Electric Perry 1RT 80S User Manual

DERTPE004EN 01/22
Description
Delay ON star/delta
1RT80S
PERRY ELECTRIC Srl
Via Milanese, 11 22070 VENIANO (Como) ITALY www.perry.it
ENGLISH
INFORMATION AND SAFETY PRECAUTIONS
It is advisable to read the installation and user instructions carefully and to keep them for future reference. The manufacturer reserves the right to make all the
&
technical and constructionchanges it deems necessary without prior notice.
Important: the installation, electrical connection and commissioning of devices and equipment must be performed by qualified personnel and in compliance withregulations and applicable laws.
Before starting the installation and maintenance of the device, disconnect the 230V ~ mainspower supply.
• Do notconnect or power the unit if any part is visibly damaged.
• Once installation is complete, inaccessibility to the terminals without the use of special tools must be guaranteed.
• The manufacturer assumes no responsibility concerning the use of products that must comply with specific environmental and/or installation regulations.
• This unit must be intended only for the use for which it was built. Any other usemust be consideredimproper and dangerous.
IMPORTANT
Device isconstructed forconnection in 1-phase AC/DC 12- 240 V main alternating current voltage and must be installed according to norms valid in the state of application. Connection according to the details in this direction. Installation, connection, setting and servicing should be installed by qualifi ed electrician sta only, who has learnt theseff instruction and functions of the device. This device contains protection against overvoltage peaks and disturbancies in supply. For correctfunction of the protection ofthis device there must be suitable protections of higher degree (A, B, C) installed in front of them. According to standards elimination of disturbancies must be ensured. Before installation the main switch must be in position “OFF” and the device should be de­energized. Don´t install the device to sources of excessive electro-magnetic interference. By correct installation ensure ideal air circulation so in case of permanent operation and higher ambient temperature the maximal operating temperature of the device is not exceeded. For installation and setting use screw-driver cca 2 mm. The device is fully­electronic - installation should be carried out according to this fact. Nonproblematic function depends alsoon the way of transportation,storing and handling. In case of any signs of destruction, deformation, non-function or missing part, don´t install and claim atyour seller. After stopusing the product itis possible to demountand recycle.
DISPOSING OFOLD ELECTRICALAND ELECTRONIC EQUIPMENT
This symbolon the product or onits packaging indicates that thisproduct cannot be treated ashousehold waste. On the contrary, it must be taken to a specific collection centre for recycling electrical and electronic equipment, such as: - outlets, if a similar product to the one being disposed of is being purchased - local collection centres (waste collection centres, local recycling centres, etc.). By making sure the product is disposed of correctly, you will help prevent potential negative consequences for the environment andhuman health, which could otherwisebe caused byinadequate disposal of this product. Recycling materials will help conserve natural resources. For more detailed information about recycling this product, please contact the local office in your area, the household waste disposal service in your area orthe shopwhere you purchasedthis product.
1 mod. DIN
&
Supply indication
Rought time setting t1
Fine time setting t1
Fine time setting t2
LED
Symbol
Connection
a = Auxiliary voltage b = Switch for start c = Wiring of star/delta motor
start
Un: AC/DC 12-240V / AC 50-60 Hz
a
b
A1
A2
25
28
2 6
15 1 6 18
S1 = contactor for motor supply
S2 = contactor (STAR) S3 = contactor (DELTA)
Supply terminals (A1-A2)
Output indication multifunction LED
Output contact 2
(terminals 25-26-28)
Output contact 1
(terminals 15-16-18)
voltage
c
Type of load
mat. contacts AgNi,
contact 16A
Type of load
mat. contacts AgNi,
contact 16A
AC1 AC2 AC3
250V / 16A 250V / 5A 250V / 3A
AC5a AC5a
250V / 3A (690VA)
AC5b AC6a AC7b AC12
800W 250V / 3A 250V / 10AXXX
AC13 AC14 AC15 DC1 DC3 DC5 DC12 DC13 DC14
250V / 6A 250V / 6A 250V / 6A
24V / 16A
24V / 4A 24V / 2A 24V / 2A24V / 6A 24V / 16A
Technical parameters
Characteristic
Power supply
Supply terminals
Voltage range
Absorbed power
Max. dissipated power
(Un + terminals)
Operating range
Supply indication
Function
Number of functions
Time scale
Time setting
Time deviation
Repeat accuracy
Temperature coe icientff
Output
Number of contacts
Current rating
Breaking capacity
Inrush current
Switching voltage
Power dissipated (contacts)
Output indication
Mechanical life
Electrical life (resistive)
Recovery time
Other information
Operating temperature
Storage temperature
Dielectric strength
Use
Mounting/DIN rail
Protection degree
Overvoltage category
Pollution degree
Terminal wire max. capacity
(mm²)
Dimensions (L x P x H)
Weight
Standards
A1 - A2
AC/DC 12-240V
AC 50-60Hz
AC 0.7-3 VA
DC 0.5-1.7 W
4W
-15% +10%
green LED
1
t1: 0.1s - 100gg
t2: 0.1s - 1s
rotary switch and potentiometer
5% - mechanical setting
0.2 % - set value stability
0.01% / °C (0.01% / °F)
2x changeover (AgNi contacts material)
16A / AC1
4000VA / AC1, 384W / DC
30A / < 3s
250V AC / 24V DC
max 1.2 W
multifunction red LED
10.000.000 cycles
50.000 cycles
max. 150ms
-20°C to +55°C (-4°F to 131°F)
-30°C ÷ +70°C (-22°F to 158°F)
4kV ( )
between the power terminals and the output terminals
domestic / tertiary / industrial
DIN rail EN 60715
IP40 from front panel / IP20 terminals
III
2
1 x 2.5 or 2 x 1.5
with sleeve 1 x 2.5
17.6 x 64 x 90 mm
84 g
EN 61812-1
• Designated ofdelay On ofmotors star/delta.
• Time t1 (star):
- time scale 0.1 s - 100 days - devided into 10time ranges (0.1 s–1 s / 1s –10 s /0.1 min –1 min / 1 min –10min / 0.1 h –1h / 1 h –10hrs / 0.1 day –1day / 1 day –10days / 3 days -30 days / 10days –100 days)
- rough time settingby rotary switch
• Time t2 (delay) between / :
- time range 0.1s - 1 s
- fine time settingby potentiometer
• Supply voltage:AC 230V,AC/DC 12-240V
• Output contact:2 x changeover16A
• Output indication:multifunction red LED.
• 1-MODULE, DINrail mounting.
Function
ST TAR/DEL A timer
Un
15-18
25-28
LED
t1
t2
More accurate setting of timing for long periods of time
Example of timesetting to8 hoursperiod: For rough settinguse timescale 1-10son the potentiomenter. For fine timesetting aimfor 8son potentiometer, then recheck accuracy(using stopwatchetc). On rough time setting, set potentiometer to originally desired scale 1-10 hours, leave a fine setting as itis.