ELECTRA WMN-7/9 RC | WMN-7/9 ST MANUALE TECNICO (EN)

Page 1

TECHNICAL AND SERVICE MANUAL

CONTENTS

  • 1. FEATURES
  • 2. SPECIFICATIONS & OPERATING RANGE
  • 3. PERFORMANCE CURVES
  • 4. OUTLINE DIMENSIONS
  • 5. OPERATING & INSTALLATION MANUAL
  • 6 REFRIGERATION DIAGRAMS
  • 7. WIRING DIAGRAMS
  • 8 CONTROLS, MAIN P.C.B
  • 9. CONTROL FUNCTION
  • 10. CONTROLS, CHECKING PROCEDURES
  • 11. TROUBLESHOOTING
  • 12. INDOOR AND OUTDOOR PARTS LIST
Page 2

WALL MOUNTED SPLIT A.C

MODES OF OPERATION , FUNCTIONS AND FEATURES

The air conditioner is based on a microcomputer control system with remote wall mounted LCD display and control unit, programmed for the following modes and functions:

r
c
COOL Cools, dehumidifies and filters the room air. Maintains desired site temperature.
HEAT Heats and filters the air. Maintains desired site temperature.
AUTO Automatically switches from COOLING to HEATING or from HEATING to COOLING, maintaining the desired temperature according to the room conditions.
DRY Dehumidifies and moderately cools the room. In DRY Mode the air conditioner operates at an increased dehumidifying power. This function is recommended to be used when temperature is rather cool but the humidity is high.
FAN Recalculates and filters the room air. Maintains constant air movement in the room.
* AUTO FAN The air conditioner automatically selects the FAN speed in accordance to the room temperature. At the start, the unit operates at high fan speed. As the room air gets closer to the desired temperature, the fan switches on a lower speed for quieter operation.
HOT KEEP In HEATING and in AUTO FAN, the fan will be turned off when the compressor is
not in operation and will not be restarted, unless the indoor coil reaches adequate
temperature. This HOT KEEP feature prevents uncomfortable cold air drafts.
AUTO FAN Is therefore, recommended to be used when the air conditioner is in
HEATING mode.
I FEEL Switches the temperature sensing point to the place where the remote control is located (in normal operation the temperature sensor is located behind the intake grille of the air conditioner). This function is designed to provide a personalized environment by transmitting the temperature control information from where the remote control is placed. The communication between the remote control and the central control unit is done by infrared signal. When using this function, the remote control should always be aimed without obstructions at the air conditioner.
TIMER Real time control and display, automatically turns the air conditioner ON or OFF according to the time of day setting, ensuring comfort conditions before returning home, without wasting electricity. It turns off the air conditioner automatically when sleeping.
SLEEP Designed to automatically reset the temperature setting. In COOLING mode the temperature rises one degree centigrade after each consecutive hour, up to three hours, from the start of the mode. In HEATING mode, the reverse occurs, the air conditioner lowers its temperature one degree every hour. When in SLEEP Mode, the operation will automatically turn off after seven hours. This function saves energy when the air conditioner is operating during off hours.
.ELECTRA consumer products LTD REV 01 1/97 SERIES WMN PG 1-1
Page 3
WALL I MOUNTED SPLIT A .C FEATURES 1
VERTICAL
AIR SWING
Automatic swing c
upward and down
room.
Automatic swing of supply air in vertical direction. The flap moves automatically in upward and downward direction to spread the conditioned air evently through the room.
AIR DIRECTION
POSITIONING
Manual positionir g of the air flap to provide desirable air flow angle.
ROOM TEMP. Measures and dis olays room temperature.
FILTER
INDICATION
Filter indicator on
cleaning. After cle
the indoor unit display is turned on when the filter reque
eaning and reinstalling the filter,the system should be re
iires
eset.
- BUZZER A soft buzzer will
command sent by
unit's memory. The
display panel.
sound from the indoor unit display to indicate that a
y the remote control has been accepted and stored in the
his feature may be easily canceled by the user from the
1e
;
_ ON UNIT
OPERATION
The aair condition
turned OFF direc
remote control.
ner can be turned ON for COOLING or HEATING or be
tly from the indoor unit display panel without the use of
the
_ 3-MIN DELAYED
RUN
The compressor is protected by a three minute delayed restart.
- MEMORY The microprocess
in. Therefore, whe
will resume operat
or retains the last data entry whether or not the unit is pluen the unit restarts after a power disruption or power failution in the same mode as before the power disruption. ıgged
ure, it
P LOCK Freezes the last activated, the rem operation setting on the remote control. When LOC
ote control will not be able to control the air conditioner.
CK is
.ELECTRA consumer products LTD REV. 01 1/97 SERIES WMN PG 1-2
Page 4
Item Coo.ing Heating Cooling only Capacity Kca/hr 1820 2050 1820 Btu/hr 7300 8200 7300 W 2140 2400 2140 Total input W 2140 2400 2140 Total input W 710 660 710 Power supply (ph. cy, voltage) 1/p, 50Hz, 220-240V 710 660 N Starting current A 0.08 8 Power supply (ph. cy, voltage) Fain dro ubput W 8 7 O Heat scchanger Fein finsin Texture 6 O Fain dro rubput W 5 5 Arfow (LO-HI) MP/hr 260-340 7 I Condensate drain I D Mm (n) 12.7 (1/12) T Dimensions W mm (n) 12.7 (1/12) T Dimensions mm (n) 12.7 (1/12) T Dimensions mm (n) 164 (6-7/16 Model WMN - 7 RC WMN - 7 ST
Function Cooling relating relating Cooling relating Item
Capacity Ream 18.20 2030 18.20 Buthr 7300 8200 7300 27300 Total input W 2140 24400 2140 Imput W 710 660 710 Imput W 710 660 710 Imput W 8 1 1 Running current A 0.3 0 5 External finish Texture 1 6 7 R Fan motor output W 5 5 Arflow (LO-HI) MPhr 200340 2000 V Operation control type Remote control LCD Noise evel (LO-M-HI) MC(A) 31-35-37 Condensate drain ID mm (in) 12.7 (1/12) 1 Noise evel (LO-M-HI) Mb(A) 31-35-37 1 Missions Wmm(in) 12.7 (1/12) 1 Missio evel (LO-M-HI) Mb(A) Function Cooling Heating
Bdml 7.300 8.200 7.300 Total input W 2140 2400 2140 Total input W 710 660 7710 Power supply (ph. cy, voltage) ip, 50Hz, 220-240V input W 8 I Running current A 0.08 3 D External finish Texture Flat finich 1 O Heat exchanger Flat finich Texture 1 O Fan difficienci (LO-M-II) M M hr 260-340 1 O Operation contro type Remote control LCD N Noise level (LO-M-HI) db(A) 31:35:37 I Condensate drain D mm.(n) 127 (1/12) D memsions mm. (n) 127 (1/12) D D Veght Kg (lbs) 8 2 (18) Packing dimensions Packing dimensions Texture U Noise level (LO-M-HI) W 700 650 710 I Dimmsions< Capacity 1820 2050 1820
Total input W 2140 2400 2140 Total input W 710 660 710 Imput W 710 660 710 Imput W 8 1 149,50Hz,220-240V Imput W 8 1 R Starting current A 0.3 1 1 D External fin 5h Texture 1 Q Heat exchanger Fild fin coll 1 R Fan notor output W 5 Airflow (LO-HI) MP/hr 263-37 1 Condensate drain I D mm.(in) 127 (1/12) T Dimensions W mm.(in) 161 (32-1/16) 1 1 Veight Kg (bs) 8 2 (18) 1 D mm.(in) 127 (1/12) 1 Btu/nr 7300 8200 7300
Total Power supply (ph, cy, voltage) Tota Formation Formation Input W 10 10 50H2, 220-240V 10 Input W 6 8 10 10 N Starting current A 0.08 10 10 N External finish Texture 10 Q Heat exchanger Flat fin coll 10 R Fan (drive) W 5 Airfow (LO-HI) M A /hr 260-340 260-340 10 U Operation control type Remote control LCD Noise level (LO-M-HI) db(A) 31-35-37 I Condensate drain LD mm (in) 1164 (6-7/16) 10 N Noise level (LO-M-HI) db(A) 31-35-37 10 U Dimensions Wm (in) 27 (1/12) 10 Mit stacking units 8 10 11 U Dimensions Tatalinn .4 2140 2400 2140
Power supp y (pr), cy, voltage) (p), 00%2, 220-240V Input W 8 Running current A 0.3 D External finish Texture O Heat exchanger Flat fin coll Fan (drive) Crossflow (direct) x 1 R Fan (drive) Crossflow (direct) x 1 R Fan motor output W 5 Ariflow (LO-H) M o /nr 260-340 O Operation control type Remote control LCD Noise level (LO-M-H) db(A) 31-35-37 Condensate drin L.D mm(n) 815 (32-1/16) D Dmm.(n) 815 (32-1/16) Packing dimensions Mm 905X355X260 Unit stacking units 8 Power supp y (ph, cy, voltage) 1$\u0per 50 Hz, 220-240V U Refrigerant control Capilary tube O Input W 700 D mm.(n) 2650 V 710 R Refrigerant control Capilary tube 710 Total Inpl ut
Doworoupply (ph. ov. volto
ac) VV 710 000
1 ≠ 50 U 220 240
/10
Imput
Running current V 0 N Starting current A 0.3 D External finish Texture O Heat exchanger Flat fin col O Fan (drive) Crossfow (direct) x 1 Fan motor output W 5 Airflow (LO-H) M?hr 260-340 Operation control type Remote control LCD Noise level (LO-M-H) db(A) 31-35-37 I Condensate drain I.D mm.(n) 12 7 (1/12) Dimensions W mm.(n) 127 (1/12) Dimensions W mm.(n) 127 (1/12) Weight Kg (ibs) 8 2 (18) Packing dimensions mm. 905355X2600 Unit stacking units 8 Power suppiy (ph, cy, voltage) 1/9 50 Hz, 220-240V Q input W 700 650 710 Refrigerant control Capilary tube Compressor type Rotary 3.1 13 Q Starter type
Power supply (pri, cy, volta) ye) 14/ V
N Starting current A 0.05 D External finish Texture O Heat exchanger Flat fin coil Fan (drive) Crossflow (direct ) x 1 R Fan (drive) Crossflow (direct ) x 1 Airflow (LO-HI) M*/hr 260-340 (LO-MH) (LO-HI) M*/hr Noise level (LO-M-HI) db(A) 31-35-37 Condensate drain I.D mm.(in) 12.7 (1/12) D mm.(in) 153 (32-1/16) D mm.(in) 164 (6-7/16) Weight Kg (bs) 8 2 (18) Packing dimensions mm 905355x260 Unit stacking units 8 Power supply (ph. cy, voltage) 10/, 50 H2 220-240V Input W 700 660 V Running current A 31 11 D Refrigerant control Capiary tube Capiary tube Compressor type Rotary Starting current A 13 R VV 8
N Starting current A U3 D External finish Texture O Fan (drive) Crossfow (direct ) x 1 R Fan motor output W Airflow (LO-HI) M*hr 280-340 (CFM) (150-200) (CFM) V Operation control type Remote control LCD Noise level (LO-M-HI) db(A) 31-35-37 I Condensate drain I.D mm.(in) 12.7 (1/12) Dimensions W mm.(in) 213-1/16) Misis level (LO-M-HI) db(A) 31-35-37 Condensate drain I.D mm.(in) 12.7 (1/12) Dimensions W mm.(in) 220-1(16) Weight Kg (bs) 8.2 (18) Packing dimensions Power supply (ph. cy, voltage) 10, 50 Hz 220-240V 10 U Running current A 3.1 2.8 Power supply (ph. cy, voltage) 10, 50 Hz 220-240V 10 U Refrigerant control Capilary tube 2.11 A 0.08
D External Initian Texture 0 Heat exchanger Flat fin coll Fan (drive) Crossflow (direct) x 1 Fan motor output W Arflow (LO-HI) MP/hr 200 Operation control type Noise level (LO-M-HI) db(A) 0 31-35-37 1 Condensate drain I.D 0 mm (in) 1 Condensate drain I.D 1 Dimensions 0 mm (in) 1 Dimensions 1 Dimensions 1 Mark (in) 1 Dimensions 1 Mark (in) 1 Dimensions 1 Mark (in) 2 Power supply (ph. ey, voltage) 1 Inistacking 1 Starting current 1 A 1 Starting current 1 A 1 А
O Heat exchanger Flat Inf Soli Q Fan (dr.ve) Crossflow (direct ) x 1 Fan motor output W 5 Airflow (LO-HI) M 9 /hr 260-340 (CFM) (150-200) U Operation control type Remote control LCD Noise level (LO-M-HI) db(A) 31-36-37 I Condensate drain I.D mm.(in) 127 (1/12) T Dimensions W mm.(in) 260-240 Weight Kg (lbs) 8.2 (18) 0 Packing dimensions mm. 905X355X260 0 Unit stacking units 8 8 Power supply (ph, cy, voltage) 14, 50 HZ 220-240V 0 U Running current A 3.1 2.8 3.1 T Starting current A 3.1 2.8 3.1 T Starting current A 13 11 13 D Refigerant control Capilary tube Compressor type Rotary D Texture
O Fan (drive) Crossition (direct ) X 1 Fan motor output W 5 Airfiow (LO-HI) M³/hr 260-340 (CFM) (150-200) N Noise level (LO-M-HI) M³/hr Condensate drain I.D mm.(in) 815 (32-1/16) Dimensions W mm.(in) Weight Kg (lbs) 8.2 (18) Packing dimensions mm. 905X355X260 Unit stacking units 8 Power supply (ph, cy, voltage) 10/, 50 Hz, 220-240V Input W 700 Refrigerant control Capilary tube O Input W Refrigerant control Capilary tube O Starting current A A 13 11 D Refrigerant control Capilary tube O Starter type Refrigerant control Compressor type Rotary Starter type U Defrost method Reverse cycle - Noise level 0 Heat exchanger
R Part motor output W b Airflow (LO-HI) M 2 /h r 260-340 U Operation control type Remote control LCD N Noise level (LO-M-HI) db(A) 31-35-37 I Condensate drain I.D mm (in) 12.7 (1/12) T Dimensions W mm (in) 816 (32-1/16) D mm (in) 10.7 (1/12) mm (in) 27.0 (10-5/8) Weight Kg (lbs) 8 2 (18) Packing dimensions mm 905X355X260 Unit stacking units 8 Power supply (ph, cy, voltage) 14/ 50 HZ, 220-240V O Input W 700 650 710 U Refrigerant control Capilary tube Compressor type Refrigerant control O Starter type Lline start Protecton device Thermal overload and electronic Heat exchanger Flat fin coil Fan (drive) x NO Propeller (direct) x 1 Motor output W - V 0 C rossflow (direct ) > K 1
Aritiow (LO-Hi) MP/nr
(CFM) 280-340
(150-200) U Operation control type Remote control LCD N Noise level (LO-M-HI) db(A) 31-35-37 I Condensate drain I.D mm (in) 12.7 (1/12) T Dimensions W mm (in) 12.7 (1/12) T Dimensions W mm (in) 12.7 (1/12) Weight Kg (ibs) 8.2 (18) 905X355X260 Unit stacking units 8 8 Power supply (ph, cy, voltage) 14/, 50 HZ, 220-240V 10/200 Input W 700 650 710 U Running current A 3.1 2.8 3.1 T Starting current A 13 11 13 D Refigerant control Capliary tube Compressor type Rotary - O Starting current A 13 11 13 U Refigerant control Capliary tube Compressor type - <
R Fan motor output W 5
U Operation control type Remote control LCD N Noise level (LO-M-HI) db(A) 31-35-37 I Condensate drain I.D mm.(in) 12.7 (1/12) T Dimensions W mm.(in) 12.7 (1/12) Dimensions W mm.(in) 164 (6-7/16) H mm (in) 270 (10-5/8) Weight Kg (bs) 8.2 (18) Packing dimensions mm 905X355X260 Unit stacking units 8 Power supply (ph, cy, voltage) 1¢, 50 Hz, 220-240V Input W 700 650 Q Input W 700 650 U Running current A 3.1 2.8 3.1 T Starter gree Capliary tube Compressor type Rotary O Starter type Line start - I Defrost method Reverse cycle - Noise level db (A) 46 - D mm. (in Airflow (LO-HI) M³/hr 260-340
U Operation control type Remote control type N Noise level (LO-M-HI) db(A) 31-35-37 I Condensate drain I.D mm.(in) 12.7 (1/12) T Dimensions W mm.(in) 12.7 (1/12) T Dimensions W mm.(in) 1464 (6-7/16) Weight Kg (lbs) 8.2 (18) Packing dimensions mm. 905X355X260 Unit stacking units 8 Power supply (ph, cy, voltage) 1φ, 50 Hz, 220-240V Input W 700 650 710 Refrigerant control Capilary tube Capilary tube O Starting current A 13 11 13 D Refrigerant control Capilary tube Capilary tube O Starter type Line start Flat fin coil Fan (drive) x NO Propeller (direct) x 1 - Motor output W - - V Defrost method Reverse cycle - D
N Noise level (LO-M-HI) db(A) 31-35-37 I Condensate drain I.D mm.(in) 12.7 (1/12) T Dimensions W mm.(in) 164 (6-7/16) H mm.(in) 164 (6-7/16) H Veight Kg (1bs) 8.2 (18) Packing dimensions mm. 905X355X260 Unit stacking units 8 Power supply (ph, cy, voltage) 1$\u0ph, 50 Hz, 220-240V O Input W 700 Running current A 3.1 2.8 T Starting current A 13 11 D Refrigerant control Capilary tube Compressor type Q Starter type Line start - R Protection device Thermal overload and electronic Heat exchanger Flat fin coil - Fan (drive) x NO Propeller (direct) x 1 - Motor output W - - N Dimensions W - U -11- ( 6 ) D
Imm. (in) Dimensions W mm. (in) 815 (32-1/16) D mm. (in) 164 (6-7/16) H mm. (in) 270 (10-5/8) Weight Kg (bs) 8.2 (18) Packing dimensions mm. 905X355X260 Unit stacking units 8 Power supply (ph, cy, voltage) 1¢, 50 Hz, 220-240V U Running current A A 3.1 2.8 Starting current A 13 D Refrigerant control Capilary tube O Starter type Line start Protection device Thermal overload and electronic Heat exchanger Flat fin coil Fan (drive) x NO Propeller (direct) x 1 Motor output W - V Defrost method Reverse cycle N Noise level db (A) 46 U Defrost method Reverse cycle - N D mm. (in.) N 31-30-37
Immensions W mm.(in) 8 is (32-1716) D mm.(in) 164 (6-7/16) mm.(in) 164 (6-7/16) Weight Kg (lbs) 8 2 (18) mm. 905X355X260 Unit stacking units 8 8 Packing dimensions mm. 905X355X260 100 Unit stacking units 8 8 Power supply (ph, cy, voltage) 10/, 50 Hz, 220-240V 100 100 U Running current A 3.1 2.8 3.1 T Starting current A 13 11 13 D Refrigerant control Capilary tube 0 Compressor type Rotary O Starter type Line start 11 13 Heat exchanger Flat fin coil Fan (drive) x NO Propeller (direct) x 1 - Motor output W - V Defrost method Reverse cycle - - N Noise level 1.14 mm.(In)
D mm.(in) 164 (5-7/16) H mm.(in) 270 (10-5/8) Weight Kg (lbs) 8.2 (18) Packing dimensions mm. 905X355X260 Unit stacking units 8 Power supply (ph, cy, voltage) 1¢, 50 Hz, 220-240V Input W 700 650 U Running current A 3.1 2.8 3.1 T Starting current A 13 11 13 D Refrigerant control Capilary tube Compressor type Rotary O Starter type Lline start 1 13 R Protection device Thermal overload and electronic Heat exchanger Flat fin coil - Ear (drive) x NO Propeller (direct) x 1 - Motor output W - - D mm. (in.) 325 - N Dimensions Mm. (in.) 30 (66) 29 (64) Packing dimensions mm. I Dimensions mm (in)
Weight Imm.(in) 270 (10-36) Weight Kg (lbs) 8.2 (18) Packing dimensions mm. 905X355X260 Unit stacking units 8 Power supply (ph, cy, voltage) 1¢, 50 Hz, 220-240V Input W 700 650 710 Imput W 700 650 710 Imput W 700 650 710 Imput W 700 650 710 Imput W 700 650 710 Imput W 700 650 710 Imput W A 13 11 13 Imput A 13 11 13 Imput Starter type Imput Capilary tube Imput Starter type Imput Noise level Mb (A) Propeller (direct) x 1 Imput Motor output W - - Imput mm.(In)
Vergin Ng (los) 6.2 (16) Packing dimensions mm. 905X355X260 Unit stacking units 8 Power supply (ph, cy, voltage) 1¢, 50 Hz, 220-240V Input W 700 650 Renning current A 3.1 2.8 3.1 T Starting current A 13 11 13 D Refrigerant control Capilary tube Compressor type Rotary O Starter type Line start Encoded and electronic R Protection device Thermal overload and electronic Heat exchanger Flat fin coil Flat fin coil Fan (drive) x NO Propelier (direct) x 1 Motor output Motor output W - - Noise level db (A) 46 I Dimensions Mm. (in.) 3255 H mm. (in.) 30 (66) 29 (64) Packing dimensions mm. 885X312X590 Unit stacking Units Maight 270 (10-5/8)
Protecting dimensions Intrin 903333200 Unit stacking units 8 Power supply (ph, cy, voltage) 1¢, 50 Hz, 220-240V Input W 700 650 710 U Input W 700 650 710 U Input W 700 650 710 U Refrigerant control A 3.1 2.8 3.1 D Refrigerant control Capilary tube Compressor type Rotary O Starter type Ine start Protection device Thermal overload and electronic R Protection device Thermal overload and electronic Fan (drive) x NO Propeller (direct) x 1 Motor output W - V Defrost method Reverse cycle - Noise level db (A) 46 - I Dimensions W mm. (in.) 325 H mm. (in.) 540 29 (64) Packing dimen Vveight
Dealving dimensione
0.2(18)
O Initial acting Initial acting Imple 90575557200
O Input W 700 650 710 U Running current A 3.1 2.8 3.1 T Starting current A 13 11 13 D Refrigerant control Capilary tube Capilary tube O Starter type Retart Retart Q Starter type Line start Retart R Protection device Thermal overload and electronic Heat exchanger Flat fin coil Fan (drive) x NO Propeller (direct) x 1 Motor output W - - Defrost method Reverse cycle - N Oise level db (A) 46 I Dimensions W mm. (in.) 3255 H mm. (in.) 30 (66) 29 (64) Packing dimensions mm. 885X312X590 Unit stacking units 3 3 T Refrigerant R-22 Charge gr.(lbs) 610 59 units 0
14 50 Hz 220 240
11/
U Input W 700 000 710 Running current A 3.1 2.8 3.1 T Starting current A 13 11 13 D Refrigerant control Capilary tube Capilary tube O Starter type Rotary Rotary O Starter type Line start Flat fin coil R Protection device Thermal overload and electronic Heat exchanger Flat fin coil Fan (drive) x NO Motor output W - - U Defrost method Reverse cycle - N Noise level db (A) 46 I Dimensions W mm. (in.) 325 H mm. (in.) 540 29 (64) Veight Kg (lbs) 30 (66) 29 (64) Packing dimensions mm. 885X312X590 Unit stacking units 3 T Refrigerant R-22 0 ge) 14/ 700 ιφ, 30 112, 220-240
650
710
U Refrigerant control A 3.1 2.6 3.1 D Refrigerant control A 13 11 13 D Refrigerant control Capilary tube Capilary tube O Starter type Line start Refrigerant control O Starter type Line start Refrigerant control Q Starter type Line start Refrigerant control R Protection device Thermal overload and electronic Heat exchanger Flat fin coil Fan (drive) x NO Propeller (direct) x 1 Motor output W - U Defrost method Reverse cycle - - N Noise level db (A) 46 - D mm. (in.) 325 - - H mm. (in.) 540 - - Veight Kg.(lbs) 30 (66) 29 (64) Packing dimensions mm. 885X312X590 U Charge Bupping ourrent VV
A
700 000 2.1
Image: Construint of the start of the s Running current A 12 2.0 12
D Reinigerant control Capitaly tube O Compressor type Rotary O Starter type Line start R Protection device Thermal overload and electronic Heat exchanger Flat fin coil Fan (drive) x NO Propeller (direct) x 1 Motor output W - U Defrost method Reverse cycle - Noise level db (A) 46 I Dimensions W mm. (in.) 740 T Weight Kg.(lbs) 30 (66) 29 (64) Packing dimensions mm. 885X312X590 29 (64) U Charge gr.(lbs) 610 595 B Tube size OD liquid mm. (in.) 6.35 (1/4) A 15 Conilony tubo 15
O Starter type Interstant R Protection device Thermal overload and electronic Heat exchanger Flat fin coil Fan (drive) x NO Propeller (direct) x 1 Motor output W - U Defrost method Reverse cycle - N Noise level db (A) 46 I Dimensions W mm. (in.) 325 H mm. (in.) 330 (66) 29 (64) Packing dimensions mm. 885X312X590 Unit stacking units 3 T Refrigerant R-22 U Charge gr.(lbs) 610 595
O Statistivye Effection R Protection device Thermal overload and electronic Heat exchanger Flat fin coil Fan (drive) x NO Propeller (direct) x 1 Motor output W - U Defrost method Reverse cycle - N Noise level db (A) 46 I Dimensions W mm. (in.) 325 H mm. (in.) 325 4 mm. (in.) 329 (64) Veight Kg.(lbs) 30 (66) 29 (64) Packing dimensions mm. 885X312X590 29 (64) Unit stacking units 3 7 Refrigerant R-22 1 1 610 595 B Tube size OD liquid mm. (in.) 6.35 (1/4) 1 Starter type Lino start
R Frotection device File fine four device Heat exchanger Flat fin coil Fan (drive) x NO Propeller (direct) x 1 Motor output W Defrost method Reverse cycle N Noise level db (A) I Dimensions W I Dimensions W Meight Kg.(lbs) 30 (66) Packing dimensions mm. 885X312X590 Unit stacking units 3 I Refrigerant R-22 U Charge gr.(lbs) 610 B Tube size OD liquid mm. (in.) 6.35 (1/4) Thorm ootronio
Heat exchanger Fan (drive) x NO Propeller (direct) x 1 Motor output W - Defrost method Reverse cycle - N Noise level db (A) 46 I Dimensions W mm. (in.) 740 T D mm. (in.) 325 H mm. (in.) 540 Weight Kg.(lbs) 30 (66) 29 (64) Packing dimensions mm. 885X312X590 Unit stacking units 3 T Refrigerant R-22 Charge gr.(lbs) 610 595 B Tube size OD liquid mm. (in.) 6.35 (1/4) R Inern al overload and en ectronic
Image: Motor output Image: Withold (Milled) X NO Motor output W Defrost method Reverse cycle N Noise level db (A) I Dimensions W mm. (in.) T D mm. (in.) Weight Kg.(lbs) 30 (66) Packing dimensions mm. 885X312X590 Unit stacking units 3 T Refrigerant R-22 U Charge gr.(lbs) 610 Sp5 Inquid mm. (in.) 6.35 (1/4) Piat III Cull
Propollor (direct) y
1
U Defrost method Reverse cycle - N Noise level db (A) 46 I Dimensions W mm. (in.) 740 T D mm. (in.) 325 H mm. (in.) 540 Weight Kg.(lbs) 30 (66) 29 (64) Packing dimensions mm. 885X312X590 Unit stacking units 3 T Refrigerant R-22 U Charge gr.(lbs) 610 595 B Tube size OD liquid mm. (in.) 6.35 (1/4) \\/
N Noise level db (A) 46 I Dimensions W mm. (in.) 740 T D mm. (in.) 325 H mm. (in.) 325 U Kg.(lbs) 30 (66) 29 (64) Packing dimensions mm. 885X312X590 Unit stacking units 3 T Refrigerant R-22 U Charge gr.(lbs) 610 595 B Tube size OD liquid mm. (in.) 6.35 (1/4) l 11 ~~ Revers
I Holdschold db (A) 1/67613 46
T Dimensions W Imm. (m.) 140 T D mm. (in.) 325 H mm. (in.) 540 Weight Kg.(lbs) 30 (66) 29 (64) Packing dimensions mm. 885X312X590 Unit stacking units 3 T Refrigerant R-22 U Charge gr.(lbs) 610 595 B Tube size OD liquid mm. (in.) 6.35 (1/4) \\/ 740
Image: Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the system Image of the syste Dimensions mm (in ) 325
Weight Kg.(lbs) 30 (66) 29 (64) Packing dimensions mm. 885X312X590 Unit stacking units 3 T Refrigerant R-22 U Charge gr.(lbs) 610 595 B Tube size OD liquid mm. (in.) 6.35 (1/4) 4 mm (in ) 540
Packing dimensions mm. 300 (00) 20 (04) Packing dimensions mm. 885X312X590 Unit stacking units 3 T Refrigerant R-22 U Charge gr.(lbs) 610 595 B Tube size OD liquid mm. (in.) 6.35 (1/4) 6.35 (1/4) Weight 30 ( 66) 29 (64)
Indexing uniteristend Initial Observe (22,000) Unit stacking units 3 T Refrigerant R-22 U Charge gr.(lbs) 610 595 B Tube size OD liquid mm. (in.) 6.35 (1/4) 6.35 (1/4) Packing dimensions mm 50 ( 885X312X590 23 (04)
T Refrigerant R-22 U Charge gr.(lbs) 610 595 B Tube size OD liquid mm. (in.) 6.35 (1/4) units 3
U Charge gr.(lbs) 610 595 B Tube size OD liquid mm. (in.) 6.35 (1/4) т Refrigerant
R-22
B Tube size OD liquid mm. (in.) 6.35 (1/4) Charge ar (lbs) ,,,,, 595
R liquid m - 6 35 (1/4)
I 95 (3/8) suction m (in ) 9.5 (3/8)
N Connection method Lindoor & outdoor Elared Connection method Flared
G between the indoor and beight diference MAX_6M (20ET) between the indoor and height d iference MAX 6M (20FT)
tubing nath MAX 10M (33FT ·)
ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG. 2-2
Page 5
Model WMN - 9 RC WMN - 9 ST
Item
Function Cooling Heating Cooling only
Capacity Kcal/hr 2250 2700 2250
Btu/hr 9000 10800 9000
W 2640 3160 2640
Total input W 960 930 970
Power supply (ph, cy, voltag ge) 1 φ , 50Hz, 220-240∖ /
Input W 10
I Running current А 0.09
Ν Starting current А 0.4
D External finish Texture
0 Heat exchanger Flat fin coil
0 Fan (drive) C Crossflow (direct ) x 1
R Fan motor output W 6.5
Airflow (LO-HI) M³/hr 310-390
(CFM) (180-230)
U Operation control type Remote contro| LCE )
Ν Noise level (LO-M-HI) db(A) 32-36-38
I Condensate drain I.D mm.(in) 12.7 (1/12)
Т Dimensions W mm.(in) 815 (32-1/16)
D mm (in) 164 (6-7/16)
Н mm.(in) 270 (10-5/8)
Weight Kg (lbs) 8.2 (18)
Packing dimensions mm. 905X355X260
Unit stacking units 8
Power supply (ph, cy, voltage ge) r 1 φ , 50 Hz, 220-240∖ /
Input W 950 920 960
Running current A 4.3 4.2 4.3
0 Starting current A 17 17 17
U Refrigerant control Capilary tube
Т Compressor type Rotary
D Starter type Line start
О Protection device Iherm al overload and ele ctronic
0 Heat exchanger Flat fin coll
R Fan (drive) x NO Propeller (direct) x 1
Motor output VV - -
U Defrost method Revers se cycle -
N 1 db (A) 48
Dimensions mm (in ) /40
Т D mm. (in.) 325
ЦН mm. (in.) 540 04 (00)
vveight Kg.(Ibs) 32 31 (68)
88573127590
units
ar (lbc) 66 5 610
liquid y:(ius)
nom (in )
00 6 25 (1/4) 010
В m (in ) 0.55(1/4)
Connection method indoor ni. (iii.)
Routdeor
S.J (J/O)
botwoon the indeer and hoight
tubing enath MΔX 10M (20FT)
1 T rabing l engui
ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG. 2-3
Page 6
Model WMN - 7+7 RC WMN · - 7+7 ST
Item
Function Cooling Heating Unit-1 Unit-2
Capacity Kcal/hr 1820X2 2050X2 1820 1820
Btu/hr 7300X2 8200X2 7300 7300
W 2140X2 2400X2 2140 2140
Total input W 1600 1500 1 610
Power supply (ph, cy, voltag e) 1φ, 50Hz, 220-3 240V
Input W 2X8
1 Running current Α 2X0.08
Ν Starting current A 2X0.3
D External finish Texture
ο Heat exchanger Flat fin coi
ο Fan (drive) Crossflow (direct ) x 1
R Fan motor output W 2X5 /
Airflow (LO-HI) M³/hr 260-340
(CFM) (150-200)
U Operation control type , Remote control LCD
Ν Noise level (LO-M-HI) db(A) 31-35-37
1 Condensate drain I.D mm (in) 12.7 (1/12 )
т Dimensions W mm (in) 815 (32-1/1 6)
D mm.(in) 164 (6-7/16 )
S)
Н mm.(in) 270 (10-5/8 ,
3)
Weight Kg (lbs) 8.2 (18) ,
Packing dimensions mm. 905X355X260
Unit stacking units 8
Power supply (ph, cy, voltag e) 1φ, 50 Hz, 220- 240V
Input W 1580 1480 1: 590
Running current А 7.6 7.1 Ī 7.6
0 Starting current A 31 28 31
U Refrigerant control Capilary tub be
Т Compressor type RotaryX2
D Starter type Line start
Ο Protection device Ther mal overload and d electronic
Ο Heat exchanger Flat fin coi
R Fan (drive) x NO Propeller (direc t) x 1
Motor output W - - -
U Defrost method Revers e cycle -
Ν Noise level db (A) 55
1 Dimensions W mm. (in.) 900
Т D mm. (in.) 340
Н mm. (in.) 580
Weight Kg (lbs) 70 ( 154) 66 (145)
Packing dimensions mm. 630X985X40 06
Unit stacking units 3
Т Refriger ant R-22
U Charge gr.(lbs) 765> K2 765 5X2
В Tube size OD liquid mm. (in.) 6.35 (1/4)
| | suction n m. (in.) 9 5 (3/8)
N Connection method indoor & outdoor Flared
G between the indoor and height diference MAX_6M (20 FT)
outdoor unit. tubing length MAX. 10M (33 3FT)
ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG 2-4
Page 7
Model WMN - 9 9+9 RC WMN - 9+9 ST
ltem
Function Cooling Heating Cooling only
Capacity Kcal/hr 2640X2 2700X2 2640X2
Btu/hr 9000X2 10800X2 9000X2
W 2630X2 3160X2 2640X2
Total input W 2000 2050 2000
Power supply (ph, cy, voltag ge) 1 φ, 50Hz, 220-24 ٥V
Input W 2X10
I Running current A 2X0.9
Ν Starting current А 2X0.4
D External finish Texture
0 Heat exchanger Flat fin coil
0 Fan (drive) С rossflow (direct) x 1
R Fan motor output W 2X6.5
Airflow (LO-HI) M³/hr 310-390
(CFM) (180-230)
U Operation control type F Remote control L CD
Ν Noise level (LO-M-HI) db(A) 32-36-38
1 Condensate drain I D mm (in) 12.7 (1/12)
Т Dimensions W mm.(in) 815 (32-1/16)
D mm.(in) 164 (6-7/16)
Н mm (in) 270 (10-5/8)
Weight Kg (lbs) 8.2 (18)
Packing dimensions mm. 905X355X260
Unit stacking units 8
Power supply (ph, cy, voltag ge) 1 φ, 50 Hz, 220-24 0V
Input W 1980 2030 1980
Running current A 9.0 9.2 9.0
0 Starting current A 38 40 38
U Refrigerant control Capilary tube
Т Compr essor type RotaryX2
D Starter type Line start
0 Protection device Therma al overload and e lectronic
0 Heat exchanger Flat fin coil
R Fan (drive) x NO Propeller (direct) Х
Motor output W - -
U Defrost method 1 Reverse e cycle -
N Noise level db (A) 59
Dimensions W mm. (in.) 900
Т D mm. (in.) 340
H mm. (in.) 580 1
Weight Kg.(lbs) 74(1 63) 70 (154)
Packing dimensions mm 630X985X406
units 3
Т Refrigerant R-22 775/0
U Charge gr (lbs) 830 X2 //5X2
B liquid n nm. (in.) 6 35 (1/4)
suction m. (in.) 95(3/8)
N Indoor 8 s outdoor Hared ,
G between the indoor and height c literence MAX. 6M (20FT )
outdoor unit. | tubing le ength MAX. 12M (40F 1)
ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG. 2-5
Page 8
14 Model WMN - 7+9 RC WMN - 7+9 ST
Item
Cooling g Hea ating
Function Kaa liha Unit-1 001t-1 011t-2
Capacity Kcal/nr 1820 2250 2050 2700
7300 9000 8200 10800
Tatalinn 4 2140 2640 2400 3160
Total inp VV 1800 60
14/ 0 20-240 0 10
V 8 8 10
A 0.08 0.09 0.08 0.09
N A 0.3 0.4 0.4
D External finish lextu re
0 Heat exchanger Flat fin coil
0 Fan (drive) ( Crossflow (di rect)x 1
R Fan motor output W 17 15 17 15
Airflow (LO-HI) M³/hr 260-340 310-390 260-340 310-390
(CFM) 150-200 180-230 150-200 180-230
U Operation control type Remote cont trol LCD
Ν Noise level (LO-M-HI) db(A) 31-35-37 32-36-38 31-36-37 32-36-38
I Condensate drain I.D mm (in) 12.7 (1 /2)
Т Dimensions W mm (in) 808 (31-1 3/16)
D mm.(in) 164 (6-7 /16)
Н mm.(in) 368 (14- 1/2)
Weight Kg (lbs) 8.2 (1) 8)
Packing dimensions mm. 905X355 X260
Unit stacking units 8
Power supply (ph, cy, voltage) 1 ϕ , 50 Hz, 2 20-240V
Input W 1785 17 740
Running current А 8.1 8 .0
ο Starting current А 32 32
U Refrigerant control Capilary tube
т Compressor type Rotar v
D Starter type Line st art
ō Protection device Thern nal overload and electroni с
Ő Heat exchanger Flat fin coil -
P Propeller (di rect) x 1
\\\/
vv Reverse ci
N db (A) 55
Dimensions \// 900
т Binichalona mm (in ) 340
1 mm (in ) 580
Weight Ka (lbs) 73 (16 1)
Packing dimensions 630, 2985 ,
X406
Unit stacking units 3
т Refrigerant unito
Charge ar (lbs) 10.20 765 10.20 765
liquid 1020 635/1 (4) ,00
suction 0.00 (1 ,
Connection method indoor 5.0 (3/
height
G between the indoor and neight anerence NANY 4014 20FT)
j outdoor unit. tubing length MAX. 10M ( 33ET) MAX.12 WI (40⊢T)

note: Unit-1 = WMN-7

Unit-2 = WMN-9

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG 2-6
Page 9
Model WMN -12 RC WMN -12 ST
ltem
Function Cooling Heating Cooling only
Capacity Kcal/hr 2900 3075 2900
Btu/hr 11600 12300 11600
W 3400 3600 3400
Total input W 1300 1310 1310
Power supply (ph, cy, voltage e) 1 φ , 50Hz, 220-240 V
Input W 15
I Running current A 0.1
Ν Starting current A 0.5
D External finish Texture
0 Heat exchanger Flat fin coil
0 Fan (drive) C crossflow (direct) x 1
R Fan motor output W 6.5
Airflow (LO-HI) M³/hr 340-450
(CFM) (200-265)
U Operation control type Remote control LC
N Noise level (LO-M-HI) db(A) 33-36-40
Condensate drain | D 1 mm.(in) 12.7 (1/12)
Т Dimensions W mm.(in) 815 (32-1/16)
(in) 164 (6-7/16)
ΙН mm.(in) 270 (10-5/8)
vveignt 8.2(18)
Packing dimensions 90573557260
2) units 0\/
-) \\/ 1200 ιφ, 30 Π2, 220-24
1310
1200
Rupping current Δ 6.1 62 61
0 Starting current Α 26 26 26
U U Refrigerant control Capilary tube 20
т Rotary
D I Starter type Line start
0 Protection device Therm al overload and e lectronic
0 Heat exchanger Flat fin coil
R Fan (drive) x NO Propeller (direct) x 1
Motor output W - _
U Defrost method Revers e cycle -
Ν Noise level db (A) 55
1 Dimensions W mm. (in.) 740
Т 1 D mm. (in.) 325
1 Н mm. (in.) 540
Weight Kg.(lbs) 43 (95) 42 (92)
Packing dimensions mm. 576X340X825 ·
Unit stacking units 3
| т Refrigerant R-22
U Charge gr.(lbs) 10 20 1020
В Tube size OD liquid mm. (in.) 6 35 (1/4)
| | suction ı m. (in.) 12.7(1/2)
Ν Connection method indoor & outdoor Flared
G between the indoor and height diference MAX 6M (20FT )
outdoor unit. tubing length MAX. 12M (40F Г)
ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG 2-7
Page 10
Mode WMN 9+12 - ST
Item Coolin g only
Function 1 Unit-1 Unit-2
Capacity 1 Kcal/hr 2900 2250
Btu/hr 11600 9000
W 3400 2640
Total inp put W 2350 2350
Power supply (ph. cy. voltage) I. 1ø, 50Hz, 220-240V
Input W 15 10
Running current А 0.1 0.09
Ň Starting current A 0.5 0.4
External finish Text
Ö Heat exchanger Flat fi
Ő Crossflow ( direct) x 1
Ean motor output \\/ 010331047 ( 65
ĸ VV
M3/br
240,450 210,200
200,265 180.230
н 200-203
Remote co
ntrol I CD
33.40 32.39
33-40 52-30
14/

-1/10)
mm.(In) 164 (6
10/5:264 Н mm.(In) 270 (1 19)
Vvelgnt
Decking dimensione
8.2 ( 18)
Packing dimensions mm. 905X35 58260
units 220.2401/
> • / 220-240 0
VV 2376 2376
Running current A 11.2 11.2
А 45 40
U Capilar y tube
Т Compressor type Rot ary
0 Starter type Line start
D Protection device Thermal overloa d and electronic
0 Hea t exchanger Flat fi n coil
R Fan (drive) x NO Propeller ( direct) x 1
Motor output W - -
U Defrost method Reverse cycle -
Ν Noise level db (A) 58 3
| | Dimensions W mm (in ) 90 0
Т D mm. (in.) 34 0
Н mm. (in.) 58 0
Weight Kg (lbs) 72 (* 63)
Packing dimensions mm. 630X98 5X406
Unit stacking units 3
Т Refrigerant R-2 22
U U Charge gr.(lbs) 990 650
В Tube size OD liquid mm. (in.) 6.35 (1/4) 6.35 (1/4)
| I suction ı m. (in.) 12.7 (1/2) 9.5 (3/8)
N Connection method indoor & outdoor Flai ed
G between the indoor and height diference MAX. 6M (20FT) MAX. 6M (20FT)
outdoor unit. tubing length MAX. 16M (52FT) MAX. 16M (52FT)
ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG 2-8
Page 11
Model WMN - 9 9+12 RC WMN - 9 +12 RC
ltem Coc oling Heat ing
Function Unit-1 Unit-2 Unit-1 Unit-2
Capacity Kcal/hr 2900 2250 3075 2700
Btu/hr 11600 9000 12300 10800
Tatalinnu + 3400 2040 3000 3105
Total IIIpu Powersupply (ph. cy. yol tane) vv 23 50
1か 50Hz
220_240\/ 10
lage) 15 15 10
Bunning current Δ 0.1 0 0.1 0.09
N Starting current Δ 0.5 0.00 0.1 0.00
External finish 0.0 Tex ture 0.4
0 Heat exchanger Flat f n coil
Ő Ean (drive) Crossflow (direct.) x 1
R Fan motor output W 9 6.5 9 6.5
Airflow (LO-HI) M 3 /hr 340-450 310-390 340-450 310-390
(CFM) 200-265 180-230 200-265 180-230
U Operation control type · Remote co ontrol LCD
Ν Noise level (LO-M-HI) db(A) 33-40 32-38 33-40 32-38
| I Condensate drain I.D mm.(in) 16 ( (5/8)
Т Dimensions W mm (in) 815 (3) 2-1/16)
D mm (in) 164 (6 5-7/16)
Н mm.(in) 270 (1 0-5/8)
Weight Kg (lbs) 8.2 (18)
Packing dimensions mm 905X38 5X260
taga) units 14 5017 220 2401/
laye) 10/ 23 220-240 V 86
Running current Δ 11 10 10 5
0 Starting current A 4 .5 42 >
Ŭ Refrigerant control Capila rv tube
Т Compressor type Rot arv
D Starter type Line start
ō Protection device Т hermal overloa d and electronic ;
0 Heat exchanger Flat fi n coil
R Fan (drive) x NO Propeller ( direct) x 1
Motor output W - - -
U Defrost method Revers e cycle -
Ν Noise level db (A) Ę 5
I Dimensions W mm. (in.) 90 00
Т D mm. (in.) 34 40
Н mm. (in.) 58 30
Weight Kg (lbs) 73 ( 161)
Packing dimensions mm. 630X98 35X406
Refrigerant units ,
つつ
Charge ar (lbs) 1020 710 1020 710
R liquid mm | 9:(103)
| (in )
1020 635 (1/4) , 10
suction m im (in ) 127 9.5 127 9.5
Ň Connection method indoor & o utdoor , Fla red
G between the indoor and height dife rence MAX 6 M (20FT)
outdoor unit. tubing lend gth MAX 16 M (52FT)
ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG. 2-9
Page 12
Model WMN -2X 12 RC WMN - : 2X12 ST
ltem
Function Cooling Heating Coolir ig only
Capacity Kcal/hr 2900x2 3075X2 290 )0x2
Btu/hr 11600x2 12300X2 116 00x2
W 3400x2 3660X2 340 )0x2
Total inpu ut W 2720 2680 27 20
Powe r supply (ph, cy, vo ltage) 19 50Hz, 220-240 V
Input W 15 3 8
Running current A 0.1 0. 17
Ν Starting current A 0.5 0 .7
D External finish Texture
0 Heat exchanger Flat fin coil
0 Fan (drive) Cro ossflow (direct ) : x 1
R Fan motor output W 17
Airflow (LO-HI) M³/hr 340-450
(CFM) (200-265)
U R D
N Noise level (LO-HI) db(A) 33-44
Condensate drain I D 1 mm.(in) 16 (5/8)
Т Dimensions mm.(in) 815 (32-1/16)
D mm.(in) 164 (6-7/16)
Н mm.(in) 270 (10-5/8)
Weight Kg (lbs) 8.2 (18)
Packing dimensions mm.
(togo) units 1. 11
Power supply (pri, cy, vo nage) 14/ 19 200
Bunning ourrent 2090 2000 20 190
7 7
0 Starting ourrent A 50 12.5 5 2.7
50 Capilary tube 0
U
T
Dotory
Starter type Line start
Therma ectronic
0 Therma ectionic
Dr opeller (direct) v 1
\\/
— п vv
N db (A) 59
Dimensions W 900
T T mm (in ) 340
Н mm (in ) 580
Weight Ka (lbs) 74 (16 3) 70 ( 154)
Packing dimensions mm 630X985X406
Unit stacking units 3
Т Refrigerant R-22
U Charge gr.(lbs) 960* 1100* 910* 1050*
В Tube size OD liquid mr n (in ) 6 35 (1/4)
| | suction n n. (in.) 12.7(1/2)
N Connection method indoor & d outdoor Flared
G between the indoor height dif erence MAX. 6M (20FT)
and autoor unit tubing las ath .)
1 i iuoma ier iutti 1

notes: * Unit 1 - For exact charge refer to outdoor unit nameplate. ** Unit 2 - For exact charge refer to outdoor unit nameplate

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG. 2-10
Page 13

WALL MOUNTED SPLIT A/C

SPECIFICATIONS & OPERATING RANGE
ltem Model WMN-18/ONG3-17ST WMN-18/0 NG3-17RC
Function Cooling Cooling Heating
Capacity 1 Kal/hr 4300 4300 4530
Btu/hr 17000 17000 18000
W 5000 5000 5270
Total Inp out W 1970 1970 1820
Running Current А 8.6 8.6 7.9
Power S upply (ph, cy, voltage) Single , 5 50Hz,220-240V,R4 .07C
External finish Texture
Heat exchanger Hydr ophilic louver fin coil
1 Fan (drive) Crossflow
N Fan motor output W 18
D Airflow (Hi) m3/h 830
ο Operation control type Re mote control LCD
ο Noise level(Hi) dB(A) 40 42 46
R Condensate drain I.D. mm(in) 16
Dimensions W mm 1115
U D mm 200
N Н mm 330
I Weight kg 14
т Packing dimensions mm 1200x300x420
Unit stacking units 7
Starting Current А 45
ο Refrigerant control Capillary tube
U Compressor type Rotary
т Compressor Model P G330X2CS-4KT3
D Starter type Line start
ο Protection device Internal
ο Heat exchanger Bare louver fin Hydropyilic I ouver fin coil
R Fan (drive) x No. Pro opeller (direct) x 1
Motor output W 35
Defrost method 1 Revers e cycle
U Noise level dB(A) 54
Ν Dimensions W mm 795
I D mm 290
Т Н mm 610
Weight kg 43
Packing dimensions mm. 945*395*655
Unit stacking units 3 leve els, 9 units per palle t
Refrigerant R-407C
Т Charge(7.5m) g 1250
U Tube size liquid mm(in) 6.35(1/4")
В O.D. suction mm(in) 12.7(1/2")
I Connection method indoor 8 & outdoor Flared
Ν between the indoor and height d lifference Max. 10m
G outdoor unit tubing length Max. 25m
篗 =L ELEC TRA AIR CO NDITIONING CO., LTD. Rev.01 Jan 2002 SERIES: WMN

Page 14
SPECIFICATIONS 2
Medal \A/8451 240.00 10/1 AN 34D ST
ltem Model VV IVI N- -24R RC vv WIN-24R 51
Function Cooling Heating C oolina Only
Capacity Kal/hr 5431 5603 5431
e ap aony Btu/hr 21496 22178 21496
W 6300 6500 6300
Total Input W 2450 2390 2360
Running Ci irrent A 11.6 11.5 11.5
Power Sup plv (ph. cv. voltage) single 50HZ 230 )V
External finish Texture
Heat exchanger Hydropyi lic louver fin coil
N Fan (drive) C rossflow
D Fan motor output W 30
o Airflow (Hi) m/hr 910
0 Operation control type Remot e control LC D
R Noise level(Lo-M-Hi) db(A) 45 48 50
Condensate drain I.D. mm - 15.88
U Dimensions W mm 1070
Ν D mm 220
I Н mm 330
т Weight Kg 14
Packing dimensions mm 1200 x 420 x 300 )
Unit stacking 8
0 Refrigerant control Ca oilary tube
U Compressor type Rotary
т Model QP 407JT24A
D Starter type L ine start
ο Protection device Ten np. Klicson
ο Heat exchanger Hydropyil ic louver fin Flat louver fin coil
R Fan (drive) x No. Propel ler (direct) x 1
Motor output W 140
Defrost method Rever se cycle
U Noise level db(A) 60
Ν Dimensions W mm 846
I D mm 302
т Н mm 690
Weight Kg. 58 57
Packing dimensions mm. 990 x 430 x 770
Unit stacking units 3
Т Refrigerant R - 22
U Charge gr.(lbs) 1 930 1930
В Tube size liquid mm. 9.53
I O.D. suction mm. 15.88
Ν Connection method indoor & outdoor Flared
G between the indoor and height di fference Ν lax. 10m
outdoor unit tubing length N lax. 16m
ELECTRA AIR CONDI TIONING CO., LTD. REV. 01 10/01 SERIES: W MN2

Γ

Page 15

NOTES:

1. Rating conditions ISO DIS 5151 Cooling: indoor : 27°C (80°F) DB 19.5°C (67°F) WB Outdoor : 35°C (95°F) DB

Heating∶indoor∶ 21°C (70°F) DB Outdoor∶7°C (45°F) DB 5°C (43°F) WB

Refrigerant tubing length (one way) 5m (16ft)

2. Guaranteed operating range:

Indoor Outdoor
Cooling Upper limit 32°C DB, 23°C WB 46°C DB
Lower limit 21°C DB, 15°C WB 10°C DB
Heating Upper limit 27°C DB 21°C DB, 15.5°C WB
Lower limit 20°C DB -5°C DB, -6.5°C WB
Voltage 193 - 2 250v

3. Above data based on indicated voltage

indoor∶1 φ , 230v, 50Hz.

outdoor : 1φ, 230ν, 50Hz.

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG. 2-18
Page 16

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG. 3-3
Page 17

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG. 3-4
Page 18

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG. 3-5
Page 19

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG. 3-6
Page 20

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG 3-7
Page 21

WALL MOUNTED SPLIT A.C

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG. 3-8
Page 22

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG. 3-9
Page 23

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG. 3-10
Page 24

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG. 3-11
Page 25

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG. 3-12
Page 26

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG. 3-13
Page 27

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG 3-14
Page 28

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG 3-23
Page 29

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG 3-24
Page 30

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG 3-25
Page 31

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG 3-26
Page 32

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG 3-27
Page 33

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG 3-28
Page 34

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG. 3-29
Page 35

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG 3-30
Page 36

.ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG. 4- 2
Page 37

WALL MOUNTED SPLIT A.C

.ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG. 4- 4
Page 38

Page 39

REFRIGERATION DIAGRAM HEAT PUMP MODEL-WMN-6-7-12-14-16

HEATING MODE

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG. 6-1
Page 40

REFRIGERATION DIAGRAM HEAT PUMP MODELS WMN-9, 18, 24

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG. 6-2
Page 41

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG. 6-4
Page 42

ADDITIONAL REFRIGERANT CHARGE (R-22 gr)

HEAT PUMP UNITS

MODEL REFRIGE RANT TUBIN G LENGTH ( ONE WAY)
TIUDEE 6M 8M 10M 12M 16M 20M
WMN/A/C/D-7 30 60
WMN/A/C/D-9,12,14,16 30 60 100
WMN/A/C/D-18,24 80 160 240 320 450

MAXIMUM REFRIGERANT TUBING LENGTH AND HEIGHT DIFFERENCE

* THE INDOOR UNIT CAN BE ABOVE OR BELOW THE OUTDOOR UNIT.

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG 6-5
Page 43

WMN-6 WIRING DIAGRAM

.ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG. 7- 1
Page 44

WMN 7-24 WIRING DIAGRAM

.ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG. 7- 2
Page 45

DUAL SPLIT WIRING DIAGRAM

.ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG. 7- 3
Page 46
.ELECTRA consumer products LTD REV. 01 1/97 SERIES:WMN PG. 8-1

Page 47

  • 1. General functions for all models
  • 1.1 For each Mode, 3 minutes minimum delay for COMP restarting, including POWER OFF or SB.
  • 1.2 10 minutes minimum for COMP operation, excluding Dry, overflow and protection Modes.
  • 1.3 Deicing control at Heating Mode only.
  • 1.4 Defrosting control at Dry and Cooling Modes only.
  • 1.5 High pressure protection at Dry, Cooling or Heating.
  • 1.6 Minimum time between changing if speeds in auto fan Modes is 30 sec.
  • 1.7 Minimum time for switching OF is 30 sec.
  • 1.8 Minimum Heaters on or off time is 30 sec.
  • 1.9 Only one output is activated at a time. The minimum delay between activating two outputs is 200 msec.
  • 1.10 POWER OFF command to the controller will turn off the system immediately,
  • 2. Abbreviations
ANY - ON or OFFstatus
COMP - Compressor
HE - Heating Element
HPC - High Pressure Control
ICP
  • Indoor Condensate Pump
ICT - Indoor Coil Temperature (RT-2) sensor
IF - Indoor Fan
OCT - Outdoor Coil Temperature (RT-3)sensor
OF - Outdoor Fan
RAT - Return Air Temperature (RT-1)sensor
RC
  • Reverse Cycle (Heat Pump)
R/C - Remote Control
RCT - Remote Control Temperature
RV - Reversing Valve
SB - Stand-By
SH
  • Supplementary Heater
SPT - Set Point Temperature
ST
  • Standard (a Model with Cooling Only)

  • 3.0 Cooling Mode General
  • 3.0.1 Return Air Temp. Is detected by RAT (RT-1) in normal operation, or RCT (R/C sensor) in I-FEEL mode.

3.0.2 RAT measured deviation is +/- 0.0°C . a) RAT is activating COMP & OF if RAT>>SPT+0°C . b) RAT is stopping COMP & OF if RAT≤SPT-0°C .

  • 3.0.3 Indoor Coil Temp. is detected by ICT (RT-2)
  • 3.0.4 Outdoor Coil Temp. is detected by OCT (RT-3).
  • 3.0.5 OF starts together with COMP.
ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG.9-1
Page 48

3.1 Cooling

Mode: Cool. Auto (At Cooling) Temp: Selected desired temperature. Fan: Hi, Med , Lo Timer: Any I Feel: On or Off

Cont Control function

Maintains room temp. at desired level by comparing RAT or RCT to SPT.

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG.9-2
Page 49

WALL MOUNTED SPLIT A.C

2 Cooling with Autofan.

Mode:Cool, Auto (At cooling)Temp:Selected desired temperature.Fan:Auto.Timer:AnyI Feel:On or Off

Control function

Maintains room temp. at desired level and controls the IF speed for optimal comfort.

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG 9- 3
Page 50

4.0 Heating modes - general

4.01 In heating or Auto Heating modes, temp. compensation schedule will be activated:

SPT°C Add to SPT
I Feel On I Feel Off
18°C - 27°C 0°C +2°C
28°C - 30°C 0°C +3°C

  • 4.0.2 Room Temp. is detected by RAT( RT-1) in normal operation, or (RCT (R/C Sensor) in I-FEEL mode.
  • 4.03 Indoor Coil Temp. is detected by ICT( RT -2).
  • 4.04 Outdoor Coil Temp. is detected by OCT (RT-3).
  • 4..05 RAT measured deviation is +/-0.0°C from SPT. (a) RAT is activating COMP & OF if ≤ SPT-0 °c.. (b) RAT is stopping COMP & OF if > SPT+0 °c.
  • 4.0.6 OF starts together with COMP.
  • 4.0.7 RV is OFF in RH group.
ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG.9-4
Page 51
4.1 Heating , Reverse Cycle.
Mode: Heat, Auto (At heating)
Temp: Selected desired temperature
Fan: Hi , Med , Lo
Timer: Any
I Feel: On or Off
Control function

Maintains room temp. at desired level by comparing RAT or RCT to SPT.

Note: IF starts when:

  • a) (ICT > 20°C) AND (30 sec after Heat Mode as started), or
  • b) (ICT thermistor is disconnected) AND (40 sec after COMP has started). IF stops when (18°C ≥ ICT).
ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG 9- 5
Page 52

WALL MOUNTED SPLIT A.C

4.2 Heating , Reverse Cycle and Autofan .

Mode:Mode: Heat, Auto (At heating)Temp:Temp: Selected desired temperatureFan:Fan:AutoTimer:Timer:AnyI Feel:I Feel: On or Off

Cont Control function

Main Maintains room Temp. at desired level by controlling Comp, IF and OF.

Note 1 : IF starts when : (a) (ICT > 40°C), or (b) (40°C ≥ ICT ≥ 30°C) AND (40 sec. After COMP is on).

Note 2 : IF stops when :

(a) (30°C > ICT), or

(b) (40°C > ICT ≥ 30°C) AND (40 sec after COMP is OFF).

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG 9-6
Page 53

ALL MOUNTED SPLIT A.C

Note 3. OF is turned ON/OFF as below if

  • (a) (RAT ≥ SPT 2°C), AND
  • (a) (10 CT ≥ 01 F 2 C) (b) (1CT ≥ 45°C), AND (c) (COMP is ON)

Otherwise. OF runs together with COMP.

5.0 Automatic Cooling or Heating - General
5.0.1 Switching temperature between Cooling and Heating is SPT +/-2°C.
5.0.2 Autofan in Automatic Cooling or Heating Mode will activate Heating and Autofan Mode or Cooling and Autofan Mode respectively.
5.0.2.a for Cooling with Autofan, refer to para. 3.2.
5.0.2.b for Heating with Autofan (RC Group), refer to para. 4.2.
5.0.2.c for Heatling with Autofan (RH Group), refer to para. 4.3.
5.0.2.d for Heating with Autofan (SH Group), refer to para. 4.6.
ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG.9-7
Page 54

WALL MOUNTED SPLIT A.C

5.1 Auto Cooling or Heating by Reverse Cycle

Mode:AutoTemp:Selected desired temperature.Fan:AnyTimer:AnyI Feel:On or Off
Control function

Maintains room temp. at desired level by selecting between cooling and heating modes.

NOTE 1: Heating Group can be either RC or SH according to Group select jumpers setup. NOTE 2: HE1 and HE2 are for SH Group only.

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG 9-8
Page 55

6.1 Dry for RC

Mode: Dry
Temp: selected - desired temp
Fan: Low (Automaticaly selected by Software
Timer: Any
l Feel: On or Off

Control function:

Cooling operation is activated to dehumidify the room, while minimizing fluctuations of temp. .

COMP. is operated by temp. and time intervals. Room temp. is detected by RAT( RT-1 sensor), or RCT (at | Feel), and is compared to SPT.

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG.9-9
Page 56

Protection.

  • 7.1 Cooling Mode
  • 7.1.1 Indoor Coil Defrost .
Mode: Cooling, Dry, Auto (At cooling).
Temp: Selected desired temp.
Fan: Any
Timer: Any
l Feel: On or Off
Control Function

Protects the indoor coil from ice formation at low Ambient temperatures.

Notes :1. When J7 is closed (connected), OF cycling is cancelled and the set temperature for COMP & OF cut-out and cut-in are changed, i.e. COMP & OF are forced off when ICT≤-6°C and are kept OFF until ICT > 14°C.

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG.9-10
Page 57

7.1.2 High Pressure Protection (Outdoor Coil).

Mode:Cooling, Dry, Auto (at cooling).Temp:Selected desired temp.Fan:AnyTimer:AnyI Feel:On or Off.

Control Function

COMP High Pressure protection by switching off the IF and Compressor.

NOTE1: In EPE-800 model, operation LED starts to blink when Comp is Off.

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG.9-11
Page 58

  • 7.2 Heating Mode
  • 7.2.1 Deicing by reverse valve (When heating).

Mode:Heating, Auto (at Heating)Temp:Selected desired Temp.Fan:AnyTimer:AnyI FEEL:On or Off

Control Function:

To Protect the outdoor coil from ice formation when unit operates at low outdoor temp. OCT is detected by OCT( RT-3 sensor). The control process is based on the combination of Temp and timed cycling.

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG.9-12
Page 59

7.2.2 High pressure protection Indoor coil (excluding RH Group)

Mode: Heating, Auto (at heating)
Fan: Any
Timer: Any
I Feel: On or Off

Control Function

To protect the Compressor from High Pressure by switching off the OF and compressor.

-----

Note : IF, HE1 and HE2 will be activated according to the relevant

ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG.9-13
Page 60

18. ON UNIT INDICATORS AND CONTROLS.

STAND BY INDICATOR Lights up when the Air Conditioner is connnected to power
and ready to receive the R/C commands.
OPERATION INDICATOR 1. Lights up during operation.
2. Blinks to announce that a R/C infrared signal has been
received and stored.
3. Blinks during High Pressure Protection mode.
4. Blinks during Deicing in Heating mode.
TIMER INDICATOR Lights up during timer and sleep operation
FILTER INDICATOR & WATER 1. Lights up when Air Filter requiers cleaning.
OVERFLOW 2. Blinks during water overflow.
INDICATOR
COOLING INDICATOR Lights up when system goes into COOLING mode by pressing
MODE SWITCH first time.
HEATING INDICATOR Lights up when system goes into COOLING mode by pressing
MODE SWITCH second time.
MODE SWITCH Used to switch the A/C unit between COOLING, HEATING and
(COO/HEAT/OFF) OFF modes, without using the R/C.
-Pressing the switch first time switches the unit to COOLING mode.
-Pressing the switch secondt time switches the unit to HEATING
mode.
-Pressing the switch third time switches the unit to OFF(STDBY)
mode.
RESET/CANCEL SWITCH 1. Press to turn off the FILTER INDICATOR after a clean filter has
been installed.
2. Press to cancel the buzzer announcer, if elected.
ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG.9-14
Page 61
WALL MOUNTED SPLIT A.C CONTROL FUNCTIONS 9
ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG.9-15
Page 62
.WALL MOUNTED SPLIT A. C CONTROLS, CHECKING PROCEDURE

SELF TEST

1(

STEP 1: ENABLE SELF TEST MODE

Short jumper j1 on the CONTROL BOARD. For WMN model short pins 5&6 on the EMERGENCY SERVICE PLUG. (see note 1)

STEP 2 : TURNING ON THE POWER .

TURN ON THE POWER The following four testing modes will take place at the same time. 1) Testing the mode of operation : ST+SH (see note 2) ACTION : THE STAND-BY LED will indicate the operation mode as following:

OPERATION MODE STAND-BY LED
ST+RH ON
RC+SH OFF

2) Testing the Model configuration. selected by jumpers j3,j4,j5. ACTION : The STAND-BY and TIMER LEDS will indicate the model configuration as follows:

MODEL OPERATE LED TIMER LED FILTER LED
ESM OFF OFF OFF
EMP OFF OFF ON
WMX OFF ON OFF
РХ OFF ON ON
PR ON OFF OFF
WMN ON OFF ON
RWK /ELD ON ON OFF
ECC ON ON ON

3) STEP MOTOR TESTING.

ACTION : The step motor will turn to HOME POSITION.

4) FREQUENCY TESTING.

If zero crossing timing is within 90HZ to 110HZ +/-5HZ. ACTION : The COOL LED will turn to OFF, otherwise the COOL LED will turn ON.

STEP 3 : PRESS MODE BUTTON.

ACTION:

1) All the LED'S will turn OFF.

2) All the LED'S will turn ON for 1 second one by one in the following sequence : STAND-BY ⇒ OPERATE ⇒ TIMER ⇒ FILTER ⇒ COOL ⇒ HEAT. 3) AUTO RELAY WALK TEST : All relays will turn ON one by one in the following sequence : COMPRESSOR ⇒ OUTDOOR FAN- ⇒ R.V. ⇒ HEATER 1 - ⇒ HEATER 2 ⇒ INDOOR WATER PUMP ⇒ SWING or OUTDOOR WATER PUMP⇒ INDOOR FAN: --LOW --MID. -- HIGH.

NOTE : ONLY the relevant relays for each model will be activated.

ELECTRA CONSUMER PRODUCTS LID | REV. 01 1/97 | SP ERIES: WIMIN PG. 10-1
Page 63
.WALL MOUNTED SPLIT A. C CONTROLS, CHECKING PROCEDURE

1(

STEP 4 : PRESS RSET BUTTON Checking the buzzer. ACTION : A single beep will sound.

STEP 5 : PRESS FAN BUTTON FROM THE REMOTE CONTROL Checking the comunication between the remote control and CPU. ACTION : A double beep will sound.

STEP 6 : PRESS MODE BUTTON. Checking thermistors analog voltage. ACTION : STAND-BY LED , OPERATE LED AND TIMER LED MAY TURN ON -PLEASE IGNOR THE RESULT FROM THIS TEST.

STEP 7 : PRESS MODE BUTTON. Checking the memory (EEPROM MEMORY TEST) ACTION : STAND-BY LED will turn ON if 9696H had been written in the EEPROM on all adresses. If the above adress is not written in the EEPROM the FILTER LED will turn ON. This test is for reference only, showing that a full computer test have been done in the production of the controller.

AT THIS POINT THE SELF-TEST IS COMPLETED.

PULL OUT THE SHORTING JUMPER FROM J1 OR PIN 5-6 ON THE EMERGENCY SERVICE PLUG.

NOTES : 1) Emergency service plug layout.

2) LEGEND for operating Modes:

ST = Standard (cooling only) RH = Resisting Heater (Heating by heater element only) RC = Reverse Cycle. SH = Supplementary Heater (Heating by RC and Heater element

3) In order to stop the self test turn off the power.

.ELECTRA consumer products LTD REV. 01 1/97 SERIES:ELECROLUX PG. 10-2
Page 64
.MOBIL SPLIT & MONOBLOCK A.C CONTROLS, CHECKING PROCEDURE 10

.ELECTRA consumer products LTD REV. 01 1/97 SERIES:ELECROLUX PG. 10-3
Page 65

WALL MOUNTED SPLIT A.C

TROUBLESHOOTING

ELECTRICAL & CONTROL TROUBLESHOOTING

ATTENTION : check for broken or loose cable lugs first.

NO SYMPTON PROBABLE CAUSE CORRECTIVE ACTION
1. The power supply
indicator (red led)
doesn't light up.
There is no correct voltage
between the line and
neutral terminals on main
P.C.B.
  • If the voltage is low repair power supply.
  • If there is no voltage repair general wiring.
  • If there is correct voltage replace main or display P.C.B'S
2. The operating
indicator (green led)
does not light up.
The remote control batteries are discharged -Replace batteries of the remote control
3. The operating
indicator (green led)
does not light up when
starting from unit
Check main P.C.B and display P.C.B. -Replace P.C.B if necessary.
4. The indoor fan does not function correctly. Check the voltage between
indoor fan terminals on the
main P.C.B
- If there is voltage replace capacitor or motor.
5. The outdoor fan does not function correctly. Check the voltage between
indoor fan terminals on the
main P.C.B.
- If there is no voltage replace main P.C.B
There is voltage between
outdoor fan terminals on
the outdoor unit.
- Replace capacitor or motor.
There is no voltage
between outdoor fan
terminals on the outdoor
unit.
- Check and repair electrical wiring between indoor and outdoor units.
6. The compressor does Check voltage on -If no voltage replace main P.C.B.
not start up. the outdoor unit. (with ampmeter) - If low voltage repair power supply.
Check if there is correct -If the voltage corrrect replace capacitor or compressor.
compressor terminals on the outdoor unit. -If there is no voltage repair electrical wiring between indoor and outdoor units.
7. The refrigeration
system does not
function correctly.
Check for leaks or
restrictions, with
ampmeter, pressure guage
or surface thermometer.
- Repair refrigeration system and charge refrigerant if necessary.
8. No cooling or heating only indoor fan works. Outdoor fan motor faulty or
other fault caused,
compresssor overload
protection cut out.
-Replace P.C.B.
- Outdoor fan blocked remove obstructions.
ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG. 11-1
Page 66

WALL MOUNTED SPLIT A.C

ATTENTION : check for broken or loose cable lugs first

SYMPTON PROBABLE CAUSE CORRECTIVE ACTION
Only indoor fan and
compressor working.
Outdoor fan blocked. - Remove obstructions.
Only indoor fan
working.
-Run capacitor of outdoor
fan motor faulty.
- Replace capacitor.
-Windings of outdoor fan
are shorted.
-Replace motor.
No cooling or - Overload safety device on - Check for proper voltage, switch off power
heating takes place,
indoor and outdoor
compressor is cut out (low voltage or high and try again after one hour.
fans working. temperature) - Replace compressor capacitor.
- Compressor run capacitor
faulty.
- Replace compressor.
- Compressor windings are shorted.
No air supply at -Indoor fan motor is - Check voltage,repair wiring if necessary.
compressor -indoor fan run capacitor -Check fan wheel if it is tight, enough on
operates faulty motor shaft, tighten if necessary.
- motor windings are shorted. -Replace indoor fan motor.
Partial, limited air Lack of refrigerant (will accompanied by whisteling -Charge the unit after localizing leak.
indoor unit. noise) cause ice formation
on indoor unit coil in cooling mode.
Water accumulates
and overflow from
Drain tube or spout of drain pan clogged. -Disasemble plastic drain tube from spout of indoor unit drain pan.
Water dripping from Water drain outlet is -Open outdoor unit cover clean out water
outdoor unit base.
(in heating mode)
clogged. outlet ,clean the base inside througly.
Freeze-up of outdoor -Faulty outdoor thermistor. -Replace thermistor.
coll in heating mode,
poor heating effect
in room, indoor fan
-Faulty control cable. - Repair control cable.
operates. - Outdoor temperature is
too low (below -2°C)
- Shut unit off, outdoor temp. is below design conditions and cannot function properly.
-Outdoor unit air outlet is
blocked.
-Remove obstructions.
SYMPTONOnly indoor fan and
compressor working.Only indoor fan
working.No cooling or
heating takes place,
indoor and outdoor
fans working.No air supply at
indoor unit,
compressor
operates.Partial, limited air
supply at indoor
indoor unit.Water accumulates
and overflow from
indoor unit section.Water dripping from
outdoor unit base.
(in heating mode)Freeze-up of outdoor
coil in heating mode,
poor heating effect
in room, indoor fan
operates.
SYMPTONPROBABLE CAUSEOnly indoor fan and
compressor working.Outdoor fan blocked.Only indoor fan
workingRun capacitor of outdoor
fan motor faulty.
-Windings of outdoor fan
are shorted.No cooling or
heating takes place,
indoor and outdoor
fans workingOverload safety device on
compressor is cut out (low
voltage or high
temperature)
- Compressor run capacitor
faulty.
- Compressor windings are
shorted.No air supply at
indoor unit,
compressor
operatesIndoor fan motor is
blocked or turns slowly.
-indoor fan run capacitor
faulty.
- motor windings are
shorted.Partial, limited air
supply at indoor
indoor unit section.Lack of refrigerant (will
accompanied by whisteling
noise) cause ice formation
on indoor unit coil in cooling
mode.Water accumulates
and overflow from
indoor unit section.Drain tube or spout of drain
pan clogged.Water dripping from
outdoor unit base.
(in heating mode)-Faulty outdoor thermistor.
-Faulty control cable.
-Faulty control cable Outdoor unit air outlet is
too low (below -2°C)
-Outdoor unit air outlet is
blockedOutdoor unit air outlet is
blocked.
ELECTRA consumer products LTD REV. 01 6/98 SERIES: WMN PG. 11-2
Page 67

ILLUSTRATED PARTS BREAKDOWN WALL MOUNTED SPLIT AIR CONDITIONER

MODEL:WMN 6,7,9,12

PRODUCT GROUP NO. WMN6 - 8016 WMN7 - 8011 WMN9 - 8012 WMN12 - 8013

3011/2/3/6-00

Page 68

Page 69

Page 70

FIG.#3 -ELECTRIC CONTROL ASSY.

Page 71

WALL MOUNTED SPLIT AIR CONDITIONER PRODUCT GROUP NO. 8361,8362

Page 72

Page 73

FIG.#2 -AIR OUTLET FRAME ASSY

PRODUCT GROUP NO. 8361,8362

FOR COMPONENTS DESCRIPTION AND CATALOG NUMBERS REFER TO SPARE PARTS LIST FOR THE RELEVANT PRODUCT NO.

G.-3

ATION No.8361/2 | REV.01-2/9

BB/PROD_EXPLOD/WHX/WHX_EVAP ; AIROUT

Page 74

FIG.#3 -ELECTRIC CONTROL ASSY

PRODUCT GROUP NO. 8361,8362

Page 75

ILLUSTRATED PARTS BREAKDOWN SPLIT AIR-CONDITIONER

MODEL:CUE 15,20,30,40 PRODUCT GROUP NO. CUE15 - 8011 CUE20 - 8012,8022,8301,8351 CUE30 - 8013,8017,8241,8302,8352 CUE40 - 8015,8242,8303

Page 76

FIG.#1 -GENERAL ASSEMBLY - CUE-15,20,30,40 PRODUCT GROUP NO. 8011/8303

Page 77

BB/PROD_EXPLOD/CUE/CUE15-40

Page 78

Page 79

ILLUSTRATED PARTS BREAKDOWN SPLIT AIR-CONDITIONER

MODEL: CUE 45,50,55,60,80

  • PRODUCT GROUP NO. CUE45 8361
    • CUE50 8243,8304,8364,8410,8437
    • CUE55 8305
    • CUE60 8212,8244,8245,8306,8362,
      • 8401,8411,8412,8421,8438,8441
    • CUE80 8213,8246,8321,8419

Page 80

Page 81

Page 82

Page 83

ILLUSTRATED PARTS BREAKDOWN SPLIT AIR-CONDITIONER

MODEL: CUE 85,90,100

PRODUCT GROUP No. CUE85 - 8402,8422,8442 CUE90 - 8214,8247,8311,8363,8406, 8423,8439,8443 CUE100 - 8403,8420,8428

Page 84

Page 85

Page 86

Page 87

ILLUSTRATED PARTS BREAKDOWN SPLIT AIR-CONDITIONER

MODEL: CUE 1515,2020,2030,3030,4040 PRODUCT GROUP NO. CUE1515 - 8354 CUE2020 - 8357 CUE2030 - 8358 CUE3030 - 8359 CUE4040 - 8360

Page 88

FIG.#1 -GENERAL ASSEMBLY- CUE-1515,2020,2030,3030,4040 PRODUCT GROUP NO. 8354/57/58/59/60
I FOR COMPONE
To spare pa
ENTS DESC
RTS LIST
RIPTI
FOR
ON AND CAT
The releva
ALOG NUMB
NT PRODUC
ERS REFER
CT NO.
4-60/01
853
CONSUMER PRODUCTS LTD. PUBLICATION I No. 8354/60 REV.03-12/98 PG2
/BB/PROD_EXPLOD/CUE/ CUE1515-4040
Page 89

FIG.#2 -REFRIGERATION- CUE-1515,2020,2030,3030,4040

PRODUCT GROUP NO. 8354/57/58/59/60

Page 90

FIG.#3 -ELECTRICAL ASSEMBLY- CUE-1515,2020,2030,3030,4040

PRODUCT GROUP NO. 8354/57/58/59/60

FOR COMPONENTS DESCRIPTION AND CATALOG NUMBERS REFER TO SPARE PARTS LIST FOR THE RELEVANT PRODUCT NO.

CONSUMER PRODUCTS LTE PUBLICATION No. 8354/60 REV.03-12/98

/BB/PROD_EXPLOD/CUE/CUE1515-4040

PG.-4

Loading...