1. INTRODUCTION
CONTENT
1.1 General
The PXD split floor and ceiling units range comprise the ST (cooling only) and RC (heat
pump) models, as follows:
• Cooling Only PXD9ST PXD12ST PXD15ST
PXD18ST PXD24ST PXD30ST
• Heat Pump PXD9RC PXD12RC PXD15RC
PXD18RC PXD24RC PXD30RC
1.2 Main Features
The PXD series benefits from the most advanced technological innovations, namely :
• R410A
INTRODUCTION
• Microprocessor control.
• Infrared remote control, and on unit.
• Possibility for treated air distribution to adjacent room (Accessory kit).
• High COP.
• Easy access to the interconnecting tubing and wiring connections.
• Possibility to connect a condensate pump kit with an integral over flow
protection (Accessory kit).
• Automatic treated air sweep (horizontal and vertical)
• Low indoor and outdoor noise levels.
• Easy installation and service.
1.3 Indoor Unit
The indoor unit can be mounted as floor or ceiling type, no special adjustment
are needed. it can be easily fitted to many types of residential and commercials
applications.
It includes:
• Casing with inlet and outlet grilles.
1.4 Filtration
• Motorized flaps (Horizontal and vertical).
• Advanced electronic control box assembly (storm 10V7).
• Coated indoor coil.
• Mounting plate
The PXD series presents several types of air filters:
• Easily accessible, and re-usable pre-filters (mesh)
• Active carbon filter.
1-1SM PXD 1-E.3 GB
Page 5
INTRODUCTION
CONTENT
1.5 Control
The microprocessor indoor controller, and an infrared remote control, supplied as
standard, provide complete operating function and programming. The unit is designed
with an on unit control board as well.
For further details please refer to the Operation Manual, Appendix A.
1.6 Outdoor Unit
The PXD outdoor units can be installed as floor or wall mounted by using a wall
supporting bracket. The metal sheets are protected by anti- corrosion paint work
allowing long life resistance. All outdoor units are pre-charged. For further information
please refer to the Product Data Sheet, Chapter 2.
It includes :
• A Rotary Compressor mounted in a soundproofed compartment.
• Axial fan.
• Outdoor coil with hydrophilic louver fins for RC units.
• Outlet air fan grill.
• Service valves” flare” type connection.
• Interconnecting wiring terminal block.
1.7 Tubing Connections
Flare type interconnecting tubing to be produced on site.
For further details please refer to the Installation Manual, Appendix A
1.8 Accessories
ASK (All Season Kit):
For low ambient working conditions in cooling, an ASK can be installed inside the
outdoor unit. This kit allows cooling operation down to outdoor temp of -10 ºC by
gradually controlling the outdoor fan speed motor.
RCW Wall Mounted Remote Control
The RCW remote control is mounted on the wall, and controls the unit either as an
infrared remote control or as a wired controller. The wired controller can control up to
10 Indoor units with the same program settings and adjustments.
For further details please refer to Optional Accessories, Chapter on this manual.
1.9 Inbox Documentation
1-2SM PXD 1-E.3 GB
Each unit is supplied with its own installation and operation manuals.
√* - the outdoor unit of this combination cannot be matched to other indoor units.
The above tables lists outdoor units and PXD indoor units, which can be matched
together. In addition the listed outdoor units can be matched with other types of indoor
units such as Ducted, Wall Mounted, and Cassettes .
For further information please refer to the relevant Service Manual.
1-3SM PXD 1-E.3 GB
Page 7
PRODUCT DATA SHEET
CONTENT
2. PRODUCT DATA SHEET
2.1 PXD 9 / ONG-9 R410A
Model Indoor UnitPXD-9
Model Outdoor UnitONG-9
Installation Method of PipeFlared
CharacteristicsUnitsCooling OnlyCoolingHeating
Capacity
Power input
EER (Cooling) or COP(Heating)
Energy efficiency classAAC
Power supplyV/Ph/Hz220-240V/Single/50Hz
Rated currentA3.73.7 4.0
Starting currentA18.7
Circuit breaker ratingA10
Operation control type Remote control
Heating elementskW
Others
(1)
(1)
(1)
Fan type & quantityCentrifugal x 2
Fan speedsH/M/LRPM740/650/600
(2)
Air flow
External static pressureMin-MaxPa0
Sound power level
Sound pressure level
Moisture removall/hr1.1
Condensate drain tube I.Dmm16
INDOOR
DimensionsWxHxDmm820x630x190
Weightkg21
Package dimensionsWxHxDmm890x710x280
Packaged weightkg25
Units per palletunits14
Stacking heightunits7 levels
Refrigerant controlCapillary tube
Compressor type, modelRotary,LG GK113PAG
Fan type & quantityPropeller(direct) x 1
Fan speedsH/LRPM780
Air flow H/Lm3/hr1780
Sound power levelH/LdB(A)5860
Sound pressure level
DimensionsWxHxDmm795x610x290
Weightkg3435
Package dimensionsWxHxDmm945x655x395
Packaged weightkg3839
Units per palletUnits9
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511.
(2) Airflow in ducted units; at nominal external static pressure.
(3) Sound power in ducted units is measured at air discharge.
(4) Sound pressure level measured at 1 meter distance from unit.
2-1SM PXD 1-E.3 GB
Page 8
PRODUCT DATA SHEET
CONTENT
2.2 PXD 12 / ONG-12 R410A
Model Indoor UnitPXD-12
Model Outdoor UnitONG-12
Installation Method of PipeFlared
CharacteristicsUnitsCooling OnlyCoolingHeating
Capacity
Power input
EER (Cooling) or COP(Heating)
(1)
(1)
(1)
Energy efficiency classBBC
Power supplyV/Ph/Hz220-240V/Single/50Hz
Rated currentA5.25.2 5.2
Starting currentA24
Circuit breaker ratingA15
Fan type & quantityCentrifugal x 2
Fan speedsH/M/LRPM830/770/710
(2)
Air flow
H/M/Lm3/hr420/390/350
External static pressureMin-MaxPa0
Sound power level
Sound pressure level
DimensionsWxHxDmm820x630 x190
Weightkg22
Package dimensionsWxHxDmm890x710x280
Packaged weightkg26
Units per palletunits14
Stacking heightunits7 levels
Refrigerant controlCapillary tube
Compressor type, modelRotary, Toshiba PA145X2C-4FT
Fan type & quantityPropeller(direct) x 1
Fan speedsH/LRPM810
Air flow H/Lm3/hr1850
Sound power levelH/LdB(A)6264
Sound pressure level
(4)
H/LdB(A)5253
DimensionsWxHxDmm795x610x290
Weightkg3536
Package dimensionsWxHxDmm945x655x395
Packaged weightkg3940
Units per palletUnits9
Operation control type Remote control
Heating elementskW
Others
Btu/hr120101201012620
kW3.523.52 3.7
kW1.1551.1551.15
W/W3.05 3.05 3.22
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511.
(2) Airflow in ducted units; at nominal external static pressure.
(3) Sound power in ducted units is measured at air discharge.
(4) Sound pressure level measured at 1 meter distance from unit.
2-2SM PXD 1-E.3 GB
Page 9
PRODUCT DATA SHEET
CONTENT
2.3 PXD 15 / ONG-14 R410A
Model Indoor UnitPXD-15
Model Outdoor UnitONG-14
Installation Method of PipeFlared
CharacteristicsUnitsCooling OnlyCoolingHeating
Capacity
Power input
EER (Cooling) or COP(Heating)
(1)
(1)
(1)
Energy efficiency classBBC
Power supplyV/Ph/Hz220-240V/Single/50Hz
Rated currentA6.46.4 6.5
Starting currentA30
Circuit breaker ratingA15
Fan type & quantityCentrifugal x 2
Fan speedsH/M/LRPM1000/780/720
(2)
Air flow
H/M/Lm3/hr510/390/350
External static pressureMin-MaxPa0
Sound power level
Sound pressure level
DimensionsWxHxDmm820x630 x190
Weightkg22
Package dimensionsWxHxDmm890x710x280
Packaged weightkg26
Units per palletunits14
Stacking heightunits7 levels
Refrigerant controlCapillary tube
Compressor type, modelRotary, MITSUBISHI RN165VHSMT
Fan type & quantityPropeller(direct) x 1
Fan speedsH/LRPM920
Air flow H/Lm3/hr2160
Sound power levelH/LdB(A)6364
Sound pressure level
(4)
H/LdB(A)5354
DimensionsWxHxDmm795x610x290
Weightkg41.542.2
Package dimensionsWxHxDmm945x655x395
Packaged weightkg45.546.5
Units per palletUnits9
Operation control type Remote control
Heating elementskW
Others
Btu/hr139901399015350
kW4.14.1 4.5
kW1.3551.3551.380
W/W3.03 3.03 3.26
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511.
(2) Airflow in ducted units; at nominal external static pressure.
(3) Sound power in ducted units is measured at air discharge.
(4) Sound pressure level measured at 1 meter distance from unit.
2-3SM PXD 1-E.3 GB
Page 10
PRODUCT DATA SHEET
CONTENT
2.4 PXD 18 / GC-18 R410A
Model Indoor UnitPXD-18
Model Outdoor UnitGC-18
Installation Method of PipeFlared
CharacteristicsUnitsCooling OnlyCoolingHeating
Capacity
Power input
EER (Cooling) or COP(Heating)
(1)
(1)
(1)
Energy efficiency classBBC
Power supplyV/Ph/Hz220-240V/Single/50Hz
Rated currentA8.28.2 7.9
Starting currentA43
Circuit breaker ratingA15
Fan type & quantityCentrifugal x 2
Fan speedsH/M/LRPM1100/1000/900
Air flow
(2)
H/M/Lm3/hr930/820/700
External static pressureMin-MaxPa0
Sound power level
Sound pressure level
DimensionsWxHxDmm1200x630x190
Weightkg30
Package dimensionsWxHxDmm1270x710x280
Packaged weightkg35
Units per palletunits7
Stacking heightunits7 levels
Refrigerant controlCapillary tube
Compressor type, modelRotary,LG GJ208PAA
Fan type & quantityPropeller(direct) x 1
Fan speedsH/LRPM815
Air flow H/Lm3/hr2480
Sound power levelH/LdB(A)68
Sound pressure level
(4)
H/LdB(A)58
DimensionsWxHxDmm846x690x302
Weightkg56
Package dimensionsWxHxDmm990x470x430
Packaged weightkg6061
Units per palletUnits9
Operation control type Remote control
Heating elementskW
Others
Btu/hr187701877019620
kW5.55.5 5.75
kW1.821.821.77
W/W3.02 3.02 3.25
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511.
(2) Airflow in ducted units; at nominal external static pressure.
(3) Sound power in ducted units is measured at air discharge.
(4) Sound pressure level measured at 1 meter distance from unit.
2-4SM PXD 1-E.3 GB
Page 11
PRODUCT DATA SHEET
CONTENT
2.5 PXD 18 / GC-18 3PH R410A
Model Indoor UnitPXD-18
Model Outdoor UnitGC-18 3PH
Installation Method of PipeFlared
CharacteristicsUnitsCooling OnlyCoolingHeating
Capacity
Power input
EER (Cooling) or COP(Heating)
(1)
(1)
(1)
Energy efficiency classBBB
Power supplyV/Ph/Hz380/3/50Hz
Rated currentA3.13.1 3
Starting currentA26
Circuit breaker ratingA15
Fan type & quantityCentrifugal x 2
Fan speedsH/M/LRPM1100/1000/900
(2)
Air flow
H/M/Lm3/hr930/820/700
External static pressureMin-MaxPa0
Sound power level
Sound pressure level
DimensionsWxHxDmm1200x630x190
Weightkg30
Package dimensionsWxHxDmm1270x710x280
Packaged weightkg35
Units per palletunits7
Stacking heightunits7 levels
Refrigerant controlCapillary tube
Compressor type, modelRotary ,Mitsubishi NN21YDAMT
Fan type & quantityPropeller(direct) x 1
Fan speedsH/LRPM815
Air flow H/Lm3/hr2480
Sound power levelH/LdB(A)68
Sound pressure level
(4)
H/LdB(A)58
DimensionsWxHxDmm846x690x302
Weightkg56
Package dimensionsWxHxDmm990x770x430
Packaged weightkg6061
Units per palletUnits9
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511.
(2) Airflow in ducted units; at nominal external static pressure.
(3) Sound power in ducted units is measured at air discharge.
(4) Sound pressure level measured at 1 meter distance from unit.
2-5SM PXD 1-E.3 GB
Page 12
PRODUCT DATA SHEET
CONTENT
2.6 PXD 24 / OU7-24 R410A
Model Indoor UnitPXD-24
Model Outdoor UnitOU7-24
Installation Method of PipeFlared
CharacteristicsUnitsCooling OnlyCoolingHeating
Capacity
Power input
EER (Cooling) or COP(Heating)
(1)
(1)
(1)
Energy efficiency classBBC
Power supplyV/Ph/Hz220-240V/Single/50Hz
Rated currentA9.79.7 8.4
Starting currentA63
Circuit breaker ratingA20
Fan type & quantityCentrifugal x 2
Fan speedsH/M/LRPM1200/980/840
Air flow
(2)
H/M/Lm3/hr1000/900/780
External static pressureMin-MaxPa0
Sound power level
Sound pressure level
DimensionsWxHxDmm1200x630x190
Weightkg33
Package dimensionsWxHxDmm1270x710x280
Packaged weightkg38
Units per palletunits7
Stacking heightunits7 levels
Refrigerant controlCapillary tube +Restrictor
Compressor type ,modelRotary, Mitsubishi NN27VBAMT
Fan type & quantityPropeller(direct) x 1
Fan speedsH/LRPM850
Air flow H/Lm3/hr3100
Sound power levelH/LdB(A)67
Sound pressure level
(4)
H/LdB(A)58
DimensionsWxHxDmm900x680x340
Weightkg74
Package dimensionsWxHxDmm985x730x406
Packaged weightkg77
Units per palletUnits6
Suction lineIn.(mm)5/8"(15.88)
Max .tubing lengthm.Max.30
Max .height differencem.Max.15
Operation control type Remote control
Heating elementskW
OthersAll Season kit factory option
.
Btu/hr233002330024000
kW6.836.837.03
kW2.272.272.13
W/W3.01 3.01 3.03
12.5m<Add 430g<25m
25m<Add 530g<30m
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511.
(2) Airflow in ducted units; at nominal external static pressure.
(3) Sound power in ducted units is measured at air discharge.
(4) Sound pressure level measured at 1 meter distance from unit.
2-6SM PXD 1-E.3 GB
Page 13
PRODUCT DATA SHEET
CONTENT
2.7 PXD 24 / OU7-24Z R410A
Model Indoor UnitPXD-24
Model Outdoor UnitOU7-24Z R410A
Installation Method of PipeFlared
CharacteristicsUnitsCooling OnlyCoolingHeating
Capacity
Power input
EER (Cooling) or COP(Heating)
(1)
(1)
(1)
Energy efficiency classBBC
Power supplyV/Ph/Hz220-240V/Single/50Hz
Rated currentA9.79.7 8.4
Starting currentA63
Circuit breaker ratingA20
Fan type & quantityCentrifugal x 2
Fan speedsH/M/LRPM1200/980/840
(2)
Air flow
H/M/Lm3/hr1000/900/780
External static pressureMin-MaxPa0
Sound power level
Sound pressure level
DimensionsWxHxDmm1200x630x190
Weightkg33
Package dimensionsWxHxDmm1270x710x280
Packaged weightkg38
Units per palletunits7
Stacking heightunits7 levels
Refrigerant controlCapillary tube +Restrictor
Compressor type ,modelRotary
Fan type & quantityAxial x 1
Fan speedsH/LRPM850
Air flow H/Lm3/hr3100
Sound power levelH/LdB(A)67
Sound pressure level
(4)
H/LdB(A)58
DimensionsWxHxDmm900x680x340
Weightkg78
Package dimensionsWxHxDmm985x730x435
Packaged weightkg82
Units per palletUnits6
Suction lineIn.(mm)5/8"(15.88)
Max .tubing lengthm.Max.15
Max .height differencem.Max.7
Operation control type LCD Remote control
Heating elementskW
Others
.
Btu/hr233002330024000
kW6.836.837.03
kW2.272.272.13
W/W3.01 3.01 3.03
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511.
(2) Airflow in ducted units; at nominal external static pressure.
(3) Sound power in ducted units is measured at air discharge.
(4) Sound pressure level measured at 1 meter distance from unit.
2-7SM PXD 1-E.3 GB
Page 14
PRODUCT DATA SHEET
CONTENT
2.8 PXD 24 / OU7-24T R410A
Model Indoor UnitPXD-24
Model Outdoor UnitOU7-24T
Installation Method of PipeFlared
CharacteristicsUnitsCooling OnlyCoolingHeating
Capacity
Power input
EER (Cooling) or COP(Heating)
(1)
(1)
(1)
Energy efficiency classBBC
Power supplyV/Ph/Hz400/3/50
Rated currentA3x73x73x7
Starting currentA55
Circuit breaker ratingA3x16
Fan type & quantityCentrifugal x 2
Fan speedsH/M/LRPM1200/980/840
Air flow
(2)
H/M/Lm3/hr1000/900/780
External static pressureMin-MaxPa0
Sound power level
Sound pressure level
DimensionsWxHxDmm1200x630x190
Weightkg33
Package dimensionsWxHxDmm1270x710x280
Packaged weightkg38
Units per palletunits7
Stacking heightunits7 levels
Refrigerant controlCapillary tube +Restrictor
Compressor type ,modelRotary, Mitsubishi NN27VBAMT
Fan type & quantityPropeller(direct) x 1
Fan speedsH/LRPM850
Air flow H/Lm3/hr3100
Sound power levelH/LdB(A)67
Sound pressure level
(4)
H/LdB(A)58
DimensionsWxHxDmm900x680x340
Weightkg74
Package dimensionsWxHxDmm985x730x406
Packaged weightkg77
Units per palletUnits6
Suction lineIn.(mm)5/8"(15.88)
Max .tubing lengthm.Max.30
Max .height differencem.Max.15
Operation control type Remote control
Heating elementskW
OthersAll Season kit factory option
Btu/hr233002330024000
kW6.836.837.03
kW2.272.272.13
W/W3.01 3.01 3.03
12.5m<Add 430g<25m
25m<Add 530g<30m
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511.
(2) Airflow in ducted units; at nominal external static pressure.
(3) Sound power in ducted units is measured at air discharge.
(4) Sound pressure level measured at 1 meter distance from unit.
2-8SM PXD 1-E.3 GB
Page 15
PRODUCT DATA SHEET
CONTENT
2.9 PXD 30 / OU8-30 R410A
Model Indoor UnitPXD 30
Model Outdoor UnitOU8-30
Installation Method of PipeFlared
CharacteristicsUnitsCooling OnlyCoolingHeating
Capacity
Power input
EER (Cooling) or COP(Heating)
(1)
(1)
(1)
Energy efficiency classCCD
Power supplyV/Ph/Hz220-240V/Single/50Hz
Rated currentA12.212.211.3
Starting currentA80
Circuit breaker ratingA25
Fan type & quantityCentrifugal x 2
Fan speedsH/M/LRPM1360/1200/1010
(2)
Air flow
H/M/Lm3/hr1020/895/700
External static pressureMin-MaxPaN/A
Sound power level
Sound pressure level
DimensionsWxHxDmm1200x630x190
Weightkg32
Package dimensionsWxHxDmm1270x710x280
Packaged weightkg36
Units per palletunits7
Stacking heightunits7 Levels
Refrigerant control Capillary
Compressor type, modelRotary, Mitsubishi NN33VAAMT
Fan type & quantityPropeller(direct) x 1
Fan speedsH/LRPM850
Air flow H/Lm3/hr3150
Sound power levelH/LdB(A)69
Sound pressure level
(4)
H/LdB(A)59
DimensionsWxHxDmm900x860x340
Weightkg78
Package dimensionsWxHxDmm985x907x435
Packaged weightkg82
Units per palletUnits6
Operation control type Remote control
Heating elementskW
OthersCrankcase heater (50W)
Btu/hr29,10029,10029,500
kW8.528.528.65
kW2.992.992.79
W/W2.85 2.85 3.10
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511.
(2) Airflow in ducted units; at nominal external static pressure.
(3) Sound power in ducted units is measured at air discharge.
(4) Sound pressure level measured at 1 meter distance from unit.
2-9SM PXD 1-E.3 GB
Page 16
PRODUCT DATA SHEET
CONTENT
2.10 PXD 30 / OU8-30T R410A
Model Indoor UnitPXD 30
Model Outdoor UnitOU8-30T
Installation Method of PipeFlared
CharacteristicsUnitsCooling OnlyCoolingHeating
Capacity
Power input
EER (Cooling) or COP(Heating)
(1)
(1)
(1)
Energy efficiency classCCD
Power supplyV/Ph/Hz400V/3/50
Rated currentA3x5.23x5.23x5.1
Starting currentA35
Circuit breaker ratingA3x16
Fan type & quantityCentrifugal x 2
Fan speedsH/M/LRPM1360/1200/1010
(2)
Air flow
H/M/Lm3/hr1020/895/700
External static pressureMin-MaxPaN/A
Sound power level
Sound pressure level
DimensionsWxHxDmm1200x630x190
Weightkg32
Package dimensionsWxHxDmm1270x710x280
Packaged weightkg36
Units per palletunits7
Stacking heightunits7 Levels
Refrigerant control Capillary
Compressor type, modelRotary, Mitsubishi NN33VAAMT
Fan type & quantityPropeller(direct) x 1
Fan speedsH/LRPM850
Air flow H/Lm3/hr3150
Sound power levelH/LdB(A)69
Sound pressure level
(4)
H/LdB(A)59
DimensionsWxHxDmm900x860x340
Weightkg78
Package dimensionsWxHxDmm985x907x435
Packaged weightkg82
Units per palletUnits6
Operation control type Remote control
Heating elementskW
OthersCrankcase heater (50W)
Btu/hr283002830028,300
kW8.308.308.30
kW2.772.772.63
W/W3.00 3.00 3.15
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511.
(2) Airflow in ducted units; at nominal external static pressure.
(3) Sound power in ducted units is measured at air discharge.
(4) Sound pressure level measured at 1 meter distance from unit.
2-10SM PXD 1-E.3 GB
Page 17
3. RATING CONDITIONS
CONTENT
Standard conditions in accordance with ISO 5151, ISO 13253 (for ducted units)
and EN 14511.
Cooling:
Indoor: 27oC DB 19oC WB
Outdoor: 35 oC DB
Heating:
Indoor: 20oC DB
Outdoor: 7oC DB 6oC WB
3.1 Operating Limits R410A
Cooling
Heating
Voltage
Upper limit32
Lower limit21
Upper limit27
Lower limit20
1PH198 – 264 V
3PH360 – 440 V
RATING CONDITIONS
IndoorOutdoor
o
C DB 23oC WB46oC DB
o
C DB 15oC WB21oC DB
o
C DB24oC DB 18oC WB
o
C DB-9oC DB -10oC WB
3-1SM PXD 1-E.3 GB
Page 18
4.OUTLINE DIMENSIONS
CONTENT
4.1 Indoor Unit : PXD 9, 12, 15 R410A
OUTLINE DIMENSIONS
4.2 Indoor Unit : PXD 18, 24, 30 R410A
4-1SM PXD 1-E.3 GB
Page 19
OUTLINE DIMENSIONS
CONTENT
4.3 Outdoor Unit : ONG 9, 12, 14
4.4 Outdoor Unit : GC 18
4-2SM PXD 1-E.3 GB
Page 20
4.5 Outdoor Unit : OU7-24 / OU7-24Z
CONTENT
OUTLINE DIMENSIONS
4.6 Outdoor Unit : OU8-30
4-3SM PXD 1-E.3 GB
Page 21
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5. PERFORMANCE DATA
5.1 PXD9 ONG9 R410A
5.1.1 Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OU COIL (°C)
(1)
15
(1)
20
25
30
35
40
46
DATA
TC
SC
PI
TC
SC
PI
TC
SC
PI
TC
SC
PI
TC
SC
PI
TC
SC
PI
TC
SC
PI
ENTERING AIR WB/DB ID COIL ( °C)
15/2117/2419/2721/2923/32
2.80 2.90 2.97 3.04 3.09
1.85 1.93 2.01 2.06 2.09
0.59 0.59 0.59 0.59 0.60
2.71 2.86 2.95 3.02 3.08
1.81 1.91 1.99 2.05 2.09
0.64 0.64 0.64 0.65 0.65
2.57 2.77 2.91 3.00 3.07
1.77 1.88 1.98 2.03 2.07
0.69 0.70 0.70 0.70 0.71
2.40 2.61 2.82 2.92 3.01
1.71 1.82 1.93 1.99 2.03
0.74 0.76
2.22 2.41
0.76
2.66
0.77 0.78
2.79 2.93
1.63 1.75 1.89 1.94 1.98
0.80 0.82
2.02 2.20
0.83
2.40
0.84 0.84
2.62 2.76
1.53 1.65 1.79 1.84 1.88
0.87 0.88 0.89 0.91 0.91
1.75 1.92 2.11 2.33 2.51
1.41 1.51 1.63 1.69 1.72
0.95 0.96 0.98 1.00 1.01
LEGEND
TC – Total Cooling Capacity, kW
SC – Sensible Capacity, kW
PI – Power Input, kW
o
WB – Wet Bulb Temp., (
C)
DB – Dry Bulb Temp., (oC)
ID – Indoor
OU – Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15).
Max Current, A7.17.610.412
Circuit Breaker10161616
Power Supply Wiring
No. X Cross Section mm
Interconnecting Cable RC Model
No. X Cross Section mm
Interconnecting Cable ST Model
No. X Cross Section mm
2
2
2
MODELPXD 24 PXD 30
Power Supply
Max Current, A
Circuit Breaker
Power Supply Wiring
No. X Cross Section mm
Interconnecting Cable RC Model
No. X Cross Section mm
Interconnecting Cable ST Model
No. X Cross Section mm
2. Refrigerant Valve Port (use Allen wrench to open/close)
3. Valve Protection Cap
4. Refrigerant Valve
5. Service Port Cap
6. Flare Nut
7. Unit Back Side
8. Copper Tube
When the outdoor unit is installed above the indoor unit an oil trap is required every 5m along the suction
line at the lowest point of the riser. Incase the indoor unit is installed above the outdoor, no trap is
required.
10-1SM PXD 1-E.3 GB
Page 67
11. CONTROL SYSTEM
CONTENT
11.1 Electronic Control
11.1.1 Introduction
The electronic control information is designed for service applications, and is common
to the following groups of air-conditioners:
ST/RC group -Cooling only / cooling and heating by heat pump.
SH group -Cooling and heating by heat pump and supplementary
heater.
RH group -Cooling, heating by heaters only.
11.1.2 Model Plug Settings
Before installation, make sure to set the model plug conforming to the suitable group.
CONTROL SYSTEM
Model Plug
GROUP
ST / RC Open Open
SH Closed Open
RH Closed Closed
J6 Setting J2 Setting
11-1SM PXD 1-E.3 GB
Page 68
CONTROL SYSTEM
CONTENT
11.1.3 Remote Control DIP Switch Settings
DEFINITION SETTING SWITCH STATUS
SW.
NO. 1
SW.
NO. 2
SW.
NO. 3
SW.
NO. 4
--OFF----
--ON----
RC-ALL MODES OF OPERATION ----OFFOFF
STD-COOL, FAN, DRY, ACTIVE ----OFFON
HEAT-COOL, FAN, DRY, ACTIVE ----ONOFF
AUTO FAN (AF) ----ONON
TEMP. DISPLAY IN C DEGREES
TEMP. DISPLAY IN F DEGREES
TIMER & CLOCK 12H AM, PM OFF------
TIMER & CLOCK 24H ON------
RC4 RC3
VERTICAL SWING ONLY
HORIZONTAL & VERTICAL
SWING FUNCTIONS
TOGETHER
DISABLE LCD & KEY
ILLUMINATION
ENABLE LCD & KEY
ILLUMINATION
Reset operation - Press the 4 buttons simultaneously: “CLEAR “, “SET”, "HR +”, ”HR -”
for 5 seconds
LEGEND
SW1, SW2 - Selection of RC/ST
SW3 – Selection of Display C or F in RC3 or swing function in RC4
SW4 – Selection of Time Display 12H AM/PM or 24H in RC3 or illumination in RC4
OFF = 0
ON = 1
NOTE
After setting the DIP switches perform reset operation.
11-2SM PXD 1-E.3 GB
Page 69
11.1.4 Main PCB Controller
CONTENT
CONTROL SYSTEM
11-3SM PXD 1-E.3 GB
Page 70
CONTROL SYSTEM
CONTENT
11.1.5 Display Board :LEXAN
11.1.6 Display Board : Assembly
11.1.7 Legend :
A) Heating LED
B) Cooling LED
C) Fan LED
D) Operation LED
E) Timer LED
F) Filter LED
G) Temp’ Set Point Indication
H) Fan Speed H,(High) I,(Medium) J,(Low) K,(AUTO)
L) Reset
M) STB’Y LED
11-4SM PXD 1-E.3 GB
Page 71
CONTROL SYSTEM
CONTENT
11.2 Control Function
11.2.1 Abbreviations
AC - Alternate Current
A/C - Air-Conditioner
ANY - ON or OFF status
CLOCK - ON/OFF Operation Input, (dry contact)
COMP - Compressor
CPU - Central Processing Unit
CTV - Compensation Temperature Value
HE - Heating Element
HPC - High Pressure Control
H/W - Hardware
ICP - Indoor Condensation Pump
ICT - Indoor Coil Temperature (RT2) sensor
IF, IFAN - Indoor Fan
IR - Infrared
LEVEL1 - Normal Water Level
LEVEL2/3 - Medium/High Waterlevel
LEVEL4 - Overflow Level
Max - Maximum
Min - Minimum
min - Minute (time)
NA - Not Applicable
OCP - Outdoor Condensation Pump
OCT - Outdoor Coil Temperature (RT3) sensor
OF, OFAN - Outdoor Fan
OPER - Operate
Para. - Paragraph
RAT - Return Air Temperature (RT1) sensor
RC - Reverse Cycle (Heat Pump)
R/C - Remote Control
RCT - Remote Control Temperature
RH - Resistance Heater
RT - Room Temperature (i.e. RCT in IFEEL mode, RAT otherwise)
RV - Reversing Valve
SB, STBY - Stand-By
sec - Second (time)
Sect - Section
SH - Supplementary Heater
SPT - Set Point Temperature
ST - Standard (Model with Cooling Only)
S/W - Software
TEMP - Temperature
W/O - Without
T - The difference between SPT and RT.
in Heat Mode: T = SPT - RT
in Cool/Dry/Fan Mode: T = RT – SPT
11-5SM PXD 1-E.3 GB
Page 72
CONTROL SYSTEM
CONTENT
11.3 General Functions
11.3.1 COMP Operation
a. For each Mode including POWER OFF & SB, a Min time delay of 3 min before
COMP restarting, excluding DEICING Mode (see para. 14.12.2).
b. The Min operation time of COMP under different operating conditions is:
Operation Mode Min Operation Time of COMP
Heat, Cool, HP protection or Auto Modes 3 min.
Fan, Dry, Overflow, Protection Modes, or Mode Change Ignored
11.3.2IFAN operation
a. Min time interval between IFAN speed change in AUTOFAN Mode is 30 sec.
b. Min time interval between IFAN speed change in H/M/L Mode is 1 sec.
c. IFAN speed in Heat/Cool AUTOFAN Mode is determined according to the
following chart:
IFAN speed
H
M
L
3142
T [oc]
Where in Heat Mode: T = SPT - RT
in Cool Mode: T = RT- SPT
11.3.3 OFAN Operation
11.3.4 HE Operation
11-6SM PXD 1-E.3 GB
Min time interval between OFAN ON/OFF state changes is 30 sec.
a. Min Heaters ON or OFF time is 30 sec.
b. Heaters can never be in operation while IFAN is OFF.
c. In RH group, HE-1 and HE-2 will be activated only when COMP is not operating,
except in Dry Mode.
Page 73
11.3.5 Protections
CONTENT
a. High pressure protection is applicable to all operating modes.
b. Deicing control is valid in Heat and Auto Heat Modes only.
c. Defrosting control is valid in Dry, Cool, and Auto Cool Modes.
11.3.6 Thermistors Operation
a. Return air Temp. is detected by RAT in normal Mode, or by RCT (R/C sensor) in
I-FEEL Mode.
b. Indoor Coil Temp. is detected by ICT.
c. Outdoor Coil Temp. is detected by OCT.
d. Definition of thermistor faults:
1) Thermistor is disconnected - the thermistor reading is below – 30
2) Thermistor is shorted - the thermistor reading is above 75
CONTROL SYSTEM
O
C.
O
C.
3) Thermistor Temp reading doesn’t change a) This test is performed only once after a unit is switched from OFF/STBY
to operation. At the first occurrence of 10 min continuous COMP
operation, the current ICT are compared with those when the COMP was
switched from OFF to ON 10 min before. If the T is less than 3
thermistor is regarded as defective.
b) The ICT no-change error can be disabled together by connecting a 4.7k
resistor (5%) to the ICT connector. These resistors are equivalent to a
thermistor 48+/-1
O
C.
e. Cases for disabling ICT thermistor disconnected detection:
1) The detection of thermistor faults a. and b. above is disabled when Deicer
Protection is started. The detection will be enabled again only after (1) the
deicing is completed, and (2) COMP has been restarted and operated for 30
sec.
2) When all the following conditions are fulfilled:
a) 4.7k resistor is connected to the OCT.
b) IFAN is OFF.
c) Compressor is ON.
d) ICT < -30 (disconnected).
O
C, the
11-7SM PXD 1-E.3 GB
Page 74
CONTROL SYSTEM
CONTENT
11.3.7 RV Fault
This test is applied only in compressor units where 4.7k resistor is not connected to
the OCT.
The test is performed every time the unit is switched from OFF/STBY to OPER in Heat
mode or changes operation mode from COOL/DRY to HEAT or (this applies also in
AUTO COOL/HEAT mode).
If ICT is lower than 35
min continuous COMP operation, ICT is compared with ICT reading when the COMP
was switched from OFF to ON 15 min before. RV fault is defined when ICT decreases
more than 5
In this case, the COMP will stop and the SB LED will blink. The fault is reset after
switching to SB or after mode change.
º
C.
º
C at the time of mode change, then at the first occurrence of 15
11.3.8 General Features
a. Allowed (control target) range for RAT is SPT +/-1ºC.
b. Whenever the unit is changed from COOL/DRY/STBY mode to HEAT mode or
vice versa, the procedures below are followed:
Stop COMP for 3 min Change RV state Start COMP if necessary.
11-8SM PXD 1-E.3 GB
Page 75
11.4 Cooling Mode
CONTENT
11.4.1 Cooling Mode – General
a. Mode Definition
Mode: COOL, AUTO (at Cooling)
Temp: Selected desired temperature.
Fan: HIGH, MED, LOW, AUTO.
Timer: Any
I-FEEL: ON or OFF
b. Room Temperature, RT, is detected by:
RAT in normal operation, or
RCT (R/C sensor) in I-FEEL mode.
CONTROL SYSTEM
c. Indoor Coil Temp is detected by ICT.
d. Outdoor Coil Temp is detected by OCT.
11.4.2 Control Functions
a. COMP Operation
COMP
ON
OFF
0
b. OFAN Operation
In normal operation OFAN operates together with the COMP.
1
RT-SPT
c. IFAN Operation
IFAN will operate in ANY speed regardless the ICT or COMP state.
IFAN speed will be determined according to user selection or
AUTO-FAN logic
d. RV and HEATERS outputs
RV and HEATERS are in OFF state in COOL mode.
11-9SM PXD 1-E.3 GB
Page 76
CONTROL SYSTEM
CONTENT
11.4.3 Sequence Diagrams
a. Maintaining room temp at desired level by comparing RT and SPT with user
defined IFAN speed.
(RT - SPT) [oc]
+3
+2
+1
0
-1
-2
COMP
(WVL)
OFAN
IFAN
RV
ON
OFF
ON
OFF
USER FAN SPEED
ON
OFF
11-10SM PXD 1-E.3 GB
Page 77
CONTROL SYSTEM
CONTENT
b. Maintaining room temp at desired level by comparing RT and SPT with
AUTO-IFAN.
+4
+3
+2
+1
0
-1
-2
(RT - SPT) [oc]
ON
COMP
(WVL)
OFAN
IFAN
RV
OFF
ON
OFF
H
M
L
ON
OFF
11-11SM PXD 1-E.3 GB
Page 78
CONTROL SYSTEM
CONTENT
11.5 Heating Mode
11.5.1 Heating Mode - General
a. Compensation Procedure
When I-FEEL is OFF during HEAT mode: RT= RAT – CTV.
When I-FEEL is ON during HEAT mode: RT= RCT.
No compensation will be activated in Forced operation modes
o
C
o
C
o
C
o
C
o
C
b. IFAN operation rules for RC and SH groups:
1) As a general rule for RC and SH groups, IFAN will be switched ON according
to the following graph:
IFAN
ANY
LOW
OFF
General:
Window:
Note 1
301732
20
Duct ed
40
25
ICT
NOTE 1
When COMP is ON (except WAX Model), IFAN will change from
LOW to OFF either when:
a) ICT<28 and IFAN is on for 5 min or longer.
Or,
b) ICT<20
11-12SM PXD 1-E.3 GB
NOTE 2
When ICT is faulty:
When the compressor switches from OFF to ON (excluding
deicing), IFAN will be on in ANY speed.
When the compressor switches from ON to OFF, the IFAN will
change to LOW speed for 30 seconds and then it will be off.
2) In SH or RC group, IFAN will operate for Min 30 sec according to 1) above
after HEs are turned off, where in a case it has to be OFF, it will be forced to
LOW speed.
Page 79
CONTROL SYSTEM
CONTENT
c. IFAN operation rules for RH group
1) In RH group, IFAN starts when HE starts. When HE switches to OFF, IFAN
switches to LOW for 30 sec and then stops.
d. Heaters operation rules for RC and SH groups:
1) For both RC and SH groups, Heaters versus T is as follows:
ON
OFF
ON
OFF
HE1
HE2
1 2 3 4
T=SP-RT [oc]
2) Operation rules for Heaters in RC group:
a) Heaters can be enabled only if IFAN is ON.
b) Heaters will operate according to T and the following graph:
HE-1
&
HE- 2
ON
OFF
General:
Window:
20
15
32
20
45
50
ICT
3) Rules for Heaters operation in SH group:
a) When heaters are to be ON and IFAN is to be OFF according to d. 1)
above, IFAN will be forced to LOW speed.
b) Heaters will operate according to T and the following graph:
ON
OFF
ON
OFF
HE -1
HE - 2
3742
45
50
ICT
4) For both RC and SH groups, excluding deicing, HE1 and HE2 can be ON only
when the compressor is ON.
11-13SM PXD 1-E.3 GB
Page 80
CONTROL SYSTEM
CONTENT
e. Heaters operation rules for RH groups:
1) In RH group, HE operation is according to the difference between RAT and
SPT.
ON
HE2
OFF
ON
HE1
OFF
-1 0 2
T=SP-RT [oc]
f. OFAN Operation for RC and SH groups
1) As a general rule for RC and SH groups, excluding protection modes, OFAN
starts with the compressor.
2) When OFAN is ON it will operate according to the following conditions:
a) OFAN operates together with the compressor.
b) When
and the 4.7k resistor is not
50)2(ICTandSPTRT
connected to the OCT, OFAN will operate according to the following
curve:
ON
OFAN
OFF
11-14SM PXD 1-E.3 GB
0 3
OCT
Page 81
11.6 Heating, RC or SH Group
CONTENT
Mode: HEAT, AUTO (at heating)
Temp: Selected desired temperature
Fan: HIGH, MED, LOW
Timer: Any
I-FEEL: ON or OFF
11.6.1 Sequence Diagram
Maintains room temp. at desired level by comparing RAT or RCT to SPT.
(RT - SPT) [oc]
CONTROL SYSTEM
+2
+1
0
-1
-2
-3
-4
COMP
(WVL)
ON
OFF
HE1
HE2
RV
ON
OFF
ON
OFF
ON
OFF
11-15SM PXD 1-E.3 GB
Page 82
CONTROL SYSTEM
CONTENT
11.7 Heating, RC or SH Group with Autofan
Mode: HEAT, AUTO (at heating)
Temp: Selected desired temperature
Fan: AUTO
Timer: Any
I-FEEL: ON or OFF
11.7.1 Sequence Diagram
Maintains room temp at desired level by controlling COMP, IFAN and OFAN.
(RT - SPT) [oc]
+2
+1
0
-1
-2
-3
-4
COMP
(WVL)
ON
OFF
11-16SM PXD 1-E.3 GB
HE1
HE2
RV
ON
OFF
ON
OFF
ON
OFF
Page 83
11.8 Heating, RH Group
CONTENT
Mode: HEAT, AUTO (at Heating)
Temp: Selected desired temperature
Fan: HIGH, MED, LOW
Timer: Any
I-FEEL: ON or OFF
11.8.1 Sequence Diagram
Maintains room temp at desired level by controlling Heating Elements: HE1 or HE2.
(RT - SPT) in oc
CONTROL SYSTEM
HE1
HE2
+2
+1
0
-1
-2
-3
ON
OFF
ON
OFF
IFAN
H/M/L
L
OFF
30 sec
11-17SM PXD 1-E.3 GB
Page 84
CONTROL SYSTEM
CONTENT
11.9 Heating, RH Group, with AUTOFAN
Mode: HEAT, AUTO (at Heating)
Temp: Selected desired temperature
Fan: AUTO
Timer: Any
I-FEEL: ON or OFF
11.9.1 Sequence Diagram
Maintains room temp. at desired level by controlling the 2-Stage Electric Heaters.
(RT - SPT) in oc
+2
+1
-1
-2
-3
HE1
HE2
IFAN
0
ON
OFF
ON
OFF
H
M
L
OFF
-2
-1
30 sec
-4
-3
11-18SM PXD 1-E.3 GB
Page 85
11.10 Automatic Cooling or Heating
CONTENT
11.10.1 Automatic Cooling or Heating - General
The AUTO Mode is for models with compressor and the WVL-RH only. The WVL-ST,
RC and SH units do not work in AUTO Mode.
a. Mode Definition
Mode: AUTO
Temp: Selected desired temperature
Fan: Any
Timer: Any
I-FEEL: ON or OFF
b. Switching-temperature between Cooling and Heating is SPT 3
c. When the AUTO Mode is started with SPT +/-0
Heat or Auto Cool mode immediately. Instead, the unit will be in a temporary FAN
Mode with IFAN operating at low speed. The proper Auto Heat mode or Auto Cool
will be started whenever the RT reaches SPT-1
CONTROL SYSTEM
O
C.
O
C, the unit will not select Auto
O
C or SPT+1OC respectively.
d. For RC & SH units, Mode change between Auto Heat & Auto Cool Modes is
possible only after the COMP has been OFF during the last T minutes.
Mode Change Time, T
Auto Cool to Auto Heat 3 min
Auto Heat to Auto Cool 4 min
e. For RH and WVL-RH units, Mode change between Auto Heat & Auto Cool Modes
is possible after the COMP/HEs have been OFF during the last T minutes.
Mode Change Time, T
Auto Cool to Auto Heat COMP off for 3 min
Auto Heat to Auto Cool HEs off for 3 min
f. When unit is changed form Cool/Dry Mode to Auto Mode, the unit will continue to
operate in (Auto) Cool Mode until the conditions for switching from Auto Cool to
Auto Heat are satisfied.
Similarly, when unit is changed from Heat Mode to Auto Mode, the unit will
continue to operate in (Auto) Heat Mode until the conditions for switching from
Auto Heat to Auto Cool are satisfied.
11-19SM PXD 1-E.3 GB
Page 86
CONTROL SYSTEM
CONTENT
11.10.2 Sequence Diagrams
a. Auto Cooling or Heating, RC or SH Groups
Maintains room temp. at desired level by selecting between cooling and heating
modes.
(RT - SPT) [oc]
+3
+2
+1
0
COMP
& OFAN
HE1
HE2
IFAN
-1
-2
-3
-4
Auto Cool ModeAuto Heat Mode
USER FAN SPEEDH/M/L/OFF
ON
OFF
ON
OFF
ON
OFF
Auto Heat Mode
> 4 min> 3 min
(3)(3)
H/M/L/OFF
11-20SM PXD 1-E.3 GB
RV
ON
OFF
> 3 min> 2 min
(4)
(4)
Page 87
b. Auto Cooling or Heating RH Group
CONTENT
Maintains room temp. at desired level by selecting between Cooling or Heating Modes.
(RT - SPT) [oc]
+3
+2
+1
0
-1
-2
-3
CONTROL SYSTEM
Auto Heat ModeAuto Cool ModeAuto Heat Mode
HE1
HE2
IFAN
RV
ON
OFF
ON
OFF
ON
OFF
H/M/L
L
OFF
OFF
30 sec
(1)
> 3 min
(2)
> 3 min
(2)
COMP
& OFAN
11.11 Dry Mode
11.11.1 Dry, ST or RC Group or P2000 Model with Any Group Settings
Mode: DRY
Temp: Selected desired temperature
Fan: LOW (automatically selected by software)
Timer: Any
I-FEEL: Any
Control function
Reduce room humidity with minimum temp. fluctuations by operating in Cool Mode with
LOW speed IFAN.
11-21SM PXD 1-E.3 GB
Page 88
CONTROL SYSTEM
&
CONTENT
(RT - SPT) [oc]
+2
+1
0
10
-1
-2
DRY-ON
DRY
DRY-OFF
20
30
4050
Time [min]
LOW
IFAN
OFF
5 minutes COMP
ON
OMP
OFF
OFAN
Max 15 minutes
ON
HE1
OFF
HE2
ON
RV
OFF
3.5
min
Note1
ON time
Max 15 minutes
6 min
Note 2
NOTES
1. When DRY is ON, the COMP is forced OFF for 3.5 min (longer
than the 3 min Min COMP- OFF time) after every 15 min of
continuous COMP operation.
2. When DRY is OFF, the COMP is forced ON for 6 min (longer
than the 3 min Min COMP- ON time) after every 15 min of
continuous COMP OFF time.
3. When DRY is changed from ON to OFF or vice versa, the
limits mentioned in (1) & (2) are ignored. The COMP operation
is only controlled by the 3 min Min OFF time and 1 min Min
ON time.
4. In DRY Mode, IFAN is LOW when COMP is ON, and is OFF
when COMP is OFF.
5. HEs are always OFF in DRY Mode.
11-22SM PXD 1-E.3 GB
Page 89
11.11.2 DRY, SH or RH group
CONTENT
Mode: DRY
Temp: Selected desired temperature
Fan: LOW (automatically selected by software)
Timer: Any
I-FEEL: Any
Control function
Reduces room humidity with minimum temp. fluctuations by operating in Cool Mode
with LOW speed IFAN and HE.
(RT - SPT) [oc]
CONTROL SYSTEM
IFAN
COMP
& OFAN
HE1
HE2
+2
+1
0
10
-1
-2
LOW
OFF
ON
OFF
ON
OFF
ON
OFF
20
30
4050
Time [min]
RV
ON
OFF
11-23SM PXD 1-E.3 GB
Page 90
CONTROL SYSTEM
CONTENT
11.12 Protection
11.12.1 Cooling Mode Protections
a. Indoor Coil Defrost
Mode: COOLING, DRY, AUTO
Temp: Selected desired temp.
Fan: Any
Timer: Any
I-FEEL: ON or OFF
Control Function
Protects the indoor coil from ice formation at low ambient temperatures.
ICT [oc]
+14
+5
+2
+1
0
-1
OFAN
COMP
t1t2t3
ON
OFF
ON
OFF
t1
11-24SM PXD 1-E.3 GB
ON
IFAN
OFF
t1 = 5 min minimum for each COMP starting.
t2 = OFAN cycling (alternate between ON and OFF every 30 sec) for 20 min maximum.
t3 = COMP and OFAN stops for 10 min minimum.
Page 91
CONTROL SYSTEM
CONTENT
b. High Pressure Protection
Mode: (AUTO) COOLING or DRY
Temp: Selected desired temperature
Fan: Any
Timer: Any
I-FEEL: ON or OFF
Control Function
To protect the COMP from the high pressure build-up in the outdoor coil during normal
cooling operation, by switching OFF the IFAN and COMP.
OCT [oc]
68
66
61
55
52
COMP
OFAN
Any
OFF
Any
ON
For all models except WAX & P2000For WAX & P2000 models
COMP is forced OFF
OFAN is forced ON
OFAN follow operation of
COMP
COMP is forced OFF
OFAN is forced ON
IFAN
OPER
LED
Any
ON
Blink
L
IFAN forced
to LOW
NOTE
The ICT is also monitored during COOL and DRY modes, in case the
RV control circuit is faulty. Whenever ICT reaches 70
o
C, which
indicates a high pressure in the indoor coil, the COMP will be forced
OFF automatically. The COMP can be turned ON again only after the
ICT is under 70
o
C again and after the 3 min COMP ON delay time. The
OPER LED will not blink in this case.
11-25SM PXD 1-E.3 GB
Page 92
CONTROL SYSTEM
CONTENT
11.12.2 Heating Mode Protections
a. Outdoor Coil Deicing (excluding RH Group)
Mode: HEATING, AUTO (at heating)
Temp: Selected desired temperature
Fan: Any
Timer: Any
I-FEEL: Any
Control function
To protect the outdoor coil from ice formation by controlling COMP & RV operation.
1) Deicer Activation Algorithm
a) Static deicer threshold is -5°C
b) Dynamic deicer threshold changes of 3°C in 3 minutes in the OCT
temperature
c) In first COMP activation (after SB or OFF), if OCT < 0°C, min time to first
deicer is 10 min else 40 min.
d) In a case of reading 3 successive OCT values below –10°C and
previously 3 successive OCT values of 43°C (4.7 K) , the unit will activate
deicing procedure.
11-26SM PXD 1-E.3 GB
Page 93
2) Deicing procedure
OCT [oc]
CONTENT
CONTROL SYSTEM
12
DOC
DST
(DDT)
COMP
OFAN
RV
0
3 min3 min
ON
OFF
DI (note 1)
ON
OFF
ON
OFF
36s36s
30s
max 12 min.
DI (note 2)
30s
DT
IFAN
all SH units
except WAX
HE
IFAN
HE
RC or WAX units
OPER
LED
ANY
L
ON
ANY
ANY
OFF
ANY
OFF
ON
BLINK
IFAN is forced to Low Speed
HEs are forced ON
Note 3
HEs are forced OFF
NOTES
1. In the following Deicing cycles, the time interval between two
Deicing cycles activation is between 30 to 80 min.
2. For RC group, IFAN is forced OFF.
3. For SH group, HEs are forced ON and IFAN is forced to operate
at LOW speed, regardless of the ICT and difference between
RAT & SPT.
4. When jumper J7 is set, the DST value is -2°C.
11-27SM PXD 1-E.3 GB
Page 94
CONTROL SYSTEM
CONTENT
b. High Pressure Protection (excluding RH Group)
Mode: (AUTO) HEATING
Fan: Any
Timer: Any
I-FEEL: ON or OFF
Control Function
Protects the compressor from high pressure by switching OFF the OFAN and COMP.
ICT [oc]
67
66
61
55
52
COMP
OFAN
Any
Off
Any
Off
For all models except WAXFor WAX model
OFAN is force
Off
COMP is forced OFF
COMP is forced OFF
OPER
LED
11-28SM PXD 1-E.3 GB
ON
BLINK
Page 95
11.12.3 Condensation Pump (ECC/K model)
CONTENT
Mode: Cool, Dry, Auto
Temp: Selected desired temperature
Fan: Any
Timer: Any
I FEEL: Any
Control function:
Prevent Condensed water from Overflowing.
CONTROL SYSTEM
Water Level
OPER
LED
COMP
(WVL)
PUMP
Overflow
Normal
ON
OFF
BLINK
ON
OFF
ON
OFF
Overflow when
unit is ON
COMP/WVL is
forced OFF
8 min8 min
Overflow when
unit is OFF
1 min
Notes:
1. The switch used for water level detection is closed under normal condition, and is open
when water overflow.
2. For the NEC version of MCU, the "Over Flow" & “Normal” condition are indicated by
logic “0” & “1” at the LEVEL4 input pin respectively.
3. For the Fujitsu version of MCU, the "Over Flow" & “Normal” condition are indicated by
logic “1” & “0” at the LEVEL4 input pin respectively.
4. The “Overflow” condition can activate the water pump in SB and operating modes.
The Sleep mode is activated by using the SLEEP button on the R/C. In Sleep Mode,
the unit will automatically adjust the SPT to turn up/down the room temperature (RT)
gradually to provide maximum comfort for the sleeping user.
Sleep is treated as TIMER function. Therefore, the TIMER LED is activated similar to
TIMER function.
11-30SM PXD 1-E.3 GB
Page 97
11.14 SPT Adjustment in Sleep Mode
CONTENT
CONTROL SYSTEM
SPT+3
SPT+2
SPT+1
SPT
SPT-1
In COOL, AUTO COOL or DRY modes, the SPT adjustment is positive
(from 0 to +3
In HEAT or AUTO HEAT modes, the SPT adjustment is negative
(from 0 to -3
o
o
C).
C).
In other modes, there is no SPT adjustment.
The SPT adjustment is cancelled when the Sleep mode is cancelled.
RT
7 Hours Sleep operation
for Normal Sleep Mode
Cool, Dry modes
Unit is turned to SB
after Sleep
SPT-2
SPT-3
Heat mode
Start
Sleep
1
485326
7
NOTE
If OFF-timer is active, the unit may go to SB before or after 7 hours of
sleep operation.
Time [Hr]
11-31SM PXD 1-E.3 GB
Page 98
CONTROL SYSTEM
CONTENT
11.14.1 Time Adjustment in SLEEP Mode
In 10V4, the user can make use of the Off-Timer to extend the Sleep Time from 7
hours to 12 hour (max). The operation of the new “Extended Sleep Mode” is illustrated
by the graphs below.
Case 1 is the Standard Sleep Mode, which is the only sleep mode in the previous
version of MCU. The A/C unit simply works for 7 hours, then goes to SB.
Case 2 is the new Extended Sleep Mode. If an active Off-Timer is set to turn off the
A/C between 7-12 hour, relative to the starting of Sleep, the Sleep time is extended.
And, instead of going to SB at the 7th hour, the A/C will work until reaching the Offtime.
Case 3 is an exception to case 2. The Sleep Mode will not be extended to the OffTime when the Off-Timer is preceded by an On-Timer, which is also between 7-12
hour.
Case 1 : Standard Sleep Mode
Condition : Off-timer is not set or is beyond 12 hour.
Oper
SB
Start
Sleep
Case 2 : Extended Sleep Mode
Condition : Off-timer is set at 7-12 hour.
Oper
SB
Start
Sleep
Case 3 : Exception to Case 2
Condition : Off-timer is set at 7-12 hour
On-timer is set at 7-12 hour and before Off-timer
Oper
48101226
48101226
7
7
Off-timer
Time [Hr]
Time [Hr]
11-32SM PXD 1-E.3 GB
SB
Start
Sleep
48101226
7
Off-timerOn-timer
Time [Hr]
Page 99
11.15 Controller Self-Test Procedure
CONTENT
11.15.1 By Shorting Test Jumper J1
SELF-TEST FLOW CHART
FOR CONTROLLER (VERSION 4V5 OR HIGHER)
SHORT JUMPER
J1
Step 1
(CONTROL PCB)
RC/ST TEST
MODEL
CONFIGURATION
TEST
CONTROL SYSTEM
Step 2
Step 3
PRESS ON
POWER
BUTTON
PRESS ON
MODE BUTTON
STEP MOTOR TEST
FREQUENCY
TEST
LEDS OFF
LEDS ON TEST
AUTO RELAY
TEST
INDOOR FAN
SPEED TEST
STANDBY
OPERATE
TIMER
COOL
HEAT
COMPRESSOR
OUTDOOR FAN
Step 4
Step 5
Step 6
Step 7
Step 8
PRESS ON RESET
BUTTON
PRESS ON FAN
BUTTON ON THE
REMOTE CONTROL
PRESS ON MODE
BUTTON
PRESS ON MODE
BUTTON
DISCONNECT
JUMPER
J1
BUZZER TEST
(ONE BEEP SOUND)
REMOTE CONTROL
TO CPU COMUNICATION
(TWO BEEPS SOUNDS)
THERMISTOR ANALOG
VOLTAGE CHECKING
EEPROM MEMORY
TEST
END OF SELF
TEST
R.V.
LOW
MEDIUM
HIGH
11-33SM PXD 1-E.3 GB
Page 100
CONTROL SYSTEM
CONTENT
11.15.2 By Remote Control Settings:
a. STEP 1: TURNING ON THE POWER.
Turn ON the power, make sure that the unit is in operation.
b. STEP 2 : ENABLE SELF-TEST MODE
1) Use the remote control to send the first settings to display / indoor unit HEAT
mode, HIGH IFAN, set temperature to 16 ºC, no I-FEEL Sleep or any other
timer settings are needed.
2) Cover the IR transmitter components in the remote control so that it will not
transmit the signals to the indoor unit display.
3) Use the remote control to send the second settings to display / indoor unit
COOL mode, LOW IFAN, no I-FEEL Sleep or any other timer settings.
4) Uncover the remote control IR transmitter and change the temperature
settings. If the display/indoor unit receive the settings properly the following
steps will start:
c. STEP 3: MODEL SETTING CONFIRMATION
1) The STAND-BY and COOL LEDS will indicate the operation mode as follows:
COOL LED STAND-BY LED OPERATION MODE
OFFONST
OFFOFFRC
ONOFFSH
ONONRH
2) Testing the Model configuration. Selected by the COMP, STAND-BY, TIMER
LEDS and FILTER will indicate the model configuration as follows (the
relevant line for this manual is highlighted):
FILTER LED TIMER LEDOPERATE LEDCOMPMODEL
OFFOFFOFFONWNG
ONOFFOFFONMBX
OFFONOFFONWNX
OFFOFFONONPRX
ONOFFONONWMN1
OFFONONONEMD/LS
ONONONONECC-K
OFFONOFFOFFWMN 4
ONONOFFOFFPXD
WMN
2/WHX
ONOFFONOFF
ONONONOFFWMN 3
11-34SM PXD 1-E.3 GB
In this term the step motor will turn to HOME POSITION.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.