Electri-Flex LNM-P Catalog Page

TYPE LNM-P
Made in the USA
This nonmetallic liquidtight conduit is ideally suited for continuous flexing situations. It is often specified in “Power Track” or cable carrier installations and on industrial robots. It does not contain a metal core, which could fatigue from repeated flexing or vibration.
CONSTRUCTION:
Type LNM-P consists of layered, Type A construction that incorporates a smooth seamless inner core of flexible PVC bonded to a covering of flexible PVC. Between these layers is a woven nylon mesh for added reinforcement. The PVC material is a high-quality, flame-retardant compound that resists oils, mild acids and exposure to sunlight.
APPLICATION:
Type LNM-P is intended for installation in accordance with Article 356 of the NEC (ANSI/NFPA-70) for flexible liquidtight nonmetallic conduit (LFNC-A or FNMC-A).
• For containment of 600 volt and lower potential circuits.
• Listed and marked for outdoor use.
• Installations in hazardous (classified) locations:
- Class I Div. 2 Article 501
- Class II Div. 1&2 Article 502
- Class III Div. 1&2 Article 503
• Electric signs and outdoor lighting over 1000 volts. Ar ticle 600.31(A).
• Wiring methods for pools and spas. Article 680.
• Conforms to the requirements of Section
14.5.5 of the electrical Standard for Industrial Machinery NFPA-79.
Listed File #E79308 Conforms to Underwriters Laboratories Standard ANSI / UL 1660 Type A.
RoHS and WEEE Compliant.
Certified File #LL18858Conforms to CSA
22.2 No. 227.2 Type A
FITTINGS: Fittings for layered conduit are
for that conduit only and are so identified by the marking “FNMC-A” or “LFNC-A” for liquidtight flexible nonmetallic conduit Type A.
1/2" straight examples include:
- Thomas & Betts (Steel)
#3721 (Plastic) #6302
- Appleton Electric #STNM-50
- Kellems / Hubell #H050CNK
Nonmetallic
PACKAGING:
Coiled in cartons or in random lengths (minimum 50 feet) on non-returnable reels.
STANDARD COLORS: Safety Orange.
Also available in Black and Gray.
WORKING TEMPERATURES:
-20° to 60°C
LNM-P
Trade
Size
(In.) Type
3 / 8 LNM-P 10 2.5 16 0.485 / 0.505 0.755 / 0.775 250 87002 500 87003 1000 87004
1 / 2 LNM-P 11 3.0 21 0.620 / 0.640 0.910 / 0.930 200 87102 500 87103 1000 87104
3 / 4 LNM-P 12 4.0 31 0.815 / 0.835 1.150 / 1.170 175 87202 500 87204 - -
1 LNM-P 13 6.0 42 1.030 / 1.055 1.415 / 1.440 100 87302 400 87304 - -
1-1 / 4 LNM-P 14 7.0 61 1.370 / 1.395 1.800 / 1.825 100 87402 200 87404 - -
1-1 / 2 LNM-P 15 8.0 79 1.585 / 1.620 2.045 / 2.080 50 87502 150 87503 - -
2 LNM-P 16 9.0 120 2.045 / 2.080 2.605 / 2.640 50 87602 100 87603 - -
Bend
Radius
(In.)
Wt.
(Lbs.)/
100 Ft.
Inside
Diameter Carton Footage Reel Footage
Inner
Min/Max.
Outer
Man/Max Length Part # Length Part #
Length Part #
www.electriflex.com
33
Colored Conduit
Made in the USA
for Custom Installations
The use of colored Type LA conduit saves time and money in maintenance and repair situations, and provides a visible warning to use caution in and around specific areas. They can provide for quick identification of circuits, such as emergency, fire, security and high
Available in Types:
LA, LT, LOR, EF, ATLA, AT, ATX, ALT, ACEA, CEA, SLA, EMS, EMCS, LNM-P, NM, NMHT
Jacketed Metallic
voltage, as well as many other applications.
SUGGESTED APPLICATIONS:
Conduit Color Suggested Application
Cream Of ce Modular Partitions
Brown Of ce Modular Partitions
Blue Computer Rooms/Data Cables, Low Voltage Wiring
Green Hospitals and Healthcare
Yellow Caution Areas, Special Equipment, High Voltage Wiring, Earth Moving Equipment
Orange Construction, Auto Repair, Fiber Optic Systems
Red Fire Alarms, Security Systems, Emergency Circuits
White Dairy Equipment, Food Processing Equipment
* Standard colors are Black and Gray. Other colors available upon request. We can blend to any color preference. Jacketed materials for extreme temperature and halogen-free applications are also available in colors.
www.electriflex.com
19