Electra WNG 25 DCI Series Service Manual

Page 1

WNG 25 / 35 DCI Series

Indoor Units Outdoor Units
WNG 25 DCI ONG 25 DCI WNG 35 DCI ONG 35 DCI
SM WNGDCI 1-E.1 GB
REFRIGERANT
R410A
NOVEMBER – 2008
HEAT PUMP
Page 2

LIST OF EFFECTIVE PAGES

LIST OF EFFECTIVE PAGES
Note: Changes in the pages are indicated by a “Revision#” in the footer of each effected page
(when none indicates no changes in the relevant page). All pages in the following list represent effected/ non effected pages divided by chapters.
Dates of issue for original and changed pages are:
Original ....... 0 ........ March 2006
Total number of pages in this publication is 76 consisting of the following:
Page No.
Title ....................... 1
A ........................... 1
i ............................. 1
1-1 - 1-4 ................ 1
2-1 - 2-3 ................ 1
3-1 ........................ 1
4-1 - 4-3 ................ 1
5-1 - 5-13 .............. 1
6-1 - 6-4 ................ 1
7-1 ........................ 1
8-1-8-2 .................. 1
9-1-9-2 .................. 1
10-1 ...................... 1
11-1-11-19 ............. 1
12-1-12-6 .............. 1
13-1-13-6 .............. 1
14-1-14-6 .............. 1
15-1-15-10 ............ 1
Appendix -A ...........1
Revision No. #
Page No.
Revision No. #
Page No.
Revision No. #
Zero in this column indicates an original page.
*Due to constant improvements please note that the data on this service manual can be modified with out notice. **Photos are not contractual
A
SM WNGDCI 1-E.1 GB
Page 3

TABLE OF CONTENTS

Table of Contents
1. INTRODUCTION ...................................................................................................1-1
2. PRODUCT DATA SHEET .....................................................................................2-1
3. RATING CONDITIONS ..........................................................................................3-1
4. OUTLINE DIMENSIONS .......................................................................................4-1
5. PERFORMANCE DATA ........................................................................................5-1
6. PRESSURE CURVES ...........................................................................................6-1
7. ELECTRICAL DATA ..............................................................................................7-1
8. WIRING DIAGRAMS .............................................................................................8-1
9. REFRIGERATION DIAGRAMS .............................................................................9-1
10. TUBING CONNECTIONS ......................................................................................10-1
11. CONTROL SYSTEM .............................................................................................11-1
12. TROUBLESHOOTING ..........................................................................................12-1
13. EXPLODED VIEWS AND SPARE PARTS LISTS .................................................13-1
14. APPENDIX A .........................................................................................................14-1
SM WNGDCI 1-E.1 GB
i
Page 4
1. INTRODUCTION
1.1 General
The new WNG DCI split wall mounted range has expanded, comprising two additional RC (heat pump) models:
WNG 25 DCI
WNG 35 DCI
The indoor WNG units are available as LED or LCD display types featuring esthetic design, compact dimensions, and low noise operation.
1.2 Main Features
The WNG DCI INV series benefits from the most advanced technological innovations, namely:
DC inverter technology.

INTRODUCTION

R410A.
High COP.
Lego concept.
Pre-Charged units up to the max’ allowing tubing distance.
Networking system connectivity.
● A dry contact for clock or power shedding functions (configurable).
Base heater connection.
Cooling operation at outdoor temperature down to -10°C.
Heating operation at outdoor temperature down to -15°C.
Supports Indoor Air Quality features, such as – Ionizer, Active Electrostatic
Filter.
Indoor large diameter cross flow fan, allowing low noise level operation.
Bended indoor coil with treated aluminum fins and coating for improved
efficiency.
Easy access to the interconnecting tubing and wiring connections, so that
removing the front grill or casing is not necessary.
Refrigerant pipes can be connected to the indoor unit from 5 different optional
directions.
SM WNGDCI 1-E.1 GB
Water condensate tray is equipped with two optional drain connections.
Automatic treated air sweep.
Low indoor and outdoor noise levels.
Easy installation and service.
1-1
Page 5
INTRODUCTION
1.3 Indoor Unit
The indoor unit is wall mounted, and can be easily fitted to many types of residential and commercials applications.
WNG 25, 35
New design is available in LCD and LED versions. Old design is available in LED version only.
Indoor Unit features:
Feature WNG 25, 35
Display LCD or LED
Ionizer YES
ESF YES
Fresh air Optional
Indoor fan motor Variable speed (PG)
Horizontal motorized louver YES
Vertical motorized louver Optional
Heating element NO
M2L Cable port YES
Dry contact
1.4 Filtration
The WNG DCI Series presents several types of air filters:
Easily accessible, and re-usable pre-filters (mesh)
Pre-charged electrostatic filter (disposable)
Active carbon filter (disposable)
ESF. Active Electro Static re-usable filter (optional)
1.5 Ionizer (Optional)
A special design Ionizer protected by unique patents integrated into the indoor unit, generating negative ions to the room providing comfort and upgraded indoor air quality.
Presence detector or (jumper selected)
power shedding
1-2
SM WNGDCI 1-E.1 GB
Page 6
1.6 Control
The microprocessor indoor controller, and an infrared remote control, supplied as standard, provide complete operating function and programming. Remote controllers: RC-2/3/4/5/7, RC-4i-1, RCW, μBMS. Networking system Airconet version 4.2 and up, MIU SW version H8 and up. For further details please refer to the Operational Manual, Appendix A.
1.7 Outdoor Unit
The WNG DCI INV / LEX DCI INV outdoor units can be installed as floor or wall mounted units by using a wall supporting bracket. The metal sheets are protected by anti- corrosion paint work allowing long life resistance. All outdoor units are pre­charged. For further information please refer to the Product Data Sheet, Chapter 2.
ONG 25 DCI
ONG 35 DCI
Outdoor Unit Feature
INTRODUCTION
Feature ONG 25, 35 DCI
Display 3 LED’s
Base Heater Optional Outdoor Fan Variable speed DC Inverter
M2L cable Port No
1.8 Tubing Connections
Flare type interconnecting tubing to be produced on site. For further details please refer to the Installation Manual, Chapter 9.
1.9 Accessories
Item Description
MIU (WNG) MODBUS interface unit
MIU (K) MODBUS interface unit
RS485 Adapter
Base Heater
To be used as an interface
with RCW or μBMS remote
controllers
1.10 Inbox Documentation
SM WNGDCI 1-E.1 GB
M2L cable Port
For further details please refer to Optional Accessories, Chapter 17.
Each unit is supplied with its own installation and operation manuals.
1-3
Page 7
INTRODUCTION
1.11 Matching Table
1.11.1 R410A
OUTDOOR UNITS
MODEL REFR WNG25 DCI WNG35 DCI K25 DCI K35 DCI
INDOOR UNITS
ONG25 DCI R410A
ONG35 DCI R410A
The above table lists outdoor units and WNG indoor units which can be matched together. In addition the listed outdoor units can be matched with other types of indoor units such as cassettes.
For further information please refer to the relevant Service Manual.
√√
√√
1-4
SM WNGDCI 1-E.1 GB
Page 8

PRODUCT DATA SHEET

2. PRODUCT DATA SHEET
2.1 WNG 25 DCI
Model Indoor Unit WNG 25 DCI Model Outdoor Unit DCI 25 R410A
Installation Method of Pipe Flared
Characteristics Units Cooling Heating
Capacity (4) Power input (4) kW 0.595(0.42-1.0) 0.81(0.39-1.6)
EER (Cooling) or COP(Heating) (4) W/W 4.20 4.20 Energy efficiency class A A
Power supply
Rated current A 2.7 3.8 Power factor 0.97 0.97 Prated (IDU) W 32 Prated (IDU+ODU) W 1600 Starting current A 10.5 Circuit breaker rating A 15
Fan type & quantity Crossflow x 1 Fan speeds H/M/L RPM 1050/900/800 Air flow (1) H/M/L m3/hr 530/430/330 External static pressure Min Pa 0 Sound power level (2) H/M/L dB(A) 51/ - /39 Sound pressure level(3) H/M/L dB(A) 39/ - /26 Moisture removal l/hr 1 Condenstate drain tube I.D mm 16
INDOOR
Dimensions WxHxD mm 810x285x190 Net Weight kg 10.5 Package dimensions WxHxD mm 870x356x282 Packaged weight kg 13.5 Units per pallet units 28 Stacking height units 7evels Refrigerant control Electronical Expansion Valve Compressor type,model Single Rotary DC Inverter,Panasonic 5RS102XAB Fan type & quantity Propeller x 1 Fan speeds H RPM 830 Air flow H m3/hr 1780 Sound power level H dB(A) 61 Sound pressure level(3) H dB(A) 51 Dimensions WxHxD mm 795x610x290 Net Weight kg 38 Package dimensions WxHxD mm 970x650x394 Packaged weight kg 42 Units per pallet Units 9
OUTDOOR
Stacking height units 3 levels Refrigerant type R410A Standard charge kg(7.5m) 1.1 Additional charge No need
Liquid line In.(mm) 1/4"(6.35) Suction line In.(mm) 3/8"(9.53)
Connections between units
Operation control type Remote control Heating elements (Option) kW Others
Max.tubing length m. Max.20 Max.height difference
Btu/hr 8530(4780-12280) 11600(5120-17060)
kW 2.5(1.4-3.6) 3.4(1.5-5.0)
V 220-240 Ph 1 Hz 50
m. Max.10
(1)Airflow in ducted units;at nominal external static pressure. (2)Sound power in ducted units is measured at air discharge. (3)Sound pressure level measured at 1-meter distance from unit. (4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
SM WNGDCI 1-E.1 GB
2-1
Page 9
PRODUCT DATA SHEET
2.2 WNG 35 DCI
Model Indoor Unit WNG 35 DCI Model Outdoor Unit DCI 35 R410A
Installation Method of Pipe Flared
Characteristics Units Cooling Heating
Capacity (4)
Power input (4) kW 0.99(0.42-1.25) 1.125(0.39-1.75) EER (Cooling) or COP(Heating) (4) W/W 3.54 3.82 Energy efficiency class A A
Power supply
Rated current A 4.6 5.2 Power factor 0.97 0.97 Prated (IDU) W 40 Prated (IDU+ODU) W 1800 Starting current A 10.5 Circuit breaker rating A 15
Fan type & quantity Crossflow x 1 Fan speeds H/M/L RPM 1100/950/800 Air flow (1) H/M/L m3/hr 550/450/350 External static pressure Min Pa 0 Sound power level (2) H/M/L dB(A) 52/ - /39 Sound pressure level(3) H/M/L dB(A) 40/ - /26 Moisture removal l/hr 1.5 Condenstate drain tube I.D mm 16
INDOOR
Dimensions WxHxD mm 810x285x190 Net Weight kg 10.5 Package dimensions WxHxD mm 870x356x282 Packaged weight kg 13.5 Units per pallet units 28 Stacking height units 7levels Refrigerant control Electronical Expansion Valve Compressor type,model Single Rotary DC Inverter,Panasonic 5RS102XAB Fan type & quantity Propeller x 1 Fan speeds H RPM 830 Air flow H m3/hr 1780 Sound power level H dB(A) 62 Sound pressure level(3) H dB(A) 52 Dimensions WxHxD mm 795x610x290 Net Weight kg 38.5 Package dimensions WxHxD mm 970x650x394 Packaged weight kg 42.5 Units per pallet Units 9
OUTDOOR
Stacking height units 3 levels Refrigerant type R410A Standard charge kg(7.5m) 1.2 Additional charge No need
Liquid line In.(mm) 1/4"(6.35) Suction line In.(mm) 3/8"(9.53)
Connections between units
Operation control type Remote control Heating elements (Option) kW Others
Max.tubing length m. Max.20 Max.height difference
Btu/hr 11940(4780-14670) 14670(5100-19790)
kW 3.5(1.4-4.3) 4.3(1.5-5.8)
V 220-240
Ph 1 Hz 50
m. Max.10
1)Airflow in ducted units;at nominal external static pressure. (2)Sound power in ducted units is measured at air discharge. (3)Sound pressure level measured at 1-meter distance from unit. (4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
2-2
SM WNGDCI 1-E.1 GB
Page 10
3. RATING CONDITIONS
Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units).
Cooling:
Indoor: 27oC DB 19oC WB Outdoor: 35 oC DB
Heating:
Indoor: 20oC DB Outdoor: 7oC DB 6oC WB
3.1 Operating Limits
3.1.1 R410A

RATING CONDITIONS

Cooling
Heating
Upper limit Lower limit Upper limit Lower limit
Voltage
Indoor Outdoor
32oC DB 23oC WB 46oC DB
21oC DB 15oC WB -10oC DB
27oC DB 24oC DB 18oC WB
10oC DB -15oC DB -16oC WB
198 – 264 V
SM WNGDCI 1-E.1 GB
3-1
Page 11
4. OUTLINE DIMENSIONS
4.1 Indoor Unit: WNG 25, 35 DCI

OUTLINE DIMENSIONS

4.2
Outdoor Unit: ONG 25,35 DCI
SM WNGDCI 1-E.1 GB
4-1
Page 12
5. PERFORMANCE DATA
5.1 WNG 25 DCI
5.1.1 Cooling Capacity (kW) - Run Mode
ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC]
OD COIL
ENTERING AIR DB
TEMPERATURE
[C
0
]
-10 - 20
(protection range)
25
30
35
40
46
DATA 22/15 24/17 27/19 29/21 32/23
TC SC
PI TC 2.42 2.57 2.73 2.89 3.05 SC 1.64 1.67 1.71 1.74 1.77
PI 0.47 0.48 0.49 0.49 0.50 TC 2.30 2.46 2.62 2.77 2.93 SC 1.60 1.63 1.67 1.70 1.73
PI 0.52 0.53 0.54 0.55 0.56
TC 2.18 2.34 SC 1.56 1.59
PI 0.58 0.59
TC 2.07 2.23 2.38 2.54 2.70 SC 1.52 1.55 1.58 1.62 1.65
PI 0.63 0.64 0.65 0.66 0.67 TC 1.93 2.09 2.24 2.40 2.56
SC 1.47 1.50 1.53 1.57 1.60
PI 0.70 0.71 0.72 0.72 0.73

PERFORMANCE DATA

80 - 110 % of nominal 80 - 105 % of nominal
25 - 50 % of nominal
2.50
1.63
0.60
2.66 2.82
1.66 1.69
0.60 0.61
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., ( DB – Dry Bulb Temp., (
o
C)
o
C) ID – Indoor OU - Outdoor
5.1.2 Capacity Correction Factors
1.2
1.1
1
0.9
0.8
0.7
Capacity Ratio
0.6
0.5
20 25 30 35 40 45
Outdoor Tempera ture [deg C]
SM WNGDCI 1-E.1 GB
5-1
Page 13
PERFORMANCE DATA
5.1.3 Heating Capacity (kW) - Run Mode)
ID COIL ENTERING AIR DB TEMPERATURE [ºC]
OD COIL
ENTERING AIR
DB/WB
TEMPERATURE
[ºC]
-15/-16
-10/-12
-7/-8
-1/-2
2/1
7/6
10/9
15/12
15-24
(Protection Range)
DATA 15 20 25
TC 2.16 2.01 1.86
PI 0.49 0.54 0.58
TC 2.41 2.26 2.11
PI 0.59 0.64 0.68
TC 2.59 2.44 2.29
PI 0.66 0.71 0.76
TC 2.68 2.53 2.38
PI 0.70 0.75 0.80
TC 2.75 2.59 2.44
PI 0.72 0.77 0.82
TC 3.55
PI 0.76
TC 3.75 3.60 3.44
PI 0.81 0.86 0.90
TC 3.94 3.79 3.64
PI 0.85 0.90 0.95
TC 85 - 105 % of nominal
PI 80 - 120 % of nominal
3.40
0.81
3.25
0.86
LEGEND
TC
TH – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., ( DB – Dry Bulb Temp., (
o
C)
o
C) ID – Indoor OU - Outdoor
5.1.4 Capacity Correction Factors
1.2
1.1
1
0.9
0.8
0.7
Capaci ty Ratio
0.6
0.5
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [deg C]
5-2
SM WNGDCI 1-E.1 GB
Page 14
PERFORMANCE DATA
5.2 Capacity Correction Factor Due to Tubing Length
5.2.1 Cooling
1.01
1.00
0.99
0.98
0.97
0.96
0.95
0.94
Capacity Ratio
0.93
0.92
0.91
3 4 5 6 7 8 9 1011121314151617181920
Tubing Length [m]
5.2.2 Heating
1.02
1.00
0.98
0.96
0.94
Capacity Ratio
0.92
0.90
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Tubing Length [m]
SM WNGDCI 1-E.1 GB
5-3
Page 15
PERFORMANCE DATA
5.3 WNG 35 DCI
5.3.1 Cooling Capacity (kW) - Run Mode
ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC]
OD COIL
ENTERING AIR DB
TEMPERATURE
[ºC]
-10 - 20
(protection range)
25
30
35
40
46
DATA 22/15 24/17 27/19 29/21 32/23
TC SC
PI TC 3.38 3.60 3.83 4.05 4.27 SC 2.40 2.45 2.50 2.55 2.60
PI 0.78 0.79 0.81 0.82 0.84 TC 3.22 3.44 3.66 3.88 4.11 SC 2.34 2.39 2.44 2.49 2.54
PI 0.87 0.88 0.90 0.91 0.93
TC 3.06 3.28 SC 2.28 2.33
PI 0.96 0.98
TC 2.89 3.12 3.34 3.56 3.78 SC 2.22 2.27 2.32 2.37 2.42
PI 1.05 1.07 1.08 1.10 1.11 TC 2.70 2.92 3.14 3.36 3.58
SC 2.15 2.20 2.25 2.30 2.34
PI 1.16 1.18 1.19 1.21 1.22
80 - 110 % of nominal 80 - 105 % of nominal
25 - 50 % of nominal
3.50
2.38
0.99
3.72 3.94
2.43 2.48
1.00 1.02
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., ( DB – Dry Bulb Temp., (
o
o
C)
C)
ID – Indoor OU - Outdoor
5.3.2 Capacity Correction Factors
1.2
1.1
1
0.9
0.8
0.7
Capacity Ratio
0.6
0.5
20 25 30 35 40 45
Outdoor Temperature [deg C]
5-4
SM WNGDCI 1-E.1 GB
Page 16
5.3.3 Heating Capacity (kW) - Run Mode
ID COIL ENTERING AIR DB TEMPERATURE [ºC]
OD COIL
ENTERING AIR
DB/WB
TEMPERATURE
[ºC]
-15/-16
-10/-12
-7/-8
-1/-2
2/1
7/6
10/9
15/12
15-24
(Protection Range)
DATA 15 20 25
TC 2.74 2.55 2.35
PI 0.68 0.74 0.81
TC 3.05 2.86 2.66
PI 0.81 0.88 0.95
TC 3.28 3.09 2.90
PI 0.92 0.99 1.06
TC 3.39 3.20 3.01
PI 0.97 1.04 1.11
TC 3.47 3.28 3.09
PI 1.00 1.07 1.14
TC 4.49
PI 1.06
TC 4.74 4.55 4.36
PI 1.12 1.19 1.26
TC 4.99 4.80 4.60
PI 1.18 1.25 1.32
TC 85 - 105 % of nominal
PI 80 - 120 % of nominal
4.30
1.13
PERFORMANCE DATA
4.11
1.19
LEGEND
TC
TH – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., ( DB – Dry Bulb Temp., (
o
C)
o
C) ID – Indoor OU - Outdoor
5.3.4 Capacity Correction Factors
1.2
1.1
1
0.9
0.8
0.7
Capacity Ratio
0.6
0.5
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [deg C]
SM WNGDCI 1-E.1 GB
5-5
Page 17
PERFORMANCE DATA
5.4 Capacity Correction Factor Due to TUbing Length
5.4.1 Cooling
1.01
1.00
0.99
0.98
0.97
0.96
0.95
0.94
Capaci ty Ratio
0.93
0.92
0.91
3 4 5 6 7 8 9 1011121314151617181920
Tubing Length [m]
5.4.2 Heating
1.02
1.00
0.98
0.96
0.94
Capacity Ratio
0.92
0.90
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Tubing Length [m]
5-6
SM WNGDCI 1-E.1 GB
Page 18
6. PRESSURE CURVES
6.1 Model: WNG 25 DCI
6.1.1 Cooling - Test Mode

PRESSURE CURVES

Suction Pressure [kPa]
Discharge Pressure [kPa]
Suction Pressure V S. Outdoor Temp'
1400
1300
1200
1100
1000
900
800
700
600
500
10 15 20 25 30 35 40 45
Outdoor Temp.(°C DB)
Discharge Pressure VS. Outdoor Temp'
4000 3750 3500 3250 3000 2750 2500 2250 2000 1750 1500 1250 1000
10 15 20 25 30 35 40 45
Indoor DB/W B
Temp.
22/15 24/17 27/19 29/21 32/23
Indoor DB/WB
Temp.
22/15
24/17
27/19
29/21
32/23
SM WNGDCI 1-E.1 GB
Outdoor Tem p.(°C DB)
6-1
Page 19
PRESSURE CURVES
6.1.2 Heating - Test Mode
Suction Pressure VS. Outdoor Temp'
1300 1200 1100 1000
900 800 700 600 500 400
Suction Pressure [kPa]
300 200
-15 -10 -5 0 5 10 15
Indoor DB
Temp'
15 20 25
Outdoor Tem p.(°C WB)
3500 3250 3000 2750 2500 2250 2000 1750 1500 1250
Discharge Pressure [kPa]
1000
Discharge Pressure VS. Outdoor Temp'
Indoor DB
Temp'
15
20
25
-15 -10 -5 0 5 10 15
Outdoor Tem p.(°C WB)
6-2
SM WNGDCI 1-E.1 GB
Page 20
6.2 Model: WNG 35 DCI
6.2.1 Cooling - Test Mode
Suction Pressure VS. Outdoor Tem p'
PRESSURE CURVES
1400
1300
1200 1100
1000
Suction Pressure [kPa]
4000 3750 3500 3250 3000 2750 2500 2250 2000 1750 1500
Discharge Pressure [kPa]
1250 1000
900
800 700
600
500
10 15 20 25 30 35 40 45
Outdoor Tem p.(°C DB)
Discharge Pressure VS. Outdoor Temp'
10 15 20 25 30 35 40 45
Indoor DB/WB
Temp.
22/15
24/17
27/19
29/21
32/23
Indoor DB/WB
Temp.
22/15 24/17 27/19 29/21 32/23
SM WNGDCI 1-E.1 GB
Outdoor Te mp.(°C DB)
6-3
Page 21
PRESSURE CURVES
6.2.2 Heating - Test Mode
Suction Pressure VS. Outdoor Temp'
4000 3750 3500 3250 3000 2750 2500 2250 2000 1750 1500
Discharge Pressure [kPa]
1300 1200 1100 1000
900 800 700 600 500 400
Suction Pressure [kPa]
300 200
-15 -10 -5 0 5 10 15
Outdoor Temp.(°C WB)
Discharge Pressure VS. Outdoor Temp'
-15 -10 -5 0 5 10 15
Indoor DB
Temp'
15 20 25
Indoor DB
Tem p'
15
20
25
6-4
Outdoor Tem p.(°C WB)
SM WNGDCI 1-E.1 GB
Page 22

ELECTRICAL DATA

7. ELECTRICAL DATA
7.1 Single Phase Unit
Model WNG 25 DCI WNG 35 DCI
Power Supply 1 PH ,220-240VAC ,50HZ Connected to Indoor Maximum Current 10A Inrush Current \ Starting Current\ Circuit Breaker 16A Power Supply wiring no. x cross section 3 X 1.5 mm² Interconnecting cable no. x cross section 4 X 1.5 mm²
NOTE
(a)
(b)
(a) Inrush current is the current when power is up (charging the DC capacitors
at outdoor unit controller).
(b) Starting current is the current at compressor start up.
Power wiring cord should comply with local lows and electrical regulations requirements.
35A 10A
SM WNGDCI 1-E.1 GB
7-1
Page 23
8. WIRING DIAGRAMS
8.1 WNG 25 / 35 DCI
Display
(clock)
Dry contact

WIRING DIAGRAMS

P9
PH-12
Power supply
~230V 50Hz
4527310
Flash port
2
P1
1
To metal sheet
P30
INDOOR UNIT CIRCUIT DIAGRAM
OUTDOOR UNIT CIRCUIT DIAGRAM
45 3
M1
step motor
t
e
r
w
o
u
F
ESF
e
i
n
r
w
F
e
Ionzer
213
i
t
e
regulator
Voltage
ICTRAT
d
6
h
i
t
e
k
a
c
45
u
e
31
IFAN
2
a
y
r
n
o
b
w
capacitor
a
y
SUCT
CTT
OCT
OAT
G
F
s
V
p
c
V
c
H
T
R
A
OFAN
E
d
V
c
Base
heater
valve
Reverse
e
i
t
e
Choke coil
c
k
w
n
COMP
d
P6
2
1
2
o
p
S
E
P12
1
2
o
p
S
E
(red)
1
P8
l
u
b
P2
h
w
P10
212
P5
(red)
1
P4
e
r
w
b
l
l
b
g
r
1uF 400V
P16 P15P11 P3P19P14
g
r
22
1
1
2
1
2
1
B
l
u
e
Y
e
l
l
o
w
5 6
O
r
a
n
g
e
a
B
l
c
k
3 4
e
R
d
1 2
2
1
2
1
B
l
u
W
h
B
l
a
W
V
B
r
o
R
e
U
P13
P20
P22
Indoor unit controller PCB
P8
P20
P19
P2
P21P22
P18
P17
P16
P1
P4
P14
Outdoor unit controller PCB
P13
P11
P9
P3
magnetic ring
Jumper
P17
31
2 4
megatool
P7
42 3
megatool
1
P6
1
2
3
P7
4 5
6
5 4
JP9
31
26
P12
EARTH
Y/G
N-COM
P10
COM
N L
Y/G
L
N
4/L
5/C
6
EEV
magnetic ring
EMI filter PCB
Blue
Brown
Y/G
Blue
Red
Brown
Y/G
Blue
Red
Brown
Y/G
N/3
L/4
C/5
Y/G
Brown
Red
FUSE
N
L
COM
EARTH
L-F
N-F
COM
NCOM
EARTH
Black
Red
Blue
SM WNGDCI 1-E.1 GB
8-1
Page 24
9. REFRIGERATION DIAGRAMS
9.1 Heat Pump Models
9.1.1 WNG 25 / 35 DCI: Cooling Mode
OUTDOOR UNIT
Sensor

REFRIGERATION DIAGRAMS

INDOOR UNIT
Sensor
Reverse
valve
EEV
Outdoor coil
Strainer
Strainer
9.1.2 WNG 25 / 35 DCI: Heating Mode
OUTDOOR UNIT
Sensor
Valves
Flared
connection
Indoor coil
INDOOR UNIT
Sensor
SM WNGDCI 1-E.1 GB
Outdoor coil
Reverse
Strainer
valve
EEV
Strainer
Valves
Flared
connection
Indoor coil
9-1
Page 25
10. TUBING CONNECTIONS
TUBE (Inch)
TORQUE (Nm)

TUBING CONNECTIONS

¼’’ Ǫ’’
Flare Nuts Valve Cap Service Port Cap
 6ALVE0ROTECTION#APEND  2EFRIGERANT6ALVE0ORTUSE!LLENWRENCHTOOPENCLOSE  6ALVE0ROTECTION#AP  2EFRIGERANT6ALVE  3ERVICE0ORT#AP  &LARE.UT  5NIT"ACK3IDE  #OPPER4UBE
7HENTHEOUTDOORUNITISINSTALLEDABOVETHEINDOORUNITANOILTRAPISREQUIREDEVERYMALONGTHESUCTIONLINE ATTHELOWESTPOINTOFTHERISER)NCASETHEINDOORUNITISINSTALLEDABOVETHEOUTDOORNOTRAPISREQUIRED
11-13 40-45 13-20 13-20 11-13 11-13
SM WNGDCI 1-E.1 GB
10-1
Page 26

CONTROL SYSTEM

11. CONTROL SYSTEM
11.1 General Functions and Operating Rules
The DCI software is fully parametric. All the model dependent parameters are shown in Blue color and with Italic style [parameter]. The parameters values are given in the last section of this control logic chapter of the service manual.
11.1.1 System Operation Concept
The control function is divided between indoor and outdoor unit controllers. Indoor unit is the System ‘Master’, requesting the outdoor unit for cooling/heating capacity supply. The outdoor unit is the system nless it enters into a protection mode'Slave’ and it must supply the required capacity avoiding it from supplying the requested capacity. The capacity request is transferred via indoor to outdoor communication, and is represented by a parameter called ‘NLOAD’. NLOAD is an integer number with values between 0 and 127, and it represents the heat or cool load felt by the indoor unit.
11.1.2 Compressor Frequency Control
11.1.2.1 NLOAD setting
The NLOAD setting is done by the indoor unit controller, based on a PI control scheme. The actual NLOAD to be sent to the outdoor unit controller is based on the preliminary LOAD calculation, the indoor fan speed, and the power shedding function.
NLOAD limits as a function of indoor fan speed: Indoor Fan Speed Maximum NLOAD Cooling Maximum NLOAD Heating Low Medium High Turbo Auto
NLOAD limits as a function of power shedding: Mode Power Shedding OFF Power Shedding ON Cool No limit Nominal Cooling Heat No limit Nominal Heating
Max NLOADIF1C Max NLOADIF2C Max NLOADIF3C Max NLOADIF4C Max NLOADIF5C
127 127 127 127 127
11.1.3 Target Frequency Setting
The compressor target frequency is a function of the NLOAD number sent from the indoor controller and the outdoor air temperature. Basic Target Frequency Setting:
NLOAD Target Frequency 127 10 < NLOAD < 127 Interpolated value between minimum and maximum frequency 10 0 Compressor is stopped
SM WNGDCI 1-E.1 GB
Maximum frequency
Minimum frequency
11-1
Page 27
CONTROL SYSTEM
Target frequency limits as a function of outdoor air temperature )OAT(: OAT Range Cool mode limits Heat mode limits OAT No limit<6 6≤OAT<15 15 ≤ OAT < 24 24 ≤ OAT No limit
MaxFreqAsOATC
MaxFreqAsOAT1H
MaxFreqAsOAT2H
11.1.4 Frequency Changes Control
Frequency change rate is 1 Hz/sec.
11.1.5 Compressor Starting Control
Frequency
Step 3
Step 2
Step 1
1
Minute
1
Minute
Time
Min 10 Minutes
11.1.6 Minimum On and Off Time
3 minutes.
11.1.7 Indoor Fan Control
10 Indoor fan speeds are determined for each model. 5 speeds for cool/dry/fan modes and 5 speeds for heat mode. When user sets the indoor fan speed to a fixed speed )Low/ Medium/ High(, unit will operate constantly at set speed. When Auto Fan is selected, indoor unit controller can operate in all speeds. The actual speed is set according to the cool/heat load.
11.1.7.1 Turbo Speed
The Turbo speed is activated during the first 30 minutes of unit operation when auto fan speed is selected and under the following conditions: Difference between set point and actual room temperature is bigger then 3 degrees. Room temperature 22 for cooling, or 25 for heating.><
11-2
SM WNGDCI 1-E.1 GB
Page 28
CONTROL SYSTEM
11.1.8 Heating Element Control
Heating element can be started if LOAD 0.8 mumNLOAD AND Indoor Coil temperature> * Maxi <45. The heating element will be stopped when LOAD 0.5 MaximumNLOAD OR if Indoor Coil<* Temperature 50.>
11.1.9 Outdoor Fan Control
7 outdoor fan speeds are determined for each model. 3 speeds for cool and dry modes, and 3 speeds for heat mode, and a very low speed. Outdoor fan speed is a function of compressor frequency and outdoor air temperature (OAT). 4 routines for fan control are determined. The control routine selection depends on operation mode, compressor speed, outdoor air temperature (OAT) and heat sink temperature (HST).
Routine Conditions A Heating with OAT 15<
or Cooling with OAT > 20
0
C
0
C, or HST 50>0C or Faulty OAT
B Cooling with 20 C Cooling with 7 D Heating with OAT 15>
0
C>OAT>500C
0
C>OAT
0
C
Outdoor Fan Speed Compressor Frequency (CF) Routine A Routine B Routine C Routine D CF 0 OFF OFF OFF OFF= 10 ≤ CF < OFLowFreq Low Low Very Low Low 10 ≤ CF < OFMedFreq Medium Low Very Low Low
OFMedFreq ≤ CF High Low Low Medium
When compressor is switched to OFF and the heat sink temperature is above 55 degrees, the outdoor fan will remain ON in low speed for up to 3 minutes.
11.1.10 EEV (electronic Expansion valve) Control
EEV opening is defined as EEV = EEVOL+EEV EEVOLis the initial EEV opening as a function of the compressor frequency, operation mode, unit model and capacity. EEV
is a correction value for the EEV opening that is based on the compressor temperature.
CV
During the first 10 minutes of compressor operation EEV Once the first 10 minutes are over, the correction value is calculated as follow: EEV EEV EEV
(N-1) + EEV
CV
is the correction based on the compressor temperature. A target compressor temperature
CTT
CTT
is set depending on frequency and outdoor air temperature, and the actual compressor temperature is compared to the target temperature to set the required correction to the EEV opening.
CV
CV
0.= (n) =
CV
11.1.11 Reversing Valve (RV) Control
Reversing valve is on in heat mode. Switching of RV state is done only after compressor is off for over 3 minutes.
11.1.12 Ioniser Control
Ioniser is on when unit is on AND indoor fan is on AND Ioniser power switch (on Ioniser) is on.
SM WNGDCI 1-E.1 GB
11-3
Page 29
CONTROL SYSTEM
11.1.13 Electro Static Filter )ESF( Control
ESF is on when ESF switch is on, Safety switch is pressed, unit is on, AND indoor fan is on.
11.1.14 Base Heater Control
0
When OAT is connected, Base Heater will be on when unit is in heating and OAT<2 When OAT is disconnected, Base Heater will be on when unit is in heating.
C.
11.2 Fan Mode
In high/ medium/ low indoor fan user setting, unit will operate fan in selected speed. In AutoFan user setting, fan speed will be ad ng to the differencejusti automatically according between actual room temperature and user set point temperature.
11.3 Cool Mode
NLOAD is calculated according to the difference between actual room temperature and user set point temperature by PI control. In high/ medium/ low indoor fan user setting, unit will operate fan in selected speed. In AutoFan user setting, fan speed will be ad8usted automatically according to the calculated NLOAD.
11.4 Heat Mode
NLOAD is calculated according to the difference between actual room temperature and user set point temperature by PI control. In high/ medium/ low indoor fan user setting, unit will operate fan in selected speed. In AutoFan user setting, fan speed will be adng to the calculated NLOAD.
11.4.1 Temperature Compensation
In wall mounted, ducted, and cassette models, 3 degrees are reduced from room temperature reading (except when in I-Feel mode), to compensate for temperature difference between high and low areas in the heated room, and for coil heat radiation on room thermistor. The temperature compensation can be enabled/disabled by shortening of J2 on the indoor unit controller.
Model J2 Shorted J2 Opened Wall mounted Compensation
Disabled Cassette Compensation Enabled Compensation Disabled Ducted Compensation Enabled Compensation Disabled Floor/Ceiling Compensation
Disabled
Compensation Enabled
Compensation Enabled
11-4
SM WNGDCI 1-E.1 GB
Page 30
11.4.2 Indoor Fan Control in Heat Mode
Indoor fan speed depends on the indoor coil temperature:
CONTROL SYSTEM
ICTST
ICTVL ICTTICTHICTL
11.5 Auto Cool/Heat Mode
When in auto cool heat mode unit will automatically select between cool and heat mode according to the difference between actual room temperature and user set point temperature )ΔT(. Unit will switch from cool to heat when compressor is off for 3 minutes, and ΔT < -3. Unit will switch from heat to cool when compressor is off for 5 minutes, and ΔT < -3.
11.6 Dry Mode
As long as room temperature is higher then the set point, indoor fan will work in low speed and compressor will work between 0 and MaxNLOADIF1C Hz. When the room temperature is lower than the set point, compressor will be switched OFF and indoor fan will cycle 3 minutes OFF, 1 minute ON.
11.7 Protections
There are 5 protection codes. Normal (Norm) – unit operate normally. Stop Rise (SR) – compressor frequency can not be raised but does not have to be decreased. HzDown1 (D1) – Compressor frequency is reduced by 2 to 5 Hz per minute. HzDown2 (D2) – Compressor frequency is reduced by 5 to 10 Hz per minute. Stop Compressor (SC) – Compressor is stopped.
11.7.1 Indoor Coil Defrost Protection
ICT<-2SCSCSCSCSC
-2 ≤ ICT < 0 D1 D1 D2 D2 D2 0 ≤ ICT < 2 SR SR D1 D2 D2 2 ≤ ICT < 4 SR SR SR D1 D2 4 ≤ ICT < 6 Norm Norm SR SR D1 6 ≤ ICT < 8 Norm Norm Norm SR SR 8 ≤ ICT Normal
SM WNGDCI 1-E.1 GB
ICT TrendICT Fast Increasing
Increasing No change Decreasing Fast
Decreasing
11-5
Page 31
CONTROL SYSTEM
11.7.2 Indoor Coil over Heating Protection
ICT TrendICT
Fast
Decreasing
Decreasing No Change Increasing Fast
Increasing ICT55SCSCSCSCSC> 53 <ICT ≤ 55 D1 D1 D2 D2 D2 49 < ICT ≤ 53 SR SR D1 D2 D2 47<ICT49SRSRSRD1D2 45 < ICT ≤ 47 Norm Norm SR SR D1 43 < ICT ≤ 45 Norm Norm Norm SR SR ICT ≤ 43 Normal
11.7.3 Compressor over Heating Protection
Compressor temperature can be in one of 5 control zones )4 in protection, and 1 normal(, according to the following chart.
CTT
Stop-Compresor
CTTOH4
CTTOH3
CTTOH2
CTTOH1
Control Status Compressor Temperature
P3
P2
P1
Normal
Else
Increases P1 Norm SR P2 D1 SR P3 D2 D1 Stop Compressor SC
11.7.4 Compressor over Current Protection
CCR
Stop-Compresor
CCROC4
11-6
CCROC3
HzDown2
HzDown1
CCROC2
Stop-Rise
CCROC1
Normal
SM WNGDCI 1-E.1 GB
Page 32
CONTROL SYSTEM
11.7.5 Heat Sink Over Heating Protection (NA for DCI 25 and 35)
HST TrendHST
Decreasing No Change Increasing HST SC SC SC>90 85<HST90D1D2D2 82 < HST ≤ 85 SR D1 D2 80 < HST ≤ 82 SR SR D1 78 < HST ≤ 80 Norm Norm SR HST ≤ 78 Normal
11.7.6 Outdoor Coil Deicing Protection
11.7.6.1 Deicing Starting Conditions
Deicing operation will start when either one of the following conditions exist: Case 1: OCT OAT – 8 AND TLD<>DI Case 2: OCT OAT – 12 AND TLD 30 minutes.<> Case 3: OCT is Invalid AND TLD DI> Case 4: Unit is ust switched to STBY AND OCTj<OAT-8 Case 5: NLOAD 0 AND OCT OAT -8=<
OCT – Outdoor Coil Temperature OAT – Outdoor Air Temperature TLD – Time from Last Deicing DI – Deicing Interval (Time Interval Between Two Deicing)
Deicing interval time when compressor is first started in heat mode, is 10 minutes if OCT < -2, and is 40 minutes in other cases. Deicing interval time is changed (increased/ decreased in 10 minutes steps) as a function of deicing time. If deicing time is shorter then former deicing time, the deicing interval time will be increased. If deicing time is longer then former deicing time, the deicing interval time will be decreased.
SM WNGDCI 1-E.1 GB
11-7
Page 33
CONTROL SYSTEM
T
11.7.6.2 Deicing Protection Procedure
OCT
12
0
Threshold
COMP
RV
OFAN
EEV
ON
HEAT
COOL
ON
OFF
Any
T1 T2
EEVDeicerOpen
36 seconds, T3 nds= 6 seco
T1
max. 12 minutes
DT
T3 T3
11.8 Condensate Water Over Flow Protection
Each of the pins P1, P2, P3 can have two options: 1 – When it is shorted with P4 0 – When it is not shorted to P4
11.8.1 3 Levels Logic (used in floor/ceiling models)
P2 P3 Level
00 L0 1 0 L1 11 L23& 01 L4
11-8
SM WNGDCI 1-E.1 GB
Page 34
Water Level
LEVEL4
LEVEL 3
LEVEL1
Pump
NLOAD
OPER LED
CONTROL SYSTEM
ON
OFF
ANY
0
BLINK
NORMAL
11.8.2 1 Level Logic (used in all models except for floor/ceiling models)
P2 P3 Level
Water Level
OPER
LED
NLOAD
PUMP
Don`t care Don`t care
Overflow
Normal
ON
OFF
BLINK
ANY
0
ON
OFF
1 Normal
0 Overflow
Overflow when
unit is ON
NLOAD is
forced to 0
8min 8min
Overflow when
unit is OFF
8min
11.9 Indoor Unit Dry Contact
Indoor unit Dry contact has two alternative functions that are selected by J8.
J8 Presence Detector Connection No Limit Forced to STBY=Open J8 Power Shedding Function No Limit Limit NLOAD=Open
SM WNGDCI 1-E.1 GB
Function Contact = Open Contact = Short
11-9
Page 35
CONTROL SYSTEM
11.10 Operating the Unit from the Mode Button
Forced operation allows to start, stop and operate in Cooling or Heating, in pre-set temperature according to the following table:
Forced operation Mode Pre-set Temperature Cooling 200C
0
Heating 28
C
11.11 On Unit Controls and Indicators
11.11.1 Indoor Unit Controller Controls and Indicators For All Models Except for Floor/Ceiling model
STAND BY
INDICATOR
OPERATION INDICATOR
TIMER INDICATOR Lights up during Timer and Sleep operation.
FILTER INDICATOR Lights up when Air Filter needs to be cleaned.
COOLING INDICATOR
HEATING INDICATOR
Mode SWITCH
(COOL/HEAT/OFF)
RESET / FILTER
SWITCH
Lights up when the Air Conditioner is connected to power and ready to receive the R/C commands Lights up during operation. Blinks for 300 msec., to announce that a R/C infrared signal has been received and stored. Blinks continuously during protections (according to the relevant spec section).
Lights up when system is switched to Cool Mode by using the Mode Switch on the unit. Lights up when system is switched Heat Mode by using the Mode Switch on the unit. Every short pressing , the next operation mode is selected, in this order : SB → Cool Mode → Heat Mode → SB → In long pressing system enters diagnostic mode. For short pressing: When Filter LED is on - turn off the FILTER INDICATOR after a clean filter has been reinstalled. When Filter LED is off able/disable the buzzer announcer, if selected.
11-10
SM WNGDCI 1-E.1 GB
Page 36
11.11.2 Indoor Unit Controls and Indicators for LCD Display
STBY Cool Heat Auto Fan Dry OFF SPT(1*)
SPT(1*)
SPT(1*)SPT(1*) SPT(1*) SPT(1*)
CONTROL SYSTEM
OFF(2*)
OFF(2*) OFF(2*) OFF(2*) OFF(2*) OFF(2*) OFF(2*)
(Low)
(Med)
(High)
(Turbo)
(Auto) Backlight(red) OFF OFF ON(3*) ON(3*) Backlight(green) OFF ON(3*) OFF
OFF
OFF
OFF
OFF
OFF
User setting IFAN speed
ON(2*)ON(2*) ON(2*) ON(2*) ON(2*)
User setting IFAN speed
User setting IFAN speed
ON(3*)
User setting IFAN speed
ON(3*) ON(3*) ON(3*)
User setting IFAN speed
OFF
SM WNGDCI 1-E.1 GB
11-11
Page 37
CONTROL SYSTEM
11.11.3 Indoor Unit Controller Controls and Indicators for Floor/Ceiling Model
STANDBY INDICATOR
OPERATE INDICATOR
(4)
TIMER INDICATOR FILTER INDICATOR COOLING INDICATOR HEATING INDICATOR FAN MODE INDICATOR
(4)
FAN SPEED INDICATORS
TEMP. SETTING INDICATORS FAN SPEED BUTTON
TEMP. SETTING UP BUTTON TEMP. SETTING DOWN BUTTON
MODE BUTTON
POWER BUTTON RESET / FILTER BUTTON
Lights up when the Air Conditioner is connected to power and is ready for operation
1. Lights up during operation.
2. Blinks for 300 msec., to announce that a R/C infrared signal has been received and stored.
3. Blinks continuously during protections (according to the relevant spec section).
Lights up during Timer and Sleep operation.
1. Lights up when Air Filter needs to be cleaned.
2. Blinks during Water Over Flow in PXD models. (Cf. Sect. 7.3) Lights up when system is switched to Cool Mode by using the Mode Switch on the unit. Lights up when system is switched Heat Mode by using the Mode Switch on the unit. Lights up in Fan Mode activated by local switches.
L -- Lights up when IFAN setting is Low. M -- Lights up when IFAN setting is Medium. H -- Lights up when IFAN setting is High. A -- Lights up when IFAN setting is Auto. Each one of the seven indicators indicates the following SPT: 18, 20, 22, 24, 26, 28, 30 ]
o
c[. The odd number temperatures are indicated by turning on the two adcent indicators. Press this button to change the speed of the IFAN. Each pressing change the speed in the sequence of:
..... L → M → H → Auto → L → ...
Pressing this button increases the SPT by 1 Note: The Max SPT is 30
Pressing this button decreases the SPT by 1 Note: The Min SPT is 18
o
C.
o
C.
o
C.
o
C.
Every short pressing , the next operation mode is selected, in this order : SB → Cool Mode → Heat Mode → SB → In long pressing system enters diagnostic mode. Toggle the unit between OPER & STBY modes.
For short pressing: When Filter LED is on - turn off the FILTER INDICATOR after a clean filter has been reinstalled. When Filter LED is off able/disable the buzzer announcer, if selected. In long pressing system enters set up mode (if in SB).
11.11.4 Outdoor Unit Controller Indicators
Unit has three LED SB LED is ON when power is ON (230 VAC, even when no communication). STATUS LED is ON when COMP is ON, and Blinks according to diagnostics mode definitions when either fault or protection occurs. FAULT LED Blinks according to diagnostics mode definitions when either fault or protection occurs.
11-12
SM WNGDCI 1-E.1 GB
Page 38
CONTROL SYSTEM
11.12 Test Mode
11.12.1 Entering Test Mode
System can enter Test mode in two ways: Automatically when the following conditions exists for 30 minutes continuously: Mode l, Set point 16, Room temper= Coo = ature = 27±1, Outdoor temperature = 35±1 Or Mode = Heat, Set point = 30, Room temperature = 20±1, Outdoor temperature = 7±1 Manually when entering diagnostics with the following settings: Mode = Cool, Set point = 16 Mode = Heat, Set point = 30
11.12.2 Unit Operation in Test Mode
In test mode, the unit will operate in fixed settings according to the indoor fan speed setting:
Indoor Fan Speed Setting Unit Setting Low Minimum Capacity Setting High Nominal Capacity Setting Auto Maximum Capacity Setting During test mode, protections are disabled, except for stop compressor status.
SM WNGDCI 1-E.1 GB
11-13
Page 39
CONTROL SYSTEM
11.13 SW Parameters
11.13.1 Indoor Units SW Parameters
General Parameters for All Models:
Parameters defining the indoor fan speed as a function of Indoor Coil temperature in heat mode (ICT):
ICTST Speed ICT to stop indoor fan 25 ICTVLSpeed ICT to go down to very low speed 28 ICTLSpeed ICT to start in very low speed 30 ICTHSpeed ICT to start in increase speed from very low 32 ICTTSpeed ICT to enable Turbo fan speed 40
Model Depended Parameters:
Parameter name
NLOAD limits as a function of selected indoor fan speed
MaxNLOADIF1C 40 40 MaxNLOADIF2C 53 53 MaxNLOADIF3C 120 120 MaxNLOADIF4C 127 127 MaxNLOADIF5C 127 127
IFVLOWC 700 700 IFLOWC 800 800 IFMEDC 900 950 IFHIGHC 1050 1100 IFTURBOC 1150 1200 IFVLOWH 700 700 IFLOWH 800 850 IFMEDH 950 1000 IFHIGHH 1100 1150 IFTURBOH 1200 1250
Nominal Compressor Frequency
NomLoadC 40 62 NomLoadH 55 67
Parameter Name
NLOAD limits as a function of selected indoor fan speed
MaxNLOADIF1C 40 40 40 40 MaxNLOADIF2C 53 56 56 60 MaxNLOADIF3C 120 90 90 90 MaxNLOADIF4C 127 90 90 90 MaxNLOADIF5C 127 90 90 90
Nominal Compressor Frequency
NomLoadC 40 60 56 63
DCI 25 DCI 35
Indoor Fan speeds
K 25 K 35 K 35S K 50
Wall Mounted Models
Cassette Models
NomLoadH 55 69 73 80
11-14
SM WNGDCI 1-E.1 GB
Page 40
11.13.2 Outdoor Units SW Parameters
Parameter Name DCI25 DCI35 DCI 50 DCI50 DUO
Compressor Parameters
MinFreqC 30 33 20 20
MaxFreqC 64 80 85 97
MinFreqH 30 35 20 26 MaxFreqH 81 93 99 106 Step1Freq 60 60 60 60 Step2Freq 70 70 70 80 Step3Freq 90 90 90 90
Frequency limits as a function of outdoor air temperature
MaxFreqAsOATC 50 50 64 62 MaxFreqAsOAT1H 65 75 85 85 MaxFreqAsOAT2H 60 60 60 60
CONTROL SYSTEM
Compressor Over Heating Protection
CTTOH1 94 94 94 90 CTTOH2 98 98 98 95 CTTOH3 102 102 102 102 CTTOH4 105 105 105 105
Compressor Over Current Protection [A]
CCR01 7.1 7.1 10 10 CCR02 7.5 7.5 10.5 10.5 CCR03 7.9 7.9 10.8 10.8 CCR04 8.3 8.3 11.2 11.2
Outdoor Fan Speed (RPM)
VL 200 200 200 200
OFLOWC 550 550 600 600
OFMEDC 700 700 760 830 OFMAXC 830 830 920 920
OFLOWH 550 550 600 600
OFMEDH 700 700 830 920 OFMAXH 830 830 1000 1000
SM WNGDCI 1-E.1 GB
Outdoor Fan Limit Control
OFLowFreq 45 45 40 40 OFMedFreq 57 57 70 70
11-15
Page 41

TROUBLESHOOTING

12. TROUBLESHOOTING WNG 25 / 35 DCI
Warning
When Power Up – the whole outdoor unit controller, including the wiring, is under HIGH
VOLTAGE
Never open the Outdoor unit before turning off the PowerHIG
When turned off, the system is still charged (400V)yle
It takes about 4 Min. to discharge the system.
Touching the controller before discharging may cause an electrical shock
For safe handling of the controller please refer to section 12.6 below.
12.1 Single Split system failures and corrective actions
No SYMPTOM PROBABLE
CAUSE
1 Power supply indicator
(Red LED) does not light up.
2 Unit does not respond to
remote control message
3 Unit responds to remote
control message but Operate indicator (Green LED) does not light up
(louvers are opened and Green LED does light up)
5 Indoor fan works when
unit is OFF, and indoor fan speed is not changed by remote control command.
6 Compressor does not
start
7 Compressor stops
during operation and Green LED remains on
No power supply Check power supply. If power supply
Remote control message not reached the indoor unit
Problem with display PCB
Unit in heat mode and coil is still not warm. Problem with PCB or capacitor
PCB problem Replace controller
Electronics control problem or protection Electronic control or power supply problem
CORRECTIVE ACTION
is OK, check display and display wiring. if OK, replace controller. Check remote control batteries, if batteries are OK, check display and display wiring, if OK, replace display PCB. If still not OK replace controller. Replace display PCB. If still not OK replace controller.
Change to cool mode and check.4 Indoor fan does not start
Change to high speed and Check power supply to motor is higher than 130VAC (for triack controlled motor) or higher than 220VAC for fixed speed motors, if OK replace capacitor, if not OK replace controller
Perform diagnostics (See 12.3 below), and follow the actions described. Perform diagnostics (See 12.3 below), and follow the actions described.
SM WNGDCI 1-E.1 GB
12-1
Page 42
TROUBLESHOOTING
No SYMPTOM PROBABLE
CAUSE
8 Compressor is on but
outdoor fan does not work
9 Unit works in wrong
mode )cool instead of heat or heat instead of cool(
10 All components are
operating properly but no cooling or no heating
11 Compressor is over
heated and unit does not generate capacity
12 Units goes into
protections and compressor is stopped with no clear reason
13 Compressor motor is
generating noise and no suction occurs
14 Water leakage from
indoor unit
15 Freezing of outdoor unit
in heat mode and outdoor unit base is blocked with ice
16 Unit operates with wrong
fan speeds or wrong frequency
Problem with outdoor electronics or outdoor fan Electronics or power connection to RV
Refrigerant leak Check refrigeration system.
EEV problem Check EEV
Control problem or refrigeration system problem
Phase order to compressor is wrong Indoor unit drainage tube is blocked
Wrong umperj settings
CORRECTIVE ACTION
Check outdoor fan motor according to the procedure in section 12.5.3 below, if not OK replace controller Check RV power connections, if OK, Check RV operation with direct 230VAC power supply, if OK, Replace outdoor controller.
Perform diagnostics )See 12.3 below(, and follow the actions described.
Check compressor phase order.
Check and open drainage tube.
Connect base heater.
Perform diagnostics (See 12.3 below), and check if units is operating by EEPROM parameters.
12.2 Checking the refrigeration system
Checking system pressures and other thermodynamic measures should be done when system is in Test Mode (in Test mode, system operates in fixed settings). The performance curves given in this manual are given for unit performance in test mode when high indoor fan speed is selected. Entering test mode: Set unit to Cool/16 degrees/High indoor fan speed, or Heat/30 degrees/High indoor fan speed, and enter diagnostics.
12-2
SM WNGDCI 1-E.1 GB
Page 43
TROUBLESHOOTING
12.3 Judgment by Indoor/Outdoor Unit Diagnostics
Enter diagnostics mode - press for five seconds Mode button in any operation mode. Acknowledgment is by 3 short beeps and lights of COOL and HEAT LEDs. Then, every short pressing of Mode button will scroll between Indoor and Outdoor unit diagnostic modes by the acknowledgment of 3 short beeps and lighting of COOL and HEAT LED s.' During the Outdoor unit diagnostics all four Indoor LED’s, (STBY, Operate, Filter and Timer) are blinking. When Indoor diagnostics is displayed, all four LED’s (STBY, Operate, Filter and Timer) are ON. When system enters diagnostics mode, only one fault code is shown. Order of priority is from the lower to the higher number. Diagnostics is continuously ON as long as power is ON. The current system operation mode will not be changed. If no fault occurred in the system, no fault code will be displayed during normal operation mode. The last fault code will be displayed even if the system has recovered from that fault. The last fault will be deleted from the EEPROM after the system has exit diagnostics mode. In diagnostics mode, system fault / status will be indicated by blinking of Heat d Cool LEDs. The coding method will be as follows: Heat LED will blink 5 times in 5 seconds, and then will be shut off for the next 5 seconds. Cool LED will blink during the same 5 seconds according to the following Indoor / Outdoor unit tables: Note: 0 – OFF, 1-ON
12.3.1 Indoor unit Diagnostics
No Problem 54321
1 RT-1 is disconnected 00001 2 RT-1 is shorted 00010 3 RT-2 is disconnected 00011 4 RT-2 is shorted 00100 5 Reserved 00101 7 Communication mismatch 0 0111 8 No Communication 0 1 0 0 0
No Encoder 0 1 0 0 19 10 Reserved 0 1 0 1 0 11 Outdoor Unit Fault 01011
... Reserved
17 Defrost protection 10001
Deicing Protection 1 0 0 1 0
18 19 Outdoor Unit Protection 1 0 0 1 1 20 Indoor Coil HP Protection 10100
21 Overflow Protection 1 0 1 0 1
22 Reserved 24 EEPROM Not Updated 11000 25 Bad EEPROM 1 1 0 0 1 26 Bad Communication 11010 27 Using EEPROM data 11011 28ModelA 11100
Model B 1 1 1 0 1
29 30 Model C 11110 31 Model D 1 1111
SM WNGDCI 1-E.1 GB
12-3
Page 44
TROUBLESHOOTING
12.3.2 Indoor unit diagnosis and corrective actions
No.
1
2
3
4
5
6
7
8
9
Fault
Sensor failures of all types
Communication mismatch
No Communication
No Encoder
Outdoor Unit Fault
EEPROM Not Updated
Bad EEPROM
Bad Communication
Using EEPROM data
Probable Cause Corrective Action
Check sensor connections or replace sensor.
Indoor and Outdoor controllers are with different Versions. Communication or grounding wiring is not good. Indoor electronics or motor Checkmotorwiring,ifok,.
Outdoor controller problem Switch to Outdoor.
System is using ROM parameters and not EEPROM parameters.
Communication quality is low Reliability.
No problem. System is using EEPROM parameters.
Replace Indoor controller.
Check Indoor to Outdoor wiring and grounding.
replace motor, if still not ok, replace Indoor controller.
diagnostics. No action, unless special parameters are required for unit operation. No action, unless special parameters are required for unit operation. Check Indoor to Outdoor wiring and grounding.
12-4
SM WNGDCI 1-E.1 GB
Page 45
 2XWGRRU XQLW 'LDJQRVWLFV
No Problem 5 4 3 2 1
1 OCT is disconnected 2 OCT is shorted 3 CTT is disconnected 4 CTT is shorted 5 HST is disconnected (when enabled) 6 HST is shorted (when enabled) 7 OAT is disconnected (when enabled) 8 OAT is shorted (when enabled)
9 TSUC is disconnected (when enabled) 10 TSUC is shorted (when enabled) 11 IPM Fault 12 Bad EEPROM 13 DC under voltage 14 DC over voltage 15 AC under voltage 16 IDU/ODU Communication mismatch 17 No Communication 18 Reserved
20 Heat sink Over Heating 21 Deicing 22 Compressor Over Heating 23 Compressor Over Current 24 No OFAN Feedback 25 OFAN locked 26 Compressor Lock 27 Bad Communication
TROUBLESHOOTING
0 0 0 0 1 0 0 0 1 0 0 0 0 1 1 0 0 1 0 0 0 0 1 0 1 0 0 1 1 0 0 0 1 1 1 0 1 0 0 0 0 1 0 0 1 0 1 0 1 0 0 1 0 1 1 0 1 1 0 0 0 1 1 0 1 0 1 1 1 0 0 1 1 1 1 1 0 0 0 0 1 0 0 0 1 1 0 0 1 0 1 0 1 0 0 1 0 1 0 1 1 0 1 1 0 1 0 1 1 1 1 1 0 0 0 1 1 0 0 1 1 1 0 1 0 1 1 0 1 1
SM WNGDCI 1-E.1 GB
1 – ON, 0 – OFF
Only one code is shown. Order of priority is 1-24. Diagnostics is continuously
ON as long power is on.
12-5
Page 46
TROUBLESHOOTING
12.3.4 Outdoor unit diagnosis and corrective actions
o.
Fault
Sensors failures of all types
IPM Fault Electronics HW
Bad EEPROM No action, unless special
DC under/over Voltage Electronics HW
AC under Voltage Check outdoor unit power
Indoor / Outdoor unit Communication mismatch No Communication Communication or
Compressor Lock Switch unit to STBY and
Bad Communication Communication quality is
Probable Cause Corrective Action
Check sensors connections or replace sensors. Check all wiring and
problem
problem
Indoor and Outdoor controllers are with different versions
grounding wiring is not good.
low reliability
umper settings, if OK, replace electronics.
parameters are required for unit operation. Check outdoor unit power supply voltage
supply voltage Replace Indoor controller
Check Indoor to Outdoor wiring and grounding
restart Check Indoor to Outdoor wiring and grounding
12-6
SM WNGDCI 1-E.1 GB
Page 47
TROUBLESHOOTING
12.4 Judgment by MegaTool
MegaTool is a special tool to monitor the system states.
Using MegaTool requires:
A computer with RS232C port.
A connection wire for MegaTool.
A special MegaTool software. Use MegaTool according to following procedure:
Setup MegaTool software: copy the software to the computer.
Connect RS232C port in computer with MegaTool port in Indoor/Outdoor unit
controller by the connection wire.
Run the software and choose the COM port, you can monitor the A/C system state in monitor tab.
12.5 Simple procedures for checking the Main Parts
12.5.1 Checking Mains Voltage.
Confirm that the Mains voltage is between 198 and 264 VAC. If Mains voltage is out of this range, abnormal operation of the system is expected. If in range check the Power (Circuit) Breaker and look for broken or loosed cable lugs or wiring mistake(s).
12.5.2 Checking Power Input.
If Indoor unit power LED is unlighted, power down the system and check the fuse of the Indoor unit. If the fuse is OK replace the Indoor unit controller. If the fuse has blown, replace the fuse and power up again. Checking Power Input procedure for the Outdoor unit is the same as with the Indoor unit.
12.5.3 Checking the Outdoor Fan Motor.
Enter Test Mode (where the OFAN speed is high) Check the voltage between lead wires according to the normal value as following:
Between red wire and black wire: 310VDC +/- 20V
Between orange wire and black wire: 15VDC +/- 1V
Between yellow wire and black wire: 2-6VDC
12.5.4 Checking the Compressor.
The compressor is brushless permanence magnetic DC motor. Three coil resistance is same. Check the resistance between three poles. The normal value should be below 0.5 ohm (TBD).
12.5.5 Checking the Reverse Valve (RV).
Running in heating mode, check the voltage between two pins of reverse valve
connector, normal voltage is 220VAC.
12.5.6 Checking the electrical expansion valve (EEV).
SM WNGDCI 1-E.1 GB
The EEV has two parts, drive part and valve. The drive part is a step motor the valve. Check the drive voltage (12VDC). When Outdoor unit is power on, EEV shall run and have click and vibration.
12-7
Page 48
TROUBLESHOOTING
12.6 Precaution, Advise and Notice Items
12.6.1 High voltage in Outdoor unit controller.
Whole controller, including the wires that are connected to the Outdoor unit controller may have the potential hazard voltage when power is on. Touching the Outdoor unit controller may cause an electrical shock. Advise: Don naked lead wire and don t insert finger, conductor or anything''t touch the else into the controller when power is on.
12.6.2 Charged Capacitors
Three large-capacity electrolytic capacitors are used in the Outdoor unit controller. Therefore, charging voltage (380VDC) remains after power down. Discharging takes about four minutes after power is off. Touching the Outdoor unit controller before discharging may cause an electrical shock.
12.6.3 Additional advises
When disassemble the controller or the front panel, turn off the power supply.
When connecting or disconnecting the connectors on the PCB, hold the whole housing, dont pull the wire.
There are sharp fringes and sting on shell. Use gloves when disassemble the A/C units.
12-8
SM WNGDCI 1-E.1 GB
Page 49

EXPLODED VIEWS AND SPARE PARTS LISTS

13. EXPLODED VIEWS AND SPARE PARTS LISTS
13.1 Outdoor Unit: ONG 25 / 35 DCI
SM WNGDCI 1-E.1 GB
13-1
Page 50
EXPLODED VIEWS AND SPARE PARTS LISTS
13.2 Outdoor Unit: ONG 25 / 35 DCI
No. Part No. Description Unit
1 433218
2 4526340
3 433223
4 4526476
5 4527092
6 433215
7 4523060
8 4526299 Partition 1
9 4526403
10 4524177 Gas valve (R410A) 1
11 4524176 Liquid valve(R410A) 1
12 4526224 EMI fliter board 901-098-00 1
13 4526396 Chock Assy. 167-021-01 1
14 4526223 AC-IN connected wire 1
15 4526968 Earthing wire for DCI 1
16 4526222 Fuse connecting wire 1
17 4526300
18 4526220
19 4526219
204107 Cable clip nylon
20
4519188 4 poles terminal block
21
433229 Value cover
22
4522509 4-Way valve coil
23
24 4526367
4526393
4518952 4-way valve (DCI25)
25
4518951 4-way valve (DCI35)
26 4526221
27 4526204
4526775 Compressor top thermistor(CTT)
28
29 4526774
30 4526776
31 4526969
32 4526828
33 4526827
34 4519606
433228 Back side net
35
36 4526368
37 4526298
38 4519614
39 4526480
4519300 Nut M5 L
40
41 433225
42 4519607
Front panel A
Air inlet ring-420
Painting insulation plate
Axial fan OD=401
DC motor for DCI25/35
Motor support
Base painting Assy.
Outdoor DC inverter controller (English)
Therminal sheet
Fuse stand JEF-511B(EHK P/N:150-038-00)
Fuse 65TS(15A,230)150-031-00
4-way valve welding Assy. (DCI25)
4-way valve welding Assy. (DCI35)
Compressor wire
DC Inverter compressor Assy. 5RS102XAB
Outside air thermistor(OAT)
Outside coil thermistor(OCT)
Suction coil thermistor(SUCT)
EEV Coil (CAN-MD 12FKS-1 White)
Electronic expansion value (CAMB20YGFKS-1)
Right side panel
Condenser soldering assy
Bridge
Painting top cover
Gasket for axial fan
Handle
Left side panel painting plate
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
13-2
SM WNGDCI 1-E.1 GB
Page 51
EXPLODED VIEWS AND SPARE PARTS LISTS
13.3 Indoor Unit: N-WNG 25 / 35 LCD DCI
SM WNGDCI 1-E.1 GB
13-3
Page 52
EXPLODED VIEWS AND SPARE PARTS LISTS
13.4 Indoor Unit: N-WNG 25 / 35 LCD DCI
No. Part No. Name Total Quan. Version
1A 4526940 Grille A 1 1 1B 4526941 Grille B 1 1 1C 4526942 Grille C 1 1 1D 4526943 Grille D 1 1 1E 4526944 Grille E 1 1
2 452811300 LCD Display 1 1 3 4518655 Air Filter 2 2 4 4519132 Active Carrbon Filter 1 1
4519744 Cold Catalyst Filter 1 1 5 4527029 Frame Assy 1 1 6 4526946 LCD Display Lens Assy 1 1 7 4526952 Screw Cover 2 1 8 433133 Ionizer Unit(Optional) 1 3
8A 4526951 Ionizer Cover(Optional) 1 1
9 4526389 R410Aevaporator Assy HPI DC WNG9/12 1 1
10 4518664 Draining Hose 1 1 11 4518682 Gear BoxAssy 1 1 12 4527434 Air Outlet Assy 1 1 13 4518646 Louver Support 2 1 14 4518638 Upper Flap 1 1 15 4526953 Lower Flap 1 1 16 4518642 Vert. Louver Link 1 1 17 4518640 Vert. Louver A 2 1
4518641 Vert. Louver B 10 1
18 4518643 Vert. Louver Lock 1 1 1
4518644 Vert. Louver Lock 2 1 1
4518645 Vert. Louver Lock 3 1 1
19 4518662 Bearing Assy 1 1 20 4518661 Cross Flow Fan 1 1 21 4518730 Base Assy 1 1 22 4518656 Mounting Hook 2 1 23 4518657 Tube Lock 1 1 24 4518670 Installation Plate 1 1 25 4518654 Tube Bracket 1 1 26 4519864 Motor 1 4 27 4518651 Motor Side Cover 1 1 28 4518650 Motor Cover 1 1 29 4519365 Step Motor Wire B 1 1 30 4518737 Step Motor Wire A 1 1 31 4518679 Step Motor 2 1 32 4520061 Power Wire (Elco) 1 1
Power Wire (Electra) 1 1
Power Wire (Airwell) 1 1 33 4519900 Ionizer Cable A(Optional) 1 1 34 433134 Ionizer Power(Optional) 1 1 35 452867800 Transformer (Optional) 1 2 36 4526180 Indoor DC inverter controller 916-512-00 1 1 37 452872800 Electrostatic Filter (Optional) 1 1
37A 4519338 Filter Frame (Optional) 1 1
38 4526950 Terminal Cover 1 1
13-4
SM WNGDCI 1-E.1 GB
Page 53
EXPLODED VIEWS AND SPARE PARTS LISTS
13.5 Indoor Unit: WNG 25 / 35 LED DCI
SM WNGDCI 1-E.1 GB
13-5
Page 54
EXPLODED VIEWS AND SPARE PARTS LISTS
r
13.6 Indoor Unit: WNG 25 / 35 LED DCI
No. Part No. Name Total Quan. Version
1 4518647 Grill A 1 1
1A 4519364
2 4518648 3 4523611 4 4518655 5 4519132
4519744 6 4518734 7 4518653 8 433133
8A 4519337
9 4526389
10 4518664
4522754
11 4518682 12 4518637
4518733
13 4518646 14 4518638 15 4518639 16 4518642 17 4518640
4518641
18 4518643
4518644
4518645
19 4518662 Bearing Assy 1 1 20 4518661 21 4518730 Base Assy 1 1 22 4518656 23 4518657 24 4518670 25 4518654 26 4519864 Motor 1 3 27 4518651 28 4518650 29 4519900 30 433134 31 4518737 32 4518679 33 4521158 34 452867800 35 4526180 36 452872800 37 4518792
Grill B Display panel (Only for grille A) Display Air filter Active carrbon filter Cold catalyst filter Frame Assy Screw cover Ionizer unit(optional) Ionizer cover(optional) R410A evaporator Assy HPI DC WNG9/12 Draining hose Draining hose (for Australia market) Gear box Assy Air outlet Air outlet Assy (It is including from No.13 to No.19) Louver support Upper flap Lower flap Vert. louver link Vert. louver A Vert. louver B Vert. louver lock 1 Vert. louver lock 2 Vert. louver lock 3
Cross flow fan
Mounting hook Tube lock Installation plate Tube bracket
Motor side cover Motor cover Ionizer cable A (optional) Ionizer power (optional) Step motor wire Step motor Power wire (European plug) Transformer (optional) Inddor DC inverter controller 916-512-00 Electrostatic filter (optional)
Terminal cove
11 11 11 21 11 11 11 21 13 11 11 11
11 11
21 11 11 11 21
10 1
11 11 11
11
21 11 11 11
11 11 11 11 11 11 11 12 11 11 11
13-6
SM WNGDCI 1-E.1 GB
Page 55
EXPLODED VIEWS AND SPARE PARTS LISTS
13.7 Indoor Unit: WNG 25 / 35 LED DCI
SM WNGDCI 1-E.1 GB
13-7
Page 56
EXPLODED VIEWS AND SPARE PARTS LISTS
No.P
N
T
n
A
A
)
A
r
A
0
13.8 Indoor Unit: N-WNG 25 / 35 LED DCI
artNo.
1 1B 1C 1D 1E
8A 4526951
10 4518664 Draining Hose 1 1 11 4518682 Gear BoxAssy 1 1 12 4527434 Air Outlet Assy 1 1 13 4518646 Louver Support 2 1 14 4518638 Upper Flap 1 1 15 4526953 Lower Flap 1 1 16 4518642 Vert. Louver Link 1 1 17 4518640 Vert. Louver A 2 1
18 4518643 Vert. Louver Lock 1 1 1
19 4518662 Bearing Assy 1 1 20 4518661 Cross Flow Fan 1 1 21 4518730 Base Assy 1 1 22 4518656 Mounting Hook 2 1 23 4518657 Tube Lock 1 1 24 4518670 Installation Plate 1 1 25 4518654 Tube Bracket 1 1 26 4519864 Motor 1 1 27 4518651 Motor Side Cover 1 1 28 4518650 Motor Cover 1 1 29 4518737 Step Motor Wire A 1 1 30 4518679 Step Motor 1 1 31 4520061 Power Wire (Elco) 1 1
33 4519900 34 433134 35 452867800 36 4526180 37 452872800 Electrostatic Filter (Optional) 1 1
37
38 452695
4526940 4526941 Grille B 1 1 4526942 4526943
4526944 2 4527557 3 4518655 Air Filter 2 2 4 4519132 Active Carrbon Filter 1 1
4519744 Cold Catalyst Filter 1 1 5 4527029 Frame Asy 1 1 6 452818600 Display Cover Assy. 1 1 7 4526952 Screw Cover 2 1 8 433133 Ionizer Unit(Optional) 1 3
9 4526389
4518641 Vert. Louver B 10 1
4518644 Vert. Louver Lock 2 1 1
4518645 Vert. Louver Lock 3 1 1
4520278
4521158
4522565
4521159
4519338
Grille A
Grille C Grille D Grille E LED Display
Ionizer Cover(Optional) R410
Power Wire (Electra without plug) Power Wire (European plug Power Wire (Airwell for Australia) Power Wire (Gorenje) Ionizer Cable Ionizer Powe Transformer (Optional) Indoor DC inverter controller 916-512-00
Filter Frame (Optional) Terminal Cover 1 1
evaporator Assy HPI DC WNG9/12
(Optional)
ame
(Optional)
otalQuan.Versio
11
11 11 11 11
11 11
11 11 11 11 11 11 11 11
11
13-8
SM WNGDCI 1-E.1 GB
Page 57
EXPLODED VIEWS AND SPARE PARTS LISTS
13.9 Outdoor Unit: ONG 25 / 35 DCI (new)
SM WNGDCI 1-E.1 GB
13-9
Page 58
EXPLODED VIEWS AND SPARE PARTS LISTS
13.10 Outdoor Unit: ONG 25 / 35 DCI (new)
No. Part No. Description Unit
1433218 2 4526340 3433223 44526476 5452889600
6 433215 7 4523060
464600016 84526299 Partition 1 94526403 Outdoor DC inverter controller (English) 1
10 4524177 Gas valve (R410A)1 11 4524176 Liquid valve(R410A)1 12 4526224 EMI fliter board 901-098-00 1 13 4526396 Chock Assy. 167-021-01 1 14 4526223 AC-IN connected wire 1 15 4526968Earthing wire for DCI 1 16 4526222 Fuse connecting wire 1 17 4526300 Therminal sheet 1 18 4526220 Fuse stand 19 4526219 Fuse 65TS(15A,230)150-031-00 1
20 204107 Cable clip nylon 1 21 4519188 4 poles terminal block 1 22 433229 Value cover 1 234522509 4-Way valve coil 1 244526367 4-way valve welding Assy. (DCI25) 1
4526393 4-way valve welding Assy. (DCI35) 1
25 4518951 4-way valve (DCI25) 1
4518952 4-way valve (DCI35) 1
26 4526221
26204 DC Inverter compressor Assy. 5RS102XAB1
27 45 284526775Compressor top thermistor(CTT) 1 294526774
453238900
30 4526776 31 4526828EEV Coil (CAN-MD 12FKS-1 White) 1 32 4526827 Electronic expansion value (CAMB20YGFKS-1) 1 33 4519606 34 433228
464800002
35 4526368 36 4526298 37 4519614 38 4526480
39 4519300 Nut M5 L 1 40 433225 41 4519607 42 453225500 43 467100004
Front panel A Air inlet ring-420 Painting insulation plate Axial fan OD=401 DC motor for DCI25/35
Motor support Base painting Assy. Base plate painting Assy.(for Nordic ma
JEF-511B(EHK P/N:150-038-00) 1
Compressor wire
Outside air thermistor(OAT) Sensor /OAT (for Nordic market) Outside coil thermistor(OCT)
Right side panel Back side net Guard net painting assy. (for Nordic market) Condenser soldering assy Bridge Painting top cover Gasket for axial fan
Handle Left side panel painting plate Support/ OAT 7
Heater/Base plate (for Nordic market)
(for Nordic market)
rket)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
13-10
SM WNGDCI 1-E.1 GB
Page 59

APPENDIX A

APPENDIX A
INSTALLATION AND OPERATION MANUAL
► INSTALLATION MANUAL WNG 25 / 35 DCI
► OPERATING MANUAL WNG 25 / 35 DCI
SM WNGDCI 1-E.1 GB
14-1
Loading...