Electrical Factory Outlet AUTOTRIP User Manual

AUTOTRIP
RCD TESTER
USER MANUAL
Safety information and explanation of symbols used
Caution read this manual for important safety information
The AUTOTRIP must only be used by suitably trained or competant
persons.
Before using the AUTOTRIP please read and fully understand these instructions paying particular attention to the safety warnings. Do not use this tester in a manner other than that described in this booklet.
Check the instrument case and test leads for damage before each use. If any
damage is noticed the unit should be withdrawn from service and returned to place of purchase for repair.
The battery cover must be fitted and secure before using the instrument.  Always verify the continuity of the protective earthing conductors and
equipotential bonds before carrying out RCD testing.
Do not operate the meter around explosive gas, vapor, or dust.  Do not apply more than the rated voltage, (300V) as marked on the meter,
between terminals or between any terminal and earth ground.
The AUTOTRIP is rated at 300V Category III.  Exposed metal work in the installation should not be touched during testing.  Ensure when handling test probes and crocodile clips that fingers are always
behind the protective guards.
Do not change ranges by turning the rotary knob while a test is in progress.  Please note the polarity LED indicator is not able to determine N-PE supply
reversal.
Always perform a relevant risk assesment before testing and concider any
critical equipment and loads that maybe connected on the circuit under test which will be turned off by tripping the RCD.
Symbols marked on the equipment
Caution refer to instruction manual and accompaning notes
Double Insulation
Equipment complies with current EU directives
ACMA mark
Batteries
Do not switch the instrument on or use it with the battery cover removed.
When installing batteries observe correct polarity do not mix old and new batteries. Dispose of used batteries in accordance with local regulations. Never incinerate batteries.
For safety reasons the tester is shipped without batteries fitted.
To install or replace batteries
Replace batteries as soon as the low battery indication appears. Switch the instrument off and disconnect from any electrical circuits. Remove test leads. Remove the small crosshead screw on the back of the instrument that retains the battery cover and fit four Alkaline batteries type AA / LR6 in accordance with the polarity shown. Replace the battery cover and ensure it is secure before use.
The batteries should not be left in the instrument if it will not be used for an extended period.
Overheating
Repetitive testing may generate heat within the instrument. If this occurs the hot symbol is displayed and the instrument should be left to cool down before further testing.
Maintenance
To clean the tester wipe with a damp cloth with a mild soap solution taking care not to allow water ingress into the input terminals. Do not use solvents and do not immerse. Allow the tester to fully dry before use.
Features of the AUTOTRIP
The AUTOTRIP is packed with design features that maximize both convenience and safety. These include:
Large LCD display
To give the clearest results the AUTOTRIP uses a large auto-backlit LCD which makes reading the test results easy even when used in poorly lit areas.
Auto shut down
To preserve battery life when not in use the AUTOTRIP incorporates an Auto-Off function that powers the unit down after three minutes of inactivity. To resume use after an Auto shut down a single press of any of the function buttons will power up the unit.
Battery check
The battery charge condition is indicated on the LCD display. For simplicity the tester is powered by just four conventional AA (LR6) alkaline batteries.
Easy to locate
The test lead inputs are located on the top of the case allowing the tester to stand vertically or be laid flat.
Hands Free
Most of the test functions can utilise the Hands-Free mode in which the tester is primed to automatically start the test as soon as the probes are connected to
a circuit, thereby leaving your hands free to hold the test probes.
Socket wiring check
To protect both the user and the instrument against harm caused by accidental connection to an incorrectly wired supply the tester will automatically check the polarity upon connection to a live supply. If the wiring has been incorrectly connected testing will be inhibited an alarm will sound along with a flashing red LED.
Please note the polarity LED indicator is not able to determine N-PE supply reversal.
Pass Fail Result
In addition to displaying the time taken for the RCD to trip the AUTOTRIP will also indicate whether it has passed or failed the RCD requirements.
Auto Type II RCD Testing
To reduce the testing time the AUTOTRIP has two automatic test functions which allows the operator to set the auto test sequence to run, resetting the RCD at the distribution board during auto test cycle then returning to the instrument to recall the results.
Quick Auto(2 Tests): 30mA x1 at 00 & 1800 Full Auto(6 Tests): 30mA x½, x1,x 5 at 0
0
& 1800
Loading...
+ 8 hidden pages