such as emergency,
fire, security and high
Available in Types:
LA, LT, LOR, EF, ATLA, AT, ATX, ALT, ACEA,
CEA, SLA, EMS, EMCS, LNM-P, NM, NMHT
Jacketed Metallic
voltage, as well as many
other applications.
SUGGESTED APPLICATIONS:
Conduit Color Suggested Application
Cream Of ce Modular Partitions
Brown Of ce Modular Partitions
Blue Computer Rooms/Data Cables, Low Voltage Wiring
Green Hospitals and Healthcare
Yellow Caution Areas, Special Equipment, High Voltage Wiring, Earth Moving Equipment
Orange Construction, Auto Repair, Fiber Optic Systems
Red Fire Alarms, Security Systems, Emergency Circuits
White Dairy Equipment, Food Processing Equipment
* Standard colors are Black and Gray. Other colors available upon request. We can blend to any color preference. Jacketed
materials for extreme temperature and halogen-free applications are also available in colors.
www.electriflex.com