Electra PXD24, PXD30 Service Manual

Page 1

PXD Series R410A

CONTENT
Indoor Unit Outdoor Unit
PXD9 ONG9 ST/RC PXD12 ONG12 ST/RC PXD15 ONG14 ST/RC PXD18 GC18 ST/RC PXD18 GC18 ST/RC 3PH
PXD24
PXD24 OU7-24T ST/RC PXD30 OU8-30 ST/RC PXD30 OU8-30T ST/RC
OU7-24 ST/RC OU7-24Z ST/RC
SM PXD 1-E.3 GB
REFRIGERANT
R410A
SEPTEMBER – 2008
COOLING ONLY
HEAT PUMP
Page 2

LIST OF EFFECTIVE PAGES

CONTENT
LIST OF EFFECTIVE PAGES
Note: Changes in the pages are indicated by a “Revision#” in the footer of each effected page
(when none indicates no changes in the relevant page). All pages in the following list represent effected/ non effected pages divided by chapters.
Dates of issue for original and changed pages are:
Original ....... 0 ........ August 2005
Total number of pages in this publication is 149 consisting of the following:
Page No.
Title ....................... 3
A ........................... 3
i ............................. 3
1-1 - 1-3 ................ 3
2-1 - 2-10 .............. 3
3-1 ........................ 3
4-1 - 4-3 ................ 3
5-1 - 5-32 .............. 3
6-1 ........................ 3
7-1 - 7-5 ................ 3
8-1 - 8-2 ................ 3
9-1 - 9-5 ................ 3
10-1 ...................... 3
11-1-11-37 ............. 3
12-1-12-2 .............. 3
13-1-13-42 ............ 3
14-1 – 14-11 ......... 3
Appendix -A ...........3
Revision No. #
Page No.
Revision No. #
Page No.
Revision No. #
*Due to constant improvements please note that the data on this service manual can be modified with out notice. **Photos are not contractual.
A SM PXD 1-E.3 GB
• Zero in this column indicates an original page.
Page 3

TABLE OF CONTENTS

Table of Contents
1. INTRODUCTION ...................................................................................................1-1
2. PRODUCT DATA SHEET ......................................................................................2-1
3. RATING CONDITIONS ..........................................................................................3-1
4. OUTLINE DIMENSIONS .......................................................................................4-1
5. PERFORMANCE DATA & PRESSURE CURVES ................................................5-1
6. ELECTRICAL DATA ..............................................................................................6-1
7. WIRING DIAGRAMS .............................................................................................7-1
8. ELECTRICAL CONNECTIONS .............................................................................8-1
9. REFRIGERATION DIAGRAMS .............................................................................9-1
10. TUBING CONNECTIONS ......................................................................................10-1
11. CONTROL SYSTEM .............................................................................................11-1
12. TROUBLESHOOTING ..........................................................................................12-1
13. EXPLODED VIEWS AND SPARE PARTS LISTS .................................................13-1
OPTIONAL ACCESSORIES .................................................................................14-1
14.
15. APPENDIX A .........................................................................................................15-1
iSM PXD 1-E.3 GB
Page 4
1. INTRODUCTION
CONTENT
1.1 General
The PXD split floor and ceiling units range comprise the ST (cooling only) and RC (heat pump) models, as follows:
Cooling Only PXD9ST PXD12ST PXD15ST
PXD18ST PXD24ST PXD30ST
Heat Pump PXD9RC PXD12RC PXD15RC
PXD18RC PXD24RC PXD30RC
1.2 Main Features
The PXD series benefits from the most advanced technological innovations, namely :
R410A

INTRODUCTION

Microprocessor control.
Infrared remote control, and on unit.
Possibility for treated air distribution to adjacent room (Accessory kit).
High COP.
Easy access to the interconnecting tubing and wiring connections.
Possibility to connect a condensate pump kit with an integral over flow
protection (Accessory kit).
Automatic treated air sweep (horizontal and vertical)
Low indoor and outdoor noise levels.
Easy installation and service.
1.3 Indoor Unit
The indoor unit can be mounted as floor or ceiling type, no special adjustment are needed. it can be easily fitted to many types of residential and commercials applications.
It includes:
Casing with inlet and outlet grilles.
1.4 Filtration
Motorized flaps (Horizontal and vertical).
Advanced electronic control box assembly (storm 10V7).
Coated indoor coil.
Mounting plate
The PXD series presents several types of air filters:
Easily accessible, and re-usable pre-filters (mesh)
Active carbon filter.
1-1SM PXD 1-E.3 GB
Page 5
INTRODUCTION
CONTENT
1.5 Control
The microprocessor indoor controller, and an infrared remote control, supplied as standard, provide complete operating function and programming. The unit is designed with an on unit control board as well. For further details please refer to the Operation Manual, Appendix A.
1.6 Outdoor Unit
The PXD outdoor units can be installed as floor or wall mounted by using a wall supporting bracket. The metal sheets are protected by anti- corrosion paint work allowing long life resistance. All outdoor units are pre-charged. For further information please refer to the Product Data Sheet, Chapter 2.
It includes :
A Rotary Compressor mounted in a soundproofed compartment.
Axial fan.
Outdoor coil with hydrophilic louver fins for RC units.
Outlet air fan grill.
Service valves” flare” type connection.
Interconnecting wiring terminal block.
1.7 Tubing Connections
Flare type interconnecting tubing to be produced on site. For further details please refer to the Installation Manual, Appendix A
1.8 Accessories
ASK (All Season Kit):
For low ambient working conditions in cooling, an ASK can be installed inside the outdoor unit. This kit allows cooling operation down to outdoor temp of -10 ºC by gradually controlling the outdoor fan speed motor.
RCW Wall Mounted Remote Control
The RCW remote control is mounted on the wall, and controls the unit either as an infrared remote control or as a wired controller. The wired controller can control up to 10 Indoor units with the same program settings and adjustments. For further details please refer to Optional Accessories, Chapter on this manual.
1.9 Inbox Documentation
1-2 SM PXD 1-E.3 GB
Each unit is supplied with its own installation and operation manuals.
Page 6
1.10 Matching Table
CONTENT
1.10.1 R410A
INDOOR UNITS
OUTDOOR UNITS
MODEL REF’ K9 K11 K15 K18 WNG9 WNG12 WNG14 WNG18 PXD9 PXD12 PXD15 PXD18
ONG9 ST R410A
ONG12 ST R410A
ONG14 ST R410A
ONG9 RC R410A
ONG12 RC R410A
ONG14 RC R410A √*
GC18 ST R410A
GC18 RC R410A
√* - the outdoor unit of this combination cannot be matched to other indoor units.
INTRODUCTION
INDOOR UNITS
OUTDOOR UNITS
MODEL REF’ KN24 KN30 WNG24 WNG30 PXD24 PXD30 DNG24 DNG30
OU724ST R410A √ OU724T ST R410A √ OU724 RC R410A * √√ OU724T RC R410A * √√ OU830 ST R410A √ OU830T ST R410A √ OU830 RC R410A √ OU830T RC R410A
√* - the outdoor unit of this combination cannot be matched to other indoor units.
The above tables lists outdoor units and PXD indoor units, which can be matched together. In addition the listed outdoor units can be matched with other types of indoor units such as Ducted, Wall Mounted, and Cassettes .
For further information please refer to the relevant Service Manual.
1-3SM PXD 1-E.3 GB
Page 7

PRODUCT DATA SHEET

CONTENT
2. PRODUCT DATA SHEET
2.1 PXD 9 / ONG-9 R410A
Model Indoor Unit PXD-9
Model Outdoor Unit ONG-9
Installation Method of Pipe Flared
Characteristics Units Cooling Only Cooling Heating
Capacity
Power input EER (Cooling) or COP(Heating) Energy efficiency class A A C Power supply V/Ph/Hz 220-240V/Single/50Hz Rated current A 3.7 3.7 4.0 Starting current A 18.7 Circuit breaker rating A 10
Operation control type Remote control Heating elements kW Others
(1)
(1)
(1)
Fan type & quantity Centrifugal x 2 Fan speeds H/M/L RPM 740/650/600
(2)
Air flow External static pressure Min-Max Pa 0 Sound power level Sound pressure level Moisture removal l/hr 1.1 Condensate drain tube I.D mm 16
INDOOR
Dimensions WxHxD mm 820x630x190 Weight kg 21 Package dimensions WxHxD mm 890x710x280 Packaged weight kg 25 Units per pallet units 14 Stacking height units 7 levels Refrigerant control Capillary tube Compressor type, model Rotary,LG GK113PAG Fan type & quantity Propeller(direct) x 1 Fan speeds H/L RPM 780 Air flow H/L m3/hr 1780 Sound power level H/L dB(A) 58 60 Sound pressure level Dimensions WxHxD mm 795x610x290 Weight kg 34 35 Package dimensions WxHxD mm 945x655x395 Packaged weight kg 38 39 Units per pallet Units 9
OUTDOOR
Stacking height units 3 levels Refrigerant type R410A
Refrigerant chargless distance kg/m 1kg/7.5m Additional charge per 1 meter g/m 7.5m<Lin<15m:+10g/m
Connections between units
(3)
(4)
H/M/L dB(A) 39/37/35
(4)
H/M/L m3/hr 370/330/290
H/M/L dB(A) 50/49/47
H/L dB(A) 48 49
Liquid line In.(mm) 1/4"(6.35) Suction line In.(mm) 3/8"(9.53) Max. tubing length m. Max.15
Max. height difference m. Max.7
Btu/hr 9080 9080 9520
kW 2.66 2.66 2.79 kW 0.825 0.825 0.86
W/W 3.22 3.22 3.24
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
2-1SM PXD 1-E.3 GB
Page 8
PRODUCT DATA SHEET
CONTENT
2.2 PXD 12 / ONG-12 R410A
Model Indoor Unit PXD-12 Model Outdoor Unit ONG-12 Installation Method of Pipe Flared
Characteristics Units Cooling Only Cooling Heating
Capacity
Power input EER (Cooling) or COP(Heating)
(1)
(1)
(1)
Energy efficiency class B B C Power supply V/Ph/Hz 220-240V/Single/50Hz Rated current A 5.2 5.2 5.2 Starting current A 24 Circuit breaker rating A 15
Fan type & quantity Centrifugal x 2 Fan speeds H/M/L RPM 830/770/710
(2)
Air flow
H/M/L m3/hr 420/390/350 External static pressure Min-Max Pa 0 Sound power level Sound pressure level
(3)
(4)
H/M/L dB(A) 56/53/51
H/M/L dB(A) 45/41/38 Moisture removal l/hr 1.5 Condensate drain tube I.D mm 16
INDOOR
Dimensions WxHxD mm 820x630 x190 Weight kg 22 Package dimensions WxHxD mm 890x710x280 Packaged weight kg 26 Units per pallet units 14 Stacking height units 7 levels Refrigerant control Capillary tube Compressor type, model Rotary, Toshiba PA145X2C-4FT Fan type & quantity Propeller(direct) x 1 Fan speeds H/L RPM 810 Air flow H/L m3/hr 1850 Sound power level H/L dB(A) 62 64 Sound pressure level
(4)
H/L dB(A) 52 53 Dimensions WxHxD mm 795x610x290 Weight kg 35 36 Package dimensions WxHxD mm 945x655x395 Packaged weight kg 39 40 Units per pallet Units 9
OUTDOOR
Stacking height units 3 levels Refrigerant type R410A Refrigerant chargless distance kg/m 1.23kg/7.5m 1.27kg/7.5m Additional charge per 1 meter g/m 7.5m<Lin<15m:+15g/m
Liquid line In.(mm) 1/4"(6.35) Suction line In.(mm) 3/8"(9.53)
Connections between units
Max. tubing length m. Max.15 Max. height difference m. Max.7
Operation control type Remote control Heating elements kW Others
Btu/hr 12010 12010 12620
kW 3.52 3.52 3.7 kW 1.155 1.155 1.15
W/W 3.05 3.05 3.22
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
2-2 SM PXD 1-E.3 GB
Page 9
PRODUCT DATA SHEET
CONTENT
2.3 PXD 15 / ONG-14 R410A
Model Indoor Unit PXD-15
Model Outdoor Unit ONG-14
Installation Method of Pipe Flared
Characteristics Units Cooling Only Cooling Heating
Capacity
Power input EER (Cooling) or COP(Heating)
(1)
(1)
(1)
Energy efficiency class B B C Power supply V/Ph/Hz 220-240V/Single/50Hz Rated current A 6.4 6.4 6.5 Starting current A 30 Circuit breaker rating A 15
Fan type & quantity Centrifugal x 2 Fan speeds H/M/L RPM 1000/780/720
(2)
Air flow
H/M/L m3/hr 510/390/350
External static pressure Min-Max Pa 0 Sound power level Sound pressure level
(3)
(4)
H/M/L dB(A) 57/53/49
H/M/L dB(A) 48/43/38
Moisture removal l/hr 1.9 Condensate drain tube I.D mm 16
INDOOR
Dimensions WxHxD mm 820x630 x190 Weight kg 22 Package dimensions WxHxD mm 890x710x280 Packaged weight kg 26 Units per pallet units 14 Stacking height units 7 levels Refrigerant control Capillary tube Compressor type, model Rotary, MITSUBISHI RN165VHSMT Fan type & quantity Propeller(direct) x 1 Fan speeds H/L RPM 920 Air flow H/L m3/hr 2160 Sound power level H/L dB(A) 63 64 Sound pressure level
(4)
H/L dB(A) 53 54 Dimensions WxHxD mm 795x610x290 Weight kg 41.5 42.2 Package dimensions WxHxD mm 945x655x395 Packaged weight kg 45.5 46.5 Units per pallet Units 9
OUTDOOR
Stacking height units 3 levels Refrigerant type R410A Refrigerant chargless distance kg/m 1.34kg/7.5m Additional charge per 1 meter g/m 7.5m<Lin<15m:+25g/m
Liquid line In.(mm) 1/4"(6.35) Suction line In.(mm) 1/2"(12.7)
Connections between units
Max. tubing length m. Max.15 Max. height difference m. Max.7
Operation control type Remote control Heating elements kW Others
Btu/hr 13990 13990 15350
kW 4.1 4.1 4.5 kW 1.355 1.355 1.380
W/W 3.03 3.03 3.26
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
2-3SM PXD 1-E.3 GB
Page 10
PRODUCT DATA SHEET
CONTENT
2.4 PXD 18 / GC-18 R410A
Model Indoor Unit PXD-18 Model Outdoor Unit GC-18 Installation Method of Pipe Flared
Characteristics Units Cooling Only Cooling Heating
Capacity
Power input EER (Cooling) or COP(Heating)
(1)
(1)
(1)
Energy efficiency class B B C Power supply V/Ph/Hz 220-240V/Single/50Hz Rated current A 8.2 8.2 7.9 Starting current A 43 Circuit breaker rating A 15
Fan type & quantity Centrifugal x 2 Fan speeds H/M/L RPM 1100/1000/900 Air flow
(2)
H/M/L m3/hr 930/820/700 External static pressure Min-Max Pa 0 Sound power level Sound pressure level
(3)
(4)
H/M/L dB(A) 65/60/56
H/M/L dB(A) 51/48/45 Moisture removal l/hr 1.9 Condensate drain tube I.D mm 16
INDOOR
Dimensions WxHxD mm 1200x630x190 Weight kg 30 Package dimensions WxHxD mm 1270x710x280 Packaged weight kg 35 Units per pallet units 7 Stacking height units 7 levels Refrigerant control Capillary tube Compressor type, model Rotary,LG GJ208PAA Fan type & quantity Propeller(direct) x 1 Fan speeds H/L RPM 815 Air flow H/L m3/hr 2480 Sound power level H/L dB(A) 68 Sound pressure level
(4)
H/L dB(A) 58 Dimensions WxHxD mm 846x690x302 Weight kg 56 Package dimensions WxHxD mm 990x470x430 Packaged weight kg 60 61 Units per pallet Units 9
OUTDOOR
Stacking height units 3 levels Refrigerant type R410A Refrigerant chargless distance kg/m 1.6kg/7.5m Additional charge per 1 meter g/m 7.5m<Lin<25m:+25g/m
Liquid line In.(mm) 1/4"(6.35) Suction line In.(mm) 1/2"(12.7)
Connections between units
Max. tubing length m. Max.25 Max. height difference m. Max.15
Operation control type Remote control Heating elements kW Others
Btu/hr 18770 18770 19620
kW 5.5 5.5 5.75 kW 1.82 1.82 1.77
W/W 3.02 3.02 3.25
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
2-4 SM PXD 1-E.3 GB
Page 11
PRODUCT DATA SHEET
CONTENT
2.5 PXD 18 / GC-18 3PH R410A
Model Indoor Unit PXD-18 Model Outdoor Unit GC-18 3PH Installation Method of Pipe Flared
Characteristics Units Cooling Only Cooling Heating
Capacity
Power input EER (Cooling) or COP(Heating)
(1)
(1)
(1)
Energy efficiency class B B B Power supply V/Ph/Hz 380/3/50Hz Rated current A 3.1 3.1 3 Starting current A 26 Circuit breaker rating A 15
Fan type & quantity Centrifugal x 2 Fan speeds H/M/L RPM 1100/1000/900
(2)
Air flow
H/M/L m3/hr 930/820/700 External static pressure Min-Max Pa 0 Sound power level Sound pressure level
(3)
(4)
H/M/L dB(A) 65/60/56
H/M/L dB(A) 51/48/45 Moisture removal l/hr 1.9 Condensate drain tube I.D mm 16
INDOOR
Dimensions WxHxD mm 1200x630x190 Weight kg 30 Package dimensions WxHxD mm 1270x710x280 Packaged weight kg 35 Units per pallet units 7 Stacking height units 7 levels Refrigerant control Capillary tube Compressor type, model Rotary ,Mitsubishi NN21YDAMT Fan type & quantity Propeller(direct) x 1 Fan speeds H/L RPM 815 Air flow H/L m3/hr 2480 Sound power level H/L dB(A) 68 Sound pressure level
(4)
H/L dB(A) 58 Dimensions WxHxD mm 846x690x302 Weight kg 56 Package dimensions WxHxD mm 990x770x430 Packaged weight kg 60 61 Units per pallet Units 9
OUTDOOR
Stacking height units 3 levels Refrigerant type R410A Refrigerant chargless distance kg/m 1.89kg/7.5m
Additional charge per 1 meter g/m
Liquid line In.(mm) 1/4"(6.35)
Connections between units
Suction line In.(mm) 1/2"(12.7) Max .tubing length m. Max.25
Max. height difference m. Max.15 Operation control type Remote control Heating elements kW Others All Season kit factory option
Btu/hr 18760 18760 19600
kW 5.5 5.5 5.75 kW 1.77 1.77 1.69
W/W 3.12 3.12 3.41
4m≤Length≤10m +0g 10m≤Length≤18m +240g 18m≤Length≤25m +560g
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
2-5SM PXD 1-E.3 GB
Page 12
PRODUCT DATA SHEET
CONTENT
2.6 PXD 24 / OU7-24 R410A
Model Indoor Unit PXD-24 Model Outdoor Unit OU7-24
Installation Method of Pipe Flared
Characteristics Units Cooling Only Cooling Heating
Capacity
Power input EER (Cooling) or COP(Heating)
(1)
(1)
(1)
Energy efficiency class B B C Power supply V/Ph/Hz 220-240V/Single/50Hz Rated current A 9.7 9.7 8.4 Starting current A 63 Circuit breaker rating A 20
Fan type & quantity Centrifugal x 2 Fan speeds H/M/L RPM 1200/980/840 Air flow
(2)
H/M/L m3/hr 1000/900/780 External static pressure Min-Max Pa 0 Sound power level Sound pressure level
(3)
(4)
H/M/L dB(A) 64/62/59
H/M/L dB(A) 53/51/48 Moisture removal l/hr 2.7 Condensate drain tube I.D mm 16
INDOOR
Dimensions WxHxD mm 1200x630x190 Weight kg 33 Package dimensions WxHxD mm 1270x710x280 Packaged weight kg 38 Units per pallet units 7 Stacking height units 7 levels Refrigerant control Capillary tube +Restrictor Compressor type ,model Rotary, Mitsubishi NN27VBAMT Fan type & quantity Propeller(direct) x 1 Fan speeds H/L RPM 850 Air flow H/L m3/hr 3100 Sound power level H/L dB(A) 67 Sound pressure level
(4)
H/L dB(A) 58 Dimensions WxHxD mm 900x680x340 Weight kg 74 Package dimensions WxHxD mm 985x730x406 Packaged weight kg 77 Units per pallet Units 6
OUTDOOR
Stacking height units 2 levels Refrigerant type R410A Refrigerant chargless distance kg/m 2.16kg/12.5m
Additional charge per 1 meter g/m
Liquid line In.(mm) 3/8"(9.53)
Connections between
units
Suction line In.(mm) 5/8"(15.88) Max .tubing length m. Max.30
Max .height difference m. Max.15 Operation control type Remote control Heating elements kW Others All Season kit factory option
.
Btu/hr 23300 23300 24000
kW 6.83 6.83 7.03 kW 2.27 2.27 2.13
W/W 3.01 3.01 3.03
12.5m<Add 430g<25m 25m<Add 530g<30m
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
2-6 SM PXD 1-E.3 GB
Page 13
PRODUCT DATA SHEET
CONTENT
2.7 PXD 24 / OU7-24Z R410A
Model Indoor Unit PXD-24
Model Outdoor Unit OU7-24Z R410A
Installation Method of Pipe Flared
Characteristics Units Cooling Only Cooling Heating
Capacity
Power input EER (Cooling) or COP(Heating)
(1)
(1)
(1)
Energy efficiency class B B C Power supply V/Ph/Hz 220-240V/Single/50Hz Rated current A 9.7 9.7 8.4 Starting current A 63 Circuit breaker rating A 20
Fan type & quantity Centrifugal x 2 Fan speeds H/M/L RPM 1200/980/840
(2)
Air flow
H/M/L m3/hr 1000/900/780 External static pressure Min-Max Pa 0 Sound power level Sound pressure level
(3)
(4)
H/M/L dB(A) 64/62/59
H/M/L dB(A) 53/51/48 Moisture removal l/hr 2.7 Condensate drain tube I.D mm 16
INDOOR
Dimensions WxHxD mm 1200x630x190 Weight kg 33 Package dimensions WxHxD mm 1270x710x280 Packaged weight kg 38 Units per pallet units 7 Stacking height units 7 levels Refrigerant control Capillary tube +Restrictor Compressor type ,model Rotary Fan type & quantity Axial x 1 Fan speeds H/L RPM 850 Air flow H/L m3/hr 3100 Sound power level H/L dB(A) 67 Sound pressure level
(4)
H/L dB(A) 58 Dimensions WxHxD mm 900x680x340 Weight kg 78 Package dimensions WxHxD mm 985x730x435 Packaged weight kg 82 Units per pallet Units 6
OUTDOOR
Stacking height units 2 levels Refrigerant type R410A Refrigerant chargless distance kg/m 2.02kg/15m
Additional charge per 1 meter g/m
Liquid line In.(mm) 3/8"(9.53)
Connections between
units
Suction line In.(mm) 5/8"(15.88) Max .tubing length m. Max.15
Max .height difference m. Max.7 Operation control type LCD Remote control Heating elements kW Others
.
Btu/hr 23300 23300 24000
kW 6.83 6.83 7.03 kW 2.27 2.27 2.13
W/W 3.01 3.01 3.03
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
2-7SM PXD 1-E.3 GB
Page 14
PRODUCT DATA SHEET
CONTENT
2.8 PXD 24 / OU7-24T R410A
Model Indoor Unit PXD-24 Model Outdoor Unit OU7-24T Installation Method of Pipe Flared
Characteristics Units Cooling Only Cooling Heating
Capacity
Power input EER (Cooling) or COP(Heating)
(1)
(1)
(1)
Energy efficiency class B B C Power supply V/Ph/Hz 400/3/50 Rated current A 3x7 3x7 3x7 Starting current A 55 Circuit breaker rating A 3x16
Fan type & quantity Centrifugal x 2 Fan speeds H/M/L RPM 1200/980/840 Air flow
(2)
H/M/L m3/hr 1000/900/780 External static pressure Min-Max Pa 0 Sound power level Sound pressure level
(3)
(4)
H/M/L dB(A) 64/62/59
H/M/L dB(A) 53/51/48 Moisture removal l/hr 2.7 Condensate drain tube I.D mm 16
INDOOR
Dimensions WxHxD mm 1200x630x190 Weight kg 33 Package dimensions WxHxD mm 1270x710x280 Packaged weight kg 38 Units per pallet units 7 Stacking height units 7 levels Refrigerant control Capillary tube +Restrictor Compressor type ,model Rotary, Mitsubishi NN27VBAMT Fan type & quantity Propeller(direct) x 1 Fan speeds H/L RPM 850 Air flow H/L m3/hr 3100 Sound power level H/L dB(A) 67 Sound pressure level
(4)
H/L dB(A) 58 Dimensions WxHxD mm 900x680x340 Weight kg 74 Package dimensions WxHxD mm 985x730x406 Packaged weight kg 77 Units per pallet Units 6
OUTDOOR
Stacking height units 2 levels Refrigerant type R410A Refrigerant chargless distance kg/m 2.16kg/12.5m
Additional charge per 1 meter g/m
Liquid line In.(mm) 3/8"(9.53)
Connections between
units
Suction line In.(mm) 5/8"(15.88) Max .tubing length m. Max.30
Max .height difference m. Max.15
Operation control type Remote control Heating elements kW Others All Season kit factory option
Btu/hr 23300 23300 24000
kW 6.83 6.83 7.03 kW 2.27 2.27 2.13
W/W 3.01 3.01 3.03
12.5m<Add 430g<25m 25m<Add 530g<30m
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
2-8 SM PXD 1-E.3 GB
Page 15
PRODUCT DATA SHEET
CONTENT
2.9 PXD 30 / OU8-30 R410A
Model Indoor Unit PXD 30 Model Outdoor Unit OU8-30 Installation Method of Pipe Flared
Characteristics Units Cooling Only Cooling Heating
Capacity
Power input EER (Cooling) or COP(Heating)
(1)
(1)
(1)
Energy efficiency class C C D Power supply V/Ph/Hz 220-240V/Single/50Hz Rated current A 12.2 12.2 11.3 Starting current A 80 Circuit breaker rating A 25
Fan type & quantity Centrifugal x 2 Fan speeds H/M/L RPM 1360/1200/1010
(2)
Air flow
H/M/L m3/hr 1020/895/700 External static pressure Min-Max Pa N/A Sound power level Sound pressure level
(3)
(4)
H/M/L dB(A) 68/64/60
H/M/L dB(A) 56/53/49 Moisture removal l/hr 3.4 Condensate drain tube I.D mm 16
INDOOR
Dimensions WxHxD mm 1200x630x190 Weight kg 32 Package dimensions WxHxD mm 1270x710x280 Packaged weight kg 36 Units per pallet units 7 Stacking height units 7 Levels Refrigerant control Capillary Compressor type, model Rotary, Mitsubishi NN33VAAMT Fan type & quantity Propeller(direct) x 1 Fan speeds H/L RPM 850 Air flow H/L m3/hr 3150 Sound power level H/L dB(A) 69 Sound pressure level
(4)
H/L dB(A) 59 Dimensions WxHxD mm 900x860x340 Weight kg 78 Package dimensions WxHxD mm 985x907x435 Packaged weight kg 82 Units per pallet Units 6
OUTDOOR
Stacking height units 2 Levels Refrigerant type R410A Refrigerant chargless distance kg/m 2.42kg/15m Additional charge per 1 meter g/m 30
Liquid line In.(mm) 3/8"(9.53) Suction line In.(mm) 5/8"(15.88)
Connections between units
Max .tubing length m. Max.30
Max .height difference m. Max.15
Operation control type Remote control Heating elements kW Others Crankcase heater (50W)
Btu/hr 29,100 29,100 29,500
kW 8.52 8.52 8.65 kW 2.99 2.99 2.79
W/W 2.85 2.85 3.10
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
2-9SM PXD 1-E.3 GB
Page 16
PRODUCT DATA SHEET
CONTENT
2.10 PXD 30 / OU8-30T R410A
Model Indoor Unit PXD 30 Model Outdoor Unit OU8-30T Installation Method of Pipe Flared
Characteristics Units Cooling Only Cooling Heating
Capacity
Power input EER (Cooling) or COP(Heating)
(1)
(1)
(1)
Energy efficiency class C C D Power supply V/Ph/Hz 400V/3/50 Rated current A 3x5.2 3x5.2 3x5.1 Starting current A 35 Circuit breaker rating A 3x16
Fan type & quantity Centrifugal x 2 Fan speeds H/M/L RPM 1360/1200/1010
(2)
Air flow
H/M/L m3/hr 1020/895/700 External static pressure Min-Max Pa N/A Sound power level Sound pressure level
(3)
(4)
H/M/L dB(A) 68/64/60
H/M/L dB(A) 56/53/49 Moisture removal l/hr 3.4 Condensate drain tube I.D mm 16
INDOOR
Dimensions WxHxD mm 1200x630x190 Weight kg 32 Package dimensions WxHxD mm 1270x710x280 Packaged weight kg 36 Units per pallet units 7 Stacking height units 7 Levels Refrigerant control Capillary Compressor type, model Rotary, Mitsubishi NN33VAAMT Fan type & quantity Propeller(direct) x 1 Fan speeds H/L RPM 850 Air flow H/L m3/hr 3150 Sound power level H/L dB(A) 69 Sound pressure level
(4)
H/L dB(A) 59 Dimensions WxHxD mm 900x860x340 Weight kg 78 Package dimensions WxHxD mm 985x907x435 Packaged weight kg 82 Units per pallet Units 6
OUTDOOR
Stacking height units 2 Levels Refrigerant type R410A Refrigerant chargless distance kg/m 2.42kg/15m
Additional charge per 1 meter g/m 30
Liquid line In.(mm) 3/8"(9.53) Suction line In.(mm) 5/8"(15.88)
Connections between units
Max .tubing length m. Max.30
Max .height difference m. Max.15
Operation control type Remote control Heating elements kW
Others Crankcase heater (50W)
Btu/hr 28300 28300 28,300
kW 8.30 8.30 8.30 kW 2.77 2.77 2.63
W/W 3.00 3.00 3.15
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
2-10 SM PXD 1-E.3 GB
Page 17
3. RATING CONDITIONS
CONTENT
Standard conditions in accordance with ISO 5151, ISO 13253 (for ducted units) and EN 14511.
Cooling:
Indoor: 27oC DB 19oC WB Outdoor: 35 oC DB
Heating:
Indoor: 20oC DB Outdoor: 7oC DB 6oC WB
3.1 Operating Limits R410A
Cooling
Heating
Voltage
Upper limit 32 Lower limit 21 Upper limit 27 Lower limit 20 1PH 198 – 264 V 3PH 360 – 440 V

RATING CONDITIONS

Indoor Outdoor
o
C DB 23oC WB 46oC DB
o
C DB 15oC WB 21oC DB
o
C DB 24oC DB 18oC WB
o
C DB -9oC DB -10oC WB
3-1SM PXD 1-E.3 GB
Page 18
4. OUTLINE DIMENSIONS
CONTENT
4.1 Indoor Unit : PXD 9, 12, 15 R410A

OUTLINE DIMENSIONS

4.2 Indoor Unit : PXD 18, 24, 30 R410A
4-1SM PXD 1-E.3 GB
Page 19
OUTLINE DIMENSIONS
CONTENT
4.3 Outdoor Unit : ONG 9, 12, 14
4.4 Outdoor Unit : GC 18
4-2 SM PXD 1-E.3 GB
Page 20
4.5 Outdoor Unit : OU7-24 / OU7-24Z
CONTENT
OUTLINE DIMENSIONS
4.6 Outdoor Unit : OU8-30
4-3SM PXD 1-E.3 GB
Page 21

PERFORMANCE DATA & PRESSURE CURVES

CONTENT
5. PERFORMANCE DATA
5.1 PXD9 ONG9 R410A
5.1.1 Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OU COIL (°C)
(1)
15
(1)
20
25
30
35
40
46
DATA
TC
SC PI
TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC
SC PI
ENTERING AIR WB/DB ID COIL ( °C)
15/21 17/24 19/27 21/29 23/32
2.80 2.90 2.97 3.04 3.09
1.85 1.93 2.01 2.06 2.09
0.59 0.59 0.59 0.59 0.60
2.71 2.86 2.95 3.02 3.08
1.81 1.91 1.99 2.05 2.09
0.64 0.64 0.64 0.65 0.65
2.57 2.77 2.91 3.00 3.07
1.77 1.88 1.98 2.03 2.07
0.69 0.70 0.70 0.70 0.71
2.40 2.61 2.82 2.92 3.01
1.71 1.82 1.93 1.99 2.03
0.74 0.76
2.22 2.41
0.76
2.66
0.77 0.78
2.79 2.93
1.63 1.75 1.89 1.94 1.98
0.80 0.82
2.02 2.20
0.83
2.40
0.84 0.84
2.62 2.76
1.53 1.65 1.79 1.84 1.88
0.87 0.88 0.89 0.91 0.91
1.75 1.92 2.11 2.33 2.51
1.41 1.51 1.63 1.69 1.72
0.95 0.96 0.98 1.00 1.01
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW
o
WB – Wet Bulb Temp., (
C) DB – Dry Bulb Temp., (oC) ID Indoor OU – Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15).
5-1SM PXD 1-E.3 GB
Page 22
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.1.2 Heating Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR DB ID COIL ( °C)
15 20 25
ENTERING AIR
WB OU COIL ( °C)
-10
-7 1.58 0.71 1.52 0.74 1.46 0.78
-2 1.67 0.71 1.62 0.76 1.56 0.80 2 2.04 0.75
6 2.87 0.80 2.79 0.86 2.69 0.91 10 3.12 0.85 15 3.38 0.89 3.29 0.95 3.21 1.01
20 3.56 0.91 3.47 0.99 3.38 1.07
TH PI TH PI TH PI
1.46 0.69 1.41 0.73 1.35 0.77
1.95 0.80
3.04 0.91
* the above chart includes the weighted deicing infleuence.
1.87 0.84
2.96 0.97
LEGEND
TH – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB – Dry Bulb Temp., (oC) ID Indoor OU – Outdoor
5.2 Capacity Correction Factor Due to Tubing Length
5.2.1 Cooling
TOTAL TUBING LENGTH
3m
1.02
7.5m 1
10m 15m 20m 25m 30m 40m 50m
0.961 0.950 --- --- --- --- ---
* Minimum recommended tubing length between indoor and outdoor units is 3m.
5.2.2 Heating
5-2 SM PXD 1-E.3 GB
TOTAL TUBING LENGTH
3m
1.04
7.5m 1
10m 15m 20m 25m 30m 40m 50m
0.975 0.961 --- --- --- --- ---
* Minimum recommended tubing length between indoor and outdoor units is 3m.
Page 23
5.3 Pressure Curves.
CONTENT
5.3.1 Cooling.
12.0
11.0
10.0
9.0
8.0
7.0
6.0
Suction Pressure (Bar[g])
5.0
15 20 25 30 35 40 46
15/21(W B/ DB ºC) 17/24(WB/DB ºC) 19/27(WB/DB ºC) 21/29(WB/DB ºC) 23/32(WB/DB ºC)
PERFORMANCE DATA & PRESSURE CURVES
Suction Pressure VS.Outdoor Temp
Outdoor Temp.(DB oC )
Discharge Pressure VS.Outdoor Temp
40 38 36 34 32 30 28 26 24 22 20 18 16 14
Discharge Pressure (Bar[g])
12 10
15 20 25 30 35 40 46
15/21(WB/DB ºC) 17/24(WB/DB ºC) 19/27(WB/DB ºC) 21/29(WB/DB ºC) 23/32(WB/DB ºC)
Outdoor Temp.(DB oC )
5-3SM PXD 1-E.3 GB
Page 24
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.3.2 Heating.
12.0
11.0
10.0
9.0
8.0
7.0
6.0
5.0
Suction Pressure(Bar[g])
4.0
3.0
-10-5 0 5 101520
15 DB (ºC) 20 DB (ºC) 25 DB (ºC)
Outdoor Temp.( WB oC )
Discharge Pressure VS.Outdoor Temp
Suction Pressure VS.Outdoor Temp
40 38 36 34 32 30 28 26 24 22 20 18 16 14 12
Discharge Pressure(Bar[g])
10
-10 -5 0 5 10 15 20
25 DB (ºC) 20 DB (ºC) 15 DB (ºC)
Outdoor Temp.( WB oC )
5-4 SM PXD 1-E.3 GB
Page 25
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.4 PXD12 ONG12 R410A
5.4.1 Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OU COIL (°C)
(1)
15
(1)
20
25
30
35
40
46
DATA
TC
SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI
TC SC PI
ENTERING AIR WB/DB ID COIL ( °C)
15/21 17/24 19/27 21/29 23/32
3.71 3.84 3.93 4.03 4.09
2.40 2.50 2.60 2.66 2.71
0.82 0.82 0.83 0.83 0.83
3.59 3.78 3.90 4.00 4.08
2.35 2.48 2.58 2.66 2.71
0.89 0.90 0.90 0.90 0.91
3.40 3.67 3.86 3.97 4.07
2.29 2.43 2.56 2.64 2.69
0.96 0.97 0.98 0.98 0.99
3.18 3.46 3.74 3.87 3.98
2.22 2.36 2.51 2.58 2.63
1.04 1.06
2.94 3.19
1.07
3.52
1.07 1.08
3.70 3.87
2.11 2.26 2.45 2.52 2.57
1.12 1.14
2.67 2.91
1.16
3.18
1.17 1.18
3.47 3.65
1.99 2.14 2.32 2.39 2.44
1.21 1.23 1.25 1.27 1.28
2.32 2.54 2.79 3.08 3.32
1.83 1.96 2.11 2.19 2.24
1.32 1.34 1.37 1.39 1.41
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C) DB – Dry Bulb Temp., (oC) ID Indoor OU – Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15).
5-5SM PXD 1-E.3 GB
Page 26
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.4.2 Heating Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR DB ID COIL ( °C)
15 20 25
ENTERING AIR
WB OU COIL (°C)
-10 1.94 0.92 1.87 0.98 1.79 1.03
-7 2.09 0.94 2.02 0.99 1.94 1.05
-2 2.22 0.95 2.15 1.01 2.07 1.07 2 2.70 1.00
6 3.81 1.08 3.70 1.15 3.57 1.22 10 4.14 1.14 15 4.48 1.18 4.37 1.28 4.26 1.36
20 4.72 1.22 4.61 1.32 4.48 1.43
TH PI TH PI TH PI
2.59 1.06
4.03 1.21
* the above chart includes the weighted deicing infleuence.
2.48 1.13
3.92 1.30
LEGEND
TH – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB – Dry Bulb Temp., (oC) ID Indoor OU – Outdoor
5.5 Capacity Correction Factor Due to Tubing Length
5.5.1 Cooling
TOTAL TUBING LENGTH
3m
1.03
7.5m 1
10m 15m 20m 25m 30m 40m 50m
0.961 0.948 —————
* Minimum recommended tubing length between indoor and outdoor units is 3m.
5.5.2 Heating
5-6 SM PXD 1-E.3 GB
TOTAL TUBING LENGTH
3m
1.05
7.5m
1
10m 15m 20m 25m 30m 40m 50m
0.975 0.963 —————
* Minimum recommended tubing length between indoor and outdoor units is 3m.
Page 27
5.6 Pressure Curves.
CONTENT
5.6.1 Cooling.
12.0
11.0
10.0
9.0
8.0
7.0
6.0
Suction Pressure (Bar[g])
5.0
15 20 25 30 35 40 46
15/21(WB/DB ºC) 17/24(WB/DB ºC) 19/27(WB/DB ºC) 21/29(WB/DB ºC) 23/32(WB/DB ºC)
PERFORMANCE DATA & PRESSURE CURVES
Suction Pressure VS.Outdoor Temp
Outdoor Temp.(DB oC )
Discharge Pressure VS.Outdoor Temp
40 38 36 34 32 30 28 26 24 22 20 18 16 14
Discharge Pressure (Bar[g])
12 10
15 20 25 30 35 40 46
15/21(WB/DB ºC) 17/24(WB/DB ºC) 19/27(WB/DB ºC) 21/29(WB/DB ºC) 23/32(WB/DB ºC)
Outdoor Temp.(DB oC )
5-7SM PXD 1-E.3 GB
Page 28
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.6.2 Heating.
Suction Pressure VS.Outdoor Temp
12.0
11.0
10.0
9.0
8.0
7.0
6.0
5.0
Suction Pressure(Bar[g])
4.0
3.0
-10 -5 0 5 10 15 20
Outdoor Temp.( WB oC )
15 DB (ºC) 20 DB (ºC) 25 DB (ºC)
Discharge Pressure VS.Outdoor Temp
40 38 36 34 32 30 28 26 24 22 20 18 16 14 12
Discharge Pressure(Bar[g])
10
-10 -5 0 5 10 15 20
Outdoor Temp.( WB oC )
25 DB (ºC) 20 DB (ºC) 15 DB (ºC)
5-8 SM PXD 1-E.3 GB
Page 29
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.7 PXD15 ONG14 R410A
5.7.1 Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OU COIL (°C)
(1)
15
(1)
20
25
30
35
40
46
DATA
TC
SC
PI TC SC
PI TC SC
PI TC SC
PI TC SC
PI TC SC
PI TC SC
PI
ENTERING AIR WB/DB ID COIL ( °C)
15/21 17/24 19/27 21/29 23/32
4.32 4.48 4.58 4.69 4.76
2.74 2.86 2.97 3.05 3.10
0.96 0.96 0.96 0.96 0.97
4.18 4.41 4.55 4.65 4.75
2.69 2.83 2.95 3.04 3.09
1.04 1.04 1.05 1.05 1.05
3.96 4.27 4.49 4.63 4.74
2.62 2.78 2.93 3.01 3.07
1.12 1.13 1.14 1.15 1.15
3.70 4.03 4.35 4.51 4.64
2.54 2.70 2.87 2.95 3.01
1.21 1.23
3.43 3.72
1.24
4.10
1.25 1.26
4.31 4.51
2.41 2.59 2.80 2.88 2.94
1.31 1.33
3.11 3.39
1.35
3.70
1.36 1.37
4.05 4.25
2.27 2.45 2.65 2.73 2.79
1.41 1.43 1.46 1.47 1.49
2.70 2.95 3.25 3.59 3.87
2.09 2.24 2.42 2.50 2.56
1.54 1.56 1.60 1.62 1.64
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB – Dry Bulb Temp., (oC) ID Indoor OU – Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15).
5-9SM PXD 1-E.3 GB
Page 30
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.7.2 Heating Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR DB ID COIL ( °C)
15 20 25
ENTERING AIR
WB OU COIL (°C)
-10 2.36 1.10 2.27 1.18 2.18 1.24
-7 2.54 1.13 2.45 1.19 2.36 1.26
-2 2.70 1.15 2.61 1.21 2.52 1.28 2 3.29 1.20
6 4.64 1.29 4.50 1.38 4.34 1.47 10 5.04 1.36 15 5.45 1.42 5.31 1.53 5.18 1.63
20 5.74 1.46 5.60 1.59 5.45 1.71
TH PI TH PI TH PI
3.15 1.28
4.91 1.46
* the above chart includes the weighted deicing infleuence.
3.02 1.35
4.77 1.56
LEGEND
TH – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB – Dry Bulb Temp., (oC) ID Indoor OU – Outdoor
5.8 Capacity Correction Factor Due to Tubing Length
5.8.1 Cooling
TOTAL TUBING LENGTH
3m
1.02
7.5m
1
10m 15m 20m 25m 30m 40m 50m
0.984 0.946 --- --- --- --- ---
* Minimum recommended tubing length between indoor and outdoor units is 3m.
5.8.2 Heating
5-10 SM PXD 1-E.3 GB
TOTAL TUBING LENGTH
3m
1.04
7.5m 1
10m 15m 20m 25m 30m 40m 50m
0.995 0.971 --- --- --- --- ---
* Minimum recommended tubing length between indoor and outdoor units is 3m.
Page 31
5.9 Pressure Curves.
CONTENT
5.9.1 Cooling.
12.0
11.0
10.0
9.0
8.0
7.0
6.0
Suction Pressure (Bar[g])
5.0
15 20 25 30 35 40 46
15/21(W B/ DB ºC) 17/24(W B/ DB ºC) 19/27(W B/ DB ºC) 21/29(W B/ DB ºC) 23/32(W B/ DB ºC)
PERFORMANCE DATA & PRESSURE CURVES
Suction Pressure VS.Outdoor Temp
Outdoor Temp.(DB oC )
Discharge Pressure VS.Outdoor Temp
40 38 36 34 32 30 28 26 24 22 20 18 16 14
Discharge Pressure (Bar[g])
12 10
15 20 25 30 35 40 46
15/21(WB/DB ºC) 17/24(WB/DB ºC) 19/27(WB/DB ºC) 21/29(WB/DB ºC) 23/32(WB/DB ºC)
Outdoor Temp.(DB oC )
5-11SM PXD 1-E.3 GB
Page 32
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.9.2 Heating.
Suction Pressure VS.Outdoor Temp
12.0
11.0
10.0
9.0
8.0
7.0
6.0
5.0
Suction Pressure(Bar[g])
4.0
3.0
-10 -5 0 5 10 15 20
Outdoor Temp.( WB oC )
15 DB (ºC) 20 DB (ºC) 25 DB (ºC)
Discharge Pressure VS.Outdoor Temp
40 38 36 34 32 30 28 26 24 22 20 18 16 14 12
Discharge Pressure(Bar[g])
10
-10 -5 0 5 10 15 20
Outdoor Temp.( WB oC )
25 DB (ºC) 20 DB (ºC) 15 DB (ºC)
5-12 SM PXD 1-E.3 GB
Page 33
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.10 PXD18 GC18 R410A
5.10.1 Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OU COIL (°C)
(1)
15
(1)
20
25
30
35
40
46
DATA
TC
SC
PI TC SC
PI TC SC
PI TC SC
PI
TC SC
PI
TC SC
PI TC SC
PI
ENTERING AIR WB/DB ID COIL ( °C)
15/21 17/24 19/27 21/29 23/32
5.80 6.00 6.15 6.29 6.39
3.94 4.11 4.27 4.37 4.45
1.29 1.29 1.30 1.30 1.31
5.61 5.91 6.10 6.24 6.38
3.86 4.07 4.24 4.36 4.44
1.40 1.41 1.41 1.42 1.42
5.31 5.73 6.02 6.21 6.36
3.76 3.99 4.21 4.33 4.41
1.51 1.52 1.53 1.54 1.56
4.96 5.40 5.84 6.05 6.22
3.64 3.87 4.11 4.24 4.32
1.63 1.66
4.59 4.99
1.67
5.50
1.68 1.70
5.78 6.05
3.46 3.71 4.02 4.14 4.22
1.76 1.79
4.18 4.55
1.82
4.96
1.83 1.84
5.43 5.71
3.26 3.51 3.80 3.92 4.00
1.90 1.93 1.96 1.99 2.01
3.62 3.96 4.36 4.82 5.19
3.01 3.22 3.47 3.59 3.67
2.08 2.11 2.16 2.19 2.21
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW
o
WB – Wet Bulb Temp., ( DB – Dry Bulb Temp., (
o
C)
C) ID Indoor OU – Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15).
5-13SM PXD 1-E.3 GB
Page 34
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.10.2 Heating Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR DB ID COIL ( °C)
15 20 25
ENTERING AIR
WB OU COIL (°C)
-10
-7 3.25 1.45 3.13 1.53 3.02 1.61
-2 3.45 1.47 3.34 1.56 3.22 1.65 2 4.20 1.54
6 5.92 1.65 5.75 1.77 5.55 1.88 10 6.44 1.75 15 6.96 1.82 6.79 1.96 6.61 2.09
20 7.33 1.88 7.16 2.04 6.96 2.19
TH PI TH PI TH PI
3.02 1.42 2.90 1.51 2.79 1.58
4.03 1.64
6.27 1.87
* the above chart includes the weighted deicing infleuence.
3.85 1.73
6.10 2.00
LEGEND
TH – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB – Dry Bulb Temp., (oC) ID Indoor OU – Outdoor
5.11 Capacity Correction Factor Due to Tubing Length
5.11.1 Cooling
TOTAL TUBING LENGTH
3m
1.02
7.5m 1
10m 15m 20m 25m 30m 40m 50m
0.990 0.975 0.960 0.945 --- --- ---
* Minimum recommended tubing length between indoor and outdoor units is 3m.
5.11.2 Heating
5-14 SM PXD 1-E.3 GB
TOTAL TUBING LENGTH
3m
1.03
7.5m
1
10m 15m 20m 25m 30m 40m 50m
1 0.997 0.992 0.988 --- --- ---
* Minimum recommended tubing length between indoor and outdoor units is 3m.
Page 35
5.12 Pressure Curves.
CONTENT
5.12.1 Cooling.
12.0
11.0
10.0
9.0
8.0
7.0
6.0
Suction Pressure (Bar[g])
5.0
15 20 25 30 35 40 46
15/21(WB/DB ºC) 17/24(WB/DB ºC) 19/27(WB/DB ºC) 21/29(WB/DB ºC) 23/32(WB/DB ºC)
PERFORMANCE DATA & PRESSURE CURVES
Suction Pressure Vs.Outdoor Temp
Outdoor Temp.(DB oC )
Discharge Pressure Vs.Outdoor Temp
40 38 36 34 32 30 28 26 24 22 20 18 16 14
Discharge Pressure (Bar[g])
12 10
15 20 25 30 35 40 46
15/21(W B/DB ºC) 17/24(W B/ DB ºC) 19/27(W B/ DB ºC) 21/29(W B/ DB ºC) 23/32(W B/ DB ºC)
Outdoor Temp.(DB oC )
5-15SM PXD 1-E.3 GB
Page 36
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.12.2 Heating.
Suction Pressure Vs.Outdoor Temp
12.0
11.0
10.0
9.0
8.0
7.0
6.0
5.0
4.0
Suction Pressure(Bar[g])
3.0
-10 -5 0 5 10 15 20
Outdoor Temp.( WB oC )
15 DB (ºC) 20 DB (ºC) 25 DB (ºC)
Discharge Pressure Vs.Outdoor Temp
40 38 36 34 32 30 28 26 24 22 20 18 16 14 12
Discharge Pressure(Bar[g])
10
-10 -5 0 5 10 15 20
Outdoor Temp.( WB oC )
25 DB (ºC) 20 DB (ºC) 15 DB (ºC)
5-16 SM PXD 1-E.3 GB
Page 37
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.13 PXD18 GC18 3PH R410A
5.13.1 Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OU COIL (°C)
(1)
15
(1)
20
25
30
35
40
46
DATA
TC
SC
PI TC SC
PI TC SC
PI TC SC
PI
TC SC
PI
TC SC
PI TC SC
PI
ENTERING AIR WB/DB ID COIL ( °C)
15/21 17/24 19/27 21/29 23/32
5.80 6.00 6.15 6.29 6.39
4.09 4.27 4.43 4.55 4.63
1.25 1.26 1.26 1.26 1.27
5.61 5.91 6.10 6.24 6.38
4.01 4.23 4.41 4.53 4.62
1.36 1.37 1.37 1.38 1.38
5.31 5.73 6.02 6.21 6.36
3.91 4.15 4.37 4.50 4.58
1.47 1.48 1.49 1.50 1.51
4.96 5.40 5.84 6.05 6.22
3.79 4.02 4.28 4.40 4.49
1.59 1.61
4.59 4.99
1.63
5.50
1.64 1.65
5.78 6.05
3.60 3.86 4.18 4.30 4.38
1.71 1.74
4.18 4.55
1.77
4.96
1.78 1.79
5.43 5.71
3.39 3.65 3.95 4.08 4.16
1.85 1.88 1.91 1.93 1.95
3.62 3.96 4.36 4.82 5.19
3.13 3.35 3.61 3.73 3.81
2.02 2.05 2.10 2.13 2.15
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW
o
WB – Wet Bulb Temp., (
C) DB – Dry Bulb Temp., (oC) ID Indoor OU – Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15).
5-17SM PXD 1-E.3 GB
Page 38
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.13.2 Heating Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR DB ID COIL ( °C)
15 20 25
ENTERING AIR
WB OU COIL (°C)
-10 3.02 1.35 2.90 1.44 2.79 1.51
-7 3.25 1.39 3.13 1.46 3.02 1.54
-2 3.45 1.40 3.34 1.49 3.22 1.57 2 4.20 1.47
6 5.92 1.58 5.75 1.69 5.55 1.79 10 6.44 1.67 15 6.96 1.74 6.79 1.88 6.61 1.99
20 7.33 1.79 7.16 1.94 6.96 2.10
TH PI TH PI TH PI
4.03 1.56
6.27 1.78
* the above chart includes the weighted deicing infleuence.
3.85 1.66
6.10 1.91
LEGEND
TH – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB – Dry Bulb Temp., (oC) ID Indoor OU – Outdoor
5.14 Capacity Correction Factor Due to Tubing Length
5.14.1 Cooling
TOTAL TUBING LENGTH
3m
1.02
7.5m 1
10m 15m 20m 25m 30m 40m 50m
0.990 0.975 0.960 0.945 --- --- ---
* Minimum recommended tubing length between indoor and outdoor units is 3m.
5.14.2 Heating
5-18 SM PXD 1-E.3 GB
TOTAL TUBING LENGTH
3m
1.03
7.5m 1
10m 15m 20m 25m 30m 40m 50m
1 0.997 0.992 0.988 --- --- ---
* Minimum recommended tubing length between indoor and outdoor units is 3m.
Page 39
5.15 Pressure Curves.
CONTENT
5.15.1 Cooling.
12.0
11.0
10.0
9.0
8.0
7.0
6.0
Suction Pressure (Bar[g])
5.0
15 20 25 30 35 40 46
15/21(WB/DB ºC) 17/24(WB/DB ºC) 19/27(WB/DB ºC) 21/29(WB/DB ºC) 23/32(WB/DB ºC)
PERFORMANCE DATA & PRESSURE CURVES
Suction Pressure Vs.Outdoor Temp
Outdoor Temp.(DB oC )
Discharge Pressure Vs.Outdoor Temp
40 38 36 34 32 30 28 26 24 22 20 18 16 14
Discharge Pressure (Bar[g])
12 10
15 20 25 30 35 40 46
15/21(WB/DB ºC) 17/24(WB/DB ºC) 19/27(WB/DB ºC) 21/29(WB/DB ºC) 23/32(WB/DB ºC)
Outdoor Temp.(DB oC )
5-19SM PXD 1-E.3 GB
Page 40
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.15.2 Heating.
Suction Pressure Vs.Outdoor Temp
12.0
11.0
10.0
9.0
8.0
7.0
6.0
5.0
4.0
Suction Pressure(Bar[g])
3.0
-10 -5 0 5 10 15 20
Outdoor Temp.( WB oC )
15 DB (ºC) 20 DB (ºC) 25 DB (ºC)
Discharge Pressure Vs.Outdoor Temp
40 38 36 34 32 30 28 26 24 22 20 18 16 14 12
Discharge Pressure(Bar[g])
10
-10 -5 0 5 10 15 20
Outdoor Temp.( WB oC )
25 DB (ºC) 20 DB (ºC) 15 DB (ºC)
5-20 SM PXD 1-E.3 GB
Page 41
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.16 PXD24 OU7-24, OU7-24Z & OU7-24T R410A
5.16.1 Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OU COIL (°C)
(1)
15
(1)
20
25
30
35
40
46
DATA
TC
SC
PI TC SC
PI TC SC
PI TC SC
PI
TC SC
PI
TC SC
PI TC SC
PI
ENTERING AIR WB/DB ID COIL ( °C)
15/21 17/24 19/27 21/29 23/32
7.20 7.46 7.63 7.81 7.93
5.02 5.24 5.44 5.58 5.68
1.61 1.61 1.62 1.62 1.63
6.97 7.34 7.57 7.75 7.92
4.92 5.19 5.41 5.56 5.67
1.75 1.75 1.76 1.77 1.77
6.59 7.12 7.48 7.71 7.89
4.80 5.09 5.37 5.52 5.63
1.89 1.90 1.91 1.93 1.94
6.16 6.71 7.25 7.51 7.73
4.65 4.94 5.25 5.40 5.51
2.04 2.07
5.71 6.19
2.08
6.83
2.10 2.12
7.17 7.51
4.42 4.74 5.13 5.28 5.38
2.20 2.23
5.19 5.65
2.27
6.16
2.29 2.30
6.74 7.09
4.16 4.48 4.85 5.01 5.11
2.37 2.41 2.45 2.48 2.50
4.50 4.92 5.41 5.98 6.44
3.84 4.11 4.43 4.58 4.68
2.59 2.63 2.69 2.73 2.76
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW
o
WB – Wet Bulb Temp., ( DB – Dry Bulb Temp., (
o
C)
C) ID Indoor OU – Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15).
5-21SM PXD 1-E.3 GB
Page 42
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.16.2 Heating Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR DB ID COIL ( °C)
15 20 25
ENTERING AIR
WB OU COIL (°C)
-10 4.06 1.70 3.91 1.81 3.75 6.29
-7 4.37 1.75 4.21 1.84 4.06 6.41
-2 4.64 1.77 4.49 1.87 4.33 6.54 2 5.65 1.85
6 7.24 1.99 7.03 2.13 6.78 7.47 10 7.87 2.10 15 8.51 2.19 8.30 2.36 8.08 8.30
20 8.96 2.26 8.75 2.45 8.51 8.72
TH PI TH PI TH PI
5.41 1.97
7.66 2.25
* the above chart includes the weighted deicing infleuence.
5.18 6.89
7.45 7.93
LEGEND
TH – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB – Dry Bulb Temp., (oC) ID Indoor OU – Outdoor
5.17 Capacity Correction Factor Due to Tubing Length
5.17.1 Cooling
TOTAL TUBING LENGTH
4m
1.01
7.5m
1
10m 15m 20m 25m 30m 40m 50m
0.98 0.97 0.96 0.95 0.94 --- ---
* Minimum recommended tubing length between indoor and outdoor units is 3m.
5.17.2 Heating
5-22 SM PXD 1-E.3 GB
TOTAL TUBING LENGTH
4m
1.02
7.5m
1
10m 15m 20m 25m 30m 40m 50m
0.99 0.99 0.98 0.97 0.97 --- ---
* Minimum recommended tubing length between indoor and outdoor units is 3m.
Page 43
5.18 Pressure Curves.
CONTENT
5.18.1 Cooling.
12.0
11.0
10.0
9.0
8.0
7.0
6.0
Suction Pressure (Bar[g])
5.0
15 20 25 30 35 40 46
15/21(W B/ DB ºC) 17/24(W B/ DB ºC) 19/27(W B/ DB ºC) 21/29(W B/ DB ºC) 23/32(W B/ DB ºC)
PERFORMANCE DATA & PRESSURE CURVES
Suction Pressure Vs.Outdoor Temp
Outdoor Temp.(DB oC )
Discharge Pressure Vs.Outdoor Temp
40 38 36 34 32 30 28 26 24 22 20 18 16 14 12
Discharge Pressure (Bar[g])
10
15 20 25 30 35 40 46
15/21(WB/DB ºC) 17/24(WB/DB ºC) 19/27(WB/DB ºC) 21/29(WB/DB ºC) 23/32(WB/DB ºC)
Outdoor Temp.(DB oC )
5-23SM PXD 1-E.3 GB
Page 44
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.18.2 Heating.
12.0
11.0
10.0
9.0
8.0
7.0
6.0
5.0
4.0
Suction Pressure(Bar[g])
3.0
-10 -5 0 5 10 15 20
Outdoor Temp.( WB oC )
Discharge Pressure Vs.Outdoor Temp
Suction Pressure Vs.Outdoor Temp
40 38 36 34 32 30 28 26 24 22 20 18 16 14 12
Discharge Pressure(Bar[g])
10
-10 -5 0 5 10 15 20
Outdoor Temp.( WB oC )
15 DB (ºC) 20 DB (ºC) 25 DB (ºC)
25 DB (ºC) 20 DB (ºC) 15 DB (ºC)
5-24 SM PXD 1-E.3 GB
Page 45
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.19 PXD30 OU8- 30 R410A
5.19.1 Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OU COIL (°C)
(1)
15
(1)
20
25
30
35
40
46
DATA
TC
SC
PI TC SC
PI TC SC
PI TC SC
PI
TC SC
PI
TC SC
PI TC SC
PI
ENTERING AIR WB/DB ID COIL ( °C)
15/21 17/24 19/27 21/29 23/32
8.98 9.30 9.52 9.75 9.89
5.68 5.92 6.15 6.31 6.42
2.12 2.12 2.13 2.13 2.14
8.69 9.16 9.45 9.67 9.88
5.57 5.87 6.12 6.29 6.41
2.30 2.31 2.32 2.33 2.33
8.22 8.88 9.33 9.61 9.85
5.42 5.76 6.07 6.24 6.36
2.49 2.50 2.52 2.54 2.55
7.69 8.37 9.04 9.36 9.64
5.25 5.58 5.94 6.11 6.23
2.68 2.72
7.12 7.72
2.75
8.52
2.77 2.79
8.95 9.37
5.00 5.36 5.80 5.97 6.08
2.89 2.94
6.47 7.05
2.99
7.69
3.01 3.03
8.41 8.84
4.71 5.07 5.49 5.66 5.78
3.12 3.17 3.22 3.26 3.30
5.62 6.14 6.75 7.46 8.04
4.34 4.65 5.00 5.18 5.29
3.41 3.46 3.54 3.59 3.63
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C) DB – Dry Bulb Temp., (oC) ID Indoor OU – Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15).
5-25SM PXD 1-E.3 GB
Page 46
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.19.2 Heating Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR DB ID COIL ( °C)
15 20 25
ENTERING AIR
WB OU COIL (°C)
-10 5.00 2.23 4.81 2.38 4.61 2.50
-7 5.38 2.29 5.19 2.41 5.00 2.54
-2 5.71 2.32 5.52 2.46 5.33 2.59 2 6.95 2.43
6 8.91 2.61 8.65 2.79 8.35 2.96 10 9.69 2.75 15 10.47 2.87 10.21 3.10 9.95 3.29
20 11.03 2.96 10.77 3.21 10.47 3.46
TH PI TH PI TH PI
6.66 2.58
9.43 2.94
* the above chart includes the weighted deicing infleuence.
6.38 2.73
9.17 3.15
LEGEND
TH – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB – Dry Bulb Temp., (oC) ID Indoor OU – Outdoor
5.20 Capacity Correction Factor Due to Tubing Length
5.20.1 Cooling
TOTAL TUBING LENGTH
4m
1.01
7.5m
1
10m 15m 20m 25m 30m 40m 50m
0.98 0.97 0.96 0.95 0.94 --- ---
* Minimum recommended tubing length between indoor and outdoor units is 3m.
5.20.2 Heating
5-26 SM PXD 1-E.3 GB
TOTAL TUBING LENGTH
4m
1.02
7.5m 1
10m 15m 20m 25m 30m 40m 50m
0.99 0.99 0.98 0.97 0.97 --- ---
* Minimum recommended tubing length between indoor and outdoor units is 3m.
Page 47
5.21 Pressure Curves.
CONTENT
5.21.1 Cooling.
12.0
11.0
10.0
9.0
8.0
7.0
6.0
Suction Pressure (Bar[g])
5.0
15 20 25 30 35 40 46
15/21(WB/DB ºC) 17/24(WB/DB ºC) 19/27(WB/DB ºC) 21/29(WB/DB ºC) 23/32(WB/DB ºC)
PERFORMANCE DATA & PRESSURE CURVES
Suction Pressure Vs.Outdoor Temp
Outdoor Temp.(DB oC )
Discharge Pressure Vs.Outdoor Temp
40 38 36 34 32 30 28 26 24 22 20 18 16 14
Discharge Pressure (Bar[g])
12 10
15 20 25 30 35 40 46
15/21(WB/DB ºC) 17/24(WB/DB ºC) 19/27(WB/DB ºC) 21/29(WB/DB ºC) 23/32(WB/DB ºC)
Outdoor Temp.(DB oC )
5-27SM PXD 1-E.3 GB
Page 48
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.21.2 Heating.
Suction Pressure Vs.Outdoor Temp
12.0
11.0
10.0
9.0
8.0
7.0
6.0
5.0
Suction Pressure(Bar[g])
4.0
3.0
-10 -5 0 5 10 15 20
Outdoor Temp.( WB oC )
15 DB (ºC) 20 DB (ºC) 25 DB (ºC)
Discharge Pressure Vs.Outdoor Temp
40 38 36 34 32 30 28 26 24 22 20 18 16 14 12
Discharge Pressure(Bar[g])
10
-10 -5 0 5 10 15 20
Outdoor Temp.( WB oC )
25 DB (ºC) 20 DB (ºC) 15 DB (ºC)
5-28 SM PXD 1-E.3 GB
Page 49
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.22 PXD30 OU8- 30T R410A
5.22.1 Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OU COIL (°C)
(1)
15
(1)
20
25
30
35
40
46
DATA
TC
SC
PI TC SC
PI TC SC
PI TC SC
PI
TC SC
PI
TC SC
PI TC SC
PI
ENTERING AIR WB/DB ID COIL ( °C)
15/21 17/24 19/27 21/29 23/32
8.75 9.06 9.27 9.49 9.64
5.53 5.77 5.99 6.14 6.26
1.96 1.97 1.97 1.98 1.99
8.46 8.92 9.20 9.42 9.62
5.42 5.72 5.96 6.13 6.24
2.13 2.14 2.15 2.16 2.16
8.01 8.65 9.09 9.37 9.59
5.28 5.61 5.91 6.08 6.20
2.30 2.32 2.34 2.35 2.37
7.49 8.15 8.81 9.12 9.39
5.12 5.44 5.78 5.95 6.07
2.49 2.52
6.93 7.52
2.54
8.30
2.56 2.59
8.72 9.13
4.87 5.22 5.65 5.81 5.93
2.68 2.73
6.31 6.86
2.77
7.49
2.79 2.81
8.19 8.61
4.59 4.94 5.34 5.51 5.63
2.89 2.94 2.99 3.02 3.05
5.47 5.98 6.58 7.27 7.83
4.23 4.53 4.87 5.04 5.16
3.16 3.21 3.28 3.33 3.36
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C) DB – Dry Bulb Temp., (oC) ID Indoor OU – Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15).
5-29SM PXD 1-E.3 GB
Page 50
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.22.2 Heating Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR DB ID COIL ( °C)
15 20 25
ENTERING AIR
WB OU COIL (°C)
-10 4.79 2.10 4.61 2.24 4.43 2.35
-7 5.16 2.16 4.98 2.27 4.79 2.40
-2 5.48 2.18 5.30 2.31 5.11 2.45 2 6.66 2.29
6 8.55 2.46 8.30 2.63 8.01 2.79 10 9.30 2.60 15 10.04 2.71 9.79 2.92 9.55 3.10
20 10.58 2.79 10.33 3.02 10.04 3.26
TH PI TH PI TH PI
6.39 2.43
9.05 2.77
* the above chart includes the weighted deicing infleuence.
6.12 2.58
8.80 2.97
LEGEND
TH – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB – Dry Bulb Temp., (oC) ID Indoor OU – Outdoor
5.23 Capacity Correction Factor Due to Tubing Length
5.23.1 Cooling
TOTAL TUBING LENGTH
4m
1.01
7.5m
1
10m 15m 20m 25m 30m 40m 50m
0.98 0.97 0.96 0.95 0.94 --- ---
* Minimum recommended tubing length between indoor and outdoor units is 3m.
5.23.2 Heating
5-30 SM PXD 1-E.3 GB
TOTAL TUBING LENGTH
4m
1.02
7.5m
1
10m 15m 20m 25m 30m 40m 50m
0.99 0.99 0.98 0.97 0.97 --- ---
* Minimum recommended tubing length between indoor and outdoor units is 3m.
Page 51
5.24 Pressure Curves.
CONTENT
5.24.1 Cooling.
12.0
11.0
10.0
9.0
8.0
7.0
6.0
Suction Pressure (Bar[g])
5.0
15 20 25 30 35 40 46
15/21(W B/ DB ºC) 17/24(W B/ DB ºC) 19/27(W B/ DB ºC) 21/29(W B/ DB ºC) 23/32(W B/ DB ºC)
PERFORMANCE DATA & PRESSURE CURVES
Suction Pressure Vs.Outdoor Temp
Outdoor Temp.(DB oC )
Discharge Pressure Vs.Outdoor Temp
40 38 36 34 32 30 28 26 24 22 20 18 16 14
Discharge Pressure (Bar[g])
12 10
15 20 25 30 35 40 46
15/21(WB/DB ºC) 17/24(WB/DB ºC) 19/27(WB/DB ºC) 21/29(WB/DB ºC) 23/32(WB/DB ºC)
Outdoor Temp.(DB oC )
5-31SM PXD 1-E.3 GB
Page 52
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.24.2 Heating.
Suction Pressure Vs.Outdoor Temp
12.0
11.0
10.0
9.0
8.0
7.0
6.0
5.0
Suction Pressure(Bar[g])
4.0
3.0
-10 -5 0 5 10 15 20
Outdoor Temp.( WB oC )
15 DB (ºC) 20 DB (ºC) 25 DB (ºC)
Discharge Pressure Vs.Outdoor Temp
40 38 36 34 32 30 28 26 24 22 20 18 16 14 12
Discharge Pressure(Bar[g])
10
-10 -5 0 5 10 15 20
Outdoor Temp.( WB oC )
25 DB (ºC) 20 DB (ºC) 15 DB (ºC)
5-32 SM PXD 1-E.3 GB
Page 53

ELECTRICAL DATA

CONTENT
6. ELECTRICAL DATA
6.1 Single Phase Units
MODEL PXD 9 PXD 12 PXD 15 PXD 18
Power Supply
Max Current, A 7.1 7.6 10.4 12 Circuit Breaker 10 16 16 16 Power Supply Wiring No. X Cross Section mm Interconnecting Cable RC Model No. X Cross Section mm Interconnecting Cable ST Model No. X Cross Section mm
2
2
2
MODEL PXD 24 PXD 30
Power Supply
Max Current, A Circuit Breaker Power Supply Wiring
No. X Cross Section mm Interconnecting Cable RC Model No. X Cross Section mm Interconnecting Cable ST Model No. X Cross Section mm
2
2
2
To indoor To indoor To indoor To Indoor To outdoor
1PH-230V-50Hz 1PH-230V-50Hz 1PH-230V-50Hz 1PH-230V-50Hz
3x1.5 mm
2
5x1.5 mm2 +2x0.5 mm2
(OCT sensor)
4x1.5 mm
2
3x1.5 mm
5x1.5 mm
(OCT sensor)
4x1.5 mm
To Outdoor
2
2
+2x0.5 mm2
2
3x1.5 mm
2
5x1.5 mm2 +2x0.5 mm2
(OCT sensor)
4x1.5 mm
2
3x2.5 mm
2
5x2.5 mm
+2x0.5 mm2
(OCT sensor)
4x2.5 mm 5x2.5 mm
To outdoor
1PH-230V-50Hz 1PH – 230V – 50 Hz
15 17 20 25
3 x 2.5 mm
2
3 x 4 mm
6 x 1.5 mm2 + 2 X 0.5 mm2 (OCT Sensor) 6 x1.5 mm2 +2 x 0.5 mm2 (OCT sensor)
5 x 1.5 mm2 + 2 X 0.5 mm2 (OCT Sensor) 5 x1.5 mm2 (OCT Sensor)
2
6x1.5 mm2 +2x0.5 mm2
(OCT sensor)
2
6.2 Three Phase Units
MODEL PXD 18T PXD 24T PXD 30T
Power Supply
Max Current, A Circuit Breaker Power Supply Wiring No. X
Cross Section mm
2
Interconnecting Cable RC Model No. X Cross Section mm
Interconnecting Cable ST Model No. X Cross Section mm
2
2
3PH-400V-50Hz 3PH – 400V – 50 Hz 3PH – 400V – 50 Hz
6x1.5 mm2 +2x0.5 mm2
(OCT senser)
To outdoor To outdoor To Outdoor
4.2 6
5x1.5mm
5x1.5 mm
3 x 7.5
3 x 10
2
5 x 1.5 mm
6 X 1.5 mm
(OCT Sensor)
2
5 X 1.5 mm2 + 2 X 0.5 mm
(OCT Sensor)
2
2
+ 2 X 0.5 mm2
6 X 1.5 mm2 + 2 X 0.5 mm2
2
5 X 1.5 mm
3 x 9.2
3 x 16
5 X 2.5 mm
(OCT Sensor)
2
+ 2 X 0.5 mm2
(OCT Sensor)
2
6-1SM PXD 1-E.3 GB
Page 54
7. WIRING DIAGRAMS
CONTENT
7.1 Indoor Unit: PXD 9, 12, 15

WIRING DIAGRAMS

7.2 Indoor Unit: PXD 18, 24, 30 1PH/3PH
7-1SM PXD 1-E.3 GB
Page 55
WIRING DIAGRAMS
CONTENT
7.3 Outdoor Unit: ONG 9, 12, 15
C
7.4 Outdoor Unit: GC 18
WIRING DIAGRAM
---Heat Pump Model
XT3
89
6
5
4
3/N
2/N
1/L
I.U. TERMINAL
Supply power: 230V/50Hz
OG
BK
BN
BU
RD
GN/YE
N
L
GN/YE
9
8
N
L
O.U. TERMINAL
DEICER TEMP. SENSOR RT3
BK
6
BK
5
BN
4
BN
BU
RD
GN/YE
4-WAY VALVE
BU
BU
R
WH
BU
BK
WH
VT
BU
S
OPTIONAL:
1.CONNECTED ONLY FOR ALL SEASON UNIT
2.SP--Pressure Control Electronic ( for all season)
3.PTCH--PTC heater for draining water
4.HPS--High Pressure Switch (Only for GC-30RC)
BK
U
BN(GC-18RC) BK(GC-22/24RC)
BK
HPS
PTCH
BN/BK
RD
CAP
OG
WH
~
GN/YE
M
FAN MOTOR
COMP.HEATER
SP
BN
BN
WH
P
BN
BN
0
CONTACTOR
BU
RD
KM
4
BN
6
RD
8
2
VT
COMP
LEGEND:
BK-Black BU-Blue BN-Brown OG-Orange RD-Red WH-White GN/YE-Yellow/Green
CAP.--Capacitor COMP.--Compressor
RUN CAP.
RD
BN
BU
C
S
R
~
M
GN/YE
7-2 SM PXD 1-E.3 GB
4525772/01
Page 56
7.5 Outdoor Unit: GC 18 3PH
CONTENT
WIRING DIAGRAMS
XT3
9
8
B
OG
BK
BN
BU
RD
GN/YE
A
P/N: 4527498/01
DEICER TEMP. SENSOR RT3
TERMINAL
6
BK
5
BK
BN
4
WH
N
BU
WH
RD
L
CAP
GN/YE GN/YE
BN
WH
WH
RD
OG
~
M
FAN MOTOR
P
BN-GC18RC
BK-GC24RC
WIRING DIAGRAM OF OUTDOOR UNIT
ANTI-PHASE PROTECTOR
B
BU
BU
BK
WH
WH BK
INDICATOR LIGHT
4-W VALVE
TERMINAL
3
5
7
RELAY
A
WH
VT
2
4
6
8
BN
WH
BK
BU
PTCH
BU
BN
COMP.HEATER
U
V
W
N
BU
A1
A2
RD
BK
BN
BU BU
5
3
KM
4
2
6
BN
RD
BU
2
1
W/T
V/T
U/T
~
M
COMPRESSOR
RD
BK BN
21
A/C CONTACTOR
22
VT
3
GN/YE
TERMINAL
RD
L1
OG
RD BK
L2
BK
BN BN BU
BU
RD
GN/YE
BK
L3
BN
N
BU
GN/YE
LEGEND: BK-BLACK BU-BLUE BN-BROWN OG-ORANGE RD-RED WH-WHITE PTCH--- PTC HEATER FOR DRAINING WATER
L1
3PH
L2
380~400V
L3
50Hz
N
YE-YELLOW GND-GROUND CAP-CAPACITOR COMP-COMPRESSOR GN/YE-YELLOW/GREEN P-PRESSURE SWITCH
---OPTINONAL
7.6 Outdoor Unit: OU7-24 / OU8-30 1PH
7-3SM PXD 1-E.3 GB
Page 57
WIRING DIAGRAMS
CONTENT
7.7 Outdoor Unit: OU7-24Z
7.8 Outdoor Unit: OU8-30 1PH (with soft starter)
7-4 SM PXD 1-E.3 GB
Page 58
7.9 Outdoor Unit: OU7-24 / OU8-30 3PH
CONTENT
WIRING DIAGRAMS
7-5SM PXD 1-E.3 GB
Page 59
8. ELECTRICAL CONNECTIONS
CONTENT
8.1 PXD 9, 12, 15, 18,

ELECTRICAL CONNECTIONS

8.2 PXD 18, 24,30 (Power Supply to Outdoor)
8-1SM PXD 1-E.3 GB
Page 60
ELECTRICAL CONNECTIONS
CONTENT
8.3 PX 18, 24, 30 3PH
8-2 SM PXD 1-E.3 GB
Page 61
9. REFRIGERATION DIAGRAMS
CONTENT
9.1 Heat Pump Models
9.1.1 PXD 9, 12, 15, 18 R410A
OUTDOOR UNIT

REFRIGERATION DIAGRAMS

INDOOR UNIT
Sensor
Outdoor coil
Reverse
valve
Capil
tube
Strainer
OUTDOOR UNIT
Service
port
rosse
r
lary
Capillary
tube
Check
valve
pmoC
Valves
Strainer
COOLING MODE
ared
Fl
connection
Sensor
Indoor coil
Sensor
Outdoor coil
Reverse
valve
Strainer
r os
s e
r p
m oC
Capillary
Capillary
tube
tube
Check
valve
Strainer
HEATING MODE
Service
port
Valves
Flared
connection
INDOOR UNIT
Sensor
Indoor coil
9-1SM PXD 1-E.3 GB
Page 62
REGRIGERATION DIAGRAMS
CONTENT
9.1.2 PXD 24 R410A
9-2 SM PXD 1-E.3 GB
Page 63
9.1.3 PXD 24 / OU7-24Z R410A
CONTENT
REFRIGERATION DIAGRAMS
9-3SM PXD 1-E.3 GB
Page 64
REGRIGERATION DIAGRAMS
CONTENT
9.1.4 PXD 30 R410A
9-4 SM PXD 1-E.3 GB
Page 65
9.2 Cooling Only Models
CONTENT
9.2.1 PXD 9, 11, 15, 18
OUTDOOR UNIT
REFRIGERATION DIAGRAMS
INDOOR UNIT
Sensor
Outdoor coil
9.2.2 PXD 24, 30
Strainer
Capillary
tube
Service
port
rosserpmoC
Valves
Flared
connection
Indoor coil
Sensor
9-5SM PXD 1-E.3 GB
Page 66
10. TUBING CONNECTIONS
CONTENT

TUBING CONNECTIONS

¼” ⅜” ½” ⅝” ¾”
TORQUE (Nm)
Flare Nuts 11-13 40-45 60-65 70-75 80-85 Valve Cap 13-20 13-20 18-25 18-25 40-50
Service Port Cap 11-13 11-13 11-13 11-13 11-13
1. Valve Protection Cap-end
2. Refrigerant Valve Port (use Allen wrench to open/close)
3. Valve Protection Cap
4. Refrigerant Valve
5. Service Port Cap
6. Flare Nut
7. Unit Back Side
8. Copper Tube
When the outdoor unit is installed above the indoor unit an oil trap is required every 5m along the suction line at the lowest point of the riser. Incase the indoor unit is installed above the outdoor, no trap is required.
10-1SM PXD 1-E.3 GB
Page 67
11. CONTROL SYSTEM
CONTENT
11.1 Electronic Control
11.1.1 Introduction
The electronic control information is designed for service applications, and is common to the following groups of air-conditioners:
ST/RC group -Cooling only / cooling and heating by heat pump. SH group -Cooling and heating by heat pump and supplementary
heater.
RH group -Cooling, heating by heaters only.
11.1.2 Model Plug Settings
Before installation, make sure to set the model plug conforming to the suitable group.

CONTROL SYSTEM

Model Plug
GROUP
ST / RC Open Open
SH Closed Open RH Closed Closed
J6 Setting J2 Setting
11-1SM PXD 1-E.3 GB
Page 68
CONTROL SYSTEM
CONTENT
11.1.3 Remote Control DIP Switch Settings
DEFINITION SETTING SWITCH STATUS
SW.
NO. 1
SW.
NO. 2
SW.
NO. 3
SW.
NO. 4
--OFF----
--ON----
RC-ALL MODES OF OPERATION ----OFFOFF STD-COOL, FAN, DRY, ACTIVE ----OFFON HEAT-COOL, FAN, DRY, ACTIVE ----ONOFF AUTO FAN (AF) ----ONON TEMP. DISPLAY IN C DEGREES
TEMP. DISPLAY IN F DEGREES
TIMER & CLOCK 12H AM, PM OFF------
TIMER & CLOCK 24H ON------
RC4 RC3
VERTICAL SWING ONLY HORIZONTAL & VERTICAL
SWING FUNCTIONS TOGETHER
DISABLE LCD & KEY ILLUMINATION
ENABLE LCD & KEY ILLUMINATION
Reset operation - Press the 4 buttons simultaneously: “CLEAR “, “SET”, "HR +”, ”HR -” for 5 seconds
LEGEND
SW1, SW2 - Selection of RC/ST SW3 – Selection of Display C or F in RC3 or swing function in RC4 SW4 – Selection of Time Display 12H AM/PM or 24H in RC3 or illumination in RC4 OFF = 0 ON = 1
NOTE
After setting the DIP switches perform reset operation.
11-2 SM PXD 1-E.3 GB
Page 69
11.1.4 Main PCB Controller
CONTENT
CONTROL SYSTEM
11-3SM PXD 1-E.3 GB
Page 70
CONTROL SYSTEM
CONTENT
11.1.5 Display Board :LEXAN
11.1.6 Display Board : Assembly
11.1.7 Legend :
A) Heating LED
B) Cooling LED
C) Fan LED
D) Operation LED
E) Timer LED
F) Filter LED
G) Temp’ Set Point Indication
H) Fan Speed H,(High) I,(Medium) J,(Low) K,(AUTO)
L) Reset
M) STB’Y LED
11-4 SM PXD 1-E.3 GB
Page 71
CONTROL SYSTEM
CONTENT
11.2 Control Function
11.2.1 Abbreviations
AC - Alternate Current
A/C - Air-Conditioner ANY - ON or OFF status CLOCK - ON/OFF Operation Input, (dry contact) COMP - Compressor CPU - Central Processing Unit CTV - Compensation Temperature Value HE - Heating Element HPC - High Pressure Control H/W - Hardware ICP - Indoor Condensation Pump ICT - Indoor Coil Temperature (RT2) sensor IF, IFAN - Indoor Fan IR - Infrared LEVEL1 - Normal Water Level LEVEL2/3 - Medium/High Waterlevel LEVEL4 - Overflow Level Max - Maximum Min - Minimum min - Minute (time) NA - Not Applicable OCP - Outdoor Condensation Pump OCT - Outdoor Coil Temperature (RT3) sensor OF, OFAN - Outdoor Fan OPER - Operate Para. - Paragraph RAT - Return Air Temperature (RT1) sensor RC - Reverse Cycle (Heat Pump) R/C - Remote Control RCT - Remote Control Temperature RH - Resistance Heater RT - Room Temperature (i.e. RCT in IFEEL mode, RAT otherwise) RV - Reversing Valve SB, STBY - Stand-By sec - Second (time) Sect - Section SH - Supplementary Heater SPT - Set Point Temperature ST - Standard (Model with Cooling Only) S/W - Software TEMP - Temperature W/O - Without
T - The difference between SPT and RT.
in Heat Mode: T = SPT - RT in Cool/Dry/Fan Mode: T = RT – SPT
11-5SM PXD 1-E.3 GB
Page 72
CONTROL SYSTEM
CONTENT
11.3 General Functions
11.3.1 COMP Operation
a. For each Mode including POWER OFF & SB, a Min time delay of 3 min before
COMP restarting, excluding DEICING Mode (see para. 14.12.2).
b. The Min operation time of COMP under different operating conditions is:
Operation Mode Min Operation Time of COMP
Heat, Cool, HP protection or Auto Modes 3 min. Fan, Dry, Overflow, Protection Modes, or Mode Change Ignored
11.3.2 IFAN operation
a. Min time interval between IFAN speed change in AUTOFAN Mode is 30 sec. b. Min time interval between IFAN speed change in H/M/L Mode is 1 sec. c. IFAN speed in Heat/Cool AUTOFAN Mode is determined according to the
following chart:
IFAN speed
H
M
L
3142
T [oc]
Where in Heat Mode: T = SPT - RT in Cool Mode: T = RT- SPT
11.3.3 OFAN Operation
11.3.4 HE Operation
11-6 SM PXD 1-E.3 GB
Min time interval between OFAN ON/OFF state changes is 30 sec.
a. Min Heaters ON or OFF time is 30 sec. b. Heaters can never be in operation while IFAN is OFF. c. In RH group, HE-1 and HE-2 will be activated only when COMP is not operating,
except in Dry Mode.
Page 73
11.3.5 Protections
CONTENT
a. High pressure protection is applicable to all operating modes. b. Deicing control is valid in Heat and Auto Heat Modes only. c. Defrosting control is valid in Dry, Cool, and Auto Cool Modes.
11.3.6 Thermistors Operation
a. Return air Temp. is detected by RAT in normal Mode, or by RCT (R/C sensor) in
I-FEEL Mode. b. Indoor Coil Temp. is detected by ICT. c. Outdoor Coil Temp. is detected by OCT. d. Definition of thermistor faults:
1) Thermistor is disconnected - the thermistor reading is below – 30
2) Thermistor is shorted - the thermistor reading is above 75
CONTROL SYSTEM
O
C.
O
C.
3) Thermistor Temp reading doesn’t change ­a) This test is performed only once after a unit is switched from OFF/STBY
to operation. At the first occurrence of 10 min continuous COMP operation, the current ICT are compared with those when the COMP was switched from OFF to ON 10 min before. If the T is less than 3 thermistor is regarded as defective.
b) The ICT no-change error can be disabled together by connecting a 4.7k
resistor (5%) to the ICT connector. These resistors are equivalent to a thermistor 48+/-1
O
C.
e. Cases for disabling ICT thermistor disconnected detection:
1) The detection of thermistor faults a. and b. above is disabled when Deicer Protection is started. The detection will be enabled again only after (1) the deicing is completed, and (2) COMP has been restarted and operated for 30 sec.
2) When all the following conditions are fulfilled: a) 4.7k resistor is connected to the OCT. b) IFAN is OFF. c) Compressor is ON. d) ICT < -30 (disconnected).
O
C, the
11-7SM PXD 1-E.3 GB
Page 74
CONTROL SYSTEM
CONTENT
11.3.7 RV Fault
This test is applied only in compressor units where 4.7k resistor is not connected to the OCT. The test is performed every time the unit is switched from OFF/STBY to OPER in Heat mode or changes operation mode from COOL/DRY to HEAT or (this applies also in AUTO COOL/HEAT mode). If ICT is lower than 35 min continuous COMP operation, ICT is compared with ICT reading when the COMP was switched from OFF to ON 15 min before. RV fault is defined when ICT decreases more than 5 In this case, the COMP will stop and the SB LED will blink. The fault is reset after switching to SB or after mode change.
º
C.
º
C at the time of mode change, then at the first occurrence of 15
11.3.8 General Features
a. Allowed (control target) range for RAT is SPT +/-1ºC. b. Whenever the unit is changed from COOL/DRY/STBY mode to HEAT mode or
vice versa, the procedures below are followed: Stop COMP for 3 min Change RV state Start COMP if necessary.
11-8 SM PXD 1-E.3 GB
Page 75
11.4 Cooling Mode
CONTENT
11.4.1 Cooling Mode – General
a. Mode Definition
Mode: COOL, AUTO (at Cooling) Temp: Selected desired temperature. Fan: HIGH, MED, LOW, AUTO. Timer: Any I-FEEL: ON or OFF
b. Room Temperature, RT, is detected by:
RAT in normal operation, or RCT (R/C sensor) in I-FEEL mode.
CONTROL SYSTEM
c. Indoor Coil Temp is detected by ICT. d. Outdoor Coil Temp is detected by OCT.
11.4.2 Control Functions
a. COMP Operation
COMP
ON
OFF
0
b. OFAN Operation
In normal operation OFAN operates together with the COMP.
1
RT-SPT
c. IFAN Operation
IFAN will operate in ANY speed regardless the ICT or COMP state. IFAN speed will be determined according to user selection or
AUTO-FAN logic
d. RV and HEATERS outputs
RV and HEATERS are in OFF state in COOL mode.
11-9SM PXD 1-E.3 GB
Page 76
CONTROL SYSTEM
CONTENT
11.4.3 Sequence Diagrams
a. Maintaining room temp at desired level by comparing RT and SPT with user
defined IFAN speed.
(RT - SPT) [oc]
+3
+2
+1
0
-1
-2
COMP (WVL)
OFAN
IFAN
RV
ON
OFF
ON
OFF
USER FAN SPEED
ON
OFF
11-10 SM PXD 1-E.3 GB
Page 77
CONTROL SYSTEM
CONTENT
b. Maintaining room temp at desired level by comparing RT and SPT with
AUTO-IFAN.
+4
+3
+2
+1
0
-1
-2
(RT - SPT) [oc]
ON
COMP (WVL)
OFAN
IFAN
RV
OFF
ON
OFF
H
M
L
ON
OFF
11-11SM PXD 1-E.3 GB
Page 78
CONTROL SYSTEM
CONTENT
11.5 Heating Mode
11.5.1 Heating Mode - General
a. Compensation Procedure
When I-FEEL is OFF during HEAT mode: RT= RAT – CTV. When I-FEEL is ON during HEAT mode: RT= RCT.
Type of Indoor CTV
Wall Mounted +3 Mobiles / Floor Ceiling +0 Square /Window +2 Ducted +4 Cassettes +4
No compensation will be activated in Forced operation modes
o
C
o
C
o
C
o
C
o
C
b. IFAN operation rules for RC and SH groups:
1) As a general rule for RC and SH groups, IFAN will be switched ON according to the following graph:
IFAN
ANY
LOW
OFF
General: Window:
Note 1
301732
20
Duct ed
40 25
ICT
NOTE 1
When COMP is ON (except WAX Model), IFAN will change from LOW to OFF either when:
a) ICT<28 and IFAN is on for 5 min or longer.
Or,
b) ICT<20
11-12 SM PXD 1-E.3 GB
NOTE 2
When ICT is faulty: When the compressor switches from OFF to ON (excluding deicing), IFAN will be on in ANY speed. When the compressor switches from ON to OFF, the IFAN will change to LOW speed for 30 seconds and then it will be off.
2) In SH or RC group, IFAN will operate for Min 30 sec according to 1) above after HEs are turned off, where in a case it has to be OFF, it will be forced to LOW speed.
Page 79
CONTROL SYSTEM
CONTENT
c. IFAN operation rules for RH group
1) In RH group, IFAN starts when HE starts. When HE switches to OFF, IFAN switches to LOW for 30 sec and then stops.
d. Heaters operation rules for RC and SH groups:
1) For both RC and SH groups, Heaters versus T is as follows:
ON
OFF
ON
OFF
HE1
HE2
1 2 3 4
T=SP-RT [oc]
2) Operation rules for Heaters in RC group: a) Heaters can be enabled only if IFAN is ON. b) Heaters will operate according to T and the following graph:
HE-1
&
HE- 2
ON
OFF
General: Window:
20 15
32 20
45
50
ICT
3) Rules for Heaters operation in SH group: a) When heaters are to be ON and IFAN is to be OFF according to d. 1)
above, IFAN will be forced to LOW speed.
b) Heaters will operate according to T and the following graph:
ON
OFF
ON
OFF
HE -1
HE - 2
37 42
45
50
ICT
4) For both RC and SH groups, excluding deicing, HE1 and HE2 can be ON only when the compressor is ON.
11-13SM PXD 1-E.3 GB
Page 80
CONTROL SYSTEM
CONTENT
e. Heaters operation rules for RH groups:
1) In RH group, HE operation is according to the difference between RAT and SPT.
ON
HE2
OFF
ON
HE1
OFF
-1 0 2
T=SP-RT [oc]
f. OFAN Operation for RC and SH groups
1) As a general rule for RC and SH groups, excluding protection modes, OFAN starts with the compressor.
2) When OFAN is ON it will operate according to the following conditions: a) OFAN operates together with the compressor. b) When
and the 4.7k resistor is not
50)2( ICTandSPTRT
connected to the OCT, OFAN will operate according to the following curve:
ON
OFAN
OFF
11-14 SM PXD 1-E.3 GB
0 3
OCT
Page 81
11.6 Heating, RC or SH Group
CONTENT
Mode: HEAT, AUTO (at heating) Temp: Selected desired temperature Fan: HIGH, MED, LOW Timer: Any I-FEEL: ON or OFF
11.6.1 Sequence Diagram
Maintains room temp. at desired level by comparing RAT or RCT to SPT.
(RT - SPT) [oc]
CONTROL SYSTEM
+2
+1
0
-1
-2
-3
-4
COMP (WVL)
ON
OFF
HE1
HE2
RV
ON
OFF
ON
OFF
ON
OFF
11-15SM PXD 1-E.3 GB
Page 82
CONTROL SYSTEM
CONTENT
11.7 Heating, RC or SH Group with Autofan
Mode: HEAT, AUTO (at heating) Temp: Selected desired temperature Fan: AUTO Timer: Any I-FEEL: ON or OFF
11.7.1 Sequence Diagram
Maintains room temp at desired level by controlling COMP, IFAN and OFAN.
(RT - SPT) [oc]
+2
+1
0
-1
-2
-3
-4
COMP (WVL)
ON
OFF
11-16 SM PXD 1-E.3 GB
HE1
HE2
RV
ON
OFF
ON
OFF
ON
OFF
Page 83
11.8 Heating, RH Group
CONTENT
Mode: HEAT, AUTO (at Heating) Temp: Selected desired temperature Fan: HIGH, MED, LOW Timer: Any I-FEEL: ON or OFF
11.8.1 Sequence Diagram
Maintains room temp at desired level by controlling Heating Elements: HE1 or HE2.
(RT - SPT) in oc
CONTROL SYSTEM
HE1
HE2
+2
+1
0
-1
-2
-3
ON
OFF
ON
OFF
IFAN
H/M/L
L
OFF
30 sec
11-17SM PXD 1-E.3 GB
Page 84
CONTROL SYSTEM
CONTENT
11.9 Heating, RH Group, with AUTOFAN
Mode: HEAT, AUTO (at Heating) Temp: Selected desired temperature Fan: AUTO Timer: Any I-FEEL: ON or OFF
11.9.1 Sequence Diagram
Maintains room temp. at desired level by controlling the 2-Stage Electric Heaters.
(RT - SPT) in oc
+2
+1
-1
-2
-3
HE1
HE2
IFAN
0
ON
OFF
ON
OFF
H
M
L
OFF
-2
-1
30 sec
-4
-3
11-18 SM PXD 1-E.3 GB
Page 85
11.10 Automatic Cooling or Heating
CONTENT
11.10.1 Automatic Cooling or Heating - General
The AUTO Mode is for models with compressor and the WVL-RH only. The WVL-ST, RC and SH units do not work in AUTO Mode.
a. Mode Definition
Mode: AUTO Temp: Selected desired temperature Fan: Any Timer: Any
I-FEEL: ON or OFF b. Switching-temperature between Cooling and Heating is SPT  3 c. When the AUTO Mode is started with SPT +/-0
Heat or Auto Cool mode immediately. Instead, the unit will be in a temporary FAN
Mode with IFAN operating at low speed. The proper Auto Heat mode or Auto Cool
will be started whenever the RT reaches SPT-1
CONTROL SYSTEM
O
C.
O
C, the unit will not select Auto
O
C or SPT+1OC respectively.
d. For RC & SH units, Mode change between Auto Heat & Auto Cool Modes is
possible only after the COMP has been OFF during the last T minutes.
Mode Change Time, T
Auto Cool to Auto Heat 3 min Auto Heat to Auto Cool 4 min
e. For RH and WVL-RH units, Mode change between Auto Heat & Auto Cool Modes
is possible after the COMP/HEs have been OFF during the last T minutes.
Mode Change Time, T
Auto Cool to Auto Heat COMP off for 3 min Auto Heat to Auto Cool HEs off for 3 min
f. When unit is changed form Cool/Dry Mode to Auto Mode, the unit will continue to
operate in (Auto) Cool Mode until the conditions for switching from Auto Cool to
Auto Heat are satisfied.
Similarly, when unit is changed from Heat Mode to Auto Mode, the unit will
continue to operate in (Auto) Heat Mode until the conditions for switching from
Auto Heat to Auto Cool are satisfied.
11-19SM PXD 1-E.3 GB
Page 86
CONTROL SYSTEM
CONTENT
11.10.2 Sequence Diagrams
a. Auto Cooling or Heating, RC or SH Groups
Maintains room temp. at desired level by selecting between cooling and heating modes.
(RT - SPT) [oc]
+3
+2
+1
0
COMP
& OFAN
HE1
HE2
IFAN
-1
-2
-3
-4
Auto Cool Mode Auto Heat Mode
USER FAN SPEED H/M/L/OFF
ON
OFF
ON
OFF
ON
OFF
Auto Heat Mode
> 4 min > 3 min
(3) (3)
H/M/L/OFF
11-20 SM PXD 1-E.3 GB
RV
ON
OFF
> 3 min > 2 min
(4)
(4)
Page 87
b. Auto Cooling or Heating RH Group
CONTENT
Maintains room temp. at desired level by selecting between Cooling or Heating Modes.
(RT - SPT) [oc]
+3
+2
+1
0
-1
-2
-3
CONTROL SYSTEM
Auto Heat Mode Auto Cool Mode Auto Heat Mode
HE1
HE2
IFAN
RV
ON
OFF
ON
OFF
ON
OFF
H/M/L
L
OFF
OFF
30 sec
(1)
> 3 min
(2)
> 3 min
(2)
COMP
& OFAN
11.11 Dry Mode
11.11.1 Dry, ST or RC Group or P2000 Model with Any Group Settings
Mode: DRY Temp: Selected desired temperature Fan: LOW (automatically selected by software) Timer: Any I-FEEL: Any
Control function Reduce room humidity with minimum temp. fluctuations by operating in Cool Mode with LOW speed IFAN.
11-21SM PXD 1-E.3 GB
Page 88
CONTROL SYSTEM
&
CONTENT
(RT - SPT) [oc]
+2
+1
0
10
-1
-2
DRY-ON
DRY
DRY-OFF
20
30
40 50
Time [min]
LOW
IFAN
OFF
5 minutes COMP
ON
OMP
OFF
OFAN
Max 15 minutes
ON
HE1
OFF
HE2
ON
RV
OFF
3.5
min
Note1
ON time
Max 15 minutes
6 min
Note 2
NOTES
1. When DRY is ON, the COMP is forced OFF for 3.5 min (longer than the 3 min Min COMP- OFF time) after every 15 min of continuous COMP operation.
2. When DRY is OFF, the COMP is forced ON for 6 min (longer than the 3 min Min COMP- ON time) after every 15 min of continuous COMP OFF time.
3. When DRY is changed from ON to OFF or vice versa, the limits mentioned in (1) & (2) are ignored. The COMP operation is only controlled by the 3 min Min OFF time and 1 min Min ON time.
4. In DRY Mode, IFAN is LOW when COMP is ON, and is OFF when COMP is OFF.
5. HEs are always OFF in DRY Mode.
11-22 SM PXD 1-E.3 GB
Page 89
11.11.2 DRY, SH or RH group
CONTENT
Mode: DRY Temp: Selected desired temperature Fan: LOW (automatically selected by software) Timer: Any I-FEEL: Any
Control function Reduces room humidity with minimum temp. fluctuations by operating in Cool Mode with LOW speed IFAN and HE.
(RT - SPT) [oc]
CONTROL SYSTEM
IFAN
COMP
& OFAN
HE1
HE2
+2
+1
0
10
-1
-2
LOW
OFF
ON
OFF
ON
OFF
ON
OFF
20
30
40 50
Time [min]
RV
ON
OFF
11-23SM PXD 1-E.3 GB
Page 90
CONTROL SYSTEM
CONTENT
11.12 Protection
11.12.1 Cooling Mode Protections
a. Indoor Coil Defrost
Mode: COOLING, DRY, AUTO Temp: Selected desired temp. Fan: Any Timer: Any I-FEEL: ON or OFF
Control Function Protects the indoor coil from ice formation at low ambient temperatures.
ICT [oc]
+14
+5
+2 +1
0
-1
OFAN
COMP
t1 t2 t3
ON
OFF
ON
OFF
t1
11-24 SM PXD 1-E.3 GB
ON
IFAN
OFF
t1 = 5 min minimum for each COMP starting. t2 = OFAN cycling (alternate between ON and OFF every 30 sec) for 20 min maximum. t3 = COMP and OFAN stops for 10 min minimum.
Page 91
CONTROL SYSTEM
CONTENT
b. High Pressure Protection
Mode: (AUTO) COOLING or DRY Temp: Selected desired temperature Fan: Any Timer: Any I-FEEL: ON or OFF
Control Function To protect the COMP from the high pressure build-up in the outdoor coil during normal cooling operation, by switching OFF the IFAN and COMP.
OCT [oc]
68
66
61
55
52
COMP
OFAN
Any
OFF
Any
ON
For all models except WAX & P2000 For WAX & P2000 models
COMP is forced OFF
OFAN is forced ON
OFAN follow operation of
COMP
COMP is forced OFF
OFAN is forced ON
IFAN
OPER
LED
Any
ON
Blink
L
IFAN forced
to LOW
NOTE
The ICT is also monitored during COOL and DRY modes, in case the RV control circuit is faulty. Whenever ICT reaches 70
o
C, which indicates a high pressure in the indoor coil, the COMP will be forced OFF automatically. The COMP can be turned ON again only after the ICT is under 70
o
C again and after the 3 min COMP ON delay time. The
OPER LED will not blink in this case.
11-25SM PXD 1-E.3 GB
Page 92
CONTROL SYSTEM
CONTENT
11.12.2 Heating Mode Protections
a. Outdoor Coil Deicing (excluding RH Group)
Mode: HEATING, AUTO (at heating) Temp: Selected desired temperature Fan: Any Timer: Any I-FEEL: Any
Control function To protect the outdoor coil from ice formation by controlling COMP & RV operation.
1) Deicer Activation Algorithm a) Static deicer threshold is -5°C b) Dynamic deicer threshold changes of 3°C in 3 minutes in the OCT
temperature
c) In first COMP activation (after SB or OFF), if OCT < 0°C, min time to first
deicer is 10 min else 40 min.
d) In a case of reading 3 successive OCT values below –10°C and
previously 3 successive OCT values of 43°C (4.7 K) , the unit will activate deicing procedure.
11-26 SM PXD 1-E.3 GB
Page 93
2) Deicing procedure
OCT [oc]
CONTENT
CONTROL SYSTEM
12
DOC
DST
(DDT)
COMP
OFAN
RV
0
3 min 3 min
ON
OFF
DI (note 1)
ON
OFF
ON
OFF
36s 36s
30s
max 12 min.
DI (note 2)
30s
DT
IFAN
all SH units
except WAX
HE
IFAN
HE
RC or WAX units
OPER
LED
ANY
L
ON
ANY
ANY
OFF
ANY
OFF
ON
BLINK
IFAN is forced to Low Speed
HEs are forced ON
Note 3
HEs are forced OFF
NOTES
1. In the following Deicing cycles, the time interval between two Deicing cycles activation is between 30 to 80 min.
2. For RC group, IFAN is forced OFF.
3. For SH group, HEs are forced ON and IFAN is forced to operate at LOW speed, regardless of the ICT and difference between RAT & SPT.
4. When jumper J7 is set, the DST value is -2°C.
11-27SM PXD 1-E.3 GB
Page 94
CONTROL SYSTEM
CONTENT
b. High Pressure Protection (excluding RH Group)
Mode: (AUTO) HEATING Fan: Any Timer: Any I-FEEL: ON or OFF
Control Function Protects the compressor from high pressure by switching OFF the OFAN and COMP.
ICT [oc]
67 66
61
55
52
COMP
OFAN
Any
Off
Any
Off
For all models except WAX For WAX model
OFAN is force
Off
COMP is forced OFF
COMP is forced OFF
OPER
LED
11-28 SM PXD 1-E.3 GB
ON
BLINK
Page 95
11.12.3 Condensation Pump (ECC/K model)
CONTENT
Mode: Cool, Dry, Auto Temp: Selected desired temperature Fan: Any Timer: Any I FEEL: Any
Control function: Prevent Condensed water from Overflowing.
CONTROL SYSTEM
Water Level
OPER
LED
COMP
(WVL)
PUMP
Overflow
Normal
ON
OFF
BLINK
ON
OFF
ON
OFF
Overflow when
unit is ON
COMP/WVL is
forced OFF
8 min 8 min
Overflow when
unit is OFF
1 min
Notes:
1. The switch used for water level detection is closed under normal condition, and is open when water overflow.
2. For the NEC version of MCU, the "Over Flow" & “Normal” condition are indicated by logic “0” & “1” at the LEVEL4 input pin respectively.
3. For the Fujitsu version of MCU, the "Over Flow" & “Normal” condition are indicated by logic “1” & “0” at the LEVEL4 input pin respectively.
4. The “Overflow” condition can activate the water pump in SB and operating modes.
11-29SM PXD 1-E.3 GB
Page 96
CONTROL SYSTEM
CONTENT
11.13 Forced Operation (Excluding PRX & PXD Models)
a. Forced operation allows units to start, stop and operate in cooling or heating in
preset temp. according to the following table:
Forced Operation Mode
Cooling 20 ºC 22 ºC Heating 25 ºC 28 ºC
Temp: Set – desired temperature selected Fan: Any Timer: Interact with Sleep Timer I-FEEL: ON or OFF
Pre-set Temp for : MBX, P2000, PX Models
1. While under the forced operation, the temperature compensation schedule is disabled.
2. The forced operation is activated when the mode button on the Display Board is used to switch the unit to COOL or HEAT mode.
3. The IFAN is always set to Autofan Speed in forced operation.
Pre-set Temp for : FCD, RWK ,ELD, ECC, WAX, WNX, WMN Models
NOTES
The Sleep mode is activated by using the SLEEP button on the R/C. In Sleep Mode, the unit will automatically adjust the SPT to turn up/down the room temperature (RT) gradually to provide maximum comfort for the sleeping user.
Sleep is treated as TIMER function. Therefore, the TIMER LED is activated similar to TIMER function.
11-30 SM PXD 1-E.3 GB
Page 97
11.14 SPT Adjustment in Sleep Mode
CONTENT
CONTROL SYSTEM
SPT+3
SPT+2
SPT+1
SPT
SPT-1
In COOL, AUTO COOL or DRY modes, the SPT adjustment is positive
(from 0 to +3
In HEAT or AUTO HEAT modes, the SPT adjustment is negative
(from 0 to -3
o
o
C).
C).
In other modes, there is no SPT adjustment. The SPT adjustment is cancelled when the Sleep mode is cancelled.
RT
7 Hours Sleep operation
for Normal Sleep Mode
Cool, Dry modes
Unit is turned to SB
after Sleep
SPT-2
SPT-3
Heat mode
Start
Sleep
1
485326
7
NOTE
If OFF-timer is active, the unit may go to SB before or after 7 hours of sleep operation.
Time [Hr]
11-31SM PXD 1-E.3 GB
Page 98
CONTROL SYSTEM
CONTENT
11.14.1 Time Adjustment in SLEEP Mode
In 10V4, the user can make use of the Off-Timer to extend the Sleep Time from 7 hours to 12 hour (max). The operation of the new “Extended Sleep Mode” is illustrated by the graphs below.
Case 1 is the Standard Sleep Mode, which is the only sleep mode in the previous version of MCU. The A/C unit simply works for 7 hours, then goes to SB.
Case 2 is the new Extended Sleep Mode. If an active Off-Timer is set to turn off the A/C between 7-12 hour, relative to the starting of Sleep, the Sleep time is extended. And, instead of going to SB at the 7th hour, the A/C will work until reaching the Off­time.
Case 3 is an exception to case 2. The Sleep Mode will not be extended to the Off­Time when the Off-Timer is preceded by an On-Timer, which is also between 7-12 hour.
Case 1 : Standard Sleep Mode
Condition : Off-timer is not set or is beyond 12 hour.
Oper
SB
Start
Sleep
Case 2 : Extended Sleep Mode
Condition : Off-timer is set at 7-12 hour.
Oper
SB
Start
Sleep
Case 3 : Exception to Case 2
Condition : Off-timer is set at 7-12 hour
On-timer is set at 7-12 hour and before Off-timer
Oper
48101226
48101226
7
7
Off-timer
Time [Hr]
Time [Hr]
11-32 SM PXD 1-E.3 GB
SB
Start
Sleep
48101226
7
Off-timerOn-timer
Time [Hr]
Page 99
11.15 Controller Self-Test Procedure
CONTENT
11.15.1 By Shorting Test Jumper J1
SELF-TEST FLOW CHART
FOR CONTROLLER (VERSION 4V5 OR HIGHER)
SHORT JUMPER
J1
Step 1
(CONTROL PCB)
RC/ST TEST
MODEL
CONFIGURATION
TEST
CONTROL SYSTEM
Step 2
Step 3
PRESS ON
POWER
BUTTON
PRESS ON
MODE BUTTON
STEP MOTOR TEST
FREQUENCY
TEST
LEDS OFF
LEDS ON TEST
AUTO RELAY
TEST
INDOOR FAN SPEED TEST
STANDBY
OPERATE
TIMER
COOL
HEAT
COMPRESSOR
OUTDOOR FAN
Step 4
Step 5
Step 6
Step 7
Step 8
PRESS ON RESET
BUTTON
PRESS ON FAN
BUTTON ON THE
REMOTE CONTROL
PRESS ON MODE
BUTTON
PRESS ON MODE
BUTTON
DISCONNECT
JUMPER
J1
BUZZER TEST
(ONE BEEP SOUND)
REMOTE CONTROL
TO CPU COMUNICATION
(TWO BEEPS SOUNDS)
THERMISTOR ANALOG
VOLTAGE CHECKING
EEPROM MEMORY
TEST
END OF SELF
TEST
R.V.
LOW
MEDIUM
HIGH
11-33SM PXD 1-E.3 GB
Page 100
CONTROL SYSTEM
CONTENT
11.15.2 By Remote Control Settings:
a. STEP 1: TURNING ON THE POWER.
Turn ON the power, make sure that the unit is in operation.
b. STEP 2 : ENABLE SELF-TEST MODE
1) Use the remote control to send the first settings to display / indoor unit HEAT mode, HIGH IFAN, set temperature to 16 ºC, no I-FEEL Sleep or any other timer settings are needed.
2) Cover the IR transmitter components in the remote control so that it will not transmit the signals to the indoor unit display.
3) Use the remote control to send the second settings to display / indoor unit COOL mode, LOW IFAN, no I-FEEL Sleep or any other timer settings.
4) Uncover the remote control IR transmitter and change the temperature settings. If the display/indoor unit receive the settings properly the following steps will start:
c. STEP 3: MODEL SETTING CONFIRMATION
1) The STAND-BY and COOL LEDS will indicate the operation mode as follows:
COOL LED STAND-BY LED OPERATION MODE
OFFONST OFFOFFRC
ONOFFSH ONONRH
2) Testing the Model configuration. Selected by the COMP, STAND-BY, TIMER LEDS and FILTER will indicate the model configuration as follows (the relevant line for this manual is highlighted):
FILTER LED TIMER LEDOPERATE LEDCOMPMODEL
OFFOFFOFFONWNG
ONOFFOFFONMBX OFFONOFFONWNX OFFOFFONONPRX
ONOFFONONWMN1 OFFONONONEMD/LS
ONONONONECC-K OFFONOFFOFFWMN 4
ONONOFFOFFPXD
WMN
2/WHX
ONOFFONOFF
ONONONOFFWMN 3
11-34 SM PXD 1-E.3 GB
In this term the step motor will turn to HOME POSITION.