Electra DELTA 21ST, GC 18 RC, DELTA 24RC, GC 18 ST, GC 22 ST Service Manual

...
Page 1
DELTA 18-21-24
Indoor Units Outdoor Units
DELTA 18
GC 18
DELTA 21
GC 22
DELTA 24
OU7-24 OU7-24Z
Service Manual
JUNE – 2010
REFRIGERANT
R410A
HEAT PUMP
COOLING ONLY
Page 2
A
LIST OF EFFECTIVE PAGES
SM DELTA 1-E.0 GB
LIST OF EFFECTIVE PAGES
Note: Changes in the pages are indicated by a “Revision#” in the footer of each effected page
(when none indicates no changes in the relevant page). All pages in the following list represent effected/ non effected pages divided by chapters.
Dates of issue for original and changed pages are:
Original ....... 0 ........ JUNE 2010
Total number of pages in this publication is 93 consisting of the following:
Page No.
Revision No. #
Page No.
Revision No. #
Page No.
Revision No. #
Title ....................... 0
A ........................... 0
i ............................. 0
1-1 - 1-3 ................ 0
2-1 - 2-5 ................ 0
3-1 ........................ 0
4-1 - 4-2 ................ 0
5-1 - 5-12 .............. 0
6-1 - 6-5 ................ 0
7-1 ........................ 0
8-1 - 8-6 ................ 0
9-1 ........................ 0
10-1-10-4 .............. 0
11-1 ....................... 0
12-1-12-34 ............ 0
13-1-13-2 .............. 0
14-1-14-24 ............ 0
15-1-15-7 .............. 0
Appendix -A ........... 0
• Zero in this column indicates an original page.
*Due to constant improvements please note that the data on this service manual can be modified with out notice. **Photos are not contractual
Page 3
i
TABLE OF CONTENTS
SM DELTA 1-E.0 GB
Table of Contents
1. INTRODUCTION ...................................................................................................1-1
2. PRODUCT DATA SHEET ......................................................................................2-1
3. RATING CONDITIONS ..........................................................................................3-1
4. OUTLINE DIMENSIONS .......................................................................................4-1
5. PERFORMANCE DATA & PRESSURE CURVES ................................................5-1
6. SOUND LEVEL CHARACTERISTICS ..................................................................6-1
7. ELECTRICAL DATA ..............................................................................................7-1
8. WIRING DIAGRAMS .............................................................................................8-1
9. ELECTRICAL CONNECTIONS .............................................................................9-1
10. REFRIGERATION DIAGRAMS .............................................................................10-1
11. TUBING CONNECTIONS ......................................................................................11-1
12. CONTROL SYSTEM .............................................................................................12-1
13. TROUBLESHOOTING ..........................................................................................13-1
14. EXPLODED VIEWS AND SPARE PARTS LISTS .................................................14-1
15. OPTIONAL ACCESSORIES .................................................................................15-1
16. APPENDIX A .........................................................................................................16-1
Page 4
1-1
INTRODUCTION
SM DELTA 1-E.0 GB
1. INTRODUCTION
1.1 General
The new DELTA split wall mounted is based on the compact range. It comprise the ST (cooling only) and RC (heat pump) models, as follows:
Cooling Only: DELTA 18ST, DELTA 21ST, DELTA 24ST Heat Pump: DELTA 18RC, DELTA 21RC, DELTA 24RC
The indoor DELTA units are available as LED display types, featuring esthetic design, compact dimensions, and low noise operation.
1.2 Main Features
The DELTA series benefits from the most advanced technological innovations, namely:
R410A refrigerant
Micro processor control.
Infrared remote control with LED display.
Indoor large diameter cross flow fan, allowing low operation sound level.
Bended Indoor coil with treated aluminum fins and coating for improved efficiency.
High COP.
Easy access to the interconnecting tubing and wiring connections.
Refrigerant pipes can be connected to the indoor unit from 5 different optional
directions.
The units are equipped.
Water condensate tray is equipped with two optional drain connections.
Automatic treated air sweep.
 Low indoor noise levels.
Easy installation and service.
1.3 Indoor Unit
The indoor unit is wall mounted, and can be easily fitted to many types of residential and commercials applications.
It includes:
Casing with air inlet and outlet grills.
A large-diameter tangential fan.
Bended coil with treated aluminum fins.
Motorized flaps.
3-speed motor with internal protection.
Advanced electronic control box assembly.
Interconnecting wiring terminal block.
Mounting plate.
Page 5
1-2
INTRODUCTION
SM DELTA 1-E.0 GB
1.4 Filtration
The DELTA series presents several types of air filters:
Easily accessible, and re-usable pre-filters (mesh).
Pre-charged electrostatic filter (diposable).
Active carbon filter (optional).
Active Electro Static re-usable filter (optional).
1.5 Control
The microprocessor indoor controller, and an infrared remote control, supplied as standard, provide complete operating function and programming. For further details please refer to the Operation Manual, Appendix A.
1.6 Outdoor Unit
The DELTA outdoor units can be installed as floor or wall mounted units by using a wall supporting bracket. The metal sheets are protected by anti- corrosion paint work allowing long life resistance. All outdoor units are pre-charged. For further information please refer to the Product Data Sheet, Chapter 2.
It includes :
Axial fan.
Outdoor coil with hydrophilic louver fins for RC units.
Compressor mounted in a soundproofed compartment.
Outlet air fan grill.
Service valves” flare” type connection.
Interconnecting wiring terminal block.
1.7 Tubing Connections
Flare type interconnecting tubing can be produced on site. For further details please refer to the Installation Manual, Chapter 11.
1.8 Accessories
ASK (All Season Kit):
For low ambient working conditions in cooling, an ASK can be installed inside the outdoor unit. This kit allows cooling operation down to outdoor temp of -10 oC by gradually controlling the outdoor fan speed motor.
RCW Wall Mounted Remote Control
The RCW remote control is mounted on the wall, and controls the unit either as an infrared remote control or as a wired controller. The wired controller can control up to 10 Indoor units with the same program settings and adjustments. For further details please refer to Optional Accessories, Chapter 15.
1.9 Inbox Documentation
Each unit is supplied with its own installation and operation manuals.
Page 6
1-3
INTRODUCTION
SM DELTA 1-E.0 GB
1.10 Matching Table
1.10.1 R410A
OUTDOOR UNITS
INDOOR UNITS
MODEL
REFRIGER.
DELTA 18 DELTA 21 DELTA 24
GC 18 ST/RC R410A
GC 22 ST/RC R410A
GC 24 ST/RC R410A
OU7-24 R410A
OU7-24Z R410A
The above table lists outdoor units and DELTA indoor units which can be matched together. In addition the listed outdoor units can be matched with other types of indoor units such as cassettes, floor/ceiling. For further information please refer to the relevant Service Manual.
Page 7
2-1
PRODUCT DATA SHEET
SM DELTA 1-E.0 GB
2. PRODUCT DATA SHEET
2.1 DELTA 18 / GC 18 R410A
Model Indoor Unit DELTA- 18 Model Outdoor Unit GC-18
Installation Method of Pipe Flared Characteristics Units Cooling Only Cooling Heating
Capacity
(4)
Btu/hr 18250 18250 18420
kW 5.35 5.35 5.40
Power input
(4)
kW 1.66 1.66 1.56
EER (Cooling) or COP(Heating)
(4)
W/W 3.22 3.22 3.46 Energy efficiency class A A B Power supply V/Hz/Ph 220-240V/50Hz/Single Rated current A 7.5 7 7.1 Starting current A 43 Circuit breaker rating A 15
INDOOR
Fan type & quantity Cross flow*1 Fan speeds H/M/L RPM 1200/1100/1000 Air flow
(1)
H/M/L m3/hr 930/840/750 External static pressure Min-Max Pa N/A Sound power level
(2)
H/M/L dB(A) 56/53/50 Sound pressure level
(3)
H/M/L dB(A) 43/40/37 Moisture removal l/hr 1.8 Condenstate drain tube I.D mm 16 Dimensions WxHxD mm 1060/295/210 Weight kg 14 Package dimensions WxHxD mm 1115/350/260 Packaged weight kg 17 Units per pallet units 16 Stacking height units 8
OUTDOOR
Refrigerant control Capillary tube Compressor type,model Rotary,TOSHIBA PA200X2CS-4KU1 Fan type & quantity Propeller(direct) x 1 Fan speeds H/L RPM 815 Air flow H/L m3/hr 2480 Sound power level H/L dB(A) 68 Sound pressure level
(3)
H/L dB(A) 57 Dimensions WxHxD mm 846/302/690 Weight kg 56 Package dimensions WxHxD mm 990/430/770 Packaged weight kg 61 Units per pallet Units 9 Stacking height units 3 Refrigerant type R410A Refrigerant chargless distance kg/m 1.54kg/7.5m
Additional charge g/m
4mLength10m 1540g 10mLength18m 1690g
18mLength25m 1900g
Connections between
units
Liquid line In.(mm) 1/4"(6.35) Suction line In.(mm) 1/2"(12.7) Max.tubing length m. 25
Max.height difference m. 15 Operation control type Remote control Heating elements kW Others All season kit Factory option
(1)
Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units). and EN 14511
(2)
Airflow in ducted units; at nominal external static pressure.
(3)
Sound power in ducted units is measured at air discharge.
(4)
Sound pressure level measured at 1 meter distance from unit.
Page 8
2-2
PRODUCT DATA SHEET
SM DELTA 1-E.0 GB
2.2 DELTA 21 / GC 22 R410A
Model Indoor Unit DELTA- 21 Model Outdoor Unit GC-22
Installation Method of Pipe Flared Characteristics Units Cooling Only Cooling Heating
Capacity
(4)
Btu/hr 21150 21150 22180
kW 6.2 6.2 6.50
Power input
(4)
kW 2.05 2.05 2.00
EER (Cooling) or COP(Heating)
(4)
W/W 3.02 3.02 3.25 Energy efficiency class B B C Power supply V/Hz/Ph 220-240V/50Hz/Single Rated current A 9.3 9.3 9.7 Starting current A 50 Circuit breaker rating A 20
INDOOR
Fan type & quantity Cross flow*1 Fan speeds H/M/L RPM 1300/1200/1100 Air flow
(1)
H/M/L m3/hr 910/820/740 External static pressure Min-Max Pa 0 Sound power level
(2)
H/M/L dB(A) 60/57/55 Sound pressure level
(3)
H/M/L dB(A) 47/44/42 Moisture removal l/hr 2.3 Condenstate drain tube I.D mm 16 Dimensions WxHxD mm 1060x295x210 Weight kg 15 Package dimensions WxHxD mm 1125x360x280 Packaged weight kg 18 Units per pallet units 16 Stacking height units 8
OUTDOOR
Refrigerant control Capillary tube Compressor type,model Rotary,TOSHIBA PA240X2CS-4KU1 Fan type & quantity Propeller(direct) x 1 Fan speeds H/L RPM 815 Air flow H/L m3/hr 2860 Sound power level H/L dB(A) 69 Sound pressure level
(3)
H/L dB(A) 59 Dimensions WxHxD mm 846/302/690 Weight kg 56 Package dimensions WxHxD mm 990/720/430 Packaged weight kg 61 Units per pallet Units 9 Stacking height units 3 levels Refrigerant type R410A Refrigerant chargless distance kg/m 2.0kg/7.5m
Additional charge g/m
4mLength10m:+0g; 10mLength15m:+330g; 15mLength20m:+460g
Connections between
units
Liquid line In.(mm) 3/8"(9.53) Suction line In.(mm) 5/8"(15.88) Max.tubing length m. Max 20
Max.height difference m. Max 15 Operation control type Remote control Heating elements kW 1.65/0.9 Others
(1)
Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units). and EN 14511
(2)
Airflow in ducted units; at nominal external static pressure.
(3)
Sound power in ducted units is measured at air discharge.
(4)
Sound pressure level measured at 1 meter distance from unit.
Page 9
2-3
PRODUCT DATA SHEET
SM DELTA 1-E.0 GB
2.3 DELTA 24 / OU7-24 R410A
Model Indoor Unit DELTA- 24 Model Outdoor Unit OU7-24
Installation Method of Pipe Flared Characteristics Units Cooling Only Cooling Heating
Capacity
(4)
Btu/hr 23100 23100 24150
kW 6.77 6.77 7.08
Power input
(4)
kW 2.24 2.24 2.35
EER (Cooling) or COP(Heating)
(4)
W/W 3.02 3.02 2.95 Energy efficiency class B B D Power supply V/Hz/Ph 220-240V/50Hz/Single Rated current A 10.5 10.5 11.0 Starting current A 63 Circuit breaker rating A 20
INDOOR
Fan type & quantity Cross flow*1 Fan speeds H/M/L RPM 1300/1200/1100 Air flow
(1)
H/M/L m3/hr 910/820/740 External static pressure Min-Max Pa N/A Sound power level
(2)
H/M/L dB(A) 60/57/55 Sound pressure level
(3)
H/M/L dB(A) 47/44/42 Moisture removal l/hr 2.3 Condenstate drain tube I.D mm 16 Dimensions WxHxD mm 1060x295x210 Weight kg 15 Package dimensions WxHxD mm 1125x360x280 Packaged weight kg 18 Units per pallet units 16 Stacking height units 8
OUTDOOR
Refrigerant control Capillary tube Compressor type,model Rotary Fan type & quantity AXIAL*1 Fan speeds H/L RPM 850 720 Air flow H/L m3/hr 3100 2600 Sound power level H/L dB(A) 67 62 Sound pressure level
(3)
H/L dB(A) 58 54 Dimensions WxHxD mm 900/680/340 Weight kg 74 Package dimensions WxHxD mm 985/730/406 Packaged weight kg 77 Units per pallet Units 6 Stacking height units 2 levels Refrigerant type R410A Refrigerant chargless distance kg/m 2.035kg/12.5m
Additional charge g/m
12.5m<dd 350g<15m; 15m
<dd 1040g<20m;
Connections between
units
Liquid line In.(mm) 3/8"(9.53) Suction line In.(mm) 5/8"(15.88) Max.tubing length m. Max 20
Max.height difference m. Max 15 Operation control type Remote control Heating elements kW Others All season kit Factory option
(1)
Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units). and EN 14511
(2)
Airflow in ducted units; at nominal external static pressure.
(3)
Sound power in ducted units is measured at air discharge.
(4)
Sound pressure level measured at 1 meter distance from unit.
Page 10
2-4
PRODUCT DATA SHEET
SM DELTA 1-E.0 GB
2.4 DELTA 24 / OU7-24Z R410A
Model Indoor Unit DELTA- 24 Model Outdoor Unit OU7-24Z
Installation Method of Pipe Flared Characteristics Units Cooling Only Cooling Heating
Capacity
(4)
Btu/hr 23100 23100 24150
kW 6.77 6.77 7.08
Power input
(4)
kW 2.24 2.24 2.35
EER (Cooling) or COP(Heating)
(4)
W/W 3.02 3.02 2.95 Energy efficiency class B B D Power supply V/Hz/Ph 220-240V/50Hz/Single Rated current A 10.5 10.5 11.0 Starting current A 63 Circuit breaker rating A 20
INDOOR
Fan type & quantity Cross flow*1 Fan speeds H/M/L RPM 1300/1200/1100 Air flow
(1)
H/M/L m3/hr 910/820/740 External static pressure Min-Max Pa N/A Sound power level
(2)
H/M/L dB(A) 60/57/55 Sound pressure level
(3)
H/M/L dB(A) 47/44/42 Moisture removal l/hr 2.3 Condenstate drain tube I.D mm 16 Dimensions WxHxD mm 1060x295x210 Weight kg 15 Package dimensions WxHxD mm 1125x360x280 Packaged weight kg 18 Units per pallet units 16 Stacking height units 8
OUTDOOR
Refrigerant control Capillary tube Compressor type,model Rotary Fan type & quantity AXIAL*1 Fan speeds H/L RPM 850 720 Air flow H/L m3/hr 3100 2600 Sound power level H/L dB(A) 67 62 Sound pressure level
(3)
H/L dB(A) 58 54 Dimensions WxHxD mm 900/680/340 Weight kg 64 Package dimensions WxHxD mm 985/730/406 Packaged weight kg 67 Units per pallet Units 6 Stacking height units 2 levels Refrigerant type R410A Refrigerant chargless distance kg/m 1.7kg / 7.5m
Additional charge g/m 7.5m<dd 30g / <15m;
Connections between
units
Liquid line In.(mm) 3/8"(9.53) Suction line In.(mm) 5/8"(15.88) Max.tubing length m. Max 15
Max.height difference m. Max 7 Operation control type LCD Remote control Heating elements kW Others
(1)
Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units). and EN 14511
(2)
Airflow in ducted units; at nominal external static pressure.
(3)
Sound power in ducted units is measured at air discharge.
(4)
Sound pressure level measured at 1 meter distance from unit.
Page 11
2-5
PRODUCT DATA SHEET
SM DELTA 1-E.0 GB
2.4 DELTA 24 / OU7-24T R410A
Model Indoor Unit DELTA- 24 Model Outdoor Unit OU7-24T
Installation Method of Pipe Flared Characteristics Units Cooling Only Cooling Heating
Capacity
(4)
Btu/hr 23220 23220 25130
kW 6.81 6.81 7.37
Power input
(4)
kW 2.26 2.26 2.4
EER (Cooling) or COP(Heating)
(4)
W/W 3.02 3.02 3.07 Energy efficiency class B B D Power supply V/Hz/Ph 400V/50Hz/3N Rated current A 4.1×3 4.1×3 4.4×3 Starting current A 55 Circuit breaker rating A 10×3
INDOOR
Fan type & quantity Cross flow*1 Fan speeds H/M/L RPM 1300/1200/1100 Air flow
(1)
H/M/L m3/hr 990/930/840 External static pressure Min-Max Pa N/A Sound power level
(2)
H/M/L dB(A) 58/55/53 Sound pressure level
(3)
H/M/L dB(A) 45/42/40 Moisture removal l/hr 2.3 Condenstate drain tube I.D mm 16 Dimensions WxHxD mm 1060/295/210 Weight kg 15 Package dimensions WxHxD mm 1115/350/260 Packaged weight kg 18 Units per pallet units 16 Stacking height units 8
OUTDOOR
Refrigerant control Capillary tube Compressor type,model Rotary Fan type & quantity AXIAL*1 Fan speeds H/L RPM 850 720 Air flow H/L m3/hr 3100 2600 Sound power level H/L dB(A) 67 62 Sound pressure level
(3)
H/L dB(A) 58 54 Dimensions WxHxD mm 900/680/340 Weight kg 74 Package dimensions WxHxD mm 985/730/406 Packaged weight kg 74 Units per pallet Units 6 Stacking height units 2 levels Refrigerant type R410A Refrigerant chargless distance kg/m 2.035kg / 12.5m
Additional charge g/m
12.5m<dd 350g <15m;
12.5m<Add 1040g<20m
Connections between
units
Liquid line In.(mm) 3/8"(9.53) Suction line In.(mm) 5/8"(15.88) Max.tubing length m. Max 20
Max.height difference m. Max 15 Operation control type LCD Remote control Heating elements kW Others
All season kit Factory option
(1)
Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units). and EN 14511
(2)
Airflow in ducted units; at nominal external static pressure.
(3)
Sound power in ducted units is measured at air discharge.
(4)
Sound pressure level measured at 1 meter distance from unit.
Page 12
3-1
RATING CONDITIONS
SM DELTA 1-E.0 GB
3. RATING CONDITIONS
Standard conditions in accordance with ISO 5151, ISO 13253 (for ducted units) and EN 14511.
Cooling:
Indoor: 27
o
C DB 19oC WB
Outdoor: 35
o
C DB
Heating:
Indoor: 20
o
C DB
Outdoor: 7
o
C DB 6oC WB
3.1 Operating Limits
3.1.1 R410A
Indoor Outdoor
Cooling
Upper limit
32
o
C DB 23oC WB 46oC DB
Lower limit 21
o
C DB 15oC WB 21oC DB
Heating
Upper limit 27
o
C DB 24oC DB 18oC WB
Lower limit 20
o
C DB -9oC DB -10oC WB
Voltage
1PH 198 – 264 V
3PH 360 – 440 V
Page 13
4-1
OUTLINE DIMENSIONS
SM DELTA 1-E.0 GB
4. OUTLINE DIMENSIONS
4.1 Indoor Unit: DELTA 18, 21, 24
4.2
Outdoor Unit: GC 18, 22
Page 14
4-2
OUTLINE DIMENSIONS
SM DELTA 1-E.0 GB
4.3 Outdoor Unit: OU7-24, OU7-24Z
Page 15
5-1
PERFORMANCE DATA & PRESSURE CURVES
SM DELTA 1-E.0 GB
5.1 DELTA18 GC18 R410A
5.1.1 Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OU COIL (°C)
DATA
ENTERING AIR WB/DB ID COIL ( °C)
15/21 17/24 19/27 21/29 23/32
15
(1)
TC
5.64 5.84 5.98 6.12 6.21
SC
3.87 4.03 4.19 4.30 4.38
PI
1.18 1.18 1.18 1.18 1.19
20
(1)
TC
5.46 5.75 5.93 6.07 6.20
SC
3.79 4.00 4.17 4.28 4.36
PI
1.28 1.28 1.29 1.29 1.30
25
TC
5.16 5.57 5.86 6.04 6.18
SC
3.69 3.92 4.13 4.25 4.33
PI
1.38 1.39 1.40 1.41 1.42
30
TC
4.83 5.26 5.68 5.88 6.05
SC
3.58 3.80 4.04 4.16 4.24
PI
1.49 1.51
1.52
1.54 1.55
35
TC
4.47 4.85
5.35
5.62 5.88
SC
3.40 3.65 3.95 4.06 4.14
PI
1.61 1.63
1.66
1.67 1.68
40
TC
4.06 4.42
4.83
5.28 5.55
SC
3.21 3.45 3.74 3.86 3.93
PI
1.73 1.76 1.79 1.81 1.83
46
TC
3.53 3.86 4.24 4.68 5.05
SC
2.95 3.16 3.41 3.53 3.60
PI
1.89 1.92 1.97 1.99 2.02
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C) ID – Indoor OU – Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15).
5. PERFORMANCE DATA & PRESSURE CURVES
Page 16
5-2
PERFORMANCE DATA & PRESSURE CURVES
SM DELTA 1-E.0 GB
5.1.2 Heating Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR DB ID COIL ( °C)
15 20 25
ENTERING AIR
WB OU COIL ( °C)
TH PI TH PI TH PI
-10 2.84 1.25 2.73 1.33 2.62 1.40
-7 3.05 1.28 2.94 1.35 2.84 1.42
-2 3.24 1.29 3.13 1.37 3.02 1.45 2 3.94 1.36
3.78 1.44
3.62 1.53
6 5.56 1.46 5.40 1.56 5.21 1.66
10 6.05 1.54
5.89 1.65
5.72 1.76 15 6.53 1.61 6.37 1.73 6.21 1.84 20 6.89 1.65 6.72 1.79 6.53 1.93
*
the above chart includes the weighted deicing infleuence.
LEGEND
TH – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C) ID – Indoor OU – Outdoor
5.2 Capacity Correction Factor Due to Tubing Length
5.2.1 Cooling
TOTAL TUBING LENGTH
3m
7.5m
10m 15m 20m 25m 30m 40m 50m
1.02
1
0.99 0.975 0.965 0.950 --- --- ---
*
Minimum recommended tubing length between indoor and outdoor units is 3m.
5.2.2 Heating
TOTAL TUBING LENGTH
3m
7.5m
10m 15m 20m 25m 30m 40m 50m
1.05
1
1 0.993 0.988 0.978 --- --- ---
*
Minimum recommended tubing length between indoor and outdoor units is 3m.
Page 17
5-3
PERFORMANCE DATA & PRESSURE CURVES
SM DELTA 1-E.0 GB
5.3 Pressure Curves.
5.3.1 Cooling.
Suction Pressure VS.Outdoor Temp
6.0
6.5
7.0
7.5
8.0
8.5
9.0
9.5
10.0
10.5
11.0
11.5
12.0
15 20 25 30 35 40 46
Outdoor Temp.(DB oC )
Suction Pressure (Bar[g])
15/21(W B/DB ºC) 17/24(W B/DB ºC) 19/27(W B/DB ºC) 21/29(W B/DB ºC) 23/32(W B/DB ºC)
Discharge Pressure VS.Outdoor Temp
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
15 20 25 30 35 40 46
Outdoor Temp.(DB oC )
Discharge Pressure (Bar[g])
15/21(W B/DB ºC) 17/24(W B/DB ºC) 19/27(W B/DB ºC) 21/29(W B/DB ºC) 23/32(W B/DB ºC)
Page 18
5-4
PERFORMANCE DATA & PRESSURE CURVES
SM DELTA 1-E.0 GB
5.3.2 Heating.
Suction Pressure VS.Outdoor Temp
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
-10-5 0 5 101520
Outdoor Temp.( WB oC )
Suction Pressure(Bar[g])
15 DB (ºC)
20 DB (ºC)
25 DB (ºC)
Discharge Pressure VS.Outdoor Temp
14
16
18
20
22
24
26
28
30
32
34
36
-10-5 0 5 101520
Outdoor Temp.( WB oC )
Discharge Pressure(Bar[g])
25 DB (ºC)
20 DB (ºC)
15 DB (ºC)
Page 19
5-5
PERFORMANCE DATA & PRESSURE CURVES
SM DELTA 1-E.0 GB
5.4 DELTA21 GC21 R410A
5.4.1 Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OU COIL (°C)
DATA
ENTERING AIR WB/DB ID COIL ( °C)
15/21 17/24 19/27 21/29 23/32
15
(1)
TC
6.53 6.77 6.93 7.09 7.20
SC
4.45 4.64 4.82 4.94 5.03
PI
1.45 1.46 1.46 1.46 1.47
20
(1)
TC
6.32 6.66 6.87 7.04 7.19
SC
4.36 4.59 4.79 4.92 5.01
PI
1.58 1.58 1.59 1.60 1.60
25
TC
5.98 6.46 6.79 7.00 7.17
SC
4.25 4.51 4.75 4.89 4.98
PI
1.71 1.72 1.73 1.74 1.75
30
TC
5.59 6.09 6.58 6.81 7.02
SC
4.11 4.37 4.65 4.78 4.87
PI
1.84 1.87
1.88
1.90 1.91
35
TC
5.18 5.62
6.20
6.51 6.82
SC
3.91 4.19 4.54 4.67 4.76
PI
1.98 2.02
2.05
2.07 2.08
40
TC
4.71 5.13
5.59
6.12 6.43
SC
3.69 3.97 4.29 4.43 4.52
PI
2.14 2.17 2.21 2.24 2.26
46
TC
4.09 4.47 4.91 5.43 5.85
SC
3.40 3.64 3.92 4.05 4.14
PI
2.34 2.37 2.43 2.46 2.49
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C) ID Indoor OU – Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15).
Page 20
5-6
PERFORMANCE DATA & PRESSURE CURVES
SM DELTA 1-E.0 GB
5.4.2 Heating Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR DB ID COIL ( °C)
15 20 25
ENTERING AIR
WB OU COIL ( °C)
TH PI TH PI TH PI
-10
3.41 1.60 3.28 1.70 3.15 1.79
-7 3.67 1.64 3.54 1.73 3.41 1.82
-2 3.90 1.66 3.77 1.76 3.64 1.86 2 4.75 1.74
4.55 1.85
4.36 1.96
6 6.70 1.87 6.50 2.00 6.27 2.12
10 7.28 1.97
7.09 2.11
6.89 2.26
15 7.87 2.06 7.67 2.22 7.48 2.36 20 8.29 2.12 8.09 2.30 7.87 2.48
*
the above chart includes the weighted deicing infleuence.
LEGEND
TH – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C) ID Indoor OU – Outdoor
5.5 Capacity Correction Factor Due to Tubing Length
5.5.1 Cooling
TOTAL TUBING LENGTH
3m
7.5m
10m 15m 20m 25m 30m 40m 50m
1.02
1
0.961 0.950 --- --- --- --- ---
*
Minimum recommended tubing length between indoor and outdoor units is 3m.
5.5.2 Heating
TOTAL TUBING LENGTH
3m
7.5m
10m 15m 20m 25m 30m 40m 50m
1.04
1
0.975 0.961 --- --- --- --- ---
*
Minimum recommended tubing length between indoor and outdoor units is 3m.
Page 21
5-7
PERFORMANCE DATA & PRESSURE CURVES
SM DELTA 1-E.0 GB
5.6 Pressure Curves.
5.6.1 Cooling.
Page 22
5-8
PERFORMANCE DATA & PRESSURE CURVES
SM DELTA 1-E.0 GB
5.6.2 Heating.
Page 23
5-9
PERFORMANCE DATA & PRESSURE CURVES
SM DELTA 1-E.0 GB
5.7
DELTA24 / OU7- 24, DELTA24 / OU7-24Z 1PH/3PH R410A
5.7.1 Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OU COIL (°C)
DATA
ENTERING AIR WB/DB ID COIL ( °C)
15/21 17/24 19/27 21/29 23/32
15
(1)
TC
7.14 7.39 7.57 7.74 7.86
SC
4.80 5.00 5.20 5.33 5.43
PI
1.59 1.59 1.59 1.60 1.61
20
(1)
TC
6.90 7.28 7.51 7.68 7.85
SC
4.70 4.96 5.17 5.31 5.41
PI
1.72 1.73 1.74 1.75 1.75
25
TC
6.53 7.05 7.42 7.64 7.83
SC
4.58 4.86 5.13 5.28 5.37
PI
1.86 1.88 1.89 1.90 1.91
30
TC
6.11 6.65 7.19 7.44 7.66
SC
4.44 4.72 5.02 5.16 5.26
PI
2.01 2.04
2.06
2.07 2.09
35
TC
5.66 6.14
6.77
7.11 7.45
SC
4.22 4.52 4.90 5.04 5.14
PI
2.17 2.20
2.24
2.26 2.27
40
TC
5.14 5.60
6.11
6.68 7.02
SC
3.98 4.28 4.64 4.78 4.88
PI
2.34 2.37 2.41 2.44 2.47
46
TC
4.46 4.88 5.37 5.93 6.39
SC
3.66 3.93 4.23 4.37 4.47
PI
2.55 2.59 2.65 2.69 2.72
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C) ID Indoor OU – Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15).
Page 24
5-10
PERFORMANCE DATA & PRESSURE CURVES
SM DELTA 1-E.0 GB
5.7.2 Heating Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR DB ID COIL ( °C)
15 20 25
ENTERING AIR
WB OU COIL ( °C)
TH PI TH PI TH PI
-10 3.72 1.88 3.58 2.00 3.43 2.10
-7 4.00 1.93 3.86 2.03 3.72 2.14
-2 4.25 1.95 4.11 2.07 3.96 2.19 2 5.17 2.04
4.96 2.17
4.74 2.30
6 7.29 2.20 7.08 2.35 6.83 2.50
10 7.93 2.32
7.72 2.48
7.50 2.65 15 8.57 2.42 8.35 2.61 8.14 2.77 20 9.03 2.49 8.81 2.70 8.57 2.91
*
the above chart includes the weighted deicing infleuence.
LEGEND
TH – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C) ID Indoor OU – Outdoor
5.8 Capacity Correction Factor Due to Tubing Length
5.8.1 Cooling
TOTAL TUBING LENGTH
3m
7.5m
10m 15m 20m 25m 30m 40m 50m
1.01
1
0.980 0.970 0.960 --- --- --- ---
*
Minimum recommended tubing length between indoor and outdoor units is 3m.
5.8.2 Heating
TOTAL TUBING LENGTH
3m
7.5m
10m 15m 20m 25m 30m 40m 50m
1.02
1
0.990 0.990 0.980 --- --- --- ---
*
Minimum recommended tubing length between indoor and outdoor units is 3m.
Page 25
5-11
PERFORMANCE DATA & PRESSURE CURVES
SM DELTA 1-E.0 GB
5.9 Pressure Curves.
5.9.1 Cooling.
Suction Pressure VS.Outdoor Temp
5
6
7
8
9
10
11
12
15 20 25 30 35 40 46
Outdoor Temp.(DB oC )
Suction Pressure (Bar[g])
21/15(DB/WB ºC) 24/17(DB/W B ºC) 27/19(DB/WB ºC) 29/21(DB/WB ºC) 32/23(DB/WB ºC)
Discharge Pressure VS.Outdoor Temp
14
16
18
20
22
24
26
28
30
32
34
36
38
40
15 20 25 30 35 40 46
Outdoor Temp.(DB oC )
Discharge Pressure (Barg])
21/15(DB/WB ºC) 24/17(DB/W B ºC) 27/19(DB/WB ºC) 29/21(DB/W B ºC) 32/23(DB/W B ºC)
Page 26
5-12
PERFORMANCE DATA & PRESSURE CURVES
SM DELTA 1-E.0 GB
5.9.2 Heating.
Suction Pressure VS.Outdoor Temp
3
4
5
6
7
8
9
10
11
12
-10 -5 0 5 10 15 20
Outdoor Temp.( WB oC )
Suction Pressure(Bar[g])
15 DB (ºC)
20 DB (ºC)
25 DB (ºC)
Discharge Pressure VS.Outdoor Temp
14
16
18
20
22
24
26
28
30
32
34
36
38
40
-10-5 0 5 101520
Outdoor Temp.( WB oC )
Discharge Pressure(Bar[g])
25 DB (ºC)
20 DB (ºC)
15 DB (ºC)
Page 27
6-1
SOUND LEVEL CHARACTERISTICS
SM DELTA 1-E.0 GB
6. SOUND LEVEL CHARACTERISTICS
6.1 Sound Pressure Level
6.2 Sound Pressure Level Spectrum
(Measured as Figure 1)
FAN SPEED LINE
HI
ME
LO
0.8m
Mic.
Unit
Wall
BAND CENTER FREQUENCIES, Hz
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
DELTA 24
DELTA 18 DELTA 21
Figure 1
Page 28
6-2
SOUND LEVEL CHARACTERISTICS
SM DELTA 1-E.0 GB
6.3 Outdoor units
6.4 Sound Pressure Level Spectrum (Measured as Figure 2)
GC 18 Cooling GC 18 Heating
GC 22 Cooling GC 22 Heating
Mic.
Unit
Ground
BAND CENTER FREQUENCIES, Hz
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
Figure 2
Page 29
6-3
SOUND LEVEL CHARACTERISTICS
SM DELTA 1-E.0 GB
Sound Pressure Level Spectrum (Measured as Figure 2)
OU7- 24 Z Cooling OU7- 24Z Heating
OU7- 24 Cooling OU7- 24 Heating
BAND CENTER FREQUENCIES, Hz
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
Page 30
7-1
ELECTRICAL DATA
SM DELTA 1-E.0 GB
7. ELECTRICAL DATA
7.1 Single Phase Units
MODEL DELTA 18 DELTA 21/24 DELTA 21/24
Power Supply
To indoor To Outdoor To Outdoor
1PH-230V-50Hz 1PH-230V-50Hz 3PH-400V-50Hz
Max Current, A 11.1 14 3×6
Circuit Breaker,A 15 20 3×10
Power Supply Wiring No. X Cross Section mm
2
3×1.5 mm
2
3×2.5 mm
2
5×1.5 mm
2
Interconnecting Cable RC Model No. X Cross Section mm
2
5×1.5 mm2 + 2×0.5 mm2
(OCT senser)
6×1.5 mm2 + 2×0.5 mm2
(OCT senser)
6×1.5 mm2 + 2×0.5 mm2
(OCT senser)
Interconnecting Cable ST Model No. X Cross Section mm
2
4×1.5 mm
2
5×1.5 mm2 + 2×0.5 mm
2
5×1.5 mm2 + 2×0.5 mm2
(OCT senser)
NOTE
Power wiring cord should comply with local lows and electrical regulations requirements.
Page 31
8-1
WIRING DIAGRAMS
SM DELTA 1-E.0 GB
8. WIRING DIAGRAMS
8.1 Indoor Unit: DELTA 18, 21, 24
Page 32
8-2
WIRING DIAGRAMS
SM DELTA 1-E.0 GB
8.2 Outdoor Unit: GC 18 1PH R410A
Page 33
8-3
WIRING DIAGRAMS
SM DELTA 1-E.0 GB
8.3 Outdoor Unit: GC 24 1PH R410A
Page 34
8-4
WIRING DIAGRAMS
SM DELTA 1-E.0 GB
8.4 Outdoor Unit: OU7-24 1PH R410A
Page 35
8-5
WIRING DIAGRAMS
SM DELTA 1-E.0 GB
8.5 Outdoor Unit: OU7-24 3PH R410A
Page 36
8-6
WIRING DIAGRAMS
SM DELTA 1-E.0 GB
8.6 Outdoor Unit: OU7-24Z R410A
Page 37
9-1
ELECTRICAL CONNECTIONS
SM DELTA 1-E.0 GB
9. ELECTRICAL CONNECTIONS
9.1 DELTA 18 / 21 1PH
9.2 DELTA 24 1PH (power supply to Outdoor unit)
INDOOR UNIT
POWER SUPPLY 1PH 220-240V 50Hz
CIRCULIT BREAKER (NOT SUPPLIED)
CONNECTED ONLY HEAT - PUMP UNIT
OUTDOOR UNIT
INDOOR UNIT
POWER SUPPLY 1PH 220-240V 50Hz
CIRCULIT BREAKER (NOT SUPPLIED)
CONNECTED ONLY
HEAT - PUMP UNIT
OUTDOOR UNIT
Page 38
10-1
REFRIGERATION DIAGRAMS
SM DELTA 1-E.0 GB
10. REFRIGERATION DIAGRAMS
10.1 Heat Pump Models
10.1.1 DELTA 18 R410A
HEATING MODE
Service
COOLING MODE
S
ervice
Outdoor coil
Sensor
Capillary
tube
Strainer
Check
valve
OUTDOOR UNIT
valve
Reverse
tube
Capillary
Compressor
Outdoor coil
Sensor
tube
Capillary
Reverse
Strainer
valve
Compressor
tube
Capillary
Check
valve
O
UTDOOR UNIT
INDOOR UNIT
Flared
connection
Val ves
port
Indoor coil
Sensor
INDOOR UNIT
connection
Flared
Val ves
port
Indoor coil
Sensor
Page 39
10-2
REFRIGERATION DIAGRAMS
Service Manual - ALPHA
10.1.2 DELTA 24 / OU7-24 R410A
Page 40
10-3
REFRIGERATION DIAGRAMS
SM DELTA 1-E.0 GB
10.1.3 DELTA 24 / OU7-24Z R410A
Page 41
10-4
REFRIGERATION DIAGRAMS
Service Manual - ALPHA
10.2 Cooling Only Models
10.2.1 DELTA 18, 21, 24 R410A
Outdoor coil
Strainer
Capillary
tube
Compressor
Service
port
OUTDOOR UNIT
connection
Valves
Flared
Indoor coil
Sensor
INDOOR UNIT
Page 42
11-1
TUBING CONNECTIONS
SM DELTA 1-E.0 GB
11. TUBING CONNECTIONS
TUBE (Inch)
TORQUE (Nm)
¼” ” ½” ” ¾”
Flare Nuts 11-13 40-45 60-65 70-75 80-85 Valve Cap 13-20 13-20 18-25 18-25 40-50
Service Port Cap 11-13 11-13 11-13 11-13 11-13
1. Valve Protection Cap-end
2. Refrigerant Valve Port (use Allen wrench to open/close)
3. Valve Protection Cap
4. Refrigerant Valve
5. Service Port Cap
6. Flare Nut
7. Unit Back Side
8. Copper Tube
When the outdoor unit is installed above the indoor unit an oil trap is required every 5m along the suction line at the lowest point of the riser. Incase the indoor unit is installed above the outdoor, no trap is required.
Page 43
12-1
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12. CONTROL SYSTEM DELTA18-21-24 TYPE UNITS
12.1 Electronic Control
12.1.1 Introduction
The electronic control information is designed for service applications, and is common to the following groups of air-conditioners:
• ST/ RC group -Cooling only / cooling and heating by heat pump.
• SH group -Cooling and heating by heat pump and supplementary
heater.
• RH group -Cooling, heating by heaters only.
12.1.2 Jumpers Settings
GROUP J6 Setting J2 Setting
ST / RC Open Open
SH Closed Open
RH Closed Closed
Page 44
12-2
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12.2 Legend
AC - Alternate Current
A/C - Air-Conditioner ANY - ON or OFF status CLOCK - ON/OFF Operation Input, (dry contact) COMP - Compressor CPU - Central Processing Unit ELUM - Extended Louver Upward Movement (Software Jumper) E²PROM, EEP - Erase Enable Programmable Read Only Memory HE - Heating Element HPC - High Pressure Control H/W - Hardware ICP - Indoor Condensation Pump ICT - Indoor Coil Temperature (RT2) sensor IF, IFAN - Indoor Fan IR - Infra Red LEVEL1 - Normal Water Level LEVEL2/3 - Medium/High Water Level LEVEL4 - Overflow Level Max - Maximum Min - Minimum min - Minute (time) NA - Not Applicable OCP - Outdoor Condensation Pump OCT - Outdoor Coil Temperature (RT3) sensor OF, OFAN - Outdoor Fan OPER - Operate Para. - Paragraph RAT - Return Air Temperature (RT1) sensor RC - Reverse Cycle (Heat Pump) R/C - Remote Control RCT - Remote Control Temperature RH - Resistance Heater RT - Room Temperature (i.e. RCT in IFEEL mode, RAT otherwise) RV - Reversing Valve SB, STBY - Stand-By sec - Second (time) Sect - Section SH - Supplementary Heater SPT - Set Point Temperature ST - Standard (a Model with Cooling Only) S/W - Software TEMP - Temperature W/O - Without
WVL - Water Valve ΔT - The difference between SPT and RT.
in Heat Mode: ΔT = SPT-RT in Cool/Dry/Fan Mode: ΔT = RT-SPT
Page 45
12-3
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12.3 Main PCB Controller
12.3.1 LED Display DELTA
STAND BY & OPER. INDICATOR
SIGNAL RECEIVER
MODE & RESET BUTTON FILTER LED TIMER LED
5HVHWEXWWRQ 0RGHEXWWRQ
7RURRPVHQVRU
7RLQGRRUVHQVRU %X]]HU
7RGLVSOD\
7RVWHSPRWRU
7RRXWGRRUVHQVRU
/RFN
&RPSUHVVRUUHOD\
)XVH$
/('OLJKW
Page 46
12-4
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12.4 General functions
12.4.1 COMP operation
For each Mode including POWER OFF & SB, a Min time delay of 3 min
before COMP restarting, excluding DEICING Mode
The Min operation time of COMP under different operating conditions is
Operation Mode
Min operation time of
COMP
Heat, Cool or Auto Modes 3 min.
Fan, Dry, Overflow, Protection modes, or mode change ignored
12.4.2 IFAN operation
Min time interval between IFAN speed change in AUTOFAN Mode, is 30 sec.
Min time interval between IFAN speed change in H/M/L Mode is 1 sec.
IFAN speed in Heat/Cool Autofan Mode is determined according to the following table:
ΔT IFAN Speed
ΔT 2 HIGH
2 ΔT 1 MED
1 ΔT LOW
where in Heat Mode: ΔT = SPT-RT in Cool Mode: ΔT = RT-SPT
Note:
In Heat Mode, the rules in section 4.0.3 have the higher priority.
The table above can be represent by a hysteresis curve which
will minimize the switching of the IFAN relay and will minimize the change in IFAN speed:
T [oc]
L
M
H
IFAN speed
321
12.4.3 OFAN operation
Min time interval between OFAN ON/OFF state change is 30 sec.
In general, OFAN starts together with COMP.
12.4.4 HE operation
Minimum Heaters ON or OFF time is 30 sec.
Heaters can be activated only if IFAN is on.
Page 47
12-5
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12.4.5 Protections
High pressure protection is applicable to all operating modes.
Deicing control is valid in Heat and Auto Heat Mode only.
Defrosting control is valid in Dry, Cool, Heat and Auto Modes.
No reset after protection modes.
12.4.6 Thermistors operation
Return air Temp. is detected by RAT (RT1) in normal Mode, or by RCT (R/C sensor) in I-FEEL Mode.
Indoor Coil Temp. is detected by ICT (RT2).
12.4.6.1 Definition of thermistor faults:
a. Thermistor is disconnected -
The thermistor reading is below -30
o
c.
b. Thermistor is shorted -
The thermistor reading is over 75
o
c.
c. Thermistor Temp reading doesn’t change (irrelevant for RT1) -
(i) This test is performed only once after a unit is switched from
OFF/STBY to operation. At the first occurrence of 10 min continuous COMP operation, the current ICT & OCT are compared with those when the COMP was switched from OFF to ON 10 min before. If the ΔT is less than 3
o
c, the thermistor is
regarded as defective.
(ii) The ICT and OCT no-change error can be disabled together by
connecting a4.7 kohm resistor (5%) to the OCT connector. These resistors are equivalent to a thermistor at 43+/-1
o
c and 48+/-1oc
respectively.
(iii) Connecting a 4.7k resistor to the ICT connector will disable the
ICT no-change error only.
Page 48
12-6
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12.4.6.2 Cases for disabling thermistor short/disconnected detection
i. The detection of thermistor faults (a) and (b) above, are disabled when Deicer
Protection is started. The detection will be enabled again only after (1) the deicing is completed, and (2) COMP has been restarted and operated for 30 sec.
ii. When all the following conditions are fulfilled:
a. 4.7K Ohm resistor is connected on the OCT b. IFAN is OFF c. Compressor is ON d. ICT < -30 (disconnected) This condition come to detect and prevent IFAN operation in Deicer in multi spilt units.
12.4.6.3 Handling the thermistor faults in a COMP unit
i. ICT/OCT thermistor is disconnected or shorted -
The invalid thermistor temperature is replaced by 43oc, so that the unit can continue the normal operation. All protections related to that faulty thermistor will be disabled. For example, in case of any ICT fault, the ICT high pressure protection in Heat Mode and ICT defrost protection in Cool Mode will not operate anymore. The same is also applied to the OCT fault.
ii. RAT thermistor is disconnected or shorted –
The RAT will be derived from the ICT by using the equations : Heat Mode: RAT=ICT/2.3
Cool Mode RAT=ICT*4
Notes:
In case of any thermistor failure, the STBY LED will be blinking until the fault condition is corrected.
User can use the system diagnostics function to find out the nature of the thermistor faults.
i. RAT thermistor is disconnected or shorted –
System will operate continuously in the last IFAN & WVL status when turned ON.
Notes:
As in the COMP unit, the STBY LED will be blinking to indicate a thermistor fault. And, the user can use the system diagnostics function to find out the nature of the fault.
Page 49
12-7
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12.5 Cooling Mode - General
1) Room Temperature, RT, is detected by
RAT in normal operation, or
RCT (R/C sensor) in I-FEEL mode.
2) The resolution of RT is 1
o
c.
RT is activating COMP/WVL if (RT > SPT), and
RT is stopping COMP/WVL if (RT =< SPT).
3) Indoor Coil Temp is detected by ICT (RT2).
4) Outdoor Coil Temp is detected by OCT (RT3).
5) A WVL-RC/SH will work in Cooling Mode when
ICT < 16
o
c in general (see Sect 2.2.2 for details), and
Unit is not operating in Fan Mode.
6) OFAN OPERATIONS
OFAN starts together with COMP in general.
Page 50
12-8
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12.5.1 Cooling
Mode: Cool, Auto (at Cooling) Temp: Selected desired temperature. Fan: HIGH, MED, LOW Timer: Any I Feel: On or Off
Control function
Maintains room temp at desired level by comparing RT and SPT.
(RT - SPT) [oc]
+3
+2
+1
0
-1
-2
ON
OFF
ON
OFF
USER FAN SPEED
ON
OFF
COMP (WVL)
OFAN
IFAN
RV
Note:
1) IFAN is always running at High, Medium or Low speed selected by user.
2) In IFEEL mode, the Room Temperature (RT) is the RCT from a R/C. Otherwise, the RT is the RAT from the Room Thermistor.
Page 51
12-9
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12.5.2 Cooling with Autofan
Mode: Cool, Auto (at cooling) Temp: Selected desired temperature Fan: Auto Timer: Any I Feel: On or Off
Control function
Maintains room temp at desired level and controls the IFAN speed for optimal comfort.
(RT - SPT) [oc]
+3
+2
+1
0
-1
-2
ON
OFF
ON
OFF
H
L
M
ON
OFF
COMP
(WVL)
OFAN
IFAN
RV
Page 52
12-10
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12.6 Heating Mode
12.6.1 Heating Mode - General
In heating Mode, temp. compensation schedule will be activated for wall mounted
units.
SPT [oc]
Add to SPT
I-FEEL ON I-FEEL OFF
18 SPT 27 0
o
c +2 oc
27 < SPT ≤ 30 0
o
c +3 oc
Notes :
No compensation will be activated in Forced operation modes
12.6.2 IF operating rules
As a general rule for RC and SH groups, when COMP is ON, excluding
protection modes, IFAN will be switched ON if
ICT > 35
o
c or at the IFTC 30 sec after the COMP is switched ON. In this case, the IFAN will be started at low speed.
Notes :
1) In SH or RC group, if HE is set to OFF due to low ICT, IFAN will be
switched to LOW and will be turned OFF after 30 sec.
2) An exception to this rule (4.0.3.a) is the Back-up mode for SH.
In RC and SH groups, whenever COMP & HE are both OFF, excluding protection modes, IFAN operation will be according
to the following:
In other models IFAN will operate in low speed for 30 sec and then stop. If
COMP is OFF for more than 3 minutes and IFEEL Mode is inactive, IFAN will operate in low speed according to the following graph:
IFAN Speed
Any
Low
Stop
30 35 40
EMD/ELD
EMD/ELD
ICT [oc]
15 20 25
General : For WAX :
SPT+4 SPT+6 ICT
[
o
c
]
ON
OFF
IFAN (Low Speed)
Page 53
12-11
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12.6.3 HE operation
For all Groups, HE can be ON only when IFAN is ON.
For all Groups, HE switches to OFF when ICT > 50
o
c, and is activated
again when ICT 45
o
c.
In SH or RC group, HE operation is limited by the following graph:
Back-up mode for SH group
After COMP has been working for 5 minutes, HE & IFAN are activated even if the ICT is still below 35
o
c. This situation is called Back-up Mode. Both
HE & IFAN will work in Back-up Mode until the ICT reaches 35
o
c. Then, the
operation goes on in the usual mode .
HE
ON
OFF
30
45 50
ICT [oc]
15
General : For WAX :
35 20
40
Page 54
12-12
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12.6.4 Heating, RC or SH Group
Mode: Heat, Auto (at heating) Temp: Selected desired temperature Fan: HIGH, MED, LOW Timer: Any I Feel: On or Off
Control function Maintains room temp. at desired level by comparing RAT or RCT to SPT.
(RT - SPT) [oc]
+2
+1
0
-1
-2
-3
ON
OFF
ON
OFF
H/M/L
OFF
L
ON
OFF
Note 1 Note 2
COMP (WVL)
HE1
HE2
IFAN
ON
OFF
RV
Page 55
12-13
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12.6.5 Heating, RC or SH Group with Autofan
Mode: Heat, Auto (at heating) Temp: Selected desired temperature Fan: Auto Timer: Any I Feel: On or Off
Control function Maintains room temp at desired level by controlling COMP, IFAN and OFAN.
(RT - SPT) [oc]
+2
+1
0
-1
-2
-3
ON
OFF
ON
OFF
H
OFF
L
M
ON
OFF
Note 1 Note 2
COMP
(WVL)
HE1
HE2
IFAN
RV
ON
OFF
Page 56
12-14
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12.6.6 OFAN operation is controlled by the graph below when
1. (RAT ≥ SPT – 2oc), AND
2. (ICT ≥ 45
o
c), AND
3. (COMP is ON)
Otherwise, OFAN runs together with COMP.
OCT [oc]
+3
+2
+1
0
-1
OFAN
ON
OFF
Page 57
12-15
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12.7 Automatic Cooling or Heating
12.7.1 Automatic Cooling or Heating - General
Switching-temperature between Cooling and Heating is SPT ± 3oc.
Autofan in Automatic Cooling and Heating Mode will activate “Cooling
with Autofan Mode” and “Heating with Autofan Mode” respectively.
When the Auto Mode is started with SPT +/-0
o
c, the unit will not select Auto Heat or Auto Cool mode immediately. Instead, the unit will be in a temporary Fan Mode with IFAN operating at low speed. The proper Auto Heat mode or Auto Cool will be started whenever the RT reaches SPT-1
o
c or SPT+1oc respectively.
For RC & SH units, Mode change between Auto Heat & Auto Cool
Modes is possible only after the COMP has been OFF during the last T minutes.
Mode Change time, T
Auto Cool to Auto Heat 3 min Auto Heat to Auto Cool 4 min
When unit is changed form Cool/Dry mode to Auto Mode, the unit
will continue to operate at (Auto) Cool Mode until the conditions for switching from Auto Cool to Auto Heat are satisfied.
Similarly, when unit is changed from Heat Mode to Auto Mode, the
unit will continue to operate at (Auto) Heat Mode until the conditions for switching from Auto Heat to Auto Cool are satisfied.
Page 58
12-16
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12.7.2 Auto Cooling or Heating, RC or SH Groups
Mode: Auto Temp: Selected desired temperature Fan: Any Timer: Any I Feel: On or Off
Control function Maintains room temp at desired level by selecting between cooling and heating modes.
(RT - SPT) [oc]
+3
+2
+1
0
-1
-2
-3
ON
OFF
ON
OFF
H/M/L/OFF
L/OFF
ON
OFF
ON
OFF
COMP
& OFAN
HE1
HE2
IFAN
RV
H/M/L/OFF
L/OFF
USER FAN SPEED H/M/L/OFF
L/OFF
Auto Cool Mode Auto Heat Mode
> 4 min > 3 min
> 3 min > 2 min
(3) (3)
(4)
(4)
(5)
Auto Heat Mode
Page 59
12-17
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12.8 Dry Mode
12.8.1 Dry, ST or RC group
Mode: Dry Temp: Selected desired temp Fan: Low (automatically selected by software) Timer: Any I FEEL: Any
Control function Reduce room humidity with minimum temp. fluctuations by operating in Cool Mode with low speed IFAN.
Notes :
When Dry is ON, the COMP is forced OFF for 3.5 min (longer than the 3 min Min COMP-Off time) after every 15 min of continuous COMP operation.
When Dry is OFF, the COMP is forced ON for 6 min (longer than the 3 min Min COMP-On time) after every 15 min of continuous COMP OFF time.
When Dry is changed from ON to OFF or vice versa, the limits mentioned in (1) & (2) are ignored. The COMP operation is only controlled by the 3 min Min OFF time and 1 min Min ON time.
In Dry Mode, IFAN is LOW when COMP is ON, and is OFF when COMP is OFF.
DRY
(RT - SPT) [oc]
+2
+1
0
-1
-2
ON
OFF
ON
OFF
LOW
OFF
DRY-ON
DRY-OFF
ON
OFF
Time [min]
10
20
30
40 50
Max 15 minutes
3.5 min
Note1
6 min
Note 2
COMP
& OFAN
HE1
& HE2
IFAN
RV
Max 15 minutes
5 minutes COMP
ON time
Page 60
12-18
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12.9 Protection
12.9.1 Cooling Mode Protections
Indoor Coil Defrost
Mode: Cooling, Dry, Auto Temp: Selected desired temp. Fan: Any Timer: Any I Feel: On or Off
Control Function Protect the indoor coil from ice formation at low ambient temperature.
t1 = 5 min minimum for each COMP starting t2 = OFAN cycling (alternate between ON and OFF every 30 sec) for 20 min maximum t3 = COMP and OFAN stop for 10 min minimum
Notes:
When J7 is closed (connected), OFAN cycling is cancelled and the set temperature for COMP & OFAN cut-out and cut-in are changed. COMP & OFAN are forced OFF when ICT =< -6
o
c, and are kept OFF
until ICT > 14
o
c.
For WAX model, the defrost processes is simpler. When J7 is open, COMP & OFAN are forced OFF when ICT =< -1
o
c, and are kept OFF
until ICT > 5
o
c. When J7 is closed, the WAX defrosting process is the same as that of the other models (R.H.S. of the graph above). In both cases, the ICT checking in t2 and t3 are not applied.
ICT [oc]
+2
ON
OFF
ON
OFF
t1 t2 t3
COMP
OFAN
+1
+5
+14
0
-1
-6
ON
OFF
IFAN
J7 OPEN J7 CLOSED
t1 t1
Page 61
12-19
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12.3.2 High Pressure Protection
Mode: (Auto) Cooling or Dry Temp: Selected desired temp. Fan: Any Timer: Any I Feel: On or Off
Control Function To protect the COMP from the high pressure built-up in the outdoor coil during normal cooling operation, by switching OFF the IFAN and COMP.
OCT [oc]
Any
OFF
Any
ON
Any
Blink
ON
COMP
OFAN
IFAN
OPER
LED
52
55
61
66
L
COMP is forced OFF
OFAN is forced ON
IFAN forced
to LOW
68
OFAN follow operation of
COMP
COMP is forced OFF
OFAN is forced ON
For all models except WAX & P2000 For WAX & P2000 models
Note:
The ICT is also monitored during Cool and Dry mode, in case the RV control circuit is faulty. Whenever ICT reaches 70
o
c, which indicates a high pressure in the indoor coil, the COMP will be forced off automatically. The COMP can be turned on again only after the ICT is under 70
o
c again and after the 3 min COMP ON delay time. The OPER
LED will not blink in this case.
Page 62
12-20
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12.9.3 Heating Mode Protections
Outdoor coil Deicing (excluding RH Group)
Mode: Heating, Auto (at heating) Temp: Selected desired Temp Fan: Any Timer: Any I FEEL: Any
Control function
Protects the Outdoor coil from ice formation by controlling COMP & RV operation.
Scope
This new deicer is designed to operate at extreme temp conditions. The deicing cycle could be triggered from:
1. OCT temp and time between two consecutive deicing cycles.
2. Detection of ice forming by change of the OCT temp.
Both algorithms adjust the time between deicing cycles to optimize the A/C performance. The algorithm will automatically increase the time between deicing cycles and reduce the deicing cycle as needed.
The algorithm uses EEPROM data to operate.
Page 63
12-21
CONTROL SYSTEM
SM DELTA 1-E.0 GB
Deicing procedure
OCT [oc]
ON
OFF
ON
OFF
ON
L
ANY
COMP
OFAN
RV
IFAN
DST
(DDT)
0
12
OFF
HEs are forced ON
DOC
ANY
ON
HE
36s 36s
DT
30s
max 12 min.
Note 3
DI (note 1)
DI (note 2)
30s
3 min 3 min
IFAN
OFF
ANY
HE
OFF
ANY
all SH units
except WAX
RC or WAX units
HEs are forced OFF
IFAN is forced to Low Speed
BLINK
ON
OPER
LED
Notes :
At the first COMP activation after SB or OFF, if (OCT < 0
o
c), then DI = 10
min, else DI = 40 min.
In the following Deicing cycles, the time interval between two Deicing cycles activation is between 30 to 80 min (refer to the flow chart).
For RC group, HEs are forced OFF. IFAN operation is as in Heat
Mode, Sect 4.0.3.a, i.e. IFAN will be set to OFF when ICT<30
o
c.
For WAX, the IFAN is simply forced OFF.
For SH group, HEs are forced ON and IFAN is forced to operate in Low speed, regardless of the ICT and difference between RAT & SPT.
Page 64
12-22
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12.9.4 High pressure protection (excluding RH Group)
Mode: (Auto) Heating Fan: Any Timer: Any I Feel: On or Off
Control Function
Protect the Compressor from high pressure by switching OFF the OFAN and COMP.
ICT [oc]
Any
Off
Any
Off
COMP
OFAN
52
55
61
66
COMP is forced OFF
67
OFAN is force
Off
COMP is forced OFF
For all models except WAX For WAX model
ON
BLINK
OPER
LED
Notes:
IFAN, HE1 and HE2 will be activated according to the relevant Heating Mode Sect.
In case of any malfunction in the relay control circuit, the OCT is also monitored during heating mode. Whenever OCT reaches 70
o
c, which indicates a high pressure in the outdoor coil, the COMP will be forced off automatically. The COMP can be turned on again only after the 3 min COMP ON delay and the OCT is under 70
o
c. The OPER LED will not blink in this case.
Page 65
12-23
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12.10 Timer
Mode: Any Temp. Selected desired temp Fan: Any Timer: Timer On, Timer Off I Feel: On or Off
Control function
Starts or stops the unit operation after pre-set time. If RC-1 is used, the timer setting will be (0.5 - 24 Hr) from the moment the timer is set. The minimum resolution is 30 minutes.
If RC-2 or later version of remote controls is used, the timer
setting will be (0:00 - 23:50) real time with 10 minutes resolution.
After power failure, all pre-set timers are cleared. The system is forced to STBY mode and the Timer LED indicator is blinked to indicate the situation. The LED keeps blinking until the timer settings can be reloaded from a R/C message.
Note: If all timers are inactive, the system will not be forced OFF after the power failure. The last OPER/STBY status will be loaded from the EEP instead.
When the A/C receives any valid message from a R/C, the current ON/OFF timer settings will be replaced by the new timer settings in the R/C message.
Note: The following timer related operations will not affect the A/C operating mode (Heat/Cool/Auto/Dry/Fan) setting.
Set ON/OFF timer
Clear ON/OFF timer
R/C ON Timer is time-up
R/C OFF Timer is time-up
E.g. When a STBY A/C unit (with Cool Mode setting in its EEP) is
turned on by the ON-TIMER of a R/C with heat mode setting, the A/C will start in Cool Mode.
Page 66
12-24
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12.11 Forced Operation
Forced operation allows units to start, stop and operate in Cooling or Heating in pre-set temperature according to the following table:
Forced operation
mode
Pre-set Temp for :
WMF, WMN, WNG models
Cooling 22°C
Heating 28°C
Note:
While under the forced operation, the temperature compensation schedule.
The forced operation is activated when the mode button on the Display Board is used to switch the unit to Cool or Heat mode.
The IFAN is always set to Autofan Speed in forced operation.
Page 67
12-25
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12.12 Sleep Mode
Mode: Any Temp: Set – desired temperature selected Fan: Any Timer: Interact with Sleep Timer as described in sect 12.2 I Feel: On or Off
The Sleep mode is activated by using the sleep button on the R/C. In Sleep Mode, the unit will automatically adjust the SPT to turn up/down the room temperature (RT) gradually to provide maximum comfort to the user in sleep.
Sleep is treated as TIMER function. Therefore, the TIMER LED is activated similar to TIMER function.
12.12.1 Adjustment in Sleep Mode
1. in cool, auto cool or dry modes, the SPT adjustment is positive (from 0 to +3oc).
2. In heat or auto heat modes, the SPT adjustment is negative (from 0 to -3
o
c).
3. In other modes, there is no SPT adjustment.
4. The SPT adjustment is cancelled when the Sleep mode is cancelled.
Note: If Off-timer is active, the unit may go to SB before or after 7 hours of
sleep operation.
SPT
Time [Hr]
485326
Start
Sleep
7
RT
SPT-1
SPT-2
SPT-3
SPT+2
SPT+1
SPT+3
1
7 Hours Sleep operation
for Normal Sleep Mode
Unit is turned to SB
after Sleep
Cool, Dry modes
Heat mode
Page 68
12-26
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12.12.2 Time adjustment in Sleep Mode
The user can make use of the Off-Timer to extend the Sleep Time from 7 hours to 12 hour (max). The operation of the new “Extended Sleep Mode” is illustrated by the graphs below.
Case 1 is the Standard Sleep Mode, which is the only sleep mode in previous version of MCU. The A/C unit simply works for 7 hours, then goes to SB.
Case 2 is the new Extended Sleep Mode. If an active Off-Timer is set to turn off the A/C between 7-12 hour, relative to the starting of Sleep, the Sleep time is extended.
And, instead of going to SB at the 7th hour, the A/C will work until reaching the Off-time.
Case 3 is an exception to case 2. The Sleep Mode will not be extended to the Off-Time when the Off-Timer is preceded by an On-Timer, which is also between 7-12 hour.
Oper
Time [Hr]
4 8 10 1226
Start
Sleep
7
Case 1 : Standard Sleep Mode
Condition : Off-timer is not set or is beyond 12 hour.
SB
Oper
Time [Hr]
4 8 10 1226
Start
Sleep
7
Case 2 : Extended Sleep Mode
Condition : Off-timer is set at 7-12 hour.
SB
Off-timer
Oper
Time [Hr]
4 8 10 1226
Start
Sleep
7
Case 3 : Exception to Case 2
Condition : Off-timer is set at 7-12 hour
On-timer is set at 7-12 hour and before Off-timer
SB
Off-timerOn-timer
Page 69
12-27
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12.13 Clogged Air Filter
Filter LED ON after 512 HR.
Filter LED is turned OFF, and the Filter Timer is restarted by pressing the reset button.
Page 70
12-28
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12.14 Controller Self-Test Procedure
12.14.1 By Shorting Test Jumper J1
RC/ST TEST
MODEL
CONFIGURATION
TEST
STEP MOTOR TEST
FREQUENCY
TEST
LEDS OFF
LEDS ON TEST
AUTO RELAY
TEST
SHORT JUMPER
J1
(CONTROL PCB)
PRESS ON
POWER
BUTTON
PRESS ON
MODE BUTTON
INDOOR FAN
SPEED TEST
SELF-TEST FLOW CHART
Step 1
Step 2
Step 3
FOR CONTROLLER (VERSION 4V5 OR HIGHER)
COOL
HEAT
COMPRESSOR
OUTDOOR FAN
R.V.
LOW
MEDIUM
HIGH
TIMER
OPERATE
STANDBY
BUZZER TEST
(ONE BEEP SOUND)
REMOTE CONTROL
TO CPU COMUNICATION
(TWO BEEPS SOUNDS)
THERMISTOR ANALOG
VOLTAGE CHECKING
EEPROM MEMORY
TEST
END OF SELF
TEST
PRESS ON RESET
BUTTON
PRESS ON FAN
BUTTON ON THE
REMOTE CONTROL
PRESS ON MODE
BUTTON
PRESS ON MODE
BUTTON
Step 4
Step 5
Step 6
Step 7
Step 8
DISCONNECT
JUMPER
J1
Page 71
12-29
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12.14.2 By Remote Control Settings:
a. 1: TURNING ON THE POWER.
Turn ON the power, make sure that the unit is in operation.
b. STEP 2 : ENABLE SELF-TEST MODE
Use the remote control to send the first settings to display / indoor unit
HEAT mode, HIGH IFAN, set temperature to 16 ºC, no I-FEEL Sleep or any other timer settings are needed.
Cover the IR transmitter components in the remote control so that it will not transmit the signals to the indoor unit display.
Use the remote control to send the second settings to display / indoor unit COOL mode, LOW IFAN, no I-FEEL Sleep or any other timer settings.
Uncover the remote control IR transmitter and change the temperature settings. If the display/indoor unit receive the settings properly the following steps will start:
c. STEP 3: MODEL SETTING CONFIRMATION
The STAND-BY and COOL LEDS will indicate the operation mode as follows:
OPERATION MODE STAND-BY LED COOL LED
ST ON OFF
RC OFF OFF
SH OFF ON
RH ON ON
Testing the Model configuration. Selected by the COMP, STAND-BY, TIMER LEDS and FILTER will indicate the model configuration as follows (the relevant line for this manual is highlighted):
MODEL COMP OPERATE LED TIMER LED FILTER LED
WNG ON OFF OFF OFF WMN1 ON ON OFF ON WMN4 OFF OFF ON OFF
WMN2/WHX OFF ON OFF ON
WMN3 OFF ON ON ON
In this term the step motor will turn to HOME POSITION.
Page 72
12-30
CONTROL SYSTEM
SM DELTA 1-E.0 GB
d. STEP 4 : AUTO LED WALK TEST.
All the LEDS will turn OFF.
All the LEDS will turn ON for 1 second one by one in the following
sequence:
STAND-BY OPERATE TIMER FILTER  COOL  HEAT.
In PRX all the LEDS will turn ON for 1 second one by one in the following
sequence : 18 °c 20 °c 22 °c 24 °c 26 °c 28 °c 30 °c High IFAN Auto IFAN  Med IFAN  Low IFAN  STAND-BY TIMER FILTER COOL HEAT.
e. STEP 5: AUTO REALY WALK TEST:
All relays will energize one by one in the following sequence:
COMPRESSOR OUTDOOR FANR. V. HEATER 1  HEATER 2 INDOOR WATER PUMP SWING or OUTDOOR WATER PUMP INDOOR FAN: LOW MID  HIGH.
When the relay walk test is completed, the next test will start automatically.
f. STEP 6: FREQUENCY TESTING:
If the frequency measuring process fails the COOL LED will turn ON. In order to move to the next step, press ON/OFF button on the remote control.
g. STEP 7: INPUT TEST.
The test purpose is to check the analog real time indicators (thermistors, LEVEL and clock) according to the table below.
LED Indicator Condition for LED to be ON
STBY LED Room thermistor ≠ 25°c OPER LED Indoor coil thermistor ≠ 25°c TIMER LED Outdoor coil thermistor ≠ 25°c FILTER LED Clock COOL LED LEVEL 2&3 HEAT LED LEVEL 4
h. STEP 8: TIMING RESET TEST (WATCH DOG).
The test purpose is to verify that the CPU rise time after power failure is between 1 to 3 sec, test results are indicated on the LEDS : STAND­BY,OPER, TIMER and FILTER turning ON one by one.
The results of the test are coded as follows:
Pass condition:
1 sec - STAND-BY and OPER are turned ON
2 sec - STAND-BY, OPER and TIMER are turned ON
Page 73
12-31
CONTROL SYSTEM
SM DELTA 1-E.0 GB
Fail condition:
0 sec - STAND-BY is turned ON
3 sec - STAND-BY, OPER, TIMER and FILTER are turned ON
When the timing reset test is completed, the next test will start automatically.
i. STEP 9: MEMORY TEST (EEPROM)
The test purpose is to check if the memory is functioning correctly. The test result is reported by using the STAND-BY and FILTER LEDS:
LED Indicator Condition for LED to be ON
STAND-BY LED Test passed
FILTER LED Test failed
AT THIS POINT THE SELF-TEST IS COMPLETED.
In order to terminate Self-Test mode the User can change the unit setting from COOL Mode, LOW FAN to COOL Mode, MED FAN or to wait without using the remote control for 60 sec.
Values of Sensors Temperature VS. Voltage (DC)
Temp. (*C) Voltage (V) Temp. (*C) Voltage (V) Temp. (*C) Voltage (V) Temp. (*C) Voltage (V)
-20 4.554 2 3.744 24 2.555 46 1.487
-19 4.529 3 3.695 25 2.5 47 1.447
-18 4.502 4 3.646 26 2.445 48 1.409
-17 4.475 5 3.595 27 2.391 49 1.371
-16 4.446 6 3.544 28 2.338 50 1.334
-15 4.417 7 3.492 29 2.284 51 1.298
-14 4.386 8 3.439 30 2.232 52 1.263
-13 4.354 9 3.386 31 2.18 53 1.228
-12 4.322 10 3.332 32 2.128 54 1.195
-11 4.287 11 3.278 33 2.077 55 1.162
-10 4.252 12 3.223 34 2.027 56 1.13
9 4.216 13 3.168 35 1.978 57 1.099
-8 4.178 14 3.113 36 1.929 58 1.069
-7 4.14 15 3.058 37 1.881 59 1.04
-6 4.1 16 3.002 38 1.834 60 1.011
-5 4.059 17 2.946 39 1.798 61 0.983
-4 4.017 18 2.89 40 1.742 62 0.956
-3 3.974 19 2.833 41 1.698 63 0.929
-2 3.93 20 2.777 42 1.654 64 0.904
-1 3.885 21 2.722 43 1.611 65 0.879
0 3.839 22 2.666 44 1.569 66 0.854
1 3.792 23 2.61 45 1.527 67 0.831
Page 74
12-32
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12.15 On Unit Indicators and Controls
STAND BY
INDICATOR
Lights up when the Air Conditioner is connected to power and ready to receive the R/C commands Blinks continuously in case of any thermistor failure.
OPERATION
INDICATOR
Lights up during operation. Blinks for 300 ms, to announce that a R/C infrared signal has been received and stored. Blinks continuously during
OCT High Pressure Protection Mode
ICT High Pressure Protection Mode
Deicing in Heating Mode
Water Over Flow in ECC Model
TIMER INDICATOR Lights up during Timer and Sleep operation.
FILTER INDICATOR
Lights up when Air Filter needs to be cleaned. Blinks during Water Over Flow in MBX/P2000 models.
COOLING
INDICATOR
Lights up when system is switched to Cool Mode by using the Mode Switch on the unit. Show the thermistor status in Diagnostic Mode
HEATING
INDICATOR
Lights up when system is switched Heat Mode by using the Mode Switch on the unit. Show the thermistor status in Diagnostic Mode.
MODE BUTTON
(Cool, Heat, SB)
Use to cycle the operation mode of the A/C unit among COOL, HEAT and SB modes, without using the R/C. Every time this switch is pressed, the next operation mode is selected, in this order : SB  Cool Mode  Heat Mode  SB  ... Press this button continuously for 5 sec or more to start the Diagnostic Mode.
RESET / FILTER
BUTTON
When the Filter LED is ON, press to turn off the Filter LED after a clean filter has been reinstalled. When the Filter LED is OFF, use this button to enable/disable the buzzer announcer.
Page 75
12-33
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12.16 Clock Random Delay From 0 to 2.5 seconds
0 = Clock Switch Open 1 = Clock Switch close
The Clock is activate according to the following table:
A/C STATE
(
before clock is changed)
CLOCK STATE
(
before clock is changed)
CLOCK ACTION
(clock is changed)
A/C NEW STATE
(after clock is changed)
ON 1 0 OFF
OFF 0 1 ON
OFF by
interrupt
(1)
1 0 OFF
ON by
interrupt
(1)
01ON
Notes :
1. Clock can be interrupted by :
R/C - POWER ON/OFF Push-button.
R/C - TIMER.
R/C - SLEEP.
A/C - MODE SWITCH.
2. Any change in the CLOCK level during the first 6 sec after the system Reset is ignored.
Page 76
12-34
CONTROL SYSTEM
SM DELTA 1-E.0 GB
12.2 System Diagnostics
Pressing Mode button for 5-10 seconds in SB or any other operation mode will activate diagnostic mode by the acknowledgment of 3 short beeps and lighting of COOL and HEAT LEDs.
In diagnostic mode, system problems will be indicated by blinking of Heat & Cool LEDs.
The coding method will be as follow:
Heat led will blink 5 times in 5 seconds, and then will be shut off for the next 5 seconds. Cool led will blink during the same 5 seconds according to the following table:
No Problem ○○○○○
1 RT1 is disconnected ○●●●●
2RT1 is shorted ○●●●○
3 (Reserved) ○●●○●
4 RT2 is disconnected ●○●●●
5RT2 is shorted ●○●●○
6 (Reserved) ●○●○●
7 RT2 temp reading doesn’t change ●○●○○
8 RT3 is disconnected ●●○●●
9RT3 is shorted ●●○●○
10 (Reserved) ●●○○●
11 RT3 temp reading doesn’t change ●●○○○
12 RT2 & RT3 temp reading doesn’t change ●○○○○
○ - ON, ● - OFF
Notes:
1. If faults occur in more than one thermistor (except case number 12 on the table above), only one fault will be indicated according to the following order: RT3, RT2, RT1.
2. A/C will jump out to normal mode if sending a command by the R/C in the system diagnostics mode. If this command from the R/C contain a Group ID, this ID will become the new Group ID of the ELCON unit.
Page 77
13-1
TROUBLESHOOTING
SM DELTA 1-E.0 GB
13. TROUBLESHOOTING
SYMPTON PROBABLE CAUSE CORRECTIVE ACTION
1. The stand-by indicator (red led) on the central control display panel doesn’t light up.
There is no correct voltage between the line and neutral terminals on main P.C.B
-If the voltage is low repair power supply.
-If there is no voltage repair general wiring.
-If there is correct voltage replace main or display P.C.B’S
2. The operation indicator (green led) on the central control display panel does not light up.
The remote control batteries are discharged
-Replace batteries of the remote control.
3. The operation indicator (green led) does not light up when starting from unit.
Check main P.C.B and display P.C.B
-Replace P.C.B if necessary.
4. The indoor fan does not function correctly.
Check the voltage between indoor fan terminals on the main P.C.B
-If there is voltage replace capacitor or motor.
5. The outdoor fan does not function correctly.
Check the voltage between out door fan terminals on the main P.C.B
There is voltage between outdoor fan terminals on the outdoor unit.
There is no voltage between outdoor fan terminals on the outdoor unit.
-If there is no voltage replace main P.C.B
-Replace capacitor or motor.
-Check and repair electrical wiring between indoor and outdoor units
6. The compressor does not start up.
Check voltage on compressor terminals on the outdoor unit. (with ammeter)
Check if there is correct voltage between compressor terminals on the outdoor unit.
-If no voltage replace main P.C.B
-If low voltage repair power supply.
-If the voltage correct replace capacitor or compressor.
-If there is no voltage repair electrical wiring between indoor and outdoor units.
7. The refrigeration system does not function correctly.
Check for leaks or restrictions. With ammeter. Pressure gauge or surface thermometer.
-Repair refrigeration system and charge refrigerant if necessary.
8 No cooling or heating
only indoor fan works.
Outdoor fan motor faulty or other fault caused, compressor overload protection cut out.
-Replace P.C.B.
-Outdoor fan blocked remove obstructions.
Page 78
13-2
TROUBLESHOOTING
SM DELTA 1-E.0 GB
SYMPTON PROBABLE CAUSE CORRECTIVE ACTION
9. Only indoor fan and compressor working.
Outdoor fan blocked. -Remove obstructions.
10. Only indoor fan working.
-Run capacitor of outdoor fan motor faulty.
-Windings of outdoor fan are shorted.
-Replace capacitor.
-Replace motor.
11. No cooling or heating takes place, indoor fans working.
-Overload safety device on compressor is cut out (low voltage or high temperature).
-Compressor runs capacitor faulty.
-Compressor windings are shorted.
-Check for proper voltage, switch off power and try again after one hour.
-Replace compressor capacitor.
-Replace compressor.
12. No air supply at indoor unit, compressor operates.
-Indoor fan motor is blocked or turns slowly.
-Indoor fan run capacitor faulty.
-Motor windings are shorted.
-Check voltage, repair wiring if necessary.
-Check fan wheel if it is tight enough on motor shaft, tighten if necessary.
13. Partial, limited air supply at indoor unit.
Lack of refrigerant (will accompanied by whistling noise) cause ice formation on indoor unit coil in cooling mode.
-charge the unit after localizing leak.
14. Water accumulates and over flow from indoor unit section.
Drain tube or spout of drain pan clogged.
-Disassemble plastic drain tube from spout of indoor unit drain pan.
15. Water dripping from outdoor unit base, (in heating mode).
Water drain outlet is clogged. -Open outdoor unit cover clean out
water outlet clean the base inside thoroughly.
16. Freeze-up of outdoor coil in heating mode, poor heating effect in room, indoor fan operates.
-Faulty outdoor thermistor.
-Faulty control cable.
-Outdoor temperature is below design conditions.
-Outdoor unit air outlet is blocked.
-Replace thermistor.
-Repair control cable.
-Shut unit off, it cannot work properly.
-Remove obstructions.
17. Unit is in heat mode but operating in cooling.
-Faulty RV coil.
-RV coil is ok valve is stuck position.
-Replace RV coil.
-Replace the reversing valve.
Page 79
14-1
EXPLODED VIEWS AND SPARE PARTS LISTS
SM DELTA 1-E.0 GB
14. EXPLODED VIEWS AND SPARE PARTS LISTS
14.1 Indoor Unit: DELTA 18, 21, 24
Page 80
14-2
EXPLODED VIEWS AND SPARE PARTS LISTS
SM DELTA 1-E.0 GB
14.2 Indoor Unit: DELTA 18, 21, 24
. Item Description Quan.
1 465020098 Front Plate/Delta 18&24 Fagor 1 2 452919800 Filter 2 3 4518113 Fiber Filter Assy. 1 4 465720204 Silk-Screen Front Frame Assy./Delta 18-24 Fagor Electra 1 5 452919600 Screw cover 3 6 462350084 Evaporator Assy./WNG21/24 R410A 1
453046600 Evaporator Assy./WNG18 R410A 1 7 452917300 Air outlet 1 8 465210009 Drain Pipe for Israel /WNG18/24/30 1 9 452917500 Horizontal flap A 1 9 452917600 Horizontal flap B 1
10 452930700 Vertical flap A 12 10 452918200 Vertical flap B 2
11 4518662 Bearing assy fan 1 12 453024900 Impeller fan 1 13 453053800 Base assy./WNG18 1 14 452920100 Mount bracket/WNG-18 1 15 452919400 Joint/Unit housing 1 16 453134300R Resin Motor 26W/WNG24 LED (DELTA21,24) 1
453116500R Resin Motor 18W/WNG18 LED (DELTA18) 1 17 452918800 Cover/motor 1 18 453050300 STEP MOTOR B 1 20 4519147 Power Cord Clip 1 20 452919200 Tie/connection Wire 1 21 467300197R Display Board/Delta 18 F 1 22 452919100 Support/sensor 1 22 4516263 SENSOR BASE 1 23 467300201R Controller/Delta F 18 S/W:10V14 1 24 438082 Thermistor Indoor coil BLACK. 1 25 467400025 Indoor Air Inlet Temperature Sensor 1 26 452919500 Cover/terminal 1 28 4520416 Defrost cable EXPORT UNITS. 1 29 438600R Remote controller RC3-RC 973-600-00 1 30 4518651 Cover Side Motor 1 31 453057900 Gear BOX ASSY 1 34 452918700 Support/horizontal louver 2 36 4518657 TUBE LOCK 1
Page 81
14-3
EXPLODED VIEWS AND SPARE PARTS LISTS
SM DELTA 1-E.0 GB
14.3 Outdoor Unit: GC 18 ST
Page 82
14-4
EXPLODED VIEWS AND SPARE PARTS LISTS
SM DELTA 1-E.0 GB
14.4 Outdoor Unit: GC 18 ST
. Part . Description Quantity
1 4517144 FAN COVER PP+UV 1 2 452795700 PAINTED LEFT CABINET ASSY 1 3 452989200 Base welding plate assy. 1 4 4516786 PAINTED RIGHT CABINET ASSY 1 5 4516985 Partition Plate 1 6 455000506 Compressor Capacitor With Screw 45uF (CBB65) 1 7 455000104 Double patch Capacitor for fan motor 4uF (CBB61S) 1 8 204107 Cable clip Nylon 2 9 4521744 3 Poles Terminal Block (4mm2) 1
10 4522469 4 LEVEL TERMINAL BLOCK 1
11 4521733 3 Poles Terminal Block ( 6mm2) 1 12 4521340 Controller Box 1 13 4525427 Clip for capacitance(d=50) 1 14 453089900 Compressor Assy.PA200X2CS-4KU1 1 15 4519000 Spring of compressor heater 1 16 4517345 COMPRESSOR WIRE ASSY. 2.5mm2 1 17 4526922 heater for compressor 1 18 4516766 PAINTED VALVE PLATE ASSY 1 19 4526530 LOW PRESS VALVE (R410A) 1 20 4526531 High press valve(R410A) 1 21 4526931 filter welding assy. 2 1 22 4526839 filter welding assy. 1 23 4523145 R.lifter 1 24 452821900 Capillary assy. for cooling 1 25 4523338 Accumulator assy. 1 26 452977200 Low pressure pipe 1 27 452976200 Suction pipe 1 1 28 4526291 Muffler 1 29 4525938 PAINTED RIGHT-BACK CABINET ASSY 1 30 452977000 Condenser pipe assy. 1 31 452976800 Discharge pipe 2 1 32 4517028 PAINTED LEFT-BACK GRILL 1 33 4516758 SMALL HANDLE 1 34 452976000 Discharge pipe 1 1 35 452821300 Condenser-Distributing Soldering Assy.GC-18ST R410A 1 36 452988800 Insulation for compressor PA215/240 1 37 4526509 MOTOR BRAKECT (new) 1 38 4526864 motor YYK85E-6 1 39 4526585 connect for motor backet 1 40 4526510 FAN D=460mm (3 blade) 1 41 4523141 Hexagon locked nut M10 1 42 4516788 PAINTED TOP COVER ASSY 1
Page 83
14-5
EXPLODED VIEWS AND SPARE PARTS LISTS
SM DELTA 1-E.0 GB
14.5 Outdoor Unit GC 18 RC
Page 84
14-6
EXPLODED VIEWS AND SPARE PARTS LISTS
SM DELTA 1-E.0 GB
14.6 Outdoor Unit: GC 18 RC
. Part . Description Quantity
1 4517144 COVER PP+UV 1 2 452795700 PAINTED LEFT CABINET ASSY 1 3 452989200 Base welding plate assy. 1 4 4516786 PAINTED RIGHT CABINET ASSY 1 5 4516985 Partition Plate 1 6 455000506 Compressor Capacitor With Screw 45uF (CBB65) 1 7 455000104 Double patch Capacitor for fan motor 4uF (CBB61S) 1 8 204107 Cable clip Nylon 2 9 4524907 contactor (CJX9B-25S/01) 1
10 4521744 3 Poles Terminal Block (4mm2) 1 11 4522469 4 LEVEL TERMINAL BLOCK 1 12 4521733 3 Poles Terminal Block ( 6mm2) 1 13 4521340 Controller Box 1 14 4525427 Clip for capacitance(d=50) 1 15 453089900 Compressor Assy.PA200X2CS-4KU1 1 16 4519000 Spring of compressor heater 1 17 4517345 COMPRESSOR WIRE ASSY. 2.5mm2 1 18 4526922 Heater for compressor 1 19 4516766 PAINTED VALVE PLATE ASSY 1 20 4526530 LOW PRESS VALVE (R410A) 1 21 4526531 High press valve(R410A) 1 22 4526931 filter welding assy. 2 1 23 4526839 filter welding assy. 1 24 4523145 R.lifter 1 25 4526840 Single-way welding assy. 1 26 4523338 Accumulator assy. 1 27 452976500 Suction pipe 2 1 28 452976600 Low pressure pipe 1 29 452976400 Condenser pipe assy. 1 30 4526291 Muffler 1 31 4525938 PAINTED RIGHT-BACK CABINET ASSY 1 32 4526522 FOUR-WAY VALVE R410A 1 33 4526589 4-Way Valve Coil FOR R410A 1 34 452976100 Discharge pipe 2 1 35 452987800 4-way welding assy. for GC18RC R410A PA200 1 36 4517028 PAINTED LEFT-BACK GRILL 1 37 4516758 SMALL HANDLE 1 38 452976000 Discharge pipe 1 1 39 452796500 Condenser-Distributing Soldering Assy.GC-18RC R410A 1 40 452988800 Insulation for compressor PA215/240 1 41 452976200 Suction pipe 1 1 42 4526509 MOTOR BRAKECT (new) 1 43 4526862 motor YYK85E-6B for GC18RC 1 44 4526585 connect for motor backet 1 45 4526510 FAN D=460mm (3 blade) 1 46 4523141 M10 Hexagon locked nut M10 1 47 4516788 PAINTED TOP COVER ASSY 1
Page 85
14-7
EXPLODED VIEWS AND SPARE PARTS LISTS
SM DELTA 1-E.0 GB
14.7 Outdoor Unit: GC 21 RC
Page 86
14-8
EXPLODED VIEWS AND SPARE PARTS LISTS
SM DELTA 1-E.0 GB
14.8 Outdoor Unit: GC 21 RC
. Part  Description Qty
1 4517144 FAN COVER PP+UV 1 2 452795700 PAINTED LEFT CABINET ASSY 1 3 452989200 Base welding plate assy. 1 4 4516786 PAINTED RIGHT CABINET ASSY 1 5 4516985 Partition Plate 1 6 455000507 Compressor Capacitor With Screw 50uF (CBB65) 1 7 455000104 Double patch Capacitor for fan motor 4uF (CBB61S) 1 8 204107 Cable clip Nylon 2 9 4524907 Contactor (CJX9B-25S/01) 1
10 4521744 3 Poles Terminal Block (4mm2) 1
11 4522469 4 LEVEL TERMINAL BLOCK 1
12 4521733 3 Poles Terminal Block ( 6mm2) 1 13 4521340 Controller Box 1 14 4525427 Clip for capacitance(d=50) 1 15 452975900 Compressor assy.PA240X2CS-4KU1 1 16 4519000 Spring fo compressor heater 1 17 4517345 COMPRESSOR WIRE ASSY. 2.5mm2 1 18 452988900 Heater for compressor 1 19 4516766 PAINTED VALVE PLATE ASSY 1 20 4526513 LOW PRESS VALVE (R410A) 1 21 4526514 Hight press valve(R410A) 1 22 452891100 Filter assy 1 1 23 452891200 Filter assy 2 1 24 4523145 R.lifter 1 25 463750005 Single-way welding assy 1 26 4523338 Accumulator assy 1 27 452976500 Suction pipe 2 1 28 452976700 Low pressure pipe 1 29 452976300 Condenser pipe assy 1 30 4526291 Muffler 1 31 4525938 PAINTED RIGHT-BACK CABINET ASSY 1 32 4526522 FOUR-WAY VALVE R410A 1 33 4526589 4-Way Valve Coil FOR R410A 1 34 452976100 Discharge pipe 2 1 35 452987700 4-way welding assy. 1 36 4517028 PAINTED LEFT-BACK GRILL 1 37 4516758 SMALL HANDLE 1 38 452976000 Discharge pipe 1 1 39 452882900 Condenser and distributor welding assy. 1 40 452988800 Insulation for compressor 1 41 452976200 Suction pipe 1 for PA240 1 42 4526509 MOTOR BRAKECT (new) 1 43 4526864 Motor YYK85E-6 1 44 452907400 Hook for condenser 1 45 4526510 FAN D=460mm (3 blade) 1 46 4523141 Hexagon locked nut M10 1 47 4516788 PAINTED TOP COVER ASSY 1
Page 87
14-9
EXPLODED VIEWS AND SPARE PARTS LISTS
SM DELTA 1-E.0 GB
14.9 Outdoor Unit: GC 21 ST
Page 88
14-10
EXPLODED VIEWS AND SPARE PARTS LISTS
SM DELTA 1-E.0 GB
14.10 Outdoor Unit: GC 21 ST
Part  Description Qty
1 4517144 COVER PP+UV 1
2 452795700 PAINTED LEFT CABINET ASSY 1
3 452989200 Base welding plate assy. 1
4 4516786 PAINTED RIGHT CABINET ASSY 1
5 4516985 Partition Plate 1
6 455000507 Compressor Capacitor With Screw 50uF (CBB65) 1
7 455000104 Double patch Capacitor for fan motor 4uF (CBB61S) 1
8 204107 Cable clip Nylon 2
9 4522469 4 LEVEL TERMINAL BLOCK 1
10 4521744 3 Poles Terminal Block (4mm2) 1
11 4521733 3 Poles Terminal Block ( 6mm2) 1
12 4521340 Controller Box 1
13 4525427 Clip for capacitance(d=50) 1
14 452975900 Compressor assy.PA240X2CS-4KU1 1
15 4519000 Spring fo compressor heater 1
16 4517345 COMPRESSOR WIRE ASSY. 2.5mm2 1
17 452988900 Heater for compressor 1
18 4516766 PAINTED VALVE PLATE ASSY 1
19 4526513 LOW PRESS VALVE (R410A) 1
20 4526514 Hight press valve(R410A) 1
21 452891100 Filter assy 1 1
22 452891200 Filter assy 2 1
23 4523145 R.lifter 1
24 463600001 Capillary welding assy. 1
25 4523338 Accumulator assy 1
26 452977300 Low pressure pipe 1
27 452976200 Suction pipe 1 for PA240 1
28 4526291 Muffler 1
29 4525938 PAINTED RIGHT-BACK CABINET ASSY 1
30 452977100 Condenser pipe assy. 1
31 453018400 Discharge pipe 2 1
32 4517028 PAINTED LEFT-BACK GRILL 1
33 4516758 SMALL HANDLE 1
34 452976000 Discharge pipe 1 1
35 452897800 Condenser and distributor welding assy. 1
36 452988800 Insulation for compressor 1
37 4526509 MOTOR BRAKECT (new) 1
38 4526864 motor YYK85E-6 1
39 452907400 Hook for condenser 1
40 4526510 FAN D=460mm (3 blade) 1
41 4523141 Hexagon locked nut M10 1 42 4516788 PAINTED TOP COVER ASSY 1
Page 89
14-11
EXPLODED VIEWS AND SPARE PARTS LISTS
SM DELTA 1-E.0 GB
14.11 Outdoor Unit GCN 12 RC
Page 90
14-12
EXPLODED VIEWS AND SPARE PARTS LISTS
SM DELTA 1-E.0 GB
14.12 Outdoor Unit: GC 24 ST
Part  Description Qty
1 4517144 FAN COVER PP+UV 1 2 452795700 PAINTED LEFT CABINET ASSY 1
3 452881901 Base plate paint assy. 1
4 4516786 PAINTED RIGHT CABINET ASSY 1
5 4516985 Partition Plate 1
6 455000301 Compressor Capacitor 55uF (CBB65) 1
7 455000104 Double patch Capacitor for fan 1
8 204107 Cable clip Nylon 2
9 4522469 4 LEVEL TERMINAL BLOCK 1
10 4521744 3 Poles Terminal Block (4mm2) 1
11 4521733 3 Poles Terminal Block ( 6mm2) 1
12 4521340 Controller Box 1
13 4525427 (d=50) clip for capacitance 1
14 452864700 Compressor NN27VBAMT assy. for 1
15 4519000 Spring fo compressor heater 1
16 4517345 COMPRESSOR WIRE ASSY. 2.5mm2 1
17 452892100 Heater for compressor 1
18 4516766 PAINTED VALVE PLATE ASSY 1
19 4526513 LOW PRESS VALVE (R410A) 1
20 4526514 Hight press valve(R410A) 1
21 452891100 Filter assy 1 1
22 452891200 Filter assy 2 1
23 4523145 R.lifter 1
24 452901200 Capillary welding assy. 1
25 452891400 Accumulation assy 1
26 452893600 Suction pipe 1
27 452883600 Suction pipe assy. 2 1
28 4526291 Muffler 1
29 4525938 PAINTED RIGHT-BACK CABINET ASSY 1
30 452893700 Discharge tube 1 1
31 4517028 PAINTED LEFT-BACK GRILL 1
32 4516758 SMALL HANDLE 1
33 452893800 Discharge pipe 2 1
34 452882900 Condenser and distributor 1
35 452891300 Insulation for compressor NN27 1
36 4526509 MOTOR BRAKECT (new) 1
37 4526864 motor YYK85E-6 1
38 452907400 Hook for condenser 1
39 4526510 FAN D=460mm (3 blade) 1
40 4523141 M10 Hexagon locked nut M10 1 41 4516788 PAINTED TOP COVER ASSY 1
Page 91
14-13
EXPLODED VIEWS AND SPARE PARTS LISTS
SM DELTA 1-E.0 GB
14.13 Outdoor Unit GC 24 RC
Page 92
14-14
EXPLODED VIEWS AND SPARE PARTS LISTS
SM DELTA 1-E.0 GB
14.14 Outdoor Unit: GC 24 RC
Part  Description Qty
1 4517144 FAN COVER PP+UV 1 2 452795700 PAINTED LEFT CABINET ASSY 1 3 452881901 Base plate paint assy. 1 4 4516786 PAINTED RIGHT CABINET ASSY 1 5 4516985 Partition Plate 1 6 455000301 Compressor Capacitor 55uF (CBB65) 1 7 455000104 Double patch Capacitor for fan 1 8 204107 Cable clip Nylon 2
9 4524907 contactor (CJX9B-25S/01) 1 10 4521744 3 Poles Terminal Block (4mm2) 1 11 4522469 4 LEVEL TERMINAL BLOCK 1 12 4521733 3 Poles Terminal Block ( 6mm2) 1 13 4521340 Controller Box 1 14 4525427 (d=50) clip for capacitance 1 15 452864700 Compressor NN27VBAMT assy. for 1 16 4519000 Spring fo compressor heater 1 17 4517345 COMPRESSOR WIRE ASSY. 2.5mm2 1 18 452862100 Base Bom for KCR-50M(SHX33SC4-U 1 18 452892100 Heater for compressor 1 19 4516766 PAINTED VALVE PLATE ASSY 1 20 4526513 LOW PRESS VALVE (R410A) 1 21 4526514 Hight press valve(R410A) 1 22 452891100 Filter assy 1 1 23 452891200 Filter assy 2 1 24 4523145 R.lifter 1 25 452891600 Single-way welding assy 1 26 452891400 Accumulation assy 1 27 452883700 Suction pipe 1 28 452883800 Low pressure pipe assy. 1 29 452883500 Condenser pipeassy. 1 30 4526291 Muffler 1 31 4525938 PAINTED RIGHT-BACK CABINET ASSY 1 32 4526522 FOUR-WAY VALVE R410A 1 33 4526589 4-Way Valve Coil FOR R410A 1 34 452890700 Dischage pipe 1 1 35 452882800 4-way welding assy. 1 36 4517028 PAINTED LEFT-BACK GRILL 1 37 4516758 SMALL HANDLE 1 38 452890800 Discharge tube 2 1 39 452882900 Condenser and distributor 1 40 452891300 Insulation for compressor NN27 1 41 452883600 Suction pipe assy. 2 1 42 4526509 MOTOR BRAKECT (new) 1 43 4526864 motor YYK85E-6 1 44 452907400 Hook for condenser 1 45 4526510 FAN D=460mm (3 blade) 1 46 4523141 M10 Hexagon locked nut M10 1 47 4516788 PAINTED TOP COVER ASSY 1 48 452925700 Pressure switch 4.2MPa/3.7MPa 1 49 192106 Relay JQX-13F/220-2Z5 OR VE-R02 2Ca2 1
Page 93
14-15
EXPLODED VIEWS AND SPARE PARTS LISTS
SM DELTA 1-E.0 GB
14.15 Outdoor Unit: OU7-24 RC 1PH
Page 94
14-16
EXPLODED VIEWS AND SPARE PARTS LISTS
SM DELTA 1-E.0 GB
14.16 Outdoor Unit: OU7-24 RC 1PH
No Part No Description Qty
1 437045 UPPER COVER EL13 OU LARGE 1
2 433280 SIDE PANEL OU7-24 R410A 1
3 436357 SMALL ELECTRICAL COVER OU 1
4 439329 FRONT COVER/CO' OU7-35/90 E 1
5 437091 OU SQUARE FAN GUARD 1
6 433705 NEW BASE ASSY OU 2005 LOCAL 1
7 433285 COIL OU7-24 HDR 1
8 4529604 AXIAL FAN D493*143 1
9 434062 MOTOR 86W,2S,OU7-24 1
10 433281 SIDE GUARD OU7-24 R410 1
11 436358 OU LEADING HANDLE 1
12 439342 MOTOR SUPPORT OU7-24 1
13 190443 HEATER CRANKCASE MITSUBISHI 1
14 433293 COMPRESSOR NN27VBAMT 1
15 433934 CAPILLARY HEATING ASSY OU7-24 1
16 433291 TUBING ASSY OU7 R410A 1
17 402495 BOARD TPHN 5B 1
18 442007 CAPACITOR 6mF 400V P1/P2 1
19 434716 THERMISTOR+CAP WTH CONNECTO 1
20 442011 CAPACITOR 25mF 400V P1/P2 1
20 442016 CAPACITOR 55mF 400V P1/P2 1
21 437274 COMPRESOR WIRING OU7/8-1PH 1
22 402283 SUCTION ACCUMULATOR 3x5/8" 1
24 437229 ELECTRICAL BOX TPHN 1
33 442466 VALVE COIL L700 MOLEX-SANHU 1
44 433816 SUCTION ASSY OU7 R410A 1
Page 95
14-17
EXPLODED VIEWS AND SPARE PARTS LISTS
SM DELTA 1-E.0 GB
14.17 Outdoor Unit: OU7-24 ST 1PH
Page 96
14-18
EXPLODED VIEWS AND SPARE PARTS LISTS
SM DELTA 1-E.0 GB
14.18 Outdoor Unit: OU7-24 ST 1PH
Part  Description Qty
1 437045 UPPER COVER EL13 OU LARGE 1
2 433280 SIDE PANEL OU7-24 R410A 1
3 436357 SMALL ELECTRICAL COVER OU 1
4 439329 FRONT COVER/CO' OU7-35/90 EL13 1
5 437091 OU SQUARE FAN GUARD 1
6 433705 NEW BASE ASSY OU 2005 LOCAL R4 1
7 433846 COIL OU7-24 ST 1
8 4529604 AXIAL FAN D493*143 1
9 434062 MOTOR 86W,2S,OU7-24 1
10 433281 SIDE GUARD OU7-24 R410 1
11 436358 OU LEADING HANDLE 1
12 439342 MOTOR SUPPORT OU7 1
13 190443 HEATER CRANKCASE MITSUBISHI CO 1
14 433293 COMPRESSOR NN27VBAMT 1
15 433845 CAPILLARY ASSY OU7-24 ST R410A 1
16 433817 TUBING ASSY OU7 ST R410A 1
17 402495 BOARD TPHN 5B 1
18 442007 CAPACITOR 6mF 400V P1/P2 1
19 434716 THERMISTOR+CAP WTH CONNECTOR L 1
20 442016 CAPACITOR 55mF 400V P1/P2 1
21 437274 COMPRESOR WIRING OU7/8-1PH MIT 1
22 402283 SUCTION ACCUMULATOR 3x5/8" 3. " 1
24 437229 ELECTRICAL BOX TPHN 1
44 433816 SUCTION ASSY OU7 R410A 1
45 433847 GAS VAVE ASSY OU7 ST R410A 1
Page 97
14-19
EXPLODED VIEWS AND SPARE PARTS LISTS
SM DELTA 1-E.0 GB
14.19 Outdoor Unit: OU7-24Z RC/ST 1PH
RSWLRQDO
20
19a
18
17
24
44
Page 98
14-20
EXPLODED VIEWS AND SPARE PARTS LISTS
SM DELTA 1-E.0 GB
14.20 Outdoor Unit: OU7-24Z RC/ST 1PH
Part Description Qty
1 437045 LARGE UPPER COVER CUE 1
2 433280 SIDE PANEL OU7-24 R410A 1
3 436357 SMALL ELECTRICAL COVER CUE 1
4 439329 COVERAIR COLLECTOR 1
5 437091 OU SQUARE FAN GUARD 1
6 433722 BASE ASSY OU7-24C EXPORT R410A 1
7 433285 COIL OU7-24 HDR 1
8 4529604 AXIAL FAN D493x143 1
9 434211 Replace by SP000000266 MOTOR+BRACKET 1
10 433281 SIDE GUARD OU7-24 R410 1
11 436358 TRANSPORT HANDLE CUE 1
12 439342 MOTOR BASE OU7 1
14 438795 COMPRESSOR GP270PAA 1
15 433934 CAPILLARY HEATING ASSY OU7-24 R410A 1
16 433660 TUBING ASSY OU7-24C R410A 1
17 413496 BOARD TPHN 5F (RoHS) 1
18 442007 CAPACITOR 6uF 400V 1
19a 434716 THERMISTOR L1050 (for coil) 1
20 442038 CAPACITOR 50mF 400V P1/P2 1
21 438627 COMPRESSOR WIRING TPHN-5F 1
24 437229 ELECTRICAL BOX TPHN 1
33 442520 VALVE COIL L700 MOLEX-DUNAN 1
44 192207 CONTACTOR 230V, 40A 1
Page 99
14-21
EXPLODED VIEWS AND SPARE PARTS LISTS
SM DELTA 1-E.0 GB
14.21 Outdoor Unit: OU7-24 RC 3PH
Page 100
14-22
EXPLODED VIEWS AND SPARE PARTS LISTS
SM DELTA 1-E.0 GB
14.22 Outdoor Unit: OU7-24 RC 3PH
Part  Description Qty
1 437045 UPPER COVER EL13 OU LARGE 1
2 433280 SIDE PANEL OU7-24 R410A 1
3 436357 SMALL ELECTRICAL COVER OU 1
4 439329 FRONT COVER/CO' OU7-35/90 EL13 1
5 437091 OU SQUARE FAN GUARD 1
6 433294 NEW BASE ASSY OU 2005 EXPORT R 1
7 433285 COIL OU7-24 HDR 1
8 4529604 AXIAL FAN D493*143 1
9 434062 MOTOR 86W,2S,OU7-24 1
10 433281 SIDE GUARD OU7-24 R410 1
11 436358 OU LEADING HANDLE 1
12 439342 MOTOR SUPPORT OU7 1
13 190443 HEATER CRANKCASE MITSUBISHI CO 1
14 433753 COMPRESSOR NN27YDAMT 1
15 433934 CAPILLARY HEATING ASSY OU7-24 1
16 433291 TUBING ASSY OU7 R410A 1
17 402494 BOARD TPHN 3C 1
18 442007 CAPACITOR 6mF 400V P1/P2 1
19 434716 THERMISTOR+CAP WTH CONNECTOR L 1
21 437278 COMPRESSOR WIRING OU7/8-3PH MI 1
22 402283 SUCTION ACCUMULATOR 3x5/8" 3. " 1
24 437229 ELECTRICAL BOX TPHN 1
25 439795 3PH MOTOR PROTECTOR 1
33 442466 VALVE COIL L700 MOLEX-SANHUA 1
44 433816 SUCTION ASSY OU7 R410A 1