Electra K 25 DCI INV, K 35 DCI INV, ONG 35 DCI INV, ONG 25 DCI INV, K 35S DCI INV Service Manual

...
Service Manual

K DCI Inverter series

Indoor Units Outdoor Units
K 35S DCI INV ONG 35S DCI INV
REFRIGERANT
R410A
DECEMBER 2004
HEAT PUMP

LIST OF EFFECTIVE PAGES

LIST OF EFFECTIVE PAGES
Note: Changes in the pages are indicated by a “Revision#” in the footer of each effected page
(when none indicates no changes in the relevant page). All pages in the following list represent effected/ non effected pages divided by chapters.
Dates of issue for original and changed pages are:
Original .......1 ........ 15 January 2005
Total number of pages in this publication is 70 consisting of the following:
Page No.
Title ....................... 0
A ........................... 0
i ............................. 0
1-1 - 1-4 ................ 0
2-1 - 2-4 ................ 0
3-1 - 3-2 ................ 0
4-1 - 4-2 ................ 0
5-1 - 5-12 .............. 0
6-1 - 6-8 ................ 0
7-1 - 7-2 ................ 0
8-1 - 8-2 ................ 0
9-1 - 9-2 ................ 0
10-1-10-2 .............. 0
11-1-11-16 ............. 0
12-1-12-8 .............. 1
13-1-13-10 ............ 0
Appendix -A ...........0
Revision No. #
Page No.
Revision No. #
Page No.
Revision No. #
Zero in this column indicates an original page.
*Due to constant improvements please note that the data on this service manual can be modified with out notice. **Photos are not contractual.
A
Revision Y05-02
Service Manual − K DCI

TABLE OF CONTENTS

Table of Contents
1. INTRODUCTION ...................................................................................................1-1
2. PRODUCT DATA SHEET ......................................................................................2-1
3. RATING CONDITIONS ..........................................................................................3-1
4. OUTLINE DIMENSIONS .......................................................................................4-1
5. PERFORMANCE DATA .......................................................................................5-1
6. PRESSURE CURVES ...........................................................................................6-1
7. ELECTRICAL DATA ..............................................................................................7-1
8. WIRING DIAGRAMS .............................................................................................8-1
9. REFRIGERATION DIAGRAMS .............................................................................9-1
10. TUBING CONNECTIONS ......................................................................................10-1
11. CONTROL SYSTEM .............................................................................................11-1
12. TROUBLESHOOTING ..........................................................................................12-1
13.
EXPLODED VIEWS AND SPARE PARTS LISTS .................................................13-1
14. APPENDIX A
Revision Y05-02Service Manual - K DCI
i
1. INTRODUCTION
CONTENTS
1.1 General
The new K DCI INVERTERS split Cassette range comprise the following RC (heat pump) models:
K 25 DCI INV
K 35 DCI INV
K 35S DCI INV
K 50 DCI INV
The New DCI K units can be easly fitted to resedential and comercial aplications featuring esthetic design, compact dimensions, and low noise operation.
1.2 Main Features

INTRODUCTION

The K DCI INV series benefits from the most advanced technological innovations, namely:
DC Inverter technolegy
R410a
High COP (level A)
Lego Concept
Pre-Charged units up to the max’ alowing tubing distance
Networking system connectivity
Base heater connection
Cooling operation at outdoor temperature down to -10ºC
Heating operation at outdoor temperature down to -15ºC
Bended indoor coil with treated aluminum fins and coating for improved
efficiency.
Easy access to the interconnecting tubing and wiring connections.
Automatic treated air sweep.
Low indoor and outdoor noise levels.
Easy installation and service.
Revision Y05-02Service Manual - K DCI
1-1
INTRODUCTION
CONTENTSCONTENTS
1.3 Filtration
The WNG DCI INV series presents several types of air filters:
Easily accessible, and re-usable pre-filters (mesh)
Pre-charged electrostatic filter (disposable)
Active carbon filter (disposable)
1.4 Control
The microprocessor indoor and outdoor controllers, and an infrared remote control, supplied as standard, provide complete operating function and programming.
Remote controlers: RC-2/3/4/5/7, RCW, µBMS
Networking system AircoNet version 4.2 and up, MIU SW version H8 and up For further details please refer to the Operation Manual, Appendix A.
1.5 Outdoor Unit
The K DCI INV outdoor units can be installed as floor or wall mounted units by using a wall supporting bracket. The metal sheets are protected by anti- corrosion paint work allowing long life resistance. All outdoor units are pre-charged. For further information please refer to the Product Data Sheet, Chapter 2.
ONG 25 DCI
ONG 35 DCI
ONG 50
Outdoor Unit Features:
Features ONG 25,35, 50, DCI
Display 3 LED’s Base Heater Optional Outdoor Fan Variable Speed DC Inverter
M2L cable Port No
1.6 Tubing Connections
Flare type interconnecting tubing to be produced on site. For further details please refer to the Installation Manual, Chapter 9.
1.7 Accessories
1.8 Inbox Documentation
1-2
MIU (K) MODBUS Interface Unit
Base heater
M2L cable
Each unit is supplied with its own installation and operation manuals.
Revision Y05-02 Service Manual - K DCI
1.9 Matching Table
CONTENTSCONTENTS
1.9.1 R410A
OUTDOOR UNITS
MODEL REF” WNG25DCI WNG35 DCI K25 DCI K35 DCI K35S DCI K50 DCI
INTRODUCTION
INDOOR UNITS
ONG 25 DCI R410A
ONG 35 DCI R410A
0NG 50 DCI R410A
√√
√√
The above table lists outdoor units and K indoor units which can be matched together. In addition the listed outdoor units can be matched with other types of indoor units such as wall mounted, For further information please refer to the relevant Service Manual.
Revision Y05-02Service Manual - K DCI
1-3

PRODUCT DATA SHEET

CONTENTSCONTENTS
2. PRODUCT DATA SHEET
2.1 K25 DCI
Model Indoor Unit K25 DCI Model Outdoor Unit ONG25 DCI
Installation Method Flare
Characteristics Units Cooling Heating
(1)
Capacity
Power Input
COP
Energy Efficiency Class A A
Power Supply V/Ph/Hz
Rated Current A
Starting Current A
Circuit Breaker Rating A 16
INDOOR
OUTDOOR
Operation Control Type IR Remote Control
(1)
(1)
W
W/W
Fan Type & Quantity Centrifugal*1
(2)
Airflow
H/M/L m3/hr
External Static Pressure Min-Max Pa N/A
Sound Power Level
Sound Pressure Level
Moisture Removal L/hr
Condensate Drain Tube I.D. mm 16
Dimensions W/H/D mm 571 287 571
Weight kg 22.7
Package Dimensions W/H/D mm 685 415 685
Units per Pallet Units 10
Stacking Height Units 5
Refrigerant Control Electronic Expansion Valve
Compressor Type, Model Single Rotary DC Inverter Panasonic 5RS102XAB
Fan Type & Quantity Axial *1
Airflow H m3/hr 1780
Sound Power Level H dB (A) 60 61
Sound Pressure Level
Dimensions W/H/D mm 795 610 290
Weight kg 40
Package Dimensions W/H/D mm 945 655 393
Units per Pallet Units 9
Stacking Height Units 3
Refrigerant Type R410A
Refrigerant Chargeless Distance g 1100
Additional Charge Per 1 Meter g/m No Need
Connections Between Units
(3)
H/L dB (A)
(4)
H/L dB (A)
(4)
H dB (A) 50 51
Liquid Line
Suction Line
Max. Tubing Length m 20
Max. Height Difference m 10
Btu/hr
W
(mm)In
(mm)In
8530 (5120-12970) 11600 (5120-17060)
2500 (1500 - 3800) 3400 (1500 - 5000)
590 (420-1000) 915 (400-1500)
4.24 3.72
220-240V / 1Ph / 50Hz
2.7 4.2
10.50
570-500-435 600-530-450
42-48 42-47
32-38 32-37
1.0
(6.35)
¼”
(9.53)
”
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
Revision Y05-02Service Manual - K DCI
2-1
PRODUCT DATA SHEET
CONTENTSCONTENTS
2.2 K35 DCI
Model Indoor Unit K35 DCI Model Outdoor Unit ONG35 DCI
Installation Method Flare
Characteristics Units Cooling Heating
Capacity
Power Input
COP
Energy Efficiency Class A A
Power Supply V/Ph/Hz
Rated Current A
Starting Current A
Circuit Breaker Rating A 16
Operation Control Type IR Remote Control
(1)
(1)
(1)
INDOOR
OUTDOOR
W
W/W
Fan Type & Quantity Centrifugal*1
(2)
Airflow
H/M/L m3/hr
External Static Pressure Min-Max Pa N/A
Sound Power Level
Sound Pressure Level
Moisture Removal L/hr
Condensate Drain Tube I.D. mm 16
Dimensions W/H/D mm 571 287 571
Weight kg 24.4
Package Dimensions W/H/D mm 685 415 685
Units per Pallet Units 10
Stacking Height Units 5
Refrigerant Control Electronic Expansion Valve
Compressor Type, Model Single Rotary DC Inverter Panasonic 5RS102XAB
Fan Type & Quantity Axial *1
Airflow H m3/hr 1780
Sound Power Level H dB (A)
Sound Pressure Level
Dimensions W/H/D mm 795 610 290
Weight kg 40
Package Dimensions W/H/D mm 945 655 393
Units per Pallet Units 9
Stacking Height Units 3
Refrigerant Type R410A
Refrigerant Chargeless Distance g 1200
Additional Charge Per 1 Meter g/m No Need
Connections Between Units
(3)
H/L dB (A)
(4)
H/L dB (A)
(4)
H dB (A)
Liquid Line
Suction Line
Max. Tubing Length m 20
Max. Height Difference m 10
Btu/hr
W
(mm)In
(mm)In
11940 (5100 - 14960) 14620 (5100 - 18700)
3500 (1500 - 4400) 4300 (1500 - 5500)
950 (420-1250) 1330 (400-1850)
3.68 3.23
220-240V / 1Ph / 50Hz
4.1 5.6
10.50
580-510-435 620-560-450
42-48 42-47
32-38 32-37
1.5
62 62
52 52
¼”
(6.35)
(9.53)
”
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
2-2
Revision Y05-02 Service Manual - K DCI
PRODUCT DATA SHEET
CONTENTSCONTENTS
2.3 K35S DCI
Model Indoor Unit K35S DCI Model Outdoor Unit ONG35 DCI
Installation Method Flare
Characteristics Units Cooling Heating
Capacity
Power Input
COP
Energy Efficiency Class A A
Power Supply V/Ph/Hz
Rated Current A
Starting Current A
Circuit Breaker Rating A 16
Operation Control Type IR Remote Control
(1)
(1)
(1)
INDOOR
OUTDOOR
W
W/W
Fan Type & Quantity Centrifugal*1
(2)
Airflow
H/M/L m3/hr
External Static Pressure Min-Max Pa N/A
Sound Power Level
Sound Pressure Level
Moisture Removal L/hr
Condensate Drain Tube I.D. mm 16
Dimensions W/H/D mm 571 287 571
Weight kg 24.4
Package Dimensions W/H/D mm 685 415 685
Units per Pallet Units 10
Stacking Height Units 5
Refrigerant Control Electronic Expansion Valve
Compressor Type, Model Single Rotary DC Inverter Panasonic 5RS102XAB
Fan Type & Quantity Axial *1
Airflow H m3/hr 1780
Sound Power Level H dB (A)
Sound Pressure Level
Dimensions W/H/D mm 795 610 290
Weight kg 40
Package Dimensions W/H/D mm 945 655 393
Units per Pallet Units 9
Stacking Height Units 3
Refrigerant Type R410A
Refrigerant Chargeless Distance g 1200
Additional Charge Per 1 Meter g/m No Need
Connections Between Units
(3)
H/L dB (A)
(4)
H/L dB (A)
(4)
H dB (A)
Liquid Line
Suction Line
Max. Tubing Length m 20
Max. Height Difference m 10
Btu/hr
W
(mm)In
(mm)In
11940 (5800 - 16380) 15300 (5780-19720)
3500 (1700 - 4800) 4500 (1700 - 5800)
870 (460 - 1300) 1180 (350-1580)
4.02 3.81
220-240V / 1Ph / 50Hz
4.0 5.4
10.50
580-510-435 620-560-450
42-49 42-48
32-38 32-38
1.5
62 62
52 52
¼”
(6.35)
(9.53)
”
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
Revision Y05-02Service Manual - K DCI
2-3
PRODUCT DATA SHEET
CONTENTSCONTENTS
2.4 K50 DCI
Model Indoor Unit K50 DCI Model Outdoor Unit ONG35 DCI
Installation Method Flare
Characteristics Units Cooling Heating
Capacity
Power Input
COP
Energy Efficiency Class A A
Power Supply V/Ph/Hz
Rated Current A
Starting Current A
Circuit Breaker Rating A 16
Operation Control Type IR Remote Control
(1)
(1)
(1)
INDOOR
OUTDOOR
W
W/W
Fan Type & Quantity Centrifugal*1
(2)
Airflow
H/M/L m3/hr
External Static Pressure Min-Max Pa N/A
Sound Power Level
Sound Pressure Level
Moisture Removal L/hr
Condensate Drain Tube I.D. mm 16
Dimensions W/H/D mm 571 287 571
Weight kg 28
Package Dimensions W/H/D mm 685 415 685
Units per Pallet Units 10
Stacking Height Units 5
Refrigerant Control Electronic Expansion Valve
Compressor Type, Model SCROLL Panasonic 5CS130XCC03
Fan Type & Quantity Axial *1
Airflow H m3/hr 2160
Sound Power Level H dB (A)
Sound Pressure Level
Dimensions W/H/D mm 795 610 290
Weight kg
Package Dimensions W/H/D mm 945 655 393
Units per Pallet Units 9
Stacking Height Units 3
Refrigerant Type R410A
Refrigerant Chargeless Distance g 1500
Additional Charge Per 1 Meter g/m No Need
Connections Between Units
(3)
H/M/L dB (A)
(4)
H/M/L dB (A)
(4)
H dB (A)
Liquid Line
Suction Line
Max. Tubing Length m 30
Max. Height Difference m 10
Btu/hr
W
(mm)In
(mm)In
17060 (4610 – 21840) 21500 (4610 - 25590)
5000 (1350 – 6400) 6300 (1350 – 7500)
1550 (530 – 2000) 1740 (350 – 2080)
3.23 3.62
220-240V / 1Ph / 50Hz
7.1 8.0
10.50
730-630-510
46 – 55 - 59
36 – 44 - 48.5
2
62 63 52 53
43
(6.35)
¼”
(12.7)
½”
2-4
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
Revision Y05-02 Service Manual - K DCI
3. RATING CONDITIONS
CONTENTSCONTENTS
Standard conditions in accordance with ISO 5151, ISO 13253 (for ducted units) and EN 14511.

RATING CONDITIONS

Cooling:
Indoor: 27 Outdoor: 35
o
C DB 19oC WB
o
C DB
Heating:
Indoor: 20 Outdoor: 7
o
C DB
o
C DB 6oC WB
3.1 Operating Limits
Cooling
Heating
Voltage
Upper limit
Lower limit 21oC DB 15oC WB -10oC DB
Upper limit
Lower limit 10oC DB -15oC DB -16oC WB
1PH
3PH N/A
Indoor Outdoor
32oC DB 23oC WB 46oC DB
27oC DB 24oC DB 18oC WB
198 – 264 V
Revision Y05-02Service Manual - K DCI
3-1
4. OUTLINE DIMENSIONS
CONTENTSCONTENTS
4.1 Indoor Unit: K 25, 35, 35S, 50 DCI

OUTLINE DIMENSIONS

4.2
Outdoor Unit: ONG 25, 35, 35S, 50 DCI
Revision Y05-02Service Manual - K DCI
4-1
5. PERFORMANCE DATA
CONTENTSCONTENTS
5.1 K25 DCI
5.1.1 Cooling Capacity (kW) - Run Mode

PERFORMANCE DATA

OD COIL
ENTERING AIR DB
TEMPERATURE [C
-10 - 20
(protection range)
25
30
35
40
46
ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC]
DATA
0
]
22/15 24/17 27/19 29/21 32/23
TC 80 - 110 % of nominal SC 80 - 105 % of nominal
PI 25 - 50 % of nominal TC 2.42 2.57 2.73 2.89 3.05 SC 2.09 2.13 2.18 2.22 2.26
PI 0.46 0.47 0.48 0.49 0.50 TC 2.30 2.46 2.62 2.77 2.93 SC 2.04 2.08 2.12 2.17 2.21
PI 0.52 0.53 TC 2.18 2.34
0.54
2.50
0.54 0.55
2.66 2.82
SC 1.98 2.03 2.07 2.11 2.16
PI 0.57 0.58 TC 2.07 2.23
0.59
2.38
0.60 0.61
2.54 2.70
SC 1.93 1.97 2.02 2.06 2.10
PI 0.63 0.64 0.64 0.65 0.66 TC 1.93 2.09 2.24 2.40 2.56 SC 1.87 1.91 1.95 2.00 2.04
PI 0.69 0.70 0.71 0.72 0.73
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., ( DB Dry Bulb Temp., (
o
o
C)
C)
ID Indoor OD – Outdoor
5.1.2 Capacity Correction Factors
Cooling Capacity Ratio Vs. Outdoor Temperature
1.2
1.1
1
0.9
0.8
0.7
Capacity Ration
0.6
0.5
20 25 30 35 40 45
Outdoor T emperature [deg C]
Revision Y05-02Service Manual - K DCI
5-1
PERFORMANCE DATA
CONTENTSCONTENTS
5.1.3 Heating Capacity (kW) - Run Mode
ID COIL ENTERING AIR DB TEMPERATURE [ºC]
OD COIL
ENTERING AIR DB/
WB TEMPERATURE
[ºC]
-15/-16
-10/-12
-7/-8
-1/-2
2/1
7/6
10/9
15/12
15-24
(Protection Range)
DATA 15 20 25
TC 2.16 2.01 1.86
PI 0.55 0.60 0.66
TC 2.41 2.26 2.11
PI 0.66 0.72 0.77
TC 2.59 2.44 2.29
PI 0.75 0.80 0.86
TC 2.68 2.53 2.38
PI 0.79 0.84 0.90
TC 2.75 2.59 2.44
PI 0.82
TC 3.55
PI 0.86
TC 3.75
PI 0.91 0.97 1.02
TC 3.94 3.79 3.64
PI 0.96 1.02 1.07
TC 85 - 105 % of nominal
PI 80 - 120 % of nominal
0.87
3.40
0.92
3.60
0.93
3.25
0.97
3.44
LEGEND
TC – Total Cooling Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., ( DB Dry Bulb Temp., (
o
o
C)
C)
ID Indoor OD – Outdoor
5.1.4 Capacity Correction Factors
Heating Capacity Ratio Vs. Outdoor Temperature
1.2
1.1
1
0.9
0.8
0.7
Capacity Rat ion
0.6
0.5
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [deg C]
5-2
Revision Y05-02 Service Manual - K DCI
PERFORMANCE DATA
CONTENTSCONTENTS
5.2 Capacity Correction Factor Due to Tubing Length
5.2.1 Cooling
1.01
1.00
0.99
0.98
0.97
0.96
0.95
0.94
Capacity Ratio
0.93
0.92
0.91
3 4 5 6 7 8 9 1011121314151617181920
Tubing Length [m]
5.2.2 Heating
1.02
1.00
0.98
0.96
0.94
Capacity Ratio
0.92
0.90
34567891011121314151617181920
Tubing Length [m]
Revision Y05-02Service Manual - K DCI
5-3
PERFORMANCE DATA
CONTENTSCONTENTS
5.3 K35 DCI
5.3.1 Cooling Capacity (kW) - Run Mode
OD COIL
ENTERING AIR DB
TEMPERATURE [ºC]
-10 - 20
(protection range)
25
30
35
40
46
ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC]
DATA
22/15 24/17 27/19 29/21 32/23
TC 80 - 110 % of nominal
SC 80 - 105 % of nominal
PI 25 - 50 % of nominal
TC 3.38 3.60 3.83 4.05 4.27 SC 2.65 2.70 2.75 2.81 2.86
PI 0.75 0.76 0.78 0.79 0.80
TC 3.22 3.44 3.66 3.88 4.11 SC 2.58 2.63 2.69 2.74 2.79
PI 0.83 0.85
TC 3.06 3.28
0.86
3.50
0.88 0.89
3.72 3.94
SC 2.51 2.57 2.62 2.67 2.73
PI 0.92 0.94
TC 2.89 3.12
0.95
3.34
0.96 0.98
3.56 3.78
SC 2.45 2.50 2.55 2.61 2.66
PI 1.01 1.02 1.04 1.05 1.07
TC 2.70 2.92 3.14 3.36 3.58 SC 2.37 2.42 2.47 2.53 2.58
PI 1.11 1.13 1.14 1.16 1.17
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., ( DB Dry Bulb Temp., (
o
o
C)
C)
ID Indoor
5.3.2 Capacity Correction Factors
Cooling Capacity Ratio Vs. Outdoor Temperature
1.2
1.1
1
0.9
0.8
0.7
Capacity Rat ion
0.6
0.5
20 25 30 35 40 45
Outdoor T emperature [deg C]
5-4
Revision Y05-02 Service Manual - K DCI
5.3.3 Heating Capacity (kW) - Run Mode
CONTENTSCONTENTS
ID COIL ENTERING AIR DB TEMPERATURE [ºC]
OD COIL
ENTERING AIR DB/
WB TEMPERATURE
[ºC]
-15/-16
-10/-12
-7/-8
-1/-2
2/1
7/6
10/9
15/12
15-24
(Protection Range)
DATA 15 20 25
TC 2.74 2.55 2.35
PI 0.80 0.88 0.96
TC 3.05 2.86 2.66
PI 0.96 1.04 1.12
TC 3.28 3.09 2.90
PI 1.09 1.17 1.25
TC 3.39 3.20 3.01
PI 1.15 1.23 1.31
TC 3.47 3.28 3.09
PI 1.19
TC 4.49
PI 1.25
TC 4.74
PI 1.32 1.40 1.49
TC 4.99 4.80 4.60
PI 1.40 1.48 1.56
TC 85 - 105 % of nominal
PI 80 - 120 % of nominal
1.27
4.30
1.33
4.55
PERFORMANCE DATA
1.35
4.11
1.41
4.36
LEGEND
TC – Total Cooling Capacity, kW PI – Power Input, kW
o
WB – Wet Bulb Temp., ( DB Dry Bulb Temp., (
o
C)
C) ID Indoor OD – Outdoor
5.3.4 Capacity Correction Factors
Heating Capacity Ratio Vs. Outdoor Temperature
1.2
1.1
1
0.9
0.8
0.7
Capacity Rat ion
0.6
0.5
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [de g C]
Revision Y05-02Service Manual - K DCI
5-5
PERFORMANCE DATA
CONTENTSCONTENTS
5.4 Capacity Correction Factor Due to Tubing Length
5.4.1 Cooling
1.01
1.00
0.99
0.98
0.97
0.96
0.95
0.94
Capacity Ratio
0.93
0.92
0.91
3 4 5 6 7 8 9 1011121314151617181920
Tubing Length [m]
5.4.2 Heating
1.02
1.00
0.98
0.96
0.94
Capacity Ratio
0.92
0.90
3 4 5 6 7 8 9 1011121314151617181920
Tubing Length [m]
5-6
Revision Y05-02 Service Manual - K DCI
5.5 K35S DCI
CONTENTSCONTENTS
5.5.1 Cooling Capacity (kW) - Run Mode
PERFORMANCE DATA
OD COIL
ENTERING AIR DB
TEMPERATURE [ºC]
-10 - 20
(protection range)
25
30
35
40
46
ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC]
DATA
22/15 24/17 27/19 29/21 32/23
TC 80 - 110 % of nominal SC 80 - 105 % of nominal
PI 25 - 50 % of nominal TC 3.38 3.60 3.83 4.05 4.27 SC 2.65 2.70 2.75 2.81 2.86
PI 0.68 0.70 0.71 0.72 0.74 TC 3.22 3.44 3.66 3.88 4.11 SC 2.58 2.63 2.69 2.74 2.79
PI 0.76 0.78 TC 3.06 3.28
0.79
3.50
0.80 0.82
3.72 3.94
SC 2.51 2.57 2.62 2.67 2.73
PI 0.84 0.86 TC 2.89 3.12
0.87
3.34
0.88 0.90
3.56 3.78
SC 2.45 2.50 2.55 2.61 2.66
PI 0.92 0.94 0.95 0.96 0.98 TC 2.70 2.92 3.14 3.36 3.58 SC 2.37 2.42 2.47 2.53 2.58
PI 1.02 1.03 1.05 1.06 1.07
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., ( DB Dry Bulb Temp., (
o
o
C)
C)
ID Indoor OD – Outdoor
5.5.2 Capacity Correction Factors
Cooling Capacity Ratio Vs. Outdoor Temperature
1.2
1.1
1
0.9
0.8
0.7
Capacity Rat ion
0.6
0.5
20 25 30 35 40 45
Outdoor Te mperature [deg C]
Revision Y05-02Service Manual - K DCI
5-7
PERFORMANCE DATA
CONTENTSCONTENTS
5.5.3 Heating Capacity (kW) - Run Mode
ID COIL ENTERING AIR DB TEMPERATURE [ºC]
OD COIL
ENTERING AIR DB/
WB TEMPERATURE
[ºC]
-15/-16
-10/-12
-7/-8
-1/-2
2/1
7/6
10/9
15/12
15-24
(Protection Range)
DATA 15 20 25
TC 2.86 2.66 2.46
PI 0.71 0.78 0.85
TC 3.19 2.99 2.79
PI 0.85 0.93 1.00
TC 3.43 3.23 3.03
PI 0.96 1.03 1.11
TC 3.55 3.35 3.15
PI 1.02 1.09 1.16
TC 3.63 3.43 3.23
PI 1.05
TC 4.70
PI 1.11
TC 4.96
PI 1.17 1.25 1.32
TC 5.22 5.02 4.82
PI 1.24 1.31 1.38
TC 85 - 105 % of nominal
PI 80 - 120 % of nominal
1.13
4.50
1.18
4.76
1.20
4.30
1.25
4.56
LEGEND
TC – Total Cooling Capacity, kW PI – Power Input, kW
o
WB – Wet Bulb Temp., ( DB Dry Bulb Temp., (
o
C)
C) ID Indoor OD – Outdoor
5.5.4 Capacity Correction Factors
Heating Capacity Ratio Vs. Outdoor Temperature
1.2
1.1
1
0.9
0.8
0.7
Capacity Ration
0.6
0.5
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [deg C]
5-8
Revision Y05-02 Service Manual - K DCI
PERFORMANCE DATA
CONTENTSCONTENTS
15.6 Capacity Correction Factor Due to Tubing Length
5.6.1 Cooling
1.01
1.00
0.99
0.98
0.97
0.96
0.95
0.94
Capacity Ratio
0.93
0.92
0.91
3 4 5 6 7 8 9 1011121314151617181920
Tubing Length [m]
5.6.2 Heating
1.02
1.00
0.98
0.96
0.94
Capacity Ratio
0.92
0.90
3 4 5 6 7 8 9 1011121314151617181920
Tubing Length [m]
Revision Y05-02Service Manual - K DCI
5-9
PERFORMANCE DATA
CONTENTSCONTENTS
5.7 K50 DCI
5.7.1 Cooling Capacity (kW) - Run Mode
OD COIL
ENTERING AIR DB
TEMPERATURE [ºC]
-10 - 20
(protection range)
25
30
35
40
46
ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC]
DATA
22/15 24/17 27/19 29/21 32/23
TC 80 - 110 % of nominal SC 80 - 105 % of nominal
PI 25 - 50 % of nominal TC 4.85 5.13 5.42 5.70 5.99 SC 3.30 3.35 3.40 3.45 3.50
PI 1.20 1.23 1.26 1.28 1.31 TC 4.60 4.88 5.17 5.45 5.74 SC 3.17 3.22 3.27 3.32 3.37
PI 1.37 1.40 TC 4.35 4.63
1.42
4.92
1.45 1.48
5.20 5.49
SC 3.04 3.09 3.14 3.19 3.24
PI 1.54 1.56 TC 4.10 4.39
1.59
4.67
1.62 1.64
4.96 5.24
SC 2.91 2.96 3.01 3.06 3.11
PI 1.70 1.73 1.76 1.78 1.81 TC 3.80 4.09 4.37 4.66 4.94 SC 2.76 2.81 2.86 2.91 2.95
PI 1.90 1.93 1.96 1.98 2.01
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., ( DB Dry Bulb Temp., (
o
o
C)
C)
ID Indoor OD – Outdoor
5.7.2 Capacity Correction Factors
Cooling Capacity Ratio Vs. Outdoor Temperature
1.2
1.1
1
0.9
0.8
0.7
Capacity Ration
0.6
0.5
20 25 30 35 40 45
Outdoor Temperature [deg C]
5-10
Revision Y05-02 Service Manual - K DCI
5.7.3 Heating Capacity (kW) - Run Mode
CONTENTSCONTENTS
ID COIL ENTERING AIR DB TEMPERATURE [ºC]
OD COIL ENTERING
AIR DB/WB
TEMPERATURE [ºC]
DATA 15 20 25
PERFORMANCE DATA
-15/-16
-10/-12
-7/-8
-1/-2
2/1
7/6
10/9
15/12
15-24
(Protection Range)
LEGEND
TC 2.66 2.28 1.90
PI 1.15 1.23 1.31
TC 3.52 3.13 2.75
PI 1.30 1.38 1.46
TC 4.16 3.77 3.39
PI 1.41 1.49 1.57
TC 4.47 4.09 3.71
PI 1.46 1.55 1.63
TC 4.69 4.30 3.92
PI 1.50
TC 6.24
PI 1.56
TC 6.56
1.58
5.85
1.64
6.18
1.66
5.47
1.72
5.79
PI 1.59 1.67 1.75
TC 6.88 6.50 6.12
PI 1.62 1.70 1.78
TC 85 - 105 % of nominal
PI 80 - 120 % of nominal
TC – Total Cooling Capacity, kW PI – Power Input, kW
o
WB – Wet Bulb Temp., ( DB Dry Bulb Temp., (
o
C)
C) ID Indoor OD – Outdoor
5.7.4 Capacity Correction Factors
Heating Capacity Ratio Vs. Outdoor Temperature
1.2
1.1
1
0.9
0.8
0.7
0.6
Capacity Rat ion
0.5
0.4
-15 -10 -5 0 5 10 15
Outdoor WB Te mperature [deg C]
Revision Y05-02Service Manual - K DCI
5-11
PERFORMANCE DATA
CONTENTSCONTENTS
5.8 Capacity Correction Factor Due to Tubing Length
5.8.1 Cooling
1.001
1.000
0.999
0.998
0.997
0.996
0.995
Capacity Ratio
0.994
0.993
0 5 10 15 20 25 30 35
Tubing Length[m]
5.8.2 Heating
1.02
1.00
0.98
0.96
0.94
0.92
0.90
Capacity Ratio
0.88
0.86
0 5 10 15 20 25 30 35
Tubing Length[m]
5-12
Revision Y05-02 Service Manual - K DCI
6. PRESSURE CURVES
CONTENTSCONTENTS
6.1 Model: K 25 DCI
6.1.1 Cooling – Test Mode
Suction Pressure Vs.Outdoor Temp' - Cooling
1400
1300
1200
1100
1000
900
800
700
600
Suction Pressure [kPa]
500
10 15 20 25 30 35 40 45

PRESSURE CURVES

Indoor DB/WB
Temp.
22/15
24/17
27/19
29/21
32/23
Discharge Pressure [kPa]
Outdoor DB Temperature [ºC]
Discharge Pressure Vs.Outdoor Temp'- Cooling
4000 3750 3500 3250 3000 2750 2500 2250 2000 1750 1500 1250 1000
10 15 20 25 30 35 40 45
Outdoor DB Temperature [ºC]
Indoor
DB/W B
22/15
24/17
27/19
29/21
32/23
Revision Y05-02Service Manual - K DCI
6-1
PRESSURE CURVES
CONTENTSCONTENTS
6.1.2 Heading – Test Mode
Suction Pressure Vs. Outdoor Temp' - Heating
1300 1200 1100 1000
900 800 700 600 500 400
Suction Pressure [kPa]
300 200
-15 -10 -5 0 5 10 15
Outdoor WB Temperature[ºC]
Indoor DB
15
20
25
Discharge Pressure [kPa]
Discharge Pressure Vs.Outdoor Temp'- Heating
4000 3750 3500 3250 3000 2750 2500 2250 2000 1750 1500 1250 1000
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [ºC]
Indoor DB
15
20
25
6-2
Revision Y05-02 Service Manual - K DCI
6.2 Model: K 35 DCI
CONTENTSCONTENTS
6.2.1 Cooling – Test Mode
Suction Pressure Vs.Outdoor Temp' - Cooling
PRESSURE CURVES
Suction Pressure [kPa]
Discharge Pressure [kPa]
1400
1300
1200
1100
1000
900
800
700
600
500
10 15 20 25 30 35 40 45
Outdoor DB Temperature [ºC]
Discharge Pressure Vs.Outdoor Temp'- Cooling
4000 3750 3500 3250 3000 2750 2500 2250 2000 1750 1500 1250 1000
10 15 20 25 30 35 40 45
Indoor
DB/W B
22/15
24/17
27/19
29/21
32/23
Indoor
DB/WB
22/15
24/17
27/19
29/21
32/23
Outdoor DB Temperature [ºC]
Revision Y05-02Service Manual - K DCI
6-3
PRESSURE CURVES
CONTENTSCONTENTS
6.2.2 Heating – Test Mode
Suction Pressure Vs.Outdoor Temp' - Cooling
Suction Pressure [kPa]
Discharge Pressure [kPa]
1400
1300
1200
1100
1000
900
800
700
600
500
10 15 20 25 30 35 40 45
Outdoor DB Temperature [ºC]
Discharge Pressure Vs.Outdoor Temp'- Cooling
4000 3750 3500 3250 3000 2750 2500 2250 2000 1750 1500 1250 1000
10 15 20 25 30 35 40 45
Indoor
DB/W B
22/15
24/17
27/19
29/21
32/23
Indoor
DB/WB
22/15
24/17
27/19
29/21
32/23
6-4
Outdoor DB Temperature [ºC]
Revision Y05-02 Service Manual - K DCI
6.3 Model: K 35S DCI
CONTENTSCONTENTS
6.3.1 Cooling – Test Mode
Suction Pressure Vs.Outdoor Temp' - Cooling
1400
1300
1200
1100
1000
900
800
700
600
Suction Pressure [kPa]
500
10 15 20 25 30 35 40 45
PRESSURE CURVES
Indoor
DB/WB
22/15
24/17
27/19
29/21
32/23
Discharge Pressure [kPa]
Outdoor DB Temperature[ºC]
Discharge Pressure Vs.Outdoor Temp' - Cooling
4000 3750 3500 3250 3000 2750 2500 2250 2000 1750 1500 1250 1000
10 15 20 25 30 35 40 45
Outdoor DB Temperature[ºC]
Indoor
DB/WB
22/15
24/17
27/19
29/21
32/23
Revision Y05-02Service Manual - K DCI
6-5