● Bended indoor coil with treated aluminum fins and coating for improved efficiency.
SM LEXDCI 1-E.1 GB
● Easy access to the interconnecting tubing and wiring connections, so that removing
the front grill or casing is not necessary.
● Refrigerant pipes can be connected to the indoor unit from 5 different optional
directions.
● Water condensate tray is equipped with two optional drain connections
● Automatic treated air sweep.
● Low indoor and outdoor noise levels.
● Easy installation and service.
1-1
INTRODUCTION
CONTENTS
1.3 Indoor Unit
The indoor unit is wall mounted, and can be easily fitted to many types of residential
and commercials applications.
New design is available in LED version.
Dry contactPresence detector or (jumper selected) power shedding
1.4 Filtration
The LEX DCI INV series presents several types of air filters:
● Easily accessible, and re-usable pre-filters (mesh)
● Pre-charged electrostatic filter (disposable)
● Active carbon filter (disposable)
● ESF. Active Electro Static re-usable filter (optional)
1.5 Ionizer (Optional)
A special design Ionizer protected by unique patents integrated into the indoor unit,
generating negative ions to the room providing comfort and upgraded indoor air quality.
1.6 Control
The microprocessor indoor controller, and an infrared remote control, supplied as
standard, provides complete operating function and programming.
Remote controllers: RC-2/3/4/5/7, RC-4i-1, RCW, μBMS.
Networking system Airconet version 4.2 and up, MIU SW version H8 and up.
For further details please refer to the Operational Manual.
1-2
SM LEXDCI 1-E.1 GB
1.7 Outdoor Unit
CONTENTS
The LEX DCI INV outdoor units can be installed as floor or wall mounted units by using
a wall supporting bracket. The metal sheets are protected from corrosion paint work
allowing long life resistance. All outdoor units are pre-charged. For further information
please refer to the Product Data Sheet, Chapter 2.
Outdoor Unit Feature
FeatureDCI 25DCI 35DCI 50DCI 60DCI 72Z
Display3 LED’s
Base HeaterOptional
Outdoor FanVariable speed DC Inverter
1.8 Tubing Connections
Flare type interconnecting tubing to be produced on site.
For further details please refer to the Installation Manual.
INTRODUCTION
1.9 Accessories
ItemDescription
MIU (LEX)MODBUS interface unit
RS485 Adapter
Base Heater
M2L cable Port
1.10 Inbox Documentation
Each unit is supplied with its own installation and operation manuals.
To be used as an interface with RCW
or μBMS remote controllers
SM LEXDCI 1-E.1 GB
1-3
INTRODUCTION
CONTENTS
1.11 Matching Table
1.11.1 R410A
OUTDOOR UNITS
INDOOR UNITS
MODELREFR”
DCI 25R410A
DCI 35R410A
DCI 50R410A
DCI 60R410A
DCI 72ZR410A
LEX 25 LEX 35 LEX 50 LEX 60 LEX 72
√
√
√
√
√
1-4
SM LEXDCI 1-E.1 GB
PRODUCT DATA SHEET
CONTENTS
2.PRODUCT DATA SHEET
2.1 LEX 25 DCI
Model Indoor UnitLEX 25 DCI
Model Outdoor UnitDCI 25 R410A
Installation Method of PipeFlared
CharacteristicsUnitsCooling Heating
Capacity
Power input
EER (Cooling) or COP(Heating)
Energy efficiency classAA
DimensionsWxHxDmm810x285x210
Net Weightkg11.5
Package dimensionsWxHxDmm870x356x282
Packaged weightkg14
Units per palletunits28
Stacking heightunits7 levels
Refrigerant controlElectronical Expansion Valve
Compressor type,modelSingle Rotary DC Inverter,Panasonic 5RS102XAB
Fan type & quantityPropeller x 1
Fan speedsHRPM830
Air flow Hm3/hr1780
Sound power levelHdB(A)61
Sound pressure level
DimensionsWxHxDmm795x610x290
Net Weightkg38
Package dimensionsWxHxDmm970x650x394
Packaged weightkg42
Units per palletUnits9
OUTDOOR
Stacking heightunits3 levels
Refrigerant typeR410A
Standard chargekg(7.5m)1.1
Additional charge No need
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511.
(2) Airflow in ducted units; at nominal external static pressure.
(3) Sound power in ducted units is measured at air discharge.
(4) Sound pressure level measured at 1 meter distance from unit.
SM LEXDCI 1-E.1 GB
2-1
PRODUCT DATA SHEET
CONTENTS
2.2 LEX 35 DCI
Model Indoor UnitLEX 35 DCI
Model Outdoor UnitDCI 35 R410A
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511.
(2) Airflow in ducted units; at nominal external static pressure.
(3) Sound power in ducted units is measured at air discharge.
(4) Sound pressure level measured at 1 meter distance from unit.
2-2
SM LEXDCI 1-E.1 GB
PRODUCT DATA SHEET
CONTENTS
2.3 LEX 50 DCI
Model Indoor UnitLEX 50 DCI
Model Outdoor UnitDCI 50
Installation Method of PipeFlared
CharacteristicsUnitsCoolingHeating
Capacity
Power input
EER (Cooling) or COP(Heating)
(1)
(1)
(1)
Energy efficiency classAA
Power supplyV/Ph/Hz220-240V/Single/50Hz
Rated currentA6.6 7.5
Starting currentA10.5
Circuit breaker ratingA20
Fan type & quantityCrossflow x 1
Fan speedsH/M/LRPM1200/1050/900
Air flow
(2)
H/M/Lm3/hr850/760/620
External static pressureMin-MaxPa0
Sound power level
DimensionsWxHxDmm1060x295x210
Weightkg15
Package dimensionsWxHxDmm1125x360x280
Packaged weightkg18
Units per palletunits16 units per pallet
Stacking heightunits8 levels
Refrigerant controlEEV
Compressor type,modelScroll,Panasonic 5CS130XCC03
Fan type & quantityPropeller(direct) x 1
Fan speedsH/LRPM920
Air flow H/Lm3/hr2160
Sound power levelH/LdB(A)63
Sound pressure level
(4)
H/LdB(A)53
DimensionsWxHxDmm795x610x290
Weightkg39
Package dimensionsWxHxDmm945x655x395
Packaged weightkg43
Units per palletUnits9 units per pallet
OUTDOOR
Stacking heightunits3 levels
Refrigerant typeR410A
Refrigerant chargless distancekg/m1.50/7.5
Additional charge per 1 meterg/mNo need
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511.
(2) Airflow in ducted units; at nominal external static pressure.
(3) Sound power in ducted units is measured at air discharge.
(4) Sound pressure level measured at 1 meter distance from unit.
SM LEXDCI 1-E.1 GB
2-3
PRODUCT DATA SHEET
CONTENTS
2.4 LEX 60 DCI
Model Indoor UnitLEX-60 DCI
Model Outdoor UnitDCI 60
Installation Method of PipeFlared
CharacteristicsUnitsCoolingHeating
Capacity
Power input
EER (Cooling) or COP(Heating)
(1)
(1)
(1)
Energy efficiency classBB
Power supplyV/Ph/Hz220-240V/Single/50Hz
Rated currentA8.9 8.6
Starting currentA10.5
Circuit breaker ratingA20
Fan type & quantityCrossflow x 1
Fan speedsH/M/LRPM1250/1100/1000
Air flow
(2)
H/M/Lm3/hr900/760/620
External static pressureMin-MaxPa0
Sound power level
DimensionsWxHxDmm1060x295x210
Weightkg15
Package dimensionsWxHxDmm1125x360x280
Packaged weightkg18
Units per palletunits16 units per pallet
Stacking heightunits8 levels
Refrigerant controlEEV
Compressor type,modelScroll,Panasonic 5CS130XCC03
Fan type & quantityPropeller(direct) x 1
Fan speedsH/LRPM820
Air flow H/Lm3/hr2860
Sound power levelH/LdB(A)65
Sound pressure level
(4)
H/LdB(A)55
DimensionsWxHxDmm846x690x302
Weightkg46
Package dimensionsWxHxDmm990x770x430
Packaged weightkg50
Units per palletUnits9 units per pallet
OUTDOOR
Stacking heightunits3 levels
Refrigerant typeR410A
Refrigerant chargless distancekg/m1.65/7.5
Additional charge per 1 meterg/mNo need
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511.
(2) Airflow in ducted units; at nominal external static pressure.
(3) Sound power in ducted units is measured at air discharge.
(4) Sound pressure level measured at 1 meter distance from unit.
2-4
SM LEXDCI 1-E.1 GB
PRODUCT DATA SHEET
CONTENTS
2.5 LEX 72 DCI
Model Indoor UnitLEX 72 DCI
Model Outdoor UnitGC-DCI 72 Z
Installation Method of PipeFlared
CharacteristicsUnitsCoolingHeating
Capacity
Power input
EER (Cooling) or COP(Heating)
(1)
(1)
(1)
Energy efficiency classBC
Power supplyV/Ph/Hz220-240V/Single/50Hz
Rated currentA9.8 10.3
Starting currentA15
Circuit breaker ratingA20
Fan type & quantityCrossflow x 1
Fan speedsH/M/LRPM1300/1150/10001350/1200/1050
Air flow
(2)
H/M/Lm3/hr950/800/6501000/850/700
External static pressureMin-MaxPa0
Sound power level
Sound pressure level
DimensionsWxHxDmm1060x295x210
Weightkg15
Package dimensionsWxHxDmm1115x350x260
Packaged weightkg18
Units per palletunits16
Stacking heightunits8 levels
Refrigerant controlEEV
Compressor type,modelTwo Rotary,Mitsubishi TNB220F
Fan type & quantityPropeller(direct) x 1
Fan speedsH/LRPM850
Air flow H/Lm3/hr3600
Sound power levelH/LdB(A)66
Sound pressure level
(4)
H/LdB(A)56
DimensionsWxHxDmm950x835x412
Weightkg65.5
Package dimensionsWxHxDmm1080x910x477
Packaged weightkg73
Units per palletUnits2
OUTDOOR
Stacking heightunits2 levels
Refrigerant typeR410A
Refrigerant chargless distancekg/m2.4kg/30m
Additional charge per 1 meterg/mNo Need
Operation control type Remote control
Heating elements (Option)kW
Others
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511.
(2) Airflow in ducted units; at nominal external static pressure.
(3) Sound power in ducted units is measured at air discharge.
(4) Sound pressure level measured at 1 meter distance from unit.