Electra FS 1200, FS KFR 120L, OU 10 RC Technical & Service Manual

Technical Service Manual
REFRIGERANT
Rev.: Date:
SERIES: FS KFR120L
Free Standing
R
HEAT PUMP
01
29/02/04
Rev.: 01
Series: FS
Date: 20/02/2004
ELECTRA CONSUMER PRODUCTS LTD
F
M
F
M
12
A
U
T
O
C
A
M
T U B E S
O U
T D O O R
U N
I
T
I
N D
O O R
U N
I
T
FS 1200
Model
Wall mountedInstallation method
HeatingCoolingUnitsCharacteristic
1280011000Kcal/hr
Capacity
5120044000Btu/hr 1500012900W
45674824WTotal input
2.862.55W/WCOP/EER
400/50/3Power supply (voltage, cycle)
3X16ACircuit breaker rating
Centrifugal
Fan type & qty.
RPM
Fan speed (HI)
2000 1177
m3/hr
)CFM(
Airflow (HI)
52 / 56dBANoise Power
25mmCondensate drain tube I.D
600mmW
Dimensions
370mmD
1900mmH
70KgWeight
2000*710*490mmPackage dimensions
4unitsUnits per palet 1unitsHeight stacking
R-407CRefrigerant control
SCROLL HR61YAB LGCompressor type & model
AXIAL X 2Fan type & qty.
1125RPMFan speed - HI 4200
(2470)
m /hr
(CFM)
Airflow
69dBANoise Power
900mmW
Dimensions
340mmD 970mmH
95KgWeight
985*406*1016mmPacking dimensions
2unitsHeight stacking 6unitsUnits per palet
R407CRefrigerant
3750gramCharge
16mmCondensate drain tube I.D
3/8in.liquid
Tube size O.D
3/4in.suction
Indoor-Outdoor
Connection between units
MAX. 20mheight difference MAX. 40mtubing length
Operation by hand on LCDOperation control type
A
WHeating elements
C
Ducts
C.
Others
Rev.: 01
Series: FS
Date: 20/02/2004
ELECTRA CONSUMER PRODUCTS LTD
NOTES:
1. Rating conditions ISO/CD 13253R Cooling: indoor: 27°C (80°F) DB 19°C (66°F) WB Outdoor: 35°C (95°F) DB
Heating: indoor: 20°C (68°F) DB Outdoor: 7°C (45°F) DB 6° C (43°F) WB
Refrigerant tubing length (one way) 7.5m (24.6 ft)
2. Guaranteed operating range:
Indoor Outdoor
Upper limit
32°C DB, 23°C WB 46°C DB
Cooling
Lower limit
21°C DB, 15°C WB 21°C DB
Upper limit
27°C DB 24°C DB, 18°C WB
Heating
Lower limit
20°C DB -9°C DB, -10°C WB
1 PH 198 – 242 V
Voltage
3 PH 360 – 440 V
Rev.: 01
Series: FS
Date: 20/02/2004
ELECTRA CONSUMER PRODUCTS LTD
FS KFR 120L /OU10-50 R407C
Rev.: 01
Series: FS
Date: 20/02/2004
ELECTRA CONSUMER PRODUCTS LTD
Model:
FS1200T R407c COOLING CAPACITY
10,000
11,000
12,000
13,000
14,000
15,000
16,000
17,000
18,000
10 15 20 25 30 35 40 45
Outdoor Te mp. (C DB)
CAPACITY [W)
30 C DB/ 50% RH 26 C DB/ 50% RH
23 C DB/ 50% RH
Indoor Temp.
FS1200T R407c HEATING CAPACITY
6,000
8,500
11,000
13,500
16,000
18,500
21,000
-10 -5 0 5 10 15
Outdoor Te mp. (C DB)
CAPACITY [W)
20 C DB
18 C DB
15 C DB
Indoor Temp.
FS KFR 120L
Rev.: 01
Series: FS
Date: 20/02/2004
ELECTRA CONSUMER PRODUCTS LTD
Model:
FS1200T R407c COOLING TOTAL INPUT
1,500
2,000
2,500
3,000
3,500
4,000
4,500
5,000
5,500
6,000
6,500
10 15 20 25 30 35 40 45
Outdoor Te mp. (C DB)
TOTAL INPUT (W
)
30 C DB/ 5 0% RH
26 C DB/ 5 0% RH
23 C WB /50 %RH
Indoor Temp.
FS1200T R407c HEATING TOTAL INPUT
2,500
3,000
3,500
4,000
4,500
5,000
5,500
6,000
6,500
-10 -5 0 5 10 15
Outdoor Te mp. (C DB)
TOTAL INPUT (W
)
20 C DB
18 C DB
15 C DB
Indoor Temp.
FS KFR 120L
Rev.: 01
Series: FS
Date: 20/02/2004
ELECTRA CONSUMER PRODUCTS LTD
Model:
FS1200T R407c COOLING DISCHARGE PRESS URE
5.0
10.0
15.0
20.0
25.0
30.0
10 15 20 25 30 35 40 45
Outdoor Te mp. (C DB)
DISCHARGE PRESSURE [Bar(g
30 C DB/50%RH
26 C DB/50%RH
23 C DB/50%RH
Indoor Temp.
FS1200T R407c HEATING SUCTION PRESSURE
1.50
2.00
2.50
3.00
3.50
4.00
4.50
5.00
-10 -5 0 5 10 15
Outdoor Te mp. (C DB)
SUCTION PRESSURE [Bar(g
)
20 C DB
18 C DB
15 C DB
Indoor Temp.
FS KFR 120L
Rev.: 01
Series: FS
Date: 20/02/2004
ELECTRA CONSUMER PRODUCTS LTD
Model:
FS1200T R407c COOLING SUCTION PRESSURE
3.0
3.5
4.0
4.5
5.0
5.5
10 15 20 25 30 35 40 45
Outdoor Te mp. (C DB)
SUCTION PRESSURE [Bar(g
)
30 C DB/50%RH
26 C DB/50%RH
23 C DB/50%RH
Indoor Temp.
FS1200T R407cHEATING DISCHARGE PRESSURE
14
15
16
17
18
19
20
21
22
23
24
-10 -5 0 5 10 15
Outdoor Te mp. (C DB)
DISCHARGE PRESSURE [Bar(g
20 C DB
18 C DB
15 C DB
Indoor Temp.
FS KFR 120L
Rev.: 01
Series: FS
Date: 20/02/2004
ELECTRA CONSUMER PRODUCTS LTD
Model:
FS KFR 120L
Rev.: 01
Series: FS
Date: 20/02/2004
ELECTRA CONSUMER PRODUCTS LTD
HEAT PUMP MODELS
SERIES:
FS KFR 120L
Rev.: 01
Series: FS
Date: 20/02/2004
ELECTRA CONSUMER PRODUCTS LTD
Tubing Connections
Model:
Tube (Inch)
1/4” 3/8” 1/2” 5/8” 3/4”
TORQUE(N.m.)
11-13
13-20
11-13 11-13 11-13 11-13 11-13
13-20 18-25 18-25 40-50
FLARE NUTS 40-45 60-65 70-75 80-85
VALVE CAP
SERVICE PORT CAP
Tightening Torque Values
2
1
4
3
5
7
8
6
1. Valve Protection Cap-end
2. Use Allen Wrench to open/close the Refrigerant Valve
3. Valve Protection Cap
4. Refrigerant Valve
5. Service Port Cap
6. Flare Nut
7. Unit Back Side
8. Copper Tube
When the outdoor unit is installed above the indoor unit an oil trap is required every 5m along the suction line at the lowest point of the riser. In case the indoor unit is installed above the outdoor no trap is required.
R
R
Tube bending
3.5
Outdoor Unit
Indoor Unit
Suction line
Liquid line
Flare nut
Pipe insulation
Insulating sleeve
Outdoor
Indoor
Outdoor
:
FS KFR 120L
R
R
Tube bending
3.5
Outdoor Unit
Indoor Unit
Suction line
Liquid line
Flare nut
Pipe insulation
Insulating sleeve
Rev.: 01
Series: FS
Date: 20/02/2004
ELECTRA CONSUMER PRODUCTS LTD
Rev.: 01
Series: FS
Date: 20/02/2004
ELECTRA CONSUMER PRODUCTS LTD
F
M
F
M
12
AUTO
C
A
M
Free Standing Air Conditioner
Operation Instructions & Installation Manual
Introduction
System Description
Operation Modes, Functions and Features
Indicator Lights of the Indoor Unit and Control Buttons on the Unit
Operational Principal of the Unit
Specifications and Technical Parameters
Operation Procedure (Operations on the Unit)
Turning on the Air Conditioner
Ventilating Operation
Cooling Operation
Cooling Operation with Auto Fan Mode
Heating Operation
Heating Operation With Auto Fan Mode
Dry Operation
Temperature Selecting
Sleep Function
Timer Function
Operation Modes for Timer Function
Air Direction Control
Turning Off
Lock Function
Protection Modes and Instructions for Service Electric Heater
Maintenance and Care
Operating Tips
Preventive Measures
Before Calling For Service
If your air conditioner is for cooling only, please disregard the heating instructions.
before
Please read these instructions
operating the air
conditioner.
The change of function parameters and circuit diagram will not be notified; please refer to the nameplate and the circuit diagram on the unit.
1
2
3
5
6
7
8
8
8
8
9
9
9
9
9
10
10
10
12
12
12
13
14
15
16
18
Operation Instructions Page
19
20
21
21
22
24
24
27
29
29
31
32
33
34
36
37
38
Installation Instructions Page
1. Outline Dimensions for Indoor & Outdoor Unit
2. Installation Process Chart
3. Installation of Indoor Unit
3.1 Selecting Location for Indoor Unit Installation
3.2 Indoor Unit Installation
3.3 Refrigerant Line Installation
3.4 Drain Line Installation
3.5 Electrical Cable Connections
4. Outdoor Unit Installation
4.1 Selecting Location for Outdoor Unit Installation
4.2 Outdoor Unit Installation
4.3 Interconnection and leak detection of Refrigerant Line
4.4 System Installation
4.5 Electrical Layout and Wiring Method
4.6 Test Operation
4.7 Drain Condensing Water (used only by heat pump unit)
5. Wiring Diagram
F
M
FM
1
2
A
U
T
O
C
A
M
The free Standing air conditioner is designed for various uses:
Cooling in summer
Dehumidifying at high humidity conditions.
Heating
Air Filter
Ventilation
INTRODUCTION
Operating Temperature Range
Indoor
Outdoor
Cooling
16C~30C
oo
Heating
16C~30C
oo
10 C ~ 46 C
oo
-10 C~21 C
oo
The air conditioner must be grounded to protect against electrical shock.
Installation of the air conditioner must be performed by an experienced air conditioning installer, observing good refrigeration practice.
Electrical connections and power cord replacement should only be made by authorized electricians and in accordance with electrical regulations and local codes.
Failure to comply with the manufacturer s installation and operation instructions could affect the performance of the air conditioner and the validity of the warranty.
IMPORTANT NOTICE:
FM
FM
12
AUTO
C
AM
Indoor Unit
Air Out
Air Outlet
Outdoor Unit
Air In
Control Panel
Air Out
Air Out
Air In
Drain Tube
Interconnecting Lines
Air Inlet
SYSTEM DESCRIPTION
OPERATION MODES, FUNCTIONS AND FEATURES
Cools, dehumidifies and filters the room air. Maintains desired room
temperature.
Heats and filters the room air. Maintains the desired room temperature.
Automatically switches from COOLING to HEATING or from HEATING to
COOLING, maintaining the desired temperature according to the room
conditions.
Decreases humidity of atmosphere and maintains the room temperature. It
is suitable to use in dankish and rainy season.
Recirculates and filters the room air. Maintains constant air movement in the
room.
The air conditioner automatically selects the fan speed according to the
room temperature. At the start, the unit operates at high fan speed. As the
room air approaches to the set temperature, the fan switches automatically
to a lower speed for quieter operation.
In HEATING and in AUTO FAN, the fan will be turned off when the
compressor is not in operation and will not be restarted, unless the indoor
coil reaches adequate temperature. This HOT KEEP feature prevents
uncomfortable cold air drafts. Use of AUTO FAN is, therefore, recommended
when the air conditioner is in HEATING mode.
Real time control and display, automatically turns the air conditioner ON and
OFF according to the time of day setting, ensuring comfort conditions before
returning home, without wasting electricity. It turns the air conditioner off
automatically when sleeping.
This series of conditioners have the following functions:
HOT KEEP
TIMER
AUTO FAN
HEAT
COOL
FAN
DRY
AUTO
SLEEP
Designed to create comfortable sleeping conditions. When in cooling mode,
the temperature rises one-degree centigrade after each consecutive hour,
up to three hours, from the start of the mode. The rising temperature
prevents the feeling of over-cooling while sleeping (when your body is at
rest). In heating mode the reverse occurs; the air conditioner lowers its
temperature one-degree every hour. When in sleeping mode, air conditioner
will be automatically turned off after operating for seven hours. The result is
a more comfortable and invigorating sleep, which leaves you feeling fresh
and energetic on the next morning.