![](/html/40/4003/4003dedee7d2f9a86e1e68d3f65f39cb8adcc05eed14928894f8b8bee6bd6b63/bg1.png)
TYPE LA
Jacketed Metallic
A flexible steel conduit that is both listed by Underwriters Laboratories Inc. and
certified by Canadian Standards Association. It offers outstanding protection against
wet, oily conditions and is permitted for use in exposed or concealed locations.
CONSTRUCTION:
The flexible inner core is made from
a spiral wound strip of heavy-gauge,
corrosion-resistant, hot-dipped galvanized
steel. The 3/8 through 1-1/4 inch trade
sizes are squarelock formed and include
an integral bonding strip of copper
that is enclosed within the convolutions
throughout their entire length. The 1-1/2
through 4-inch trade sizes are designed
with a fully interlocked strip.
The liquidtight jacketing material is of
a high-quality, rugged, flame-retardant
flexible PVC compound that resists oils,
mild acids and exposure to sunlight. Refer
to the Chemical Resistance Guide on our
website for further information.
APPLICATION:
This conduit is intended for installation in
accordance with Article 350 of the NEC
(ANSI /NFPA-70) and in section 14.5.4 of
the ANSI /NFPA-79 Standard for Industrial
Machinery:
Listed and marked for direct burial and
in poured concrete.
For containment of 600 volt and lower
potential circuits.
Sunlight-resistant.
Suitable as a grounding conductor
when used for circuits rated up to 20A
for the 3/8 and 1/2 inch grade sizes
®
and 60A for the 3/4 through 1-1/4 inch
trade sizes in lengths six feet or less per
NEC Article 250.118(6).
Installations in hazardous (classied)
locations:
–
Class I Div. 2 Article 501
– Class II Div. 1 and 2 Article 502
– Class III Div. 1 and 2 Article 503
Installed under raised oors in data
processing areas. Articles 645.5(E)(2).
Electric signs and outline lighting over
1,000 volts. Articles 600.7/600.32(A)(1).
Permitted for service entrance wiring
to six feet. Article 230.43.
Used as feeders and services at marinas
and boatyards. Article 553.7(B).
Wiring on building. Article 225.10.
Conductor enclosures adjacent to
motors over 600V. Article 430.223.
Underground service, feeder, branch
circuit and recreational vehicle site
feeder circuit conductors. Article 551.80.
Elevators and hoistways. Article 620.21.
Pools and fountains. Article 680.
Bodies of water. Article 682.
Fire pumps. Article 695.
Listed File #E29278. Conforms to
Underwriters Laboratories Standard ANSI /
UL-360 for Liquidtight Flexible Steel conduit.
RoHS and WEEE Compliant.
Certified File #LL18858. Conforms to
CSA 22.2 No.56 for use per the Canadian
Electrical Code C22.1 Section 12-1300.
STANDARD COLORS:
Machine Tool Gray and Black. Other colors
available upon request. Blue is commonly
used for computer room installations. See
Type CBLA.
WORKING TEMPERATURES:
-20°C to 60°C
METAL USED: STEEL
PLASTIC USED: PVC
See the Chemical Resistance Guide on our website.
Squarelock with Filler SIZES: 3/8" – 1-1/4"
Interlock SIZES: 1-1/2" – 4"
Trade
Size (In.) Type
3 / 8 LA-10 2.0 29 100 20101 / 20801 500 20103 / 20803 1000 20104 / 20804
1 / 2 LA-11 3.0 32 100 21101 / 21801 500 21103 / 21803 1000 21104 / 21804
3 / 4 LA-12 4.2 53 100 22101 / 22801 500 22104 / 22804 1000 22110 / 22810
1 LA-13 5.5 82 100 23102 / 23802 400 23104 / 23804 - - / -
1-1 / 4 LA-14 7.0 102 50 24102 / 24802 200 24104 / 24804 - - / -
1-1 / 2 LA-15 4.5 124 50 25102 / 25802 150 25104 / 25804 - - / -
2 LA-16 6.0 145 50 26102 / 26802 100 26104 / 26804 - - / -
2-1 / 2 LA / LT-17 8.0 192 25 27102 / 27802 275 27105 / 27805 - - / -
3 LA / LT-18 10.0 252 25 28102 / 28802 175 28105 / 28805 - - / -
3-1 / 2 LA / LT-350 11.0 308 25 28502 / - 175 28505 / - - - / -
4 LA / LT-19 12.0 350 25 29102 / 29502 100 29105 / 29505 - - / -
3-1 / 2 LA / LT-350 11.0 308 25 28502 / - 175 28505 / - - - / -
4 LA / LT-19 12.0 350 25 29102 / 29502 100 29105 / 29505 - - / -
See page 37 for Dimensions.
Bend
Radius (In.)
Inside
Weight
(Lbs.) /100
Ft.
Carton Footage Reel Footage
Length
Part #
Gray / Black Length
Part #
Gray / Black Length
Gray / Black
www.electriflex.com
Part #
7
![](/html/40/4003/4003dedee7d2f9a86e1e68d3f65f39cb8adcc05eed14928894f8b8bee6bd6b63/bg2.png)
Colored Conduit
for Custom Installations
The use of colored
Type LA conduit saves
time and money in
maintenance and repair
situations, and provides
a visible warning to use
caution in and around
specific areas. They
can provide for quick
identification of circuits,
such as emergency,
fire, security and high
Available in Types:
LA, LT, LOR, EF, ATLA, AT, ATX, ALT, ACEA,
CEA, SLA, EMS, EMCS, LNM-P, NM, NMHT
Jacketed Metallic
voltage, as well as many
other applications.
SUGGESTED APPLICATIONS:
Conduit Color Suggested Application
Cream Of ce Modular Partitions
Brown Of ce Modular Partitions
Blue Computer Rooms/Data Cables, Low Voltage Wiring
Green Hospitals and Healthcare
Yellow Caution Areas, Special Equipment, High Voltage Wiring, Earth Moving Equipment
Orange Construction, Auto Repair, Fiber Optic Systems
Red Fire Alarms, Security Systems, Emergency Circuits
White Dairy Equipment, Food Processing Equipment
* Standard colors are Black and Gray. Other colors available upon request. We can blend to any color preference. Jacketed
materials for extreme temperature and halogen-free applications are also available in colors.
www.electriflex.com
19