Electrex Zepto D6 Installation Instructions Manual

ZEPTO D6
INSTALLATION INSTRUCTIONS
COPYRIGHT
Electrex is a trademark of Akse S.r.l. All rights reserved. It is forbidden to duplicate, adapt, transcript this document without Akse written authorization, except when regulated accordingly by the Copyright Laws.
WARRANTY
• Negligent and improper use
• Failures caused by atmospheric hazards
• Acts of vandalism
• Wear out of materials
• Firmware upgrades Akse reserves the right, at its discretion, to repair or substitute the faulty products The warranty is not applicable to the products that will result defective in consequence of a negligent and improper use or an operating procedure not contemplated in this manual.
RETURN AND REPAIR FORMALITIES
Akse accepts the return of instruments for repair only when authorized in advance. The transport costs are at customer charge.
RE-SHIPPING OF REPAIRED PRODUCT
The terms for re-shipment of repaired products are ex-works, i.e. the transport costs are at customer charge. Products returned as detective but found to be perfectly working by our laboratories, will be charged a fl at fee to account for checking and testing time irrespective of the warranty terms.
SAFETY
This instrument was manufactured and tested in compliance with IEC 61010 class 2 standards for operating voltages up to 250 VAC rms phase to neutral. In order to maintain this condition and to ensure safe operation, the user must comply with the indications and markings contained in the following instructions:
• When the instrument is received, before starting its installation, check that it is intact and no damage occurred during transport.
• Before mounting, ensure that the instrument operating voltages and the mains voltage are compatible then proceed with the installation.
• The instrument power supply needs no earth connection.
• The instrument is not equipped with a power supply fuse; a suitable external protection fuse must be foreseen by the contractor.
!
• Maintenance and/or repair must be carried out only by qualifi ed, authorized personnel
• If there is ever the suspicion that safe operation is no longer possible, the instrument must be taken out of service and precautions taken againstits accidental use.
• Operation is no longer safe when:
1) There is clearly visible damage.
2) The instrument no longer functions.
3) After lengthy storage in unfavorable conditions.
4) After serious damage occurred during transport
The instruments must be installed in respect of all the local regulations.
OPERATOR SAFETY
Warning: Failure to observe the following instructions may lead to a serious danger
of death.
• During normal operation dangerous voltages can occur on instrument terminals and on voltage and current transformers. Energized voltage and current transformers may generate lethal voltages. Follow carefully the standard safety precautions while carrying out any installation or service operation.
• The terminals of the instrument must not be accessible by the user after the installation. The user should only be allowed to access the instrument front panel where the display is located.
• Do not use the digital outputs for protection functions nor for power limitation functions. The instrument is suitable only for secondary protection functions.
• The instrument must be protected by a breaking device capable of interrupting both the power supply and the measurement terminals. It must be easily reachable by the operator and well identifi ed as instrument cut-off device.
• The instrument and its connections must be carefully protected against short­circuit.
Precautions: Failure to respect the following instructions may irreversibly damage to the instrument.
• The instrument is equipped with PTC current limiting device but a suitable external protection fuse should be foreseen by the contractor.
• The outputs and the options operate at low voltage level; they cannot be powered by any unspecifi ed external voltage.
• The application of currents not compatible with the current inputs levels will damage to the instrument.
READINGS
READINGS DISPLAYED (The parameters available vary according to instrument confi guration)
Uf I P QSPF
L-N f I P Q S PF
L-L In P Avg Q L Avg S Avg
THD L-N THD P MD Q C Avg S MD
THD L-L I Avg Q L MD
Press to scroll readings
READINGS DISPLAYED (The parameters available vary according to instrument confi guration)
Ea Er L Er C Es
Ea E2 Er L E2 Er C E2 Es E2
CNT
seconds
Press for 2
TIME
LEGEND OF PARAMETERS AND SYMBOLS
L-N Phase Neutral U Voltage
L-L Phase Phase I Current
THD Total Harmonic Distortion In Neutral current
Avg Average (rolling) value P Active Power
MD Maximum Demand Q Reactive Power
L Inductive S Apparent Power
C Capacitive PF Power Factor
TIME Life Time (total) (hour/100) Ea Active Energy
Life Time (partial) (hour/100) Er Reactive Energy
TIME E2
CNT Pulse count (total) Es Apparent Energy
Pulse count (partial) f Frequency
CNT E2
MECHANICAL CHARACTERISTICS
Enclosure Self-extinguishing plastic material class V0 Protection degree IP40 on front panel, IP20 terminals side Dimensions 105 x 90 x 58 mm (6 DIN modules)
VOLTAGE INPUT
Direct Up to 300 Vrms phase-neutral
With external PT(VT) Primary: programmable (max. 400 kV)
Power supply 230/240Vac +/- 10% 50/60Hz Self consumption < 3VA
MODELS
PFA8611-02 ZEPTO D6 RS485 230-240V
PFA8611-12 ZEPTO D6 RS485 230-240V 1DI 2DO
Further documentation may be downloaded from our web site www.electrex.it.
This document is owned by company AKSE that reserves all rights.
I MD Q C MD
Press to change readings
CNT E2
TIME E2
or 519 Vrms phase to phase
Secondary: programmable (max. 300 V) Overload: 900 Vrms phase to phase for 1 sec
ENERGY ANALYSER
ENERGY ANALYSER
DECLARATION OF CONFORMITY
Akse hereby declares that its range of products complies with the following directives EMC 89/336/EEC 73/23CE 93/68 CE and complies with the following product’s standard CEI EN 61326 – IEC 61326 CEI EN 61010 – IEC 1010. The product has been tested in the typical wiring confi guration and with peripherals conforming to the EMC directive and the LV directive. Subject to modifi cation without notice. Preliminary. Edition 18-02-2008.
akse srl Via Aldo Moro, 39 42100 Reggio Emilia Italy Tel. +39 0522 924 244 Fax +39 0522 924 245 info@akse.it www.akse.it
VAT IT 01544980350 R.E.A. 194296 Cap. Soc. Euro 85.800,00 i.v.
Voltage connection
Use cables with max cross-section of 2,5 mm diagrams that follow.
Current connection
It is necessary to use external CTs with a primary rating adequate to the load to be metered and with a 5A or 1A secondary rating. The number of CTs to be used (1, 2 or 3) depends upon the type of network. Connect the CT output(s) to the terminals marked I1, I2, I3 (current input) of the instrument according to the applicable diagrams that follow. Use cables with cross-section adequate to the VA rating of the CT and to the distance to be covered. The max cross-section for the terminals is 4 mm2.
N.B. The CT secondary must always be in short circuit when not connected to the instrument in order to avoid damages and risks for the operator. Warning: The phase relationship among voltage and current signals, the P1-P2 orientation and the S1-S2 connection of the CT(s) must be carefully respected.
All disregard of this rule or of the wiring diagram leads to severe measurement errors.
4W Star (4 wire) 3PH-4W
P1 P2 S1 S2
P1 P2 S1 S2
P1 P2 S1 S2
17 18 19 20U1 U2 U3 N
L1
L2
L3
N
2
if fl exible 4 mm2 if rigid and connect them to the terminals marked voltage input on the instrument according to the applicable
3W Delta (3 wire) 3PH-3W-2CT SINGLE PHASE 1PH-2W
P1 P2
L1
S1 S2
N
17 18 19 20U1 U2 U3 N
AUXVOLTAGE INPUT POWER
P1 P2 S1 S2
P1 P2 S1 S2
17 18 19 20U1 U2 U3 N
AUXVOLTAGE INPUT POWER
L1
L2
L3
AUXVOLTAGE INPUT POWER
BI-PHASE 2PH-2W
P1 P2
L1
S1 S2
L2
17 18 19 20U1 U2 U3 N
AUXVOLTAGE INPUT POWER
VOLTAGE AND CURRENT CONNECTION
I1 I2 I3 RS-485 AUX
S1 S2 S1 S2 S1 S2 A BT10 11 12
I1 I2 I3 RS-485 AUX
S1 S2 S1 S2 S1 S2 A BT10 11 12
POWER SUPPLY and SERIAL LINE CONNECTION CONFIGURATION SETUP
The instrument is fi tted with a separate power supply. The power supply terminals are numbered (17) and (18). Use cables with max cross-section of 2,5 mm2 if fl exible, 4 mm2 if rigid.
I1 I2 I3 RS-485 AUX
S1 S2 S1 S2 S1 S2 A BT10 11 12
DIGITAL INPUTS AND OUTPUTS CONNECTION
20
19
Digital Inputs
Supply voltage (external): from 10 to 30
Current consumption: from 2 to 10mA
Max. count frequency 10 or 100Hz
N.B. For gas meters a galvanic separation is needed per ATEX standards
(Applicable only to type PFA8611-12)
+
DI (-)
DI (+)
19
!
Vdc
AUX
230 ÷ 240 V ±10%
LN
FUSE (50mA T)
17 18 19 20U1 U2 U3 N
AUXVOLTAGE INPUT POWER
Serial RS485 port
T
A
B
-
20
Digital outputs (optocoupled NPN transistor type per DIN 43864)
12
11
10
Maximum applicable voltage: 27 Vdc
Maximum switchable current: 27 mA
DO2
DO1
Common
!
C101
AUX
IN/OUT
11212
I1 I2 I3 RS-485 AUX
S1 S2 S1 S2 S1 S2 A BT10 11 12
I1 I2 I3 RS-485 AUX
S1 S2 S1 S2 S1 S2 A BT10 11 12
The instrument is programmed with the following default values:
RS485 address Communication
Initial Password 0000
27 9600, 8, N, 2
Type CT VT (PT)
OPERATING KEYS
Click Change selected fi eld
value
Click
Go to next window Back to initial entry fi eld Exits setup
2 sec
Change selected fi eld value Go to next fi eld
SETUP SEQUENCE
ENTERS INTO SET UP MODE (Push together for 2 seconds)
REQUEST PASSWORD 0000 ... 9999
RS-485
RS485 address 1 ... 247 Speed 2400, 4800, 9600, 19200, 38400 Data Bit 7 or 8 Parity N = No parity, E = Even parity, O = Odd parity Stop Bit 1 or 2
NETWORK
Type 3PH-3W-2CT, 3PH-4W, 2PH-2W, 1PH-2W CT (Primary) 10000 CT (Secondary) 1 o 5 VT (Primary) 400000 VT (Secondary) 300
CLEAR TOTAL COUNTERS NO, YES
CLEAR PARTIAL COUNTERS NO, YES
CLEAR MAX DEMAND NO, YES
ENTER NEW PASSWORD 0000 ... 9999
EXIT SETUP (Push for 2 seconds)
3PH-4W 5/5 1/1