
Contents
Contents i
Part 1 General Information .................................................................................................... 1
Part 2 Indoor Units ............................................................................................................... 11
Part 3 Outdoor Units ............................................................................................................. 46
Part 4 Installation .................................................................................................................. 68
Part 5 Electrical Control System ......................................................................................... 79
※The specifications, designs, and information in this book are subject to change without notice for
product improvement.

General Information
General Information 1
Part 1
General Information
1. Model Lists .......................................................................... 2
2. External Appearance ........................................................ 3
2.1 Indoor Units ................................................................................. 3
2.2 Outdoor Units .............................................................................. 3
3. Product specification ....................................................... 4

Model Lists
2 General Information
1. Model Lists
1.1 Indoor Units
Four-way cassette(compact)
Universal Outdoor unit Model

External Appearance
General Information 3
2. External Appearance
2.1 Indoor Units
Four-way cassette(Compact)

Product specification
4 General Information
Installation Method of Pipe
Installation Method of Pipe
Annual energy consumption
Circuit breaker rating A 25
Rated power input (Maximum power input)
Rated current (Maximum current)
Refrigerant charge (standard connecting
tubing length)
Additional charge per 1 meter
Connection
s between
units
Max. length for all rooms m 30
Max. length for one indoor unit
Max.
height
difference
between
indoor and
outdoor
unit
Max. height difference between
indoor units

Product specification
General Information 5
Installation Method of Pipe
Installation Method of Pipe
Annual energy consumption
Circuit breaker rating A 25
Rated power input (Maximum power input)
Rated current (Maximum current)
Refrigerant charge (standard connecting tubing length)
Additional charge per 1 meter
Connections
between
units
Max. length for all rooms m 45
Max. length for one indoor unit
Max. height
difference
between
indoor and
outdoor unit
Max. height difference between indoor
units

Product specification
6 General Information
Installation Method of Pipe
Installation Method of Pipe
Annual energy consumption
Circuit breaker rating A 25
Rated power input (Maximum power input)
Rated current (Maximum current)
Refrigerant charge (standard connecting tubing length)
Additional charge per 1 meter
Connections
between
units
Max. length for all rooms m 60
Max. length for one indoor unit
Max. height
difference
between
indoor and
outdoor unit
Max. height difference between indoor
units

Product specification
General Information 7
Installation Method of Pipe
Installation Method of Pipe
Annual energy consumption
Circuit breaker rating A 32
Rated power input (Maximum power input)
Rated current (Maximum current)
Refrigerant charge (standard connecting tubing length)
Additional charge per 1 meter
Connections
between
units
Max. length for all rooms m 75
Max. length for one indoor unit
Max. height
difference
between
indoor and
outdoor unit
Max. height difference between indoor
units

Product specification
8 General Information
Installation Method of Pipe
Condensate drain tube I.D
Installation Method of Pipe
Condensate drain tube I.D

Product specification
General Information 9
Installation Method of Pipe
Condensate drain tube I.D

Product specification
10 General Information
Installation Method of Pipe
Condensate drain tube I.D

Indoor Units
Indoor Units 11
Part 2
Indoor Units
JKD Type ............................................................................. 12
Light Commercial ................................................................ 22

JKD Type
1. Function ........................................................................... 13
2. Dimensions ...................................................................... 14
3. Wiring Diagrams ............................................................. 15
4. Exploded View and Spare Part list ................................ 16

Function
Indoor Units 13
1. Function
Killer Of Formaldehyde
Silver Ico Filter(O)
Vitamin C Filter(O)
3M HAM Filter(O)
Bio Filter(O)
Golden Fin(O)
Ionizer(O)
1W Standby
Louver Position Memory Function
Refrigerant Leakage Detect
Self-diag. Function
Hydrophilic Aluminum Fin
PTC Heating Belt(O)
Filter
2 ways of drainage

Dimensions
14 Indoor Units
Dimension of installation
hole(mm)

Wiring Diagrams
Indoor Units 15
3. Wiring Diagrams
ELSI-JKD009-N11, ELSI-JKD012-N11, ELSI-JKD018-N11

Exploded View and Spare Part list
16 Indoor Units
4. Exploded View and Spare Part list
Exploded View of indoor unit: ELSI-JKD009-N11

Exploded View and Spare Part list
Indoor Units 17
Spare part list of indoor unit: ELSI-JKD009-N11
Structure Subassembly of Display Box
Temperature Sensing Element Fixing clip
Evaporator assembly Gas valve assembly
Electronic control box assembly
Indoor main control board assembly
Electrical Control Box Cover
Filter net of cold catalyst

Exploded View and Spare Part list
18 Indoor Units
Exploded View of indoor unit: ELSI-JKD012-N11

Exploded View and Spare Part list
Indoor Units 19
Spare part list of indoor unit: ELSI-JKD012-N11
Structure Subassembly of Display Box
Temperature Sensing Element Fixing clip
Electronic control box assembly
Indoor main control board assembly
Electrical Control Box Cover
Filter net of cold catalyst

Exploded View and Spare Part list
20 Indoor Units
Exploded View of indoor unit: ELSI-JKD018-N11

Exploded View and Spare Part list
Indoor Units 21
Spare part list of indoor unit: ELSI-JKD018-N11
Structure Subassembly of Display Box
Temperature Sensing Element Fixing clip
Electronic control box assembly
Indoor main control board assembly
Electrical Control Box Cover
Filter net of cold catalyst

Light Commercial
22 Indoor Units
Light Commercial
1. Features ........................................................................... 23
2. Dimensions ...................................................................... 32
3. Service Space(unit:mm) ................................................. 35
4. Wiring Diagrams ............................................................. 37
5. Exploded View and Spare Part list ................................ 40

Features
Light Commercial 23
1. Features
1.1 Four-way cassette type(compact)
⑴ New panel
360°surrounding air outlet design, affords comfortable feeling
⑵ Compact design
The body size is 570×260×570mm, it’s just smaller than the ceiling board, so it’s very easy for
installation and will not damage the decoration. The panel size is 647×50×647mm.
The hooks are designed in the four corners of the body, which can save installation space.

⑶ Electric control box built-in design
The E-box is simply and safely built inside the indoor unit. It’s convenient for installation and
maintenance. Can check the control part easily, you only need to open the air return grille.
⑷ Fresh air intake function:
Fresh air fulfills air quality more healthy and comfortable.

Features
Light Commercial 25
⑸ Air passage function
Reserves the space for air outlet from the side of indoor unit; It’s availed to connect air duct
from the two sides to the nearby small rooms.

1.2 A5 Duct
⑴ Installation accessories: (Optional)
Front Board, Canvas Air Passage, Filter, Panel, for easy installation
⑵ Easy Installation: Two air inlet styles (Bottom side or Rear side)
Air inlet from rear is standard for all capacity; air inlet from bottom is optional.
The size of air inlet frame from rear and bottom is same, it’s very easy to move the cover from bottom to
rear side, or from rear to the bottom, in order to matching the installation condition.
⑶ Fresh air intake function
Install one duct from the reserved fresh-air intake to outdoor.
Continually inhale the fresh air to improve the quality of the indoor air, fulfills air quality more healthy and
comfortable.
Air intake from rear (Standard)
Air intake from bottom (Optional)

Features
Light Commercial 27
⑷ Easy maintenance
Clean the filter (Optional, standard product without filter)
It is easy to draw out the filter from the indoor unit for cleaning, even the filter is installed in rear side or
bottom side.
Replace the motor or centrifugal fan
Remove the ventilated panel firstly. Remove a half of blower housing and take out the motor with
centrifugal fan. Directly remove two bolts, and then replace the motor or centrifugal fan easily.

⑸ Reserved remote on-off and central control ports
Reserved remote on-off ports and central control ports, can connect the cable of an on-off controller or a
central controller to realize remote on-off control function or group control function.
⑹ Built-in drain pump (Optional):
Built-in drain pump can lift the water to 750mm upmost. It’s convenient to install drainage piping under
most space condition.

Features
Light Commercial 29
⑺ Built-in display board
The standard indoor unit can be controlled by wired controller.
There is a display board with a receiver in the E-box. Move out the display, and fix it in other place, even
in the distance of 10m. The unit will realized remoter control.
The wired controller and the display board can display the error code or production code when the chips
detect some failure.
Wired Controller (Standard)
Remote Controller (Optional)

1.3 Console
(1) Consumes up to 30% less energy than non-inverter units
——DC inverter compressor
——indoor fan motor adopts DC motor
(2) Achieves set temperature more quickly
——air supplying from top and bottom or from top only
——air inlet from four directions

Features
Light Commercial 31
(3) Compact unit body, space saving
——this unit body is very thin and harmonious with room. It is beautiful, elegant and space saving.
——lightweight and compact.
(4) Flexible installation.
——can be used for floor standing or lower wall applications
——as a floor standing floor model, it can be semi or fully recessed without loss of capacity.
(5) High efficiency filter
——built in Formaldehyde nemesis filter
——active-carbon and biological anti-virus filter is optional.
(6) Comfort
——flexible air blow: vertical auto swing and wide angle louvers ensure that warm air reaches the furthest
corners of the room and increase the air flow coverage
——Low noise operation, lowest to 23Db
——Low starting power and precise room temperature adjustment
(7) Powerful mode can be selected for rapid cooling or heating.
(8) Easy cleaning grille and maintenance
(9) Indoor unit adopts DC motor, it has five level fan speed meet different requirements.

Dimensions
32 Indoor Units
2. Dimensions
2.1 Four-way cassette type(compact):
2.2 A5 Duct

Dimensions
Light Commercial 33
Size of outline dimension
mounted plug
A B C D E F G H I J K L M

Service Space(unit:mm)
Light Commercial 35
3. Service Space(unit:mm)
3.1 Four-way cassette(compact)
3.2 A5 Duct
Ensure enough space required for installation and maintenance.
All the indoor units reserve the hole to joint the fresh air pipe. The hole size as following:

Wiring Diagrams
Light Commercial 37
4. Wiring Diagrams
ELSI-KBD012-N11(7SP042243)
CN13
10
CN8
M
INDOOR UNIT
MAINBOARD
5
Remote
Control
CN33
ALARM
Alarm
Output
CN15
M
5
CN1
CN5
CN3
JR6
JR6
H
CH
Y/G
4
Y/G
TO OUTDOOR UNIT
P5
S2 S1(1-2)
Address
(Central control)
0-F OFF-OFF 0-15(Default=0)
0-F ON-OFF 16-31
0-F OFF-ON 32-47
0-F ON-ON 48-63
SW1-1 SW1-2 Anti Cold Air Setting
OFF OFF Fan OFF when ICT<24(Default)
ON OFF Fan OFF when ICT<15
OFF ON Fan OFF when ICT<8
ON ON Reserved
SW6-1 SW6-2
Temp. Compensation
(Heating)
OFF OFF 6(Default)
ON OFF 4
OFF ON 2
ON ON Reserved
Auto Restart
With Auto Restart (Default)
W/O Auto Restart
SW3
OFF
ON
Fan Status When Thermo-OFF
FAN ON(Default)
FAN OFFON
SW2
OFF
RCW8(Optional)
RCW6
(Optional)
Fresh Air
To Central
Control

Exploded View and Spare Part list
40 Indoor Units
1. Exploded View and Spare Part list
Exploded View of indoor unit:ELSI-KBD012-N11

Exploded View and Spare Part list
Light Commercial 41
Spare part list of indoor unit:ELSI-KBD012-N11
Evaporator assembly Gas valve assembly
Outlet Pipes of Evaporator
Input pipes of Evaporator assembly Joint board of
Evaporator
Sealing board for Pipe Tie-in Subassembly
Joint board of Evaporator
Motor Installing Foundation
Welding Parts of Electrical Control Box
Indoor Main Control Board Subassembly (Sticker)
Electrical Control Box Cover Subassembly
Rubber Gasket of Water Drain Pump
Drain pump rubber washer II
Installing Plate of Water Drain Pump(RoHS)

Exploded View and Spare Part list
42 Indoor Units
Exploded View of indoor unit: ELSI-OCD012-N11

Exploded View and Spare Part list
Light Commercial 43
Spare part list of indoor unit: ELSI-OCD012-N11
Fan motor axes clamp (left)
Fan motor axes clamp (right)
Evaporator right support board assembly
Pipe temperature sensor assembly
Electronic control box assembly
Ambient temperature sensor assembly
Main control board assembly
Cover of electronic control box
Pipe clamp board assembly

Exploded View and Spare Part list
44 Indoor Units
Exploded View of indoor unit:ELSI-QAD012-N11

Exploded View and Spare Part list
Light Commercial 45
Spare part list of indoor unit:ELSI-QAD012-N11
Pipe temperature sensor assembly
Electronic control box assembly
Installation plate of electric parts I
Fixing board of electronic control box II
Ambient temperature sensor assembly
Electronic control box seal plate
Installation plate of electric parts
Main control board assembly
Fixing board of electronic control box I
Auxiliary electric heater control board
Cover of electronic control box
Supporter assembly of fan motor

Outdoor Units
46 Outdoor Units
Part 3
Outdoor Units
1. Dimensions ...................................................................... 47
2. Service Space .................................................................. 51
3. Refrigeration Cycle Diagram.......................................... 52
4. Wiring Diagrams ............................................................. 54
5. Indoor units combination ............................................... 56
6. Operation Limits .............................................................. 57
7. Sound Levels ................................................................... 58
8. Exploded View and Spare Part list ................................ 59

Refrigeration Cycle Diagram
52 Outdoor Units
3. Refrigeration Cycle Diagram
3.1 Refrigeration cycle diagram of inverter 1 drive 2 type
LIQUID VALVE A
GAS VALVE A
HEAT
EXCHANGE
(EVAPORATOR)
HEAT
EXCHANGE
(CONDENSER)
Compressor
4-WAY VALVE
COOLING
HEATING
T2 Evaporator
temp. sensor
middle
T1 Room
temp. sensor
T3
Condenser
temp. sensor
T5 Discharge
temp. sensor
T4 Ambient
temp. sensor
INDOOR OUTDOOR
EXV A
CAPILIARY A
CHECK VALVE
CAPILIARY TUBE
EXV B
CAPILIARY B
LIQUID VALVE B
GAS VALVE B
Accumulator
T2B-A Evaporator
temp. sensor outlet
T2B-B
3.2 Refrigeration cycle diagram of inverter 1 drive 3 type
LIQUID VALVE A
GAS VALVE A
HEAT
EXCHANGE
(EVAPORATOR)
HEAT
EXCHANGE
(CONDENSER)
Compressor
4-WAY VALVE
COOLING
HEATING
T2 Evaporator
temp. sensor
middle
T1 Room
temp. sensor
T3
Condenser
temp. sensor
T5 Discharge
temp. sensor
T4 Ambient
temp. sensor
INDOOR OUTDOOR
EXV A
CAPILIARY A
CHECK VALVE
CAPILIARY TUBE
EXV B
CAPILIARY B
LIQUID VALVE B
GAS VALVE B
EXV C
CAPILIARY C
LIQUID VALVE C
GAS VALVE C
Accumulator
T2B-A Evaporator
temp. sensor outlet
T2B-B
T2B-C
3.3 Refrigeration cycle diagram of inverter 1 drive 4 type

Refrigeration
Cycle Diagram
Outdoor Units 53
LIQUID VALVE A
GAS VALVE A
HEAT
EXCHANGE
(EVAPORATOR)
HEAT
EXCHANGE
(CONDENSER)
Compressor
4-WAY VALVE
COOLING
HEATING
T2 Evaporator
temp. sensor
middle
T1 Room
temp. sensor
T3
Condenser
temp. sensor
T5 Discharge
temp. sensor
T4 Ambient
temp. sensor
INDOOR OUTDOOR
EXV A
CAPILIARY A
CHECK VALVE
CAPILIARY TUBE
EXV B
CAPILIARY B
LIQUID VALVE B
GAS VALVE B
EXV C
CAPILIARY C
LIQUID VALVE C
GAS VALVE C
EXV D
CAPILIARY D
LIQUID VALVE D
GAS VALVE D
Accumulator
High pressure
switch
Low pressure
switch
T2B-A Evaporator
temp. sensor outlet
T2B-B
T2B-C
T2B-D
3.4 Refrigeration cycle diagram of inverter 1 drive 5 type
LIQUID VALVE A
GAS VALVE A
HEAT
EXCHANGE
(EVAPORATOR)
HEAT
EXCHANGE
(CONDENSER)
COOLING
HEATING
T2 Evaporator
temp. sensor
middle
T1 Room
temp. sensor
T3
Condenser
temp. sensor
T4 Ambient
temp. sensor
INDOOR OUTDOOR
EXV A
CAPILIARY A
CHECK VALVE
CAPILIARY TUBE
EXV B
CAPILIARY B
LIQUID VALVE B
GAS VALVE B
EXV C
CAPILIARY C
LIQUID VALVE C
GAS VALVE C
EXV D
CAPILIARY D
LIQUID VALVE D
GAS VALVE D
EXV E
CAPILIARY E
LIQUID VALVE E
GAS VALVE E
Compressor
4-WAY VALVE
T5 Discharge
temp. sensor
Accumulator
High pressure
switch
Low pressure
switch
T2B-A Evaporator
temp. sensor outlet
T2B-B
T2B-C
T2B-D
T2B-E

Indoor units combination
56 Outdoor Units
5. Indoor units combination
5.1 Indoor unit combination for ELAU-VCZ218-H11
5.2 Indoor unit combination for ELAU-VCZ327-H11
5.3 Indoor unit combination for ELAU-VCZ430-H11
5.4 Indoor unit combination for ELAU-VCZ536-H11

Operation Li
mits
Outdoor Units 57
6. Operation Limits
-15℃~50℃
(For the models with
low temperature
cooling system)
CAUTION:
1. If the air conditioner is used beyond the above conditions, certain safety protection features may come
into operation and cause the unit to operate abnormally.
2. The room relative humidity should be less than 80%. If the air conditioner operates beyond this figure, the
surface of the air conditioner may attract condensation. Please set the vertical air flow louver to its maximum
angle (vertically to the floor), and set HIGH fan mode.
3. The optimum performance will be achieved during this operating temperature zone.

Sound Levels
58 Outdoor Units
H
1.0m
Outdoor Unit
Microphone
Note: H= 0.5 × height of outdoor unit

Exploded Vi
ew and Spare Part list
Outdoor Units 59
8. Exploded View and Spare Part list
Exploded View of outdoor unit: ELAU-VCZ218-H11

Exploded View and Spare Part list
60 Outdoor Units
Spare part list of outdoor unit: ELAU-VCZ218-H11
Ambient temperature
sensor assembly
Electronic control box
assembly
Cover of electronic
control box
Outdoor main control
board assembly
Inverter control board
assembly
Installation plate of
electric parts
Pipe temperature
sensor assembly
Pipe temperature
sensor assembly
Rear right clapboard
assembly
Front right clapboard
assembly
Electronic expansion
valve assembly
Round sticker of air
outlet grille
Discharge
temperature sensor
assembly
Supporter assembly
of fan motor

Exploded Vi
ew and Spare Part list
Outdoor Units 61
Exploded View of outdoor unit: ELAU-VCZ327-H11

Exploded View and Spare Part list
62 Outdoor Units
Spare part list of outdoor unit: ELAU-VCZ327-H11
Ambient temperature
sensor assembly
Pipe temperature
sensor assembly
Pipe temperature
sensor assembly
Electronic expansion
valve assembly
Rear right clapboard
assembly
Front right clapboard
assembly
Electronic expansion
valve assembly
Round sticker of air
outlet grille
Electronic expansion
valve assembly
Supporter assembly
of fan motor
Discharge
temperature sensor
assembly
Electronic control box
assembly
Cover of electronic
control box
Outdoor main control
board assembly
Inverter control board
assembly
Electronic installing
box

Exploded Vi
ew and Spare Part list
Outdoor Units 63
Exploded View of outdoor unit: ELAU-VCZ430-H11

Exploded View and Spare Part list
64 Outdoor Units
Spare part list of outdoor unit: ELAU-VCZ430-H11
Ambient temperature
sensor assembly
Pipe temperature
sensor assembly
Electronic expansion
valve assembly
Pipe temperature
sensor assembly
Electronic expansion
valve assembly
Rear right clapboard
assembly
Front right clapboard
assembly
Electronic expansion
valve assembly
Round sticker of air
outlet grille
Supporter assembly
of fan motor
Discharge
temperature sensor
Electronic control box
assembly
Cover of electronic
control box
Outdoor main control
board assembly
Inverter control board
assembly
Electronic expansion
valve assembly
Installation plate of
electric parts

Exploded View and Spare Part list
66 Outdoor Units
Exploded View of outdoor unit: ELAU-VCZ536-H11

Exploded Vi
ew and Spare Part list
Outdoor Units 67
Spare part list of outdoor unit: ELAU-VCZ536-H11
Electronic installing
box assembly
Ambient temperature
sensor assembly
Active PFC Module
Subassembly
Discharge
temperature sensor
assembly
Pipe temperature
sensor assembly
Pipe temperature
sensor assembly
Rear right clapboard
assembly
Electronic expansion
valve assembly
Front right clapboard
assembly
Electronic expansion
valve assembly
Round sticker of air
outlet grille
Electronic expansion
valve assembly
Electronic expansion
valve assembly
Supporter assembly
of fan motor
Electronic control box
assembly
Inverter control board
assembly
Outdoor main control
board assembly
Installation plate of
electric parts
Electronic expansion
valve assembly

Installation
68 Installation
Part 4
Installation
1.Wrench torque sheet for installation ................................................... 69
2.Connecting the cables .......................................................................... 69
3.Pipe length and the elevation ............................................................... 69
4 Installation for the first time ................................................................. 71
5 Adding the refrigerant after running the system for many years ..... 74
6 Re-installation while the indoor unit need to be repaired ................. 75
7 Re-installation while the outdoor unit need to be repaired ............... 77

Wrench torque sheet for installation
Installation 69
1. Wrench torque sheet for installation
Additional tightening torque
2. Connecting the cables
The power cord of connect should be selected according to the following specifications sheet.
Rated current of appliance
Nominal cross-sectional area (mm²)
The cable size and the current of the fuse or switch are determined by the maximum current indicated on the
nameplate which located on the side panel of the unit. Please refer to the nameplate before selecting the
cable, fuse and switch.
3. Pipe length and the elevation
Maximum piping length and height difference
Max. length for all rooms (m)
Max. length for one IU (m)
Max. height difference
between IU and OU (m)
Max. height difference between IUs (m)
Additional refrigerant charge
Chargeless pipe
length (m)
Additional
refrigerant charge
(g)
15 x (length for all
rooms - 10)
15 x (length for all
rooms - 15)
15 x (length for all
rooms - 20)
15 x (length for all
rooms - 25)
Caution:
● Refrigerant pipe diameter is different according to indoor unit to be connected. When using the
extension pipe, refer to the tables below.
● When refrigerant pipe diameter is different from that of outdoor unit union (for 18K indoor unit), additional
transfer connector needs to be used on outdoor unit union.

Pipe length and the elevation
70 Installation
Extension pipe diameter (mm/inch)
Outdoor unit union diameter (mm/inch)
Indoor unit A/B/C/D
Liquid

Installation for the first time
Installation 71
4. Installation for the first time
Air and moisture in the refrigerant system have undesirable effects as below:
● Pressure in the system rises.
● Operating current rises.
● Cooling or heating efficiency drops.
● Moisture in the refrigerant circuit may freeze and block capillary tubing.
● Water may lead to corrosion of parts in the refrigerant system.
Therefore, the indoor units and the pipes between indoor and outdoor units must be leak tested and
evacuated to remove gas and moisture from the system.
Gas leak check (Soap water method):
Apply soap water or a liquid neutral detergent on the indoor unit connections or outdoor unit
connections by a soft brush to check for leakage of the connecting points of the piping. If bubbles come out,
the pipes have leakage.
4.1. Air purging with vacuum pump
1) Completely tighten the flare nuts of the indoor and outdoor units, confirm that both the 2-way and 3-way
valves are set to the closed position.
2) Connect the charge hose with the push pin of handle lo to the 3-way valves gas service port..
3) Connect the charge hose of handle hi connection to the vacuum pump.
4) Fully open the handle Lo of the manifold valve.
5) Operate the vacuum pump to evacuate.
6) Make evacuation for 30 minutes and check whether the compound meter indicates -0.1Mpa. If
the meter does not indicate -0.1Mpa after pumping 30 minutes, it should be pumped 20 minutes more. If the
pressure can’t achieve -0.1Mpa after pumping 50 minutes, please check if there are some leakage points.
Fully close the handle Lo valve of the manifold valve and stop the operation of the vacuum pump. Confirm
that the gauge needle does not move (approximately 5 minutes after turning off the vacuum pump).
7) Turn the flare nut of the 3-way valves about 45° counterclockwise for 6 or 7seconds after the gas

Installation for the first time
72 Installation
coming out, then tighten the flare nut again. Make sure the pressure display in the pressure indicator is a
little higher than the atmosphere pressure. Then remove the charge hose from the 3 way valve.
8) Fully open the 2 way valve and 3 way valve and securely tighten the cap of the 3 way valve.
4.2. Air purging by refrigerant
Procedure:
1). Confirm that both the 2-way and 3-way valves are set to the closed position.
2). Connect the charge set and a charging cylinder to the service port of the 3-way valve.
3). Air purging.
Open the valves on the charging cylinder and the charge set. Purge the air by loosening the flare nut on the
2-way valve approximately 45’ for 3 seconds then closing it for 1 minute; repeat 3 times.
After purging the air, use a torque wrench to tighten the flare nut on the 2-way valve.
4). Check the gas leakage.
Check the flare connections for gas leakage.
5). Discharge the refrigerant.
Close the valve on the charging cylinder and discharge the refrigerant by loosening the flare nut on the
2-way valve approximately 45’ until the gauge indicates 0.3 to 0.5 Mpa.
6). Disconnect the charge set and the charging cylinder, and set the 2-way and 3-way valves to the open
position.
Be sure to use a hexagonal wrench to operate the valve stems.
7). Mount the valve stems nuts and the service port cap.

Installation for the first time
Installation 73
Be sure to use a torque wrench to tighten the service port cap to a torque 18N·m.
Be sure to check the gas leakage.
4.3. Adding the refrigerant if the pipe length >5m
Procedure:
1). Connect the charge hose to the charging cylinder, open the 2-way valve and the 3-way valve.
Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the
cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure the liquid charge.
2). Purge the air from the charge hose.
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be
careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic scale and record the weight.
4) Operate the air conditioner at the cooling mode.
5) Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.
6).When the electronic scale displays the proper weight (refer to the table), disconnect the charge hose from
the 3-way valve’s service port immediately and turn off the air conditioner before disconnecting the hose.
7). Mount the valve stem caps and the service port
Use torque wrench to tighten the service port cap to a torque of 18N.m.
Be sure to check for gas leakage.

Adding the refrigerant after running the system for many years
74 Installation
5. Adding the refrigerant after running the system for many years
Procedure:
1). Connect the charge hose to the 3-way service port, open the 2-way valve and the 3-way valve.
Connect the charge hose to the valve at the bottom of the cylinder. If the refrigerant is R410A, make the
cylinder bottom up to ensure liquid charge.
2). Purge the air from the charge hose.
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be
careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic scale and record the weight.
4) Operate the air conditioner at the cooling mode.
5) Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.
6).When the electronic scale displays the proper weight (refer to the gauge and the pressure of the low side),
disconnect the charge hose from the 3-way valve’s service port immediately and turn off the air conditioner
before disconnecting the hose.
7). Mount the valve stem caps and the service port
Use torque wrench to tighten the service port cap to a torque of 18N.m.
Be sure to check for gas leakage.

Re-installation while the indoor unit need to be repaired
Installation 75
6. Re-installation while the indoor unit need to be repaired
6.1. Collecting the refrigerant into the outdoor unit
Procedure
1). Confirm that both the 2-way and 3-way valves are set to the opened position
Remove the valve stem caps and confirm that the valve stems are in the opened position.
Be sure to use a hexagonal wrench to operate the valve stems.
2). Connect the charge hose with the push pin of handle lo to the 3-way valves gas service port.
3). Air purging of the charge hose.
Open the handle Lo valve of the manifold valve slightly to purge air from the charge hose for 5 seconds and
then close it quickly.
4). Set the 2-way valve to the close position.
5). Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 0.1MPa.
6). Set the 3-way valve to the closed position immediately
Do this quickly so that the gauge ends up indicating 0.3 to 0.5Mpa.
Disconnect the charge set, and tighten the 2-way and 3-way valve’s stem nuts.
Use a torque wrench to tighten the 3-way valves service port cap to a torque of 1.8 kgf.m.
Be sure to check for gas leakage.

Re-installation while the indoor unit need to be repaired
76 Installation
6.2. Air purging by the refrigerant
Procedure:
1). Confirm that both the 2-way and 3-way valves are set to the closed position.
2). Connect the charge set and a charging cylinder to the service port of the 3-way valve
Leave the valve on the charging cylinder closed.
3). Air purging.
Open the valves on the charging cylinder and the charge set. Purge the air by loosening the flare nut on the
2-way valve approximately 45’ for 3 seconds then closing it for 1 minute; repeat 3 times.
After purging the air, use a torque wrench to tighten the flare nut on the 2-way valve.
4). Check the gas leakage
Check the flare connections for gas leakage.
5). Discharge the refrigerant.
Close the valve on the charging cylinder and discharge the refrigerant by loosening the flare nut on the
2-way valve approximately 45’ until the gauge indicates 0.3 to 0.5 Mpa.
6). Disconnect the charge set and the charging cylinder, and set the 2-way and 3-way valves to the open
position
Be sure to use a hexagonal wrench to operate the valve stems.
7). Mount the valve stems nuts and the service port cap
Be sure to use a torque wrench to tighten the service port cap to a torque 18N.m.

Re-installation while the outdoor unit need to be repaired
Installation 77
Be sure to check the gas leakage.
7. Re-installation while the outdoor unit need to be repaired
7.1. Evacuation for the whole system
Procedure:
1). Confirm that both the 2-way and 3-way valves are set to the opened position.
2). Connect the vacuum pump to 3-way valve’s service port.
3). Evacuation for approximately one hour. Confirm that the compound meter indicates -0.1Mpa.
4). Close the valve (Low side) on the charge set, turn off the vacuum pump, and confirm that the gauge
needle does not move (approximately 5 minutes after turning off the vacuum pump).
5). Disconnect the charge hose from the vacuum pump.

Re-installation while the outdoor unit need to be repaired
78 Installation
7.2. Refrigerant charging
Procedure:
1). Connect the charge hose to the charging cylinder, open the 2-way valve and the 3-way valve
Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the
cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure liquid charge.
2). Purge the air from the charge hose
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be
careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic scale and record the weight.
4). Open the valves (Low side) on the charge set and charge the system with liquid refrigerant
If the system cannot be charge with the specified amount of refrigerant, or can be charged with a little at a
time (approximately 150g each time) , operating the air conditioner in the cooling cycle; however, one time is
not sufficient, wait approximately 1 minute and then repeat the procedure.
5).When the electronic scale displays the proper weight, disconnect the charge hose from the 3-way valve’s
service port immediately
If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air
conditioner before disconnecting the hose.
6). Mounted the valve stem caps and the service port
Use torque wrench to tighten the service port cap to a torque of 18N.m.
Be sure to check for gas leakage

Electrical Control System
Electrical Control System 79
Part 5
Electrical Control System
1. Electrical Control Function ........................................... 80
2. Troubleshooting ............................................................. 94

Electrical Control Function
80 Electrical Control System
1. Electrical Control Function
1.1 Definition
T1: Room Air Thermistor (RAT)
T2: Indoor Coil Thermistor (ICT)
T2B: Indoor Return Gas Thermistor (RGT)
T3: Outdoor Coil Thermistor (OCT)
T4: Outdoor Air Thermistor (OAT)
T5: Compressor Discharge Thermistor (CTT)
1.2 Main Protection
1.2.1 Three minutes delay at restart for compressor.
1.2.2 Temperature protection of compressor discharge
When the compressor discharge temp. is getting higher, the running frequency will be limited as below rules:
----If 102℃<T5<115℃, decrease the frequency to the lower level every 2 minutes till to F1.
---If T5>115℃ for 10 seconds, the compressor will stop and restart till T5<90℃.
1.2.3 Sensor protection at open circuit and breaking disconnection.
1.2.4 Indoor fan delayed open function
When the unit starts up, the louver will be active immediately and the indoor fan will open 10s later.
If the unit runs in heating mode, the indoor fan will be also controlled by anti-cold wind function.
1.2.5 Fan speed is out of control(Excluding ELSI-JKD009-N11)
When indoor fan speed keeps too low for certain time, the unit will stop and the LED will display the failure.
1.2.6 Zero crossing detection error protection(only for ELSI-JKD009-N11)
If AC detects time interval is not correct for continuous 240s, the unit will stop and the LED will display the
failure. The correct zero crossing signal time interval should be between 6-13ms.
1.2.7 Inverter module protection
The Inverter module has a protection function about current, voltage and temperature. If these protections
happen, the corresponding code will display on indoor unit and the unit will stop working.
1.2.8 Compressor current limit protection
If the compressor current exceeds the current limit value for 10 seconds, the compressor frequency will be
limited as below table.
Cooling mode:
Decrease the frequency to COOL_F4 and run at COOL_F4 for
3 minutes.
After that, the frequency will be adjusted according to the
capacity demand and rise to the upper level every 3 minutes
(When the frequency>COOL_F4 via capacity demand).

Electrical Control Function
Electrical Control System 81
If the current frequency is lower than COOL_F4, the frequency will not be limited.
After 10s of the compressor start, if the current>ICOOL, the AC will display the failure for 30 seconds and stop. The AC
will restart 3 minutes later.
Decrease the frequency to HEAT_F4 and run at HEAT_F4 for
3 minutes.
After that, the frequency will be adjusted according to the
capacity demand and rise to the upper level every 3 minutes
(When the frequency>Heat_F4 via capacity demand).
If the current frequency is lower than HEAT_F4, the frequency will not be limited.
After 10s of the compressor start, if the current>IHEAT, the AC will display the failure for 30 seconds and stop. The AC
will restart 3 minutes later.
1.2.9 Indoor / outdoor units communication protection
If the indoor units cannot receive the feedback signal from the outdoor units for 2 minutes, the AC will stop
and display the failure.
1.2.10 Oil return
Running rules:
1. If the compressor frequency keeps lower than RET_OIL_FREQ1_ADD for RET_OIL_TIME1_ADD, the
AC will rise the frequency to RET_OIL_FREQ2_ADD for RET_OIL_TIME2_ADD and then resume to
former frequency.
2. The EXV will keep 300p while the indoor units will keep the current running mode.
3. If the outdoor ambient is higher than TempT4HeatLimit_ADD during the oil return, the AC quit oil return.
1.3 Operation Modes and Functions
1.3.1 Fan mode
(1) Outdoor fan and compressor stop.
(2) Temperature setting function is disabled, and no setting temperature is displayed.
(3) Indoor fan can be set to high/med/low/auto;
(4) The louver operates same as in cooling mode.
(5) Auto fan:
For Cassette、Duct

Electrical Control Function
82 Electrical Control System
3.5
3.0
High
Low
1.0
Medium
1.5
a
b
c
d
5.0
4.0
2.5
1.0
6.0
T1-24
e
H
(H-L)*0.75+L
(H-L)*0.5+L
(H-L)*0.25+L
L
1.3.2 Cooling Mode
1.3.2.1 Compressor running rules
The compressor will run at corresponding frequency according to the gross amendatory capacity demand.
Amendatory capacity demand.
Meanwhile the maximum running frequency will be adjusted according to the outdoor ambient temp.
43
41
38
T4LimFre1_ADD
No limit
T4LimFre2_ADD
T4LimFre3_ADD
42
39
37
49
46
T4LimFre4_ADD
T4LimFre5_ADD
48
45
1.3.2.2 Outdoor fan running rules

Electrical Control Function
Electrical Control System 83
T4
A DC_FAN_HI_SPD_ADD
B DC_FAN_MID_SPD_ADD
C DC_FAN_MIN_SPD_ADD
D DC_FAN_SLOW_SPD_ADD
E DC_FAN_SSLOW_SPD_ADD
1.3.2.3 Indoor fan running rules
For Cassette、A5
In cooling mode, indoor fan runs all the time and the speed can be selected as high, medium, low and auto.
The auto fan:
3.5
3.0
High
Low
1.0
Medium
1.5
For JKD,HND, Console:
In cooling mode, indoor fan runs all the time and the speed can be selected as high, medium, low and auto.
When the compressor is running, the indoor fan is controlled as below:

Electrical Control Function
84 Electrical Control System
The auto fan acts as below rules:
a
b
c
d
5.0
4.0
2.5
1.0
6.0
T1-Ts
e
H
(H-L)*0.75+L
(H-L)*0.5+L
(H-L)*0.25+L
L
1.3.2.4 Condenser temperature protection
When T3>65℃ for 3 seconds, the compressor will stop while the indoor fan and outdoor fan will continue.
When T3<52℃, the protection will release and the compressor will restart after 3 minutes.
1.3.2.5 Evaporator low temperature protection
When T2B<0℃ for 250 seconds, the indoor unit has no capacity demand and resume till T2B>10℃.
When T2<4℃, the indoor has no capacity demand and resume till T2>8℃.
1.3.3 Heating Mode
1.3.3.1 Compressor running rules
The compressor will run at corresponding frequency according to the gross amendatory capacity demand.
Amendatory capacity demand.
1.3.3.2 Outdoor fan running rules:

Electrical Control Function
Electrical Control System 85
T4
E DC_FAN_SSLOW_SPD_ADD
D DC_FAN_SLOW_SPD_ADD
C DC_FAN_MIN_SPD_ADD
B DC_FAN_MID_SPD_ADD
A DC_FAN_HI_SPD_ADD
1.3.3.3 Indoor fan running rules:
For JKD,HND, Console
In heating mode, indoor fan can be selected as high, medium, low, auto and silent. The anti-cold-wind
function has the priority.
When the compressor is running, the indoor fan is controlled as below:
If the compressor stops caused by the room temperature rising, the indoor fan will be forced to run 127
seconds with breeze. During this period, the anti-cold-wind is disabled.
Auto fan action in heating mode:

Electrical Control Function
86 Electrical Control System
-1.0
-2.0
-3.0
-4.0
0.0
T1-Ts+ΔT
L
(H+-L)*0.4+L
(H+-L)*0.6+L
-5.0
-6.0
-6.5
H+
(H+-L)*0.8+L
(H+-L)*0.6+L
(H+-L)*0.2+L
For Cassette & Duct:
When the compressor is on, the indoor fan can be set to high, medium, low and auto. And the anti-cold wind
function has the priority.
Auto fan action:
-3.5
T1-Ts-ΔT
-4
High
Low
-5
Medium
-4.5
1.3.3.4 Prevent Over-Heating
In heating mode, when the indoor unit has no capacity requirement due to indoor room temperature
increased, the Indoor fan will run in super breeze. (Anti-cold wind function has the priority)
1.3.3.5 Defrosting mode:
Condition of defrosting:
If any one of the following items is satisfied, AC will enter the defrosting mode.
After the compressor starts up and keeps running, mark the minimum value of T3 from the 10th minutes to
15th minutes as T30.
1)If the compressor cumulate running time is up to 29 minutes and T3< TCDI1, T3+T30SUBT3ONE≦T30.
2)If the compressor cumulate running time is up to 35 minutes and T3< TCDI2, T3+T30SUBT3TWO≦T30.
3)If the compressor cumulate running time is up to 29 minutes and T3< TCDI3 for 3 minutes.
4)If the compressor cumulate running time is up to 120 minutes and T3<-15℃.
Condition of ending defrosting:
If any one of the following items is satisfied, the defrosting will finish and the machine will turn to normal
heating mode.

Electrical Control Function
Electrical Control System 87
----T3 rises to be higher than TCDE1℃.
----T3 keeps to be higher than TCDE2℃ for 80 seconds.
----The machine has run for 10 minutes in defrosting mode.
Defrosting action:
PMV running
4 mins with 480P
1.3.3.5 High evaporator coil temp.T2 protection:
If T2>63℃, the indoor unit has no capacity demand and resume till 48℃.
.
1.3.4 Auto-mode
This mode can be chosen with remote controller and the setting temperature can be changed between
17~30℃.
In auto mode, the machine will choose cooling, heating or fan-only mode according to ΔT (ΔT =T1-Ts).
Indoor fan will run at auto fan of the relevant mode.
The louver operates same as in relevant mode.
If the machine switches mode between heating and cooling, the compressor will keep stopping for 15
minutes and then choose mode according to T1-Ts.
If the setting temperature is modified, the machine will choose running function again.
1.3.5 Drying mode
JKD,HND(9K,12K)
Indoor fan speed is fixed at breeze and can’t be changed. The louver angle is the same as in cooling mode.

Electrical Control Function
88 Electrical Control System
Low indoor room temperature protection
All protections are active and the same as that in cooling mode.
For other models:
Indoor fan speed is fixed at breeze and can’t be changed. The louver angle is the same as in cooling mode.
Low indoor room temperature protection
In drying mode, if room temperature is lower than 10℃, the compressor will stop and not resume until room
temperature exceeds 12℃.
All protections are active and the same as that in cooling mode.
1.3.6 Timer function
1.3.6.1 Timing range is 24 hours.
1.3.6.2 Timer on. The machine will turn on automatically when reaching the setting time.
1.3.6.3 Timer off. The machine will turn off automatically when reaching the setting time.
1.3.6.4 Timer on/off. The machine will turn on automatically when reaching the setting “on” time, and then
turn off automatically when reaching the setting “off” time.
1.3.6.5 Timer off/on. The machine will turn off automatically when reaching the setting “off” time, and then
turn on automatically when reaching the setting “on” time.
1.3.6.6 The timer function will not change the AC current operation mode. Suppose AC is off now, it will not
start up firstly after setting the “timer off” function. And when reaching the setting time, the timer LED will be
off and the AC running mode has not been changed.
1.3.6.7 The setting time is relative time.
1.3.7 Economy function
1.3.7.1 The sleep function is available in cooling, heating or auto mode.
1.3.7.2. Operation process in sleep mode is as follow:
When cooling, the setting temperature rises 1℃ (be lower than 30℃) every one hour, 2 hours later the
setting temperature stops rising and the indoor fan is fixed at low speed.
When heating, the setting temperature decreases 1℃ (be higher than 17℃) every one hour, 2 hours later
the setting temperature stops rising and indoor fan is fixed at low speed. (Anti-cold wind function has the
priority).
1.3.7.3 Operation time in sleep mode is 7 hours. After 7 hours the AC quits this mode, the unit will turn off.
1.3.7.4 Timer setting is available
1.3.8 Auto-Restart function
The indoor unit is equipped with auto-restart function, which is carried out through an auto-restart module. In
case of a sudden power failure, the module memorizes the setting conditions before the power failure. The
unit will resume the previous operation setting (not including Swing function) automatically after 3 minutes
when power returns.
1.3.10 Forced operation function

Electrical Control Function
Electrical Control System 89
1.3.10.1 Enter forced operation function:
Press the touch button continually, the AC will run as below sequence:
Forced auto→Forced cooling→Off
When the machine is off, pressing the touch button will carry the machine to forced auto mode, after this, if
pressing the button once again, the machine will turn into forced cooling mode.
In forced cooling mode, pressing touch button will turn off the machine.
1.3.10.2 In forced operation mode, all general protections and remote control are available.
1.3.10.3 Operation rules:
Forced cooling mode:
The compressor runs at F2 frequency and indoor fan runs as breeze. After running for 30 minutes. the
machine will turn to auto mode as 24℃ setting temperature.
Forced auto mode:
The action of forced auto mode is the same as normal auto mode with 24℃ setting temperature.
1.3.10.4 When there’s indoor unit running in forced cooling, it is the master forced cooling unit. Other indoor
units will run at forced cooling mode too and they will be the slave forced cooling units. The slave forced
cooling units cannot quit forced cooling mode until the master forced cooling unit quit, and turn to cooling
mode in low speed with 24℃ setting temperature.
1.3.10.5 The slave forced cooling units will not be controlled by other signals.
1.3.11 Drain pump control (For Cassette)
Adopt the water-level switch to control the action of drain pump.
Main action under different condition :( every 5 seconds the system will check the water level one time)
1. When the A/C operates with cooling (including auto cooling) and forced cooling mode, the pump will start
running immediately and continuously, till stop cooling.
2. Once the water level increase and up to the control point, LED will alarm and the drain pump open and
continue checking the water level. If the water level fall down and LED disalarmed (drain pump delay close 1
minute) and operate with the last mode. Otherwise the entire system stop operating ( including the pump)
and LED remain alarming after 3 minutes.
1.3.12 Follow me
1) If the indoor PCB receives the signal which results from pressing the FOLLOW ME button on remote
controller, the buzzer will emit a sound and this indicates the follow me function is initiated. But when the
indoor PCB receives signal which sent from remote controller every 3 minutes, the buzzer will not
respond. When the unit is running with follow-me function, the PCB will control the unit according to the
temperature from follow-me signal, and the temperature collection function of room temperature sensor
will be shielded.
2) When the follow-me function is available, the PCB will not respond according to the setting temperature
from follow-me signal every 3 minutes.

Electrical Control Function
90 Electrical Control System
3) The PCB will take action to the mode change information from remote controller signal, and the
follow-me function will be turned off. (if the wired remote controller does not initiate follow me function).
4) When the unit is running with follow-me function, if the PCB doesn’t receive any signal from remote
controller for 7 minutes or pressing FOLLOW ME button again, the follow-me function will be turned off
automatically, and the temperature collection function of room temperature sensor will be available, the
PCB will control the unit according to the room temperature detected from its own room temperature
sensor and setting temperature.
5) When the indoor PCB receives the follow-me signal from wired remote controller, the control is the
same as that from wireless remote controller, but buzzer will not respond. When the PCB receives
turning-off follow-me signal from wired remote controller, the unit will quit follow-me function at once.
The follow-me function controlled by wired remote controller prevails that by wireless remote controller.
1.3.13 8℃ Heating(optional)
In heating operation, the preset temperature of the air conditioner can be as lower as 8℃, which keeps the
room temperature steady at 8℃ and prevents household things freezing when the house is unoccupied for
a long time in severe cold weather.
1.3.14 Mode conflict
The indoor units cannot work cooling mode and heating at same time.
Heating mode has a priority.
(1) Definition
No: No mode conflict;
Yes: Mode conflict
(2) Unit action
In case of one Indoor unit working in cooling mode or fan mode, and another indoor unit is set to heating
mode, the indoor unit working in cooling mode or fan mode will change to off. The outdoor unit will
change to heating mode after compressor stop 3 minutes. .
In case of one Indoor unit working in heating mode, and another indoor unit is set to cooling mode or fan
mode, the indoor unit setting to cooling mode or fan mode will change to stand by. The outdoor unit will
continue working in heating mode.
If heating mode stops (not including the indoor unit in heating mode reaching the set temperature), 3
minutes after the outdoor unit restarts and works in cooling mode or fan-only mode.
1.3.15 Point Check Function
There is a check switch in outdoor PCB.
Press the switch SW1 to check the states of unit when the unit is running.
Press the switch N times it will display the content corresponding to No. N. After getting into the check
function, it will display No. N with 1.5s, meanwhile the low bit decimal of digit display flashing, indicated to
get into the check function display. After 1.5s, it will display the content corresponding to No. N.

Electrical Control Function
Electrical Control System 91
The digital display tube will display the follow procedure when push SW1 each time.
Display running frequency, running state or malfunction code
No. of indoor units in good connection
Outdoor unit running mode code
Off:0,Fan only 1, Cooling:2, Heating:3, Forced cooling:4
The capacity unit is horse power. If the indoor unit is not connected,
the digital display tube will show: “――”
(7K:0.8HP, 9K:1HP,12K:1.2HP,18K:1.5HP)
A Indoor unit capacity demand code
Norm value*HP
(7K:0.8HP, 9K:1HP,12K:1.2HP,18K:1.5HP)
B Indoor unit capacity demand code
C Indoor unit capacity demand code
D Indoor unit capacity demand code
E Indoor unit capacity demand code
Total indoor units amendatory capacity
demand code
The frequency corresponding to the total
indoor units amendatory capacity demand
The frequency after the frequency limit
The frequency sending to compressor
control chip
A indoor unit evaporator outlet temp.(T2BA)
If the temp. is lower than -9 degree, the digital display tube will show
“-9”.If the temp. is higher than 70 degree, the digital display tube will
show “70”. If the indoor unit is not connected, the digital display tube
will show: “――”
B indoor unit evaporator outlet temp.(T2BB)
C indoor unit evaporator outlet temp.(T2BC)
D indoor unit evaporator outlet temp.(T2BD)
E indoor unit evaporator outlet temp.(T2BE)
A indoor unit room temp.(T1A)
If the temp. is lower than 0 degree, the digital display tube will show
“0”.If the temp. is higher than 50 degree, the digital display tube will
show “50”. If the indoor unit is not connected, the digital display tube
will show: “――”
B indoor unit room temp.(T1B)
C indoor unit room temp.(T1C)
D indoor unit room temp.(T1D)
E indoor unit room temp.(T1E)
A indoor unit evaporator temp.(T2A)
If the temp. is lower than -9 degree, the digital display tube will show
“-9”.If the temp. is higher than 70 degree, the digital display tube will
show “70”. If the indoor unit is not connected, the digital display tube
will show: “――”
B indoor unit evaporator temp.(T2B)
C indoor unit evaporator temp.(T2C)
D indoor unit evaporator temp.(T2D)
E indoor unit evaporator temp.(T2E)
Outdoor ambient temp.(T4)
Compressor discharge temp.(T5)
The display value is between 30~129 degree. If the temp. is lower
than 30 degree, the digital display tube will show “30”.If the temp. is
higher than 99 degree, the digital display tube will show single digit
and tens digit. For example, the digital display tube show “0.5”,it
means the compressor discharge temp. is 105 degree.)
The display value is hex number.
For example ,the digital display tube show “Cd”, it means AD value is
205.
EXV open angle for A indoor unit
Actual data/4.
If the value is higher than 99, the digital display tube will show single
digit and tens digit.
For example ,the digital display tube show “2.0”,it means the EXV
open angle is 120×4=480p.)
EXV open angle for B indoor unit
EXV open angle for C indoor unit
EXV open angle for D indoor unit

Electrical Control Function
92 Electrical Control System
EXV open angle for E indoor unit
Frequency limit caused by IGBT
radiator
The display value
is hex number. For
example, the
digital display tube
show 2A,then
Bit5=1, Bit3=1,
Bit1=1.
It means
frequency limit
caused by T4,T3
and current.
Frequency limit caused by PFC
Frequency limit caused by T4.
Frequency limit caused by T2.
Frequency limit caused by T3.
Frequency limit caused by T5
Frequency limit caused by current
Frequency limit caused by voltage
(Sum T2 value of all indoor units)/( number of indoor units in good
connection)
Outdoor unit fan motor state
Off:0, High speed:1, Med speed:2, Low speed:3 Breeze:4, Super
breeze:5
The last error or protection code
00 means no malfunction and protection
The following items from 1.3.12.1 to 1.3.12.5 are for the explanation of the point check functions.
1.3.12.1 Frequency of compressor:
Frequency of compressor (Hz)
1.3.12.3 Capacity demand:
Cooling mode
T1 Ts
3
1
1
e
c
a
4
2
0
2
3
0
1
f
d
b
T1 Ts
4
0
a
3
1
-1
3
1
2
0
b
c
d
e
f
2

Electrical Control Function
Electrical Control System 93
1.3.12.4 Number of indoor unit
1.3.12.5 Opening degree of electronic expansion valve:
Actual opening degree equals the display data times 4

Troubleshooting
94 Electrical Control System
2. Troubleshooting
2.1 Display board
2.1.1 Icon explanation on indoor display board (JKD& HND).
ION indication lamp(optional function):This lamp illuminates when Clean Air
feature is activated.
DEFROST indication lamp(For cooling & heating models only): Lights up
when the air conditioner starts defrosting automatically or when the warm air
control feature is activated in heating operation.
OPERATION indication lamp:This lamp illuminates when the air conditioner is in
operation.
TIMER indication lamp:Lights up during Timer operation.
Temperature indicator:Displays the temperature settings when the air conditioner
is operational. Displays the malfunction code.
2.1.2 Icon explanation on indoor display board (Duct)
PRE-DEF indicator(cooling and heating type)
or fan only indicator(cooling only type)

Troubleshooting
Electrical Control System 95
2.1.3 Icon explanation on indoor display board (Compact cassette).
2.1.4 Icon explanation on indoor display board (Console)
2.1.5 Outdoor unit’s digital display tube
There is a digital display tube in outdoor PCB.
Digital display tube display function
In standby , the LED displays “- -”
In compressor operation, the LED display the running frequency,
In defrosting mode, The LED displays “dF” or alternative displays between running frequency and
“dF”(each displays 0.5s)
In compressor pre-heating, The LED displays “PH” or alternative displays between running frequency
and “PH”(each displays 0.5s)
During the oil return process, The LED displays “RO” or alternative displays between running
frequency and “RO”(each displays 0.5s)
In low ambient cooling mode, the LED displays “LC” or alternative displays between running
frequency and “LC”(each displays 0.5s)
In forced cooling mode, the LED displays “FC” or alternative displays between running frequency and
“FC”(each displays 0.5s)
When PFC module protection occurs three times within 15 minutes, the LED displays “E6” or
alternative displays between running frequency and “E6”(each displays 0.5s)
In protection or malfunction, the LED displays error code or protection code.
PRE-DEF indicator(cooling and
heating type)
or fan only indicator(cooling only
type)
Infrared signal receiver
Operation temp.
PRE-DEF indicator(cooling and
heating type)
or fan only indicator(cooling only
type)

Troubleshooting
96 Electrical Control System
2.2 Indoor unit malfunction
For JKD,HND
Operation lamp flash times
Indoor EEPROM malfunction
Indoor / outdoor units communication error
Indoor fan speed has been out of control
Open or short circuit of T1 temperature sensor
Open or short circuit of T2 temperature sensor
Open or short circuit of T4 temperature sensor
Open or short circuit of T3 temperature sensor
Open or short circuit of T5 temperature sensor
Outdoor EEPROM parameter error
Outdoor fan speed out of control
Open or short circuit of T2B temperature sensor
Inverter compressor drive protection
O(light) X(off) ☆(flash)
For Cassette & Duct:
Open or short circuit of T1 temperature sensor
Open or short circuit of T2 temperature sensor
Indoor / outdoor units communication error
Indoor EEPROM malfunction
Open or short circuit of T3 or T4 temperature sensor or
Outdoor EEPROM malfunction
Outdoor fan speed has been out of control
Indoor fan speed has been out of control
Outdoor unit over-current protection
Inverter compressor drive protection
☆ Flash(at 2.5Hz) ◎ Flash(at 0.5Hz) O light X(off)
Note: Digital display is only available for A5 duct type.

Troubleshooting
Electrical Control System 97
For Console:
Open or short circuit of T1 temperature sensor
Open or short circuit of T2 temperature sensor
Communication malfunction between indoor and outdoor
units.
Outdoor fan speed has been out of control
Indoor EEPROM malfunction
Open or short circuit of T3 or T4 temperature sensor or
Outdoor unit EEPROM parameter error
Inverter compressor drive protection
Indoor fan Speed has been out of control.
O(light) X(off) ☆(flash at 5Hz) ◎(flash at 0.5Hz)

Troubleshooting
98 Electrical Control System
2.3 Outdoor unit malfunction
Outdoor EEPROM malfunction
Indoor / outdoor units communication error
Communication malfunction between IPM board and outdoor main board
Open or short circuit of outdoor unit temperature sensor(T3,T4,T5,T2B)
Outdoor fan speed has been out of control
No A Indoor unit coil outlet temperature sensor or connector of sensor is defective
No B Indoor unit coil outlet temperature sensor or connector of sensor is defective
No C Indoor unit coil outlet temperature sensor or connector of sensor is defective
No D Indoor unit coil outlet temperature sensor or connector of sensor is defective
No E Indoor unit coil outlet temperature sensor or connector of sensor is defective
High pressure protection (For ELAU-VCZ430-H11, ELAU-VCZ536-H11)
Low pressure protection (For ELAU-VCZ430-H11, ELAU-VCZ536-H11)
Current protection of compressor
Temperature protection of compressor discharge
High temperature protection of condenser
Note: Once these error codes display, they will disappear in at least 30 seconds if the unit come back to
normal.(Except E3&E4)

Troubleshooting
Electrical Control System 99
2.4 Solving steps for typical malfunction
2.4.1 For the indoor unit
2.4.1.1 Indoor EEPROM malfunction
If the EEPROM chip
is welded on PCB,
replace the PCB
directly. Otherwise,
check whether the
EEPROM chip
plugged in PCB well?
Yes
No
Yes
Insert the EEPROM well
Replace the indoor PCB.
Shut off the power supply and
turn it on 1 minute later. Is it
still displaying the error code?