Electric Signal MMXV AD User Manual

Electric Signal
MMXV AD
User manual
Delta Transconductance
band Compressor
Electric Signal 2016 - Revision Alpha
Delta Transconductance band Compressor
User manual
Serial
number
a priori
Line voltage
Table of Contents
I
2. Introduction 5
3. Warning 6
1. Thank You 5
V
3.1 Paralell compression
3.2 Crossover frequency
3.3 Lp bypass
3.4 Hp bypass 30
3.5 Order
3. Filter 29
II
2. Heat and ventilation 7
3. Operation voltage 8
III
1. Power 9
2. Balance measurement 9
3. Balance calibration 10
4. Meter zero/bias 10
5. Output stage balance/ measurement 11
IV
1. Block chain of the Machine 13
2. Control Matrix 15
2.1 Input gain 16
2.2 Attack time
2.3 Release time
2.4 Threshold
2.5 Recovery gain
2.6 Stereo link 17
2.7 Mute
3. Gain reduction meters
4. Main output 18
4.1 Main mute
4.2 Main system bypass
4.3 Main input
V
2. Bode plot’s of filter settings
1. Getting Started 7
Powering up the machine
Using the system 12
1. Filter block chain 19
2.1. high to mid 6dB/oct - mid to low 6dB/oct 21
2.2. high to mid 12dB/oct - mid to low 12dB/oct 23
2.3. high to mid 12dB/oct - mid to low 6dB/oct 25
2.4. high to mid 6dB/oct - mid to low 12dB/oct 27
VI
2. Replacing the tubes 32
VII
2. Warrenty
VIII
IX
X
XI
XII
1. Tube complement 31
1. Disclaimer 33
Specifications
Edison Effect 35
Declaration of Confirmity 36
Contact details 36
Recall sheet 37
Page 3
Delta Transconductace band Compressor User Manual
Page 4
I.
1
Thank You
For choosing the Electric Signal Delta Transconductance band Compressor and trust in us.
Eletric Signal has the mission to ensure the professional audio engineer has reliable, high quality equipment.
By knowing the status quo, annihilating the dogma’s and standing on a many shoulders, Electric Signal is always innovating. Pushing the envelope further and tries to leave the real decisions for the engineer. By knowing we are only a switch in the chain we try to achieve to give the engineer the maximum potential by providing him the relevant choices.
It is tough to vocolise, however Arthur Shoppenhauwer writes in ‘the world as will and reprentation’
“The effect of music is so very much more powerful and penetrating than is that of the other arts, for these others speak only of the shadow, but music of the essence.”
I.2
Introduction
The Delta Transconductance band compressor is a vacuum tube based three band compressor and is essentially three stereo compressors, a three band passive crossover filter and a tube based mixer
For the compression, the delta mu technology is used. The 6386 tiode, used in many classic compressors is ideal for this task, nowadays difficult to obtain. Therefore the Delta Transconductance band Compressor uses the 6ba6/5749 penthode in triode configuration and has the same characteristics as the 6386 triode.
Like all delta mu compressors, balance needs to be (re)calibrate to cancel out 2nd order harmonics. Therefore these calibration settings are on the front panel. To make proper settings there are sockets on the front panel to measure the (in)balance.
Furthermore, solid state components are used in the power supply and the side chain. There are no integrated circuit's, electrolytes or transistors in the audio chain. The input and output are transformer balanced. The controls on the front panel are toggle switches or rotary switches, so recall is possible. These switches control relay based attenuators, never touch the audio signal directly and make a short as possible audio chain.
I.3
For personal safety, please read this user manual and warning thoroughly before using the equipment. To reduce the risk of electric shock, it is essential that the unit is disconnected from the mains supply before removing the cover. The Delta Transconductance band Compressor uses thermionic vacuum electron tubes and works on a lethal voltage up to 300 volts. Even after a long period of disconnection, components can still be charged.
Use and store the Delta Transconductance band Compressor only in studio conditions. Do NOT operate the Delta Transconductance band Compressor in a hazardous area, near water or moisture.
Due the amount of tubes, the Delta Transconductance band Compressor
generates heat. However the unit should never run this hot so that it makes it untouchable. Ensure that adequate ventilation is provided(see II.2).
In the event that this unit has been suffered an impact, an electrical safety test must be carried out before reconnection to the mains supply.
Refer servicing of the unit to qualified personnel only.
Warning
Page 5
Delta Transconductace band Compressor User Manual
Page 6
II.1
Getting Started
II.3
Operation voltage
The package contains:
-this manual
-the Delta Transconductance band Compressor
-a power inlet cable
If you’re not sure, control the operating voltage is the correct one(II.3) While doing so check for compromised vacuum and broken glass.
Use short XLR cables for input/output where:
pin 1: ground, shield pin 2: positive phase, hot pin 3: negative phase,cold
Use the power inlet cable to connect the equipment with a earthed power source.
Make sure the unit is installed in a rack, with sufficient ventilation(see II.2) or on a stable flat surface.
II.2 Heat and ventilation
Due to the amount of tubes the Delta Transconductance band Compressor uses more energy than a laptop and therefore generates significantly amount of heat.
The machine is equipped with a very low noise noctus fan and had a operation time of 100000 hour. Installed in a rack the unit should be inaudible. It is recomended to have 1U of space between the unit and other equipment. Make sure that the ventilation slots are not obstructed. When rack mounting this equipment, an external fan may be required to provide sufficient airflow.
The Delta transconductance band compressor can operate from 240 vac 50 Hz or 120 vac 60 Hz. The line voltage is set at the factory based on the buyers request at time of the order. To change the line voltage, padlock the machine from mains. The line voltage switches are located at the back of the machin. Switch it in the correct position. Do NOT operate the equipment with the line voltage switch in the wrong position.
Page 7
Delta Transconductace band Compressor User Manual
Page 8
III
Powering up
the Machine
Now that the Delta transconductance band Compressor is installed and all connections are made, it is ready to operate
III.
1
Power
Set the multimeter to mV and connect the wires of the meter to pin 1and pin 2 of the right D sub socket, If the multimeter measures anthing other than 0 volts the balance of this stage is not calibrated properly. See next chapter for balance calibration (III.3).
III.
3
Balance calibration
Push the power button:
Now the light in the power button will illuminate, and the machine generate sa few clicks from the relays. Now the tubes heat up, inside them a physical process occures named ‘the Edison effect’ and electrons will flow into the micro universe of the tube. The gain reduction meters measure the current trough the tubes responsible for the compression and the leds of the meters will lit up. After 30 to 60 seconds the machine is ready for operation.
III.
2
Balance measurement
The machine is calibrated in our factory, however the procedure is as follows. The tubes can drift directly after the warm up so it is recommended to leave the unit on for half an hour, before calibration /measurement. For this procedure is needed:
-a flat screwdriver
-a (digital) multimeter
Remove the the measurement panel. Behind the measurement panel there are two 9pins d-sub sockets, with the numbering of pins:
5 4 3 2
9 8 7 6
1
Power
5 4 3 2
9 8 7 6
Right
5 4 3 2
9 8 7 6
Left
Pinout 1, 2: High 3, 4: Mid 5, 6: Low 7, 8: Main 9 : Gnd
If an unbalance is measured, second order harmonics occure. To rebalance the stage, apply the multimeter to the correct stage (see III.2) and use the flat screw driver to adjust the balance trim-pot until the multimeter indicates 0 volts.
bal
III.
4
Meter zero/bias
While tubes age, their conductance decrease and therefore the gain reduction meters will indicate compression. Although this is not immediately a problem, there is a way to recalibrate the idle current of the tubes. Use a flat screwdriver to adjust the zero pot-meter of the desired channel
1
1
(mid, high, low, and left or right) and set the meter to 0 dB. If thie problem is not solved, a tube replacement may be necessary. After altering the bias, it is recommended to re balance the stage.
level
zero
bal
r
l
i
e
g
f
h
t
t
level
zero
bal
level
zero
bal
zero
Page 9
Delta Transconductace band Compressor User Manual
Page 10
Loading...
+ 14 hidden pages