Electra ECF9 DCI INV, OUECF 9 DCI INV, ECF12 DCI INV, OUECF 12 DCI INV, ECF18 DCI INV Service Manual

...
Page 1
Service Manual
ECF DCI Inverter series
REFRIGERANT
R410A
HEAT PUMP
Indoor Units Outdoor Units
ECF12 DCI INV OUECF 12 DCI INV
ECF18 DCI INV OUECF 18 DCI INV
TM-ECFDCI-E-1-GB 12-2004
Page 2
A
LIST OF EFFECTIVE PAGES
Service Manual − ECF DCI
LIST OF EFFECTIVE PAGES
Note: Changes in the pages are indicated by a “Revision#” in the footer of each effected page
(when none indicates no changes in the relevant page). All pages in the following list represent effected/ non effected pages divided by chapters.
Dates of issue for original and changed pages are:
Original ....... 0 ........ December 2004
Total number of pages in this publication is 70 consisting of the following:
Page No.
Revision No. #
Page No.
Revision No. #
Page No.
Revision No. #
Title ....................... 0
A ........................... 0
i ............................. 0
1-1 - 1-4 ................ 0
2-1 - 2-4 ................ 0
3-1 - 3-2 ................ 0
4-1 - 4-2 ................ 0
5-1 - 5-12 .............. 0
6-1 - 6-8 ................ 0
7-1 - 7-2 ................ 0
8-1 - 8-2 ................ 1
9-1 - 9-2 ................ 0
10-1-10-2 .............. 0
11-1-11-16 ............. 2
12-1-12-8 .............. 0
13-1-13-10 ............ 0
Zero in this column indicates an original page.
*Due to constant improvements please note that the data on this service manual can be modified with out notice. **Photos are not contractual
Page 3
i
TABLE OF CONTENTS
Revision Y05-02Service Manual - ECF DCI
Table of Contents
1. INTRODUCTION ...................................................................................................1-1
2. PRODUCT DATA SHEET ......................................................................................2-1
3. RATING CONDITIONS ..........................................................................................3-1
4. OUTLINE DIMENSIONS .......................................................................................4-1
5. PERFORMANCE DATA .......................................................................................5-1
6. PRESSURE CURVES ...........................................................................................6-1
7. ELECTRICAL DATA ..............................................................................................7-1
8. WIRING DIAGRAMS .............................................................................................8-1
9. REFRIGERATION DIAGRAMS .............................................................................9-1
10. TUBING CONNECTIONS ......................................................................................10-1
11. CONTROL SYSTEM .............................................................................................11-1
12. TROUBLESHOOTING ..........................................................................................12-1
13.
EXPLODED VIEWS AND SPARE PARTS LISTS .................................................13-1
Page 4
1-1
INTRODUCTION
Revision Y05-02Service Manual - ECF DCI
1. INTRODUCTION
1.1 General
The new ECF DCI INVERTERS split Cassette range comprise the following RC (heat pump) models:
ECF 9 DCI INV
ECF 12 DCI INV
ECF 18 DCI INV
The New DCI ECF units can be easily fitted to residential and commercial applications featuring esthetic design, compact dimensions, and low noise operation.
1.2 Main Features
The ECF DCI INV series benefits from the most advanced innovations, namely:
DC Inverter technology
R410A
High COP (level A)
Lego Concept
Pre-Charged units up to the max’ allowing tubing distance
Networking system connectivity
Base heater connection
Cooling operation at outdoor temperature down to -10ºC
Heating operation at outdoor temperature down to -15ºC
Bended indoor coil with treated aluminum fins and coating for improved
efficiency.
Easy access to the interconnecting tubing and wiring connections.
Automatic treated air sweep.
Low indoor and outdoor noise levels.
Easy installation and service.
Page 5
1-2
INTRODUCTION
Revision Y05 Service Manual - ECF DCI
1.3 Filtration
The ECF DC INV series presents several types of air filters:
Easily accessible, and re-usable pre-filters (mesh)
Pre-charged electrostatic filter (disposable)
Active carbon filter (disposable)
1.4 Control
The microprocessor indoor and outdoor controllers, and an infrared remote control, supplied as standard, provide complete operating function and programming.
Remote controllers: RC-2/3/4/5/7, RCW, µBMS
Networking system AircoNet version 4.2 and up, MIU SW version H8 and up For further details please refer to the Operation Manual.
1.5 Outdoor Unit
The ECF DCI INV outdoor units can be installed as floor or wall mounted units by using a wall supporting bracket. The metal sheets are protected by anti- corrosion paint work allowing long life resistance. All outdoor units are pre-charged. For further information please refer to the Product Data Sheet, Chapter 2.
ONG 9 DCI
ONG 12 DCI
ONG 18
Outdoor Unit Features:
Features ONG 9,12, 18, DCI
Display 3 LED’s Base Heater Optional Outdoor Fan Variable Speed DC Inverter
M2L cable Port No
1.6 Tubing Connections
Flare type interconnecting tubing to be produced on site. For further details please refer to the Installation Manual, Chapter 9.
1.7 Accessories
MIU (K) MODBUS Interface Unit
Base heater
M2L cable
1.8 Inbox Documentation
Each unit is supplied with its own installation and operation manuals.
Page 6
1-3
INTRODUCTION
Revision Y05-02Service Manual - ECF DCI
1.9 Matching Table
1.9.1 R410A
OUTDOOR UNITS
INDOOR UNITS
MODEL REF FLO 9DCI FLO12 DCI ECF9 DCI ECF12 DCI ECF18 DCI
OUECF9 DCI R410A
√√
OUECF12 DCI R410A
√√
OUECF18DCI R410A
The above table lists outdoor units and ECF indoor units which can be matched together. In addition the listed outdoor units can be matched with other types of indoor units such as wall mounted,
Page 7
2-1
PRODUCT DATA SHEET
Revision Y05-02Service Manual - ECF DCI
2. PRODUCT DATA SHEET
2.1 ECF25 DCI
Model Indoor Unit ECF25 DCI Model Outdoor Unit ONG25 DCI
Installation Method Flare
Characteristics Units Cooling Heating
Btu/hr
8530 (5120-12970) 11600 (5120-17060)
Capacity
(1)
W
2500 (1500 - 3800) 3400 (1500 - 5000)
Power Input
(1)
W
590 (420-1000) 915 (400-1500)
COP
(1)
W/W
4.24 3.72
Energy Efficiency Class A A
Power Supply V/Ph/Hz
220-240V / 1Ph / 50Hz
Rated Current A
2.7 4.2
Starting Current A
10.50
Circuit Breaker Rating A 16
Fan Type & Quantity Centrifugal*1
Airflow
(2)
H/M/L m3/hr
570-500-435 600-530-450
External Static Pressure Min-Max Pa N/A
Sound Power Level
(3)
H/L dB (A)
42-48 42-47
Sound Pressure Level
(4)
H/L dB (A)
32-38 32-37
Moisture Removal L/hr
1.0
Condensate Drain Tube I.D. mm 16
Dimensions W/H/D mm 571 287 571
Weight kg 22.7
Package Dimensions W/H/D mm 685 415 685
Units per Pallet Units 10
INDOOR
Stacking Height Units 5
Refrigerant Control Electronic Expansion Valve
Compressor Type, Model Single Rotary DC Inverter Panasonic 5RS102XAB
Fan Type & Quantity Axial *1
Airflow H m3/hr 1780
Sound Power Level H dB (A) 60 61
Sound Pressure Level
(4)
H dB (A) 50 51
Dimensions W/H/D mm 795 610 290
Weight kg 40
Package Dimensions W/H/D mm 945 655 393
Units per Pallet Units 9
Stacking Height Units 3
Refrigerant Type R410A
Refrigerant Chargeless Distance g 1100
Additional Charge Per 1 Meter g/m No Need
Liquid Line
(mm)In
(6.35)
¼”
Suction Line
(mm)In
(9.53)
”
Max. Tubing Length m 20
OUTDOOR
Connections Between Units
Max. Height Difference m 10
Operation Control Type IR Remote Control
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
38
395
Page 8
2-2
PRODUCT DATA SHEET
Revision Y05-02 Service Manual - ECF DCI
2.2 ECF35 DCI
Model Indoor Unit ECF35 DCI Model Outdoor Unit ONG35 DCI
Installation Method Flare
Characteristics Units Cooling Heating
Btu/hr
11940 (5100 - 14960) 14620 (5100 - 18700)
Capacity
(1)
W
3500 (1500 - 4400) 4300 (1500 - 5500)
Power Input
(1)
W
950 (420-1250) 1330 (400-1850)
COP
(1)
W/W
3.68 3.23
Energy Efficiency Class A A
Power Supply V/Ph/Hz
220-240V / 1Ph / 50Hz
Rated Current A
4.1 5.6
Starting Current A
10.50
Circuit Breaker Rating A 16
Fan Type & Quantity Centrifugal*1
Airflow
(2)
H/M/L m3/hr
580-510-435 620-560-450
External Static Pressure Min-Max Pa N/A
Sound Power Level
(3)
H/L dB (A)
42-48 42-47
Sound Pressure Level
(4)
H/L dB (A)
32-38 32-37
Moisture Removal L/hr
1.5
Condensate Drain Tube I.D. mm 16
Dimensions W/H/D mm 571 287 571
Weight kg 24.4
Package Dimensions W/H/D mm 685 415 685
Units per Pallet Units 10
INDOOR
Stacking Height Units 5
Refrigerant Control Electronic Expansion Valve
Compressor Type, Model Single Rotary DC Inverter Panasonic 5RS102XAB
Fan Type & Quantity Axial *1
Airflow H m3/hr 1780
Sound Power Level H dB (A)
62 62
Sound Pressure Level
(4)
H dB (A)
52 52
Dimensions W/H/D mm 795 610 290
Weight kg 40
Package Dimensions W/H/D mm 945 655 393
Units per Pallet Units 9
Stacking Height Units 3
Refrigerant Type R410A
Refrigerant Chargeless Distance g 1200
Additional Charge Per 1 Meter g/m No Need
Liquid Line
(mm)In
(6.35)
¼”
Suction Line
(mm)In
(9.53)
”
Max. Tubing Length m 20
OUTDOOR
Connections Between Units
Max. Height Difference m 10
Operation Control Type IR Remote Control
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
38
395
Page 9
2-4
PRODUCT DATA SHEET
Revision Y05-0 Service Manual -ECF DCI
2.4 ECF18 DCI
Model Indoor Unit ECF18 DCI Model Outdoor Unit ONG35 DCI
Installation Method Flare
Characteristics Units Cooling Heating
Btu/hr
17060 (4610 – 21840) 21500 (4610 - 25590)
Capacity
(1)
W
5000 (1350 – 6400) 6300 (1350 – 7500)
Power Input
(1)
W
1550 (530 – 2000) 1740 (350 – 2080)
COP
(1)
W/W
3.23 3.62
Energy Efficiency Class A A
Power Supply V/Ph/Hz
220-240V / 1Ph / 50Hz
Rated Current A
7.1 8.0
Starting Current A
10.50
Circuit Breaker Rating A 16
Fan Type & Quantity Centrifugal*1
Airflow
(2)
H/M/L m3/hr
730-630-510
External Static Pressure Min-Max Pa N/A
Sound Power Level
(3)
H/M/L dB (A)
46 – 55 - 59
Sound Pressure Level
(4)
H/M/L dB (A)
36 – 44 - 48.5
Moisture Removal L/hr
2
Condensate Drain Tube I.D. mm 16
Dimensions W/H/D mm 571 287 571
Weight kg 28
Package Dimensions W/H/D mm 685 415 685
Units per Pallet Units 10
INDOOR
Stacking Height Units 5
Refrigerant Control Electronic Expansion Valve
Compressor Type, Model SCROLL Panasonic 5CS130XCC03
Fan Type & Quantity Axial *1
Airflow H m3/hr 2160
Sound Power Level H dB (A)
62 63
Sound Pressure Level
(4)
H dB (A)
52 53
Dimensions W/H/D mm 795 610 290
Weight kg
43
Package Dimensions W/H/D mm 945 655 393
Units per Pallet Units 9
Stacking Height Units 3
Refrigerant Type R410A
Refrigerant Chargeless Distance g 1500
Additional Charge Per 1 Meter g/m No Need
Liquid Line
(mm)In
(6.35)
¼”
Suction Line
(mm)In
(12.7)
½”
Max. Tubing Length m 30
OUTDOOR
Connections Between Units
Max. Height Difference m 10
Operation Control Type IR Remote Control
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
395
Page 10
3-1
RATING CONDITIONS
Revision Y05-02Service Manual - ECF DCI
3. RATING CONDITIONS
Standard conditions in accordance with ISO 5151, ISO 13253 (for ducted units) and EN 14511.
Cooling:
Indoor: 27
o
C DB 19oC WB
Outdoor: 35
o
C DB
Heating:
Indoor: 20
o
C DB
Outdoor: 7
o
C DB 6oC WB
3.1 Operating Limits
Indoor Outdoor
Cooling
Upper limit 32
o
C DB 23oC WB 46oC DB
Lower limit 21
o
C DB 15oC WB -10oC DB
Heating
Upper limit 27oC DB 24oC DB 18oC WB
Lower limit 10
o
C DB -15oC DB -16oC WB
Voltage
1PH 198 – 264 V
3PH N/A
Page 11
4-1
OUTLINE DIMENSIONS
Revision Y05-02Service Manual - ECF DCI
4. OUTLINE DIMENSIONS
4.1 Indoor Unit: ECF 25, 35, 35S, 50 DCI
4.2
Outdoor Unit: ONG 25, 35, 35S, 50 DCI
Page 12
5-1
PERFORMANCE DATA
Revision Y05-02Service Manual - ECF DCI
5. PERFORMANCE DATA
5.1 ECF25 DCI
5.1.1 Cooling Capacity (kW) - Run Mode
ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC]
OD COIL
ENTERING AIR DB
TEMPERATURE [C
0
]
DATA
22/15 24/17 27/19 29/21 32/23
-10 - 20
(protection range)
TC 80 - 110 % of nominal SC 80 - 105 % of nominal
PI 25 - 50 % of nominal
25
TC 2.42 2.57 2.73 2.89 3.05 SC 2.09 2.13 2.18 2.22 2.26
PI 0.46 0.47 0.48 0.49 0.50
30
TC 2.30 2.46 2.62 2.77 2.93 SC 2.04 2.08 2.12 2.17 2.21
PI 0.52 0.53
0.54
0.54 0.55
35
TC 2.18 2.34
2.50
2.66 2.82
SC 1.98 2.03 2.07 2.11 2.16
PI 0.57 0.58
0.59
0.60 0.61
40
TC 2.07 2.23
2.38
2.54 2.70
SC 1.93 1.97 2.02 2.06 2.10
PI 0.63 0.64 0.64 0.65 0.66
46
TC 1.93 2.09 2.24 2.40 2.56 SC 1.87 1.91 1.95 2.00 2.04
PI 0.69 0.70 0.71 0.72 0.73
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C) ID – Indoor OD – Outdoor
5.1.2 Capacity Correction Factors
Cooling Capacity Ratio Vs. Outdoor Temperature
0.5
0.6
0.7
0.8
0.9
1
1.1
1.2
20 25 30 35 40 45
Outdoor T emperature [deg C]
Capacity Rat ion
Page 13
5-2
PERFORMANCE DATA
Revision Y05-02 Service Manual - ECF DCI
5.1.3 Heating Capacity (kW) - Run Mode
ID COIL ENTERING AIR DB TEMPERATURE [ºC]
OD COIL
ENTERING AIR DB/
WB TEMPERATURE
[ºC]
DATA 15 20 25
-15/-16
TC 2.16 2.01 1.86
PI 0.55 0.60 0.66
-10/-12
TC 2.41 2.26 2.11
PI 0.66 0.72 0.77
-7/-8
TC 2.59 2.44 2.29
PI 0.75 0.80 0.86
-1/-2
TC 2.68 2.53 2.38
PI 0.79 0.84 0.90
2/1
TC 2.75 2.59 2.44
PI 0.82
0.87
0.93
7/6
TC 3.55
3.40
3.25
PI 0.86
0.92
0.97
10/9
TC 3.75
3.60
3.44
PI 0.91 0.97 1.02
15/12
TC 3.94 3.79 3.64
PI 0.96 1.02 1.07
15-24
TC 85 - 105 % of nominal
(Protection Range)
PI 80 - 120 % of nominal
LEGEND
TC – Total Cooling Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C) ID – Indoor OD – Outdoor
5.1.4 Capacity Correction Factors
Heating Capacity Ratio Vs. Outdoor Temperature
0.5
0.6
0.7
0.8
0.9
1
1.1
1.2
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [deg C]
Capacity Rat ion
Page 14
5-3
PERFORMANCE DATA
Revision Y05-02Service Manual - ECF DCI
5.2 Capacity Correction Factor Due to Tubing Length
5.2.1 Cooling
0.91
0.92
0.93
0.94
0.95
0.96
0.97
0.98
0.99
1.00
1.01
3 4 5 6 7 8 9 1011121314151617181920
Tubing Length [m]
Capacity Rati o
5.2.2 Heating
0.90
0.92
0.94
0.96
0.98
1.00
1.02
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Tubing Length [m]
Capacity Ratio
Page 15
5-4
PERFORMANCE DATA
Revision Y05-02 Service Manual - ECF DCI
5.3 ECF35 DCI
5.3.1 Cooling Capacity (kW) - Run Mode
ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC]
OD COIL
ENTERING AIR DB
TEMPERATURE [ºC]
DATA
22/15 24/17 27/19 29/21 32/23
-10 - 20
(protection range)
TC 80 - 110 % of nominal SC 80 - 105 % of nominal
PI 25 - 50 % of nominal
25
TC 3.38 3.60 3.83 4.05 4.27 SC 2.65 2.70 2.75 2.81 2.86
PI 0.75 0.76 0.78 0.79 0.80
30
TC 3.22 3.44 3.66 3.88 4.11 SC 2.58 2.63 2.69 2.74 2.79
PI 0.83 0.85
0.86
0.88 0.89
35
TC 3.06 3.28
3.50
3.72 3.94
SC 2.51 2.57 2.62 2.67 2.73
PI 0.92 0.94
0.95
0.96 0.98
40
TC 2.89 3.12
3.34
3.56 3.78
SC 2.45 2.50 2.55 2.61 2.66
PI 1.01 1.02 1.04 1.05 1.07
46
TC 2.70 2.92 3.14 3.36 3.58 SC 2.37 2.42 2.47 2.53 2.58
PI 1.11 1.13 1.14 1.16 1.17
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C) ID – Indoor
5.3.2 Capacity Correction Factors
Cooling Capacity Ratio Vs. Outdoor Temperature
0.5
0.6
0.7
0.8
0.9
1
1.1
1.2
20 25 30 35 40 45
Outdoor T emperature [de g C]
Capacity Rat ion
Page 16
5-5
PERFORMANCE DATA
Revision Y05-02Service Manual - ECF DCI
5.3.3 Heating Capacity (kW) - Run Mode
ID COIL ENTERING AIR DB TEMPERATURE [ºC]
OD COIL
ENTERING AIR DB/
WB TEMPERATURE
[ºC]
DATA 15 20 25
-15/-16
TC 2.74 2.55 2.35
PI 0.80 0.88 0.96
-10/-12
TC 3.05 2.86 2.66
PI 0.96 1.04 1.12
-7/-8
TC 3.28 3.09 2.90
PI 1.09 1.17 1.25
-1/-2
TC 3.39 3.20 3.01
PI 1.15 1.23 1.31
2/1
TC 3.47 3.28 3.09
PI 1.19
1.27
1.35
7/6
TC 4.49
4.30
4.11
PI 1.25
1.33
1.41
10/9
TC 4.74
4.55
4.36
PI 1.32 1.40 1.49
15/12
TC 4.99 4.80 4.60
PI 1.40 1.48 1.56
15-24
TC 85 - 105 % of nominal
(Protection Range)
PI 80 - 120 % of nominal
LEGEND
TC – Total Cooling Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C) ID – Indoor OD – Outdoor
5.3.4 Capacity Correction Factors
Heating Capacity Ratio Vs. Outdoor Temperature
0.5
0.6
0.7
0.8
0.9
1
1.1
1.2
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [de g C]
Capacity Rat ion
Page 17
5-6
PERFORMANCE DATA
Revision Y05-02 Service Manual - ECF DCI
5.4 Capacity Correction Factor Due to Tubing Length
5.4.1 Cooling
0.91
0.92
0.93
0.94
0.95
0.96
0.97
0.98
0.99
1.00
1.01
3 4 5 6 7 8 9 1011121314151617181920
Tubing Length [m]
Capacity Ratio
5.4.2 Heating
0.90
0.92
0.94
0.96
0.98
1.00
1.02
3 4 5 6 7 8 9 1011121314151617181920
Tubing Length [m]
Capacity Rati o
Page 18
5-7
PERFORMANCE DATA
Revision Y05-02Service Manual - ECF DCI
5.5 ECF35S DCI
5.5.1 Cooling Capacity (kW) - Run Mode
ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC]
OD COIL
ENTERING AIR DB
TEMPERATURE [ºC]
DATA
22/15 24/17 27/19 29/21 32/23
-10 - 20
(protection range)
TC 80 - 110 % of nominal SC 80 - 105 % of nominal
PI 25 - 50 % of nominal
25
TC 3.38 3.60 3.83 4.05 4.27 SC 2.65 2.70 2.75 2.81 2.86
PI 0.68 0.70 0.71 0.72 0.74
30
TC 3.22 3.44 3.66 3.88 4.11 SC 2.58 2.63 2.69 2.74 2.79
PI 0.76 0.78
0.79
0.80 0.82
35
TC 3.06 3.28
3.50
3.72 3.94
SC 2.51 2.57 2.62 2.67 2.73
PI 0.84 0.86
0.87
0.88 0.90
40
TC 2.89 3.12
3.34
3.56 3.78
SC 2.45 2.50 2.55 2.61 2.66
PI 0.92 0.94 0.95 0.96 0.98
46
TC 2.70 2.92 3.14 3.36 3.58 SC 2.37 2.42 2.47 2.53 2.58
PI 1.02 1.03 1.05 1.06 1.07
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C) ID – Indoor OD – Outdoor
5.5.2 Capacity Correction Factors
Cooling Capacity Ratio Vs. Outdoor Temperature
0.5
0.6
0.7
0.8
0.9
1
1.1
1.2
20 25 30 35 40 45
Outdoor Te mperature [deg C]
Capacity Rat ion
Page 19
5-8
PERFORMANCE DATA
Revision Y05-02 Service Manual - ECF DCI
5.5.3 Heating Capacity (kW) - Run Mode
ID COIL ENTERING AIR DB TEMPERATURE [ºC]
OD COIL
ENTERING AIR DB/
WB TEMPERATURE
[ºC]
DATA 15 20 25
-15/-16
TC 2.86 2.66 2.46
PI 0.71 0.78 0.85
-10/-12
TC 3.19 2.99 2.79
PI 0.85 0.93 1.00
-7/-8
TC 3.43 3.23 3.03
PI 0.96 1.03 1.11
-1/-2
TC 3.55 3.35 3.15
PI 1.02 1.09 1.16
2/1
TC 3.63 3.43 3.23
PI 1.05
1.13
1.20
7/6
TC 4.70
4.50
4.30
PI 1.11
1.18
1.25
10/9
TC 4.96
4.76
4.56
PI 1.17 1.25 1.32
15/12
TC 5.22 5.02 4.82
PI 1.24 1.31 1.38
15-24
TC 85 - 105 % of nominal
(Protection Range)
PI 80 - 120 % of nominal
LEGEND
TC – Total Cooling Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C) ID – Indoor OD – Outdoor
5.5.4 Capacity Correction Factors
Heating Capacity Ratio Vs. Outdoor Temperature
0.5
0.6
0.7
0.8
0.9
1
1.1
1.2
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [deg C]
Capacity Ration
Page 20
5-9
PERFORMANCE DATA
Revision Y05-02Service Manual - ECF DCI
15.6 Capacity Correction Factor Due to Tubing Length
5.6.1 Cooling
0.91
0.92
0.93
0.94
0.95
0.96
0.97
0.98
0.99
1.00
1.01
3 4 5 6 7 8 9 1011121314151617181920
Tubing Length [m]
Capacity Ratio
5.6.2 Heating
0.90
0.92
0.94
0.96
0.98
1.00
1.02
3 4 5 6 7 8 9 1011121314151617181920
Tubing Length [m]
Capacity Rati o
Page 21
5-10
PERFORMANCE DATA
Revision Y05-02 Service Manual - ECF DCI
5.7 ECF50 DCI
5.7.1 Cooling Capacity (kW) - Run Mode
ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC]
OD COIL
ENTERING AIR DB
TEMPERATURE [ºC]
DATA
22/15 24/17 27/19 29/21 32/23
-10 - 20
(protection range)
TC 80 - 110 % of nominal SC 80 - 105 % of nominal
PI 25 - 50 % of nominal
25
TC 4.85 5.13 5.42 5.70 5.99 SC 3.30 3.35 3.40 3.45 3.50
PI 1.20 1.23 1.26 1.28 1.31
30
TC 4.60 4.88 5.17 5.45 5.74 SC 3.17 3.22 3.27 3.32 3.37
PI 1.37 1.40
1.42
1.45 1.48
35
TC 4.35 4.63
4.92
5.20 5.49
SC 3.04 3.09 3.14 3.19 3.24
PI 1.54 1.56
1.59
1.62 1.64
40
TC 4.10 4.39
4.67
4.96 5.24
SC 2.91 2.96 3.01 3.06 3.11
PI 1.70 1.73 1.76 1.78 1.81
46
TC 3.80 4.09 4.37 4.66 4.94 SC 2.76 2.81 2.86 2.91 2.95
PI 1.90 1.93 1.96 1.98 2.01
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C) ID – Indoor OD – Outdoor
5.7.2 Capacity Correction Factors
Cooling Capacity Ratio Vs. Outdoor Temperature
0.5
0.6
0.7
0.8
0.9
1
1.1
1.2
20 25 30 35 40 45
Outdoor Temperature [deg C]
Capacity Ration
Page 22
5-11
PERFORMANCE DATA
Revision Y05-02Service Manual - ECF DCI
5.7.3 Heating Capacity (kW) - Run Mode
ID COIL ENTERING AIR DB TEMPERATURE [ºC]
OD COIL ENTERING
AIR DB/WB
TEMPERATURE [ºC]
DATA 15 20 25
-15/-16
TC 2.66 2.28 1.90
PI 1.15 1.23 1.31
-10/-12
TC 3.52 3.13 2.75
PI 1.30 1.38 1.46
-7/-8
TC 4.16 3.77 3.39
PI 1.41 1.49 1.57
-1/-2
TC 4.47 4.09 3.71
PI 1.46 1.55 1.63
2/1
TC 4.69 4.30 3.92
PI 1.50
1.58
1.66
7/6
TC 6.24
5.85
5.47
PI 1.56
1.64
1.72
10/9
TC 6.56
6.18
5.79
PI 1.59 1.67 1.75
15/12
TC 6.88 6.50 6.12
PI 1.62 1.70 1.78
15-24
(Protection Range)
TC 85 - 105 % of nominal
PI 80 - 120 % of nominal
LEGEND
TC – Total Cooling Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C) ID – Indoor OD – Outdoor
5.7.4 Capacity Correction Factors
Heating Capacity Ratio Vs. Outdoor Temperature
0.4
0.5
0.6
0.7
0.8
0.9
1
1.1
1.2
-15 -10 -5 0 5 10 15
Outdoor WB Te mperature [deg C]
Capacity Rat ion
Page 23
5-12
PERFORMANCE DATA
Revision Y05-02 Service Manual - ECF DCI
5.8 Capacity Correction Factor Due to Tubing Length
5.8.1 Cooling
0.993
0.994
0.995
0.996
0.997
0.998
0.999
1.000
1.001
0 5 10 15 20 25 30 35
Tubing Length[m]
Capacity Ratio
5.8.2 Heating
0.86
0.88
0.90
0.92
0.94
0.96
0.98
1.00
1.02
0 5 10 15 20 25 30 35
Tubing Length[m]
Capacity Ratio
Page 24
6-1
PRESSURE CURVES
Revision Y05-02Service Manual - ECF DCI
6. PRESSURE CURVES
6.1 Model: ECF 25 DCI
6.1.1 Cooling – Test Mode
Suction Pressure Vs.Outdoor Temp' - Cooling
500
600
700
800
900
1000
1100
1200
1300
1400
10 15 20 25 30 35 40 45
Outdoor DB Temperature [ºC]
Suction Pressure [kPa]
22/15
24/17
27/19
29/21
32/23
Indoor DB/WB
Temp.
Discharge Pressure Vs.Outdoor Temp'- Cooling
1000
1250
1500
1750
2000
2250
2500
2750
3000
3250
3500
3750
4000
10 15 20 25 30 35 40 45
Outdoor DB Temperature [ºC]
Discharge Pressure [kPa]
22/15
24/17
27/19
29/21
32/23
Indoor
DB/W B
Page 25
6-2
PRESSURE CURVES
Revision Y05-02 Service Manual - ECF DCI
6.1.2 Heading – Test Mode
Suction Pressure Vs. Outdoor Temp' - Heating
200
300
400
500
600
700
800
900
1000
1100
1200
1300
-15 -10 -5 0 5 10 15
Outdoor WB Temperature[ºC]
Suction Pressure [kPa]
15
20
25
Indoor DB
Discharge Pressure Vs.Outdoor Temp'- Heating
1000
1250
1500
1750
2000
2250
2500
2750
3000
3250
3500
3750
4000
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [ºC]
Discharge Pressure [kPa]
15
20
25
Indoor DB
Page 26
6-3
PRESSURE CURVES
Revision Y05-02Service Manual - ECF DCI
6.2 Model: ECF 35 DCI
6.2.1 Cooling – Test Mode
Suction Pressure Vs.Outdoor Temp' - Cooling
500
600
700
800
900
1000
1100
1200
1300
1400
10 15 20 25 30 35 40 45
Outdoor DB Temperature [ºC]
Suction Pressure [kPa]
22/15
24/17
27/19
29/21
32/23
Indoor
DB/W B
Discharge Pressure Vs.Outdoor Temp'- Cooling
1000
1250
1500
1750
2000
2250
2500
2750
3000
3250
3500
3750
4000
10 15 20 25 30 35 40 45
Outdoor DB Temperature [ºC]
Discharge Pressure [kPa]
22/15
24/17
27/19
29/21
32/23
Indoor
DB/WB
Page 27
6-4
PRESSURE CURVES
Revision Y05-02 Service Manual - ECF DCI
6.2.2 Heating – Test Mode
Suction Pressure Vs.Outdoor Temp' - Cooling
500
600
700
800
900
1000
1100
1200
1300
1400
10 15 20 25 30 35 40 45
Outdoor DB Temperature [ºC]
Suction Pressure [kPa]
22/15
24/17
27/19
29/21
32/23
Indoor
DB/W B
Discharge Pressure Vs.Outdoor Temp'- Cooling
1000
1250
1500
1750
2000
2250
2500
2750
3000
3250
3500
3750
4000
10 15 20 25 30 35 40 45
Outdoor DB Temperature [ºC]
Discharge Pressure [kPa]
22/15
24/17
27/19
29/21
32/23
Indoor
DB/WB
Page 28
6-5
PRESSURE CURVES
Revision Y05-02Service Manual - ECF DCI
6.3 Model: ECF 35S DCI
6.3.1 Cooling – Test Mode
Suction Pressure Vs.Outdoor Temp' - Cooling
500
600
700
800
900
1000
1100
1200
1300
1400
10 15 20 25 30 35 40 45
Outdoor DB Temperature[ºC]
Suction Pressure [kPa]
22/15
24/17
27/19
29/21
32/23
Indoor
DB/WB
Discharge Pressure Vs.Outdoor Temp' - Cooling
1000
1250
1500
1750
2000
2250
2500
2750
3000
3250
3500
3750
4000
10 15 20 25 30 35 40 45
Outdoor DB Temperature[ºC]
Discharge Pressure [kPa]
22/15
24/17
27/19
29/21
32/23
Indoor
DB/WB
Page 29
6-6
PRESSURE CURVES
Revision Y05-02 Service Manual - ECF DCI
6.3.2 Heating – Test Mode
Suction Pressure Vs.Outdoor Temp' - Heating
200
300
400
500
600
700
800
900
1000
1100
1200
1300
-15 -10 -5 0 5 10 15
Outdoor WB Temperature[ºC]
Suction Pressure [kPa]
15
20
25
Discharge Pressure Vs.Outdoor Temp' - Heating
1000
1250
1500
1750
2000
2250
2500
2750
3000
3250
3500
3750
4000
-15 -10 -5 0 5 10 15
Outdoor WB Temperature[ºC]
Discharge Pressure [kPa]
15
20
25
Indoor DB
Indoor DB
Page 30
6-7
PRESSURE CURVES
Revision Y05-02Service Manual - ECF DCI
6.4 Model: ECF 50 DCI
6.4.1 Cooling – Test Mode
Suction Pressure Vs.Outdoor Temp' - Cooling
500
600
700
800
900
1000
1100
1200
1300
1400
10 15 20 25 30 35 40 45
Outdoor DB Temperature[ºC]
Suction Pressure [kPa]
22/15
24/17
27/19
29/21
32/23
Indoor
DB/WB
Discharge Pressure Vs.Outdoor Temp' - Cooling
1000
1250
1500
1750
2000
2250
2500
2750
3000
3250
3500
3750
4000
4250
10 15 20 25 30 35 40 45
Outdoor DB Temperature[ºC]
Discharge Pressure [kPa]
22/15
24/17
27/19
29/21
32/23
Indoor
DB/WB
Page 31
6-8
PRESSURE CURVES
Revision Y05-02 Service Manual - ECF DCI
6.4.2 Cooling – Test Mode
Suction Pressure Vs.Outdoor Temp' - Heating
200
300
400
500
600
700
800
900
1000
1100
-15 -10 -5 0 5 10 15
Outdoor WB Temperature[ºC]
Suction Pressure [kPa]
15
20
25
Discharge Pressure Vs.Outdoor Temp' - Heating
1000
1250
1500
1750
2000
2250
2500
2750
3000
3250
3500
3750
4000
-15 -10 -5 0 5 10 15
Outdoor WB Temperature[ºC]
Discharge Pressure [kPa]
15
20
25
Indoor DB
Indoor DB
Page 32
7-1
ELECTRICAL DATA
Revision Y05-02Service Manual - ECF DCI
7. ELECTRICAL DATA
7.1 Single Phase Units
Model ECF 25 DCI ECF35/35S DCI ECF 50 DCI Power Supply 1 PH, 220-240 VAC, 50Hz
Connected to Indoor Maximum Current 10 A 12 A
Inrush Current
(a)
35 A
Starting Current
(b)
10 A 10.5 A
Circuit breaker 16 A 20 A
Power supply wiring no. x cross section 3 X 1.5 mm
2
3 X 2.5 mm
2
Interconnecting cable no. x cross section 4 X 1.5 mm
2
4 X 2.5 mm
2
(a) Inrush current is the current when power is up (charging the DC capacitors
at outdoor unit controller).
(b) Starting current is the current when starting the compressor.
NOTE
Power wiring cord should comply with local lows and electrical regulations requirements
Page 33
8-1
WIRING DIAGRAMS
Revision Y05-02Service Manual - ECF DCI
8. WIRING DIAGRAMS
8.1 ECF25, 35, 35S, 50 DCI
esaB
retaeh
2
kcalB
eulB
deR
MOC
F-L
F-N
N
L
MOCN
HTRAE
MOC
HTRAE
01P
21P
MOC
N L
MOC-N
G/Y
G/Y
HTRAE
V
9P
U
3P
W
31P11P
1
4 P
41P
2
1
1P
lioc ekohC
Brown Red
Black
White
PMOC
Blue
esreveR
evlav
YLPPUS REWOP
gnir citengam
nworB
eulB
deR
ESUF
nworB
deR
G/Y
3/N
4/L
5/C
G/Y
8P
3
lootagem
7P9PJ
5
31 2
5 4
6
6
EEV
3 4
1 2
6P
1
2
71P
Red
61P
Blue
Black
Orange
Yellow
12P
2 2 P
8 1 P
2
91P
1 2
1
2P
11 2
02P
4
TCUS
EARTH
2 1
Vdc
4 3
6 5
Vsp Vcc
FG
NAFO
TCOTTCTAO
yalpsiD
2
eulB
G/Y
nworB
deR
Outdoor Unit Controller PCB
Outdoor Unit Circuit Diagram
EMI filter PCB
Page 34
9-1
REFRIGERATION DIAGRAMS
Revision Y05-02Service Manual -ECF DCI
9. REFRIGERATION DIAGRAMS
9.1 ECF 25, 35,35S, 50 DCI
Page 35
10-1
TUBING CONNECTIONS
Revision Y05-02Service Manual - ECF DCI
10. TUBING CONNECTIONS
TUBE (Inch)
TORQUE (Nm)
¼” ⅜” ½” ⅝” ¾”
Flare Nuts 11-13 40-45 60-65 70-75 80-85 Valve Cap 13-20 13-20 18-25 18-25 40-50
Service Port Cap 11-13 11-13 11-13 11-13 11-13
1. Valve Protection Cap-end
2. Refrigerant Valve Port (use Allen wrench to open/close)
3. Valve Protection Cap
4. Refrigerant Valve
5. Service Port Cap
6. Flare Nut
7. Unit Back Side
8. Copper Tube
When the outdoor unit is installed above the indoor unit an oil trap is required every 5m along the suction line at the lowest point of the riser. Incase the indoor unit is installed above the outdoor, no trap is required.
Page 36
11-1
CONTROL SYSTEM
Revision Y05-02Service Manual - ECF DCI
11. CONTROL SYSTEM
11.1 General Functions and Operating Rules
The DCI software is fully parametric. All the model dependent parameters are shown in Blue color and with Italic style [parameter]. The parameters values are given in the last section of this control logic chapter of the service manual.
11.1.1 System Operation Concept
The control function is divided between indoor and outdoor unit controllers. Indoor unit is the System ‘Master’, requesting the outdoor unit for cooling/heating capacity supply. The outdoor unit is the system nless it enters into a protection mode'Slave’ and it must supply the required capacity avoiding it from supplying the requested capacity. The capacity request is transferred via indoor to outdoor communication, and is represented by a parameter called ‘NLOAD’. NLOAD is an integer number with values between 0 and 127, and it represents the heat or cool load felt by the indoor unit.
11.1.2 Compressor Frequency Control
11.1.2.1 NLOAD setting
The NLOAD setting is done by the indoor unit controller, based on a PI control scheme. The actual NLOAD to be sent to the outdoor unit controller is based on the preliminary LOAD calculation, the indoor fan speed, and the power shedding function.
NLOAD limits as a function of indoor fan speed: Indoor Fan Speed Maximum NLOAD Cooling Maximum NLOAD Heating Low
Max NLOADIF1C
127
Medium
Max NLOADIF2C
127
High
Max NLOADIF3C
127
Turbo
Max NLOADIF4C
127
Auto
Max NLOADIF5C
127
NLOAD limits as a function of power shedding: Mode Power Shedding OFF Power Shedding ON Cool No limit Nominal Cooling Heat No limit Nominal Heating
11.1.3 Target Frequency Setting
The compressor target frequency is a function of the NLOAD number sent from the indoor controller and the outdoor air temperature. Basic Target Frequency Setting:
NLOAD Target Frequency 127
Maximum frequency
10 < NLOAD < 127 Interpolated value between minimum and maximum frequency 10
Minimum frequency
0 Compressor is stopped
Page 37
11-2
CONTROL SYSTEM
Revision Y05-02 Service Manual - ECF DCI
Target frequency limits as a function of outdoor air temperature )OAT(: OAT Range Cool mode limits Heat mode limits OAT No limit<6 6≤OAT<15
MaxFreqAsOAT1H
15 ≤ OAT < 24
MaxFreqAsOATC
24 ≤ OAT No limit
MaxFreqAsOAT2H
11.1.4 Frequency Changes Control
Frequency change rate is 1 Hz/sec.
11.1.5 Compressor Starting Control
Frequency
Time
Min 10 Minutes
1
Minute
Step 1
Step 3
1
Minute
Step 2
11.1.6 Minimum On and Off Time
3 minutes.
11.1.7 Indoor Fan Control
10 Indoor fan speeds are determined for each model. 5 speeds for cool/dry/fan modes and 5 speeds for heat mode. When user sets the indoor fan speed to a fixed speed )Low/ Medium/ High(, unit will operate constantly at set speed. When Auto Fan is selected, indoor unit controller can operate in all speeds. The actual speed is set according to the cool/heat load.
11.1.7.1 Turbo Speed
The Turbo speed is activated during the first 30 minutes of unit operation when auto fan speed is selected and under the following conditions: Difference between set point and actual room temperature is bigger then 3 degrees. Room temperature 22 for cooling, or 25 for heating.><
Page 38
11-3
CONTROL SYSTEM
Revision Y05-02Service Manual - ECF DCI
11.1.8 Heating Element Control
Heating element can be started if LOAD 0.8 mumNLOAD AND Indoor Coil temperature> * Maxi <45. The heating element will be stopped when LOAD 0.5 MaximumNLOAD OR if Indoor Coil<* Temperature 50.>
11.1.9 Outdoor Fan Control
7 outdoor fan speeds are determined for each model. 3 speeds for cool and dry modes, and 3 speeds for heat mode, and a very low speed. Outdoor fan speed is a function of compressor frequency and outdoor air temperature (OAT). 4 routines for fan control are determined. The control routine selection depends on operation mode, compressor speed, outdoor air temperature (OAT) and heat sink temperature (HST).
Routine Conditions A Heating with OAT 15<0C
or Cooling with OAT > 20
0
C, or HST 50>0C or Faulty OAT
B Cooling with 20
0
C>OAT>500C
C Cooling with 7
0
C>OAT
D Heating with OAT 15>
0
C
Outdoor Fan Speed Compressor Frequency (CF) Routine A Routine B Routine C Routine D CF 0 OFF OFF OFF OFF= 10 ≤ CF < OFLowFreq Low Low Very Low Low 10 ≤ CF < OFMedFreq Medium Low Very Low Low
OFMedFreq ≤ CF High Low Low Medium
When compressor is switched to OFF and the heat sink temperature is above 55 degrees, the outdoor fan will remain ON in low speed for up to 3 minutes.
11.1.10 EEV (electronic Ex pansion valve) Control
EEV opening is defined as EEV = EEVOL+ EEV
CV
EEVOLis the initial EEV opening as a function of the compressor frequency, operation mode, unit model and capacity. EEV
CV
is a correction value for the EEV opening that is based on the compressor temperature.
During the first 10 minutes of compressor operation EEV
CV
0.=
Once the first 10 minutes are over, the correction value is calculated as follow: EEV
CV
(n) =
EEV
CV
(N-1) + EEV
CTT
EEV
CTT
is the correction based on the compressor temperature. A target compressor temperature is set depending on frequency and outdoor air temperature, and the actual compressor temperature is compared to the target temperature to set the required correction to the EEV opening.
11.1.11 Reversing Valve (RV) Control
Reversing valve is on in heat mode. Switching of RV state is done only after compressor is off for over 3 minutes.
11.1.12 Ioniser Control
Ioniser is on when unit is on AND indoor fan is on AND Ioniser power switch (on Ioniser) is on.
Page 39
11-4
CONTROL SYSTEM
Revision Y05-02 Service Manual -ECF DCI
11.1.13 Electro Static Filter )ESF( Control
ESF is on when ESF switch is on, Safety switch is pressed, unit is on, AND indoor fan is on.
11.1.14 Base Heater Control
When OAT is connected, Base Heater will be on when unit is in heating and OAT<2
0
C.
When OAT is disconnected, Base Heater will be on when unit is in heating.
11.2 Fan Mode
In high/ medium/ low indoor fan user setting, unit will operate fan in selected speed. In AutoFan user setting, fan speed will be ad ng to the differencejusti automatically according between actual room temperature and user set point temperature.
11.3 Cool Mode
NLOAD is calculated according to the difference between actual room temperature and user set point temperature by PI control. In high/ medium/ low indoor fan user setting, unit will operate fan in selected speed. In AutoFan user setting, fan speed will be ad8usted automatically according to the calculated NLOAD.
11.4 Heat Mode
NLOAD is calculated according to the difference between actual room temperature and user set point temperature by PI control. In high/ medium/ low indoor fan user setting, unit will operate fan in selected speed. In AutoFan user setting, fan speed will be adng to the calculated NLOAD.
11.4.1 Temperature Compensation
In wall mounted, ducted, and cassette models, 3 degrees are reduced from room temperature reading (except when in I-Feel mode), to compensate for temperature difference between high and low areas in the heated room, and for coil heat radiation on room thermistor. The temperature compensation can be enabled/disabled by shortening of J2 on the indoor unit controller.
Model J2 Shorted J2 Opened Wall mounted Compensation
Disabled
Compensation Enabled
Cassette Compensation Enabled Compensation Disabled Ducted Compensation Enabled Compensation Disabled Floor/Ceiling Compensation
Disabled
Compensation Enabled
Page 40
11-5
CONTROL SYSTEM
Revision Y05-02Service Manual - ECF DCI
11.4.2 Indoor Fan Control in Heat Mode
Indoor fan speed depends on the indoor coil temperature:
11.5 Auto Cool/Heat Mode
When in auto cool heat mode unit will automatically select between cool and heat mode according to the difference between actual room temperature and user set point temperature )∆T(. Unit will switch from cool to heat when compressor is off for 3 minutes, and ∆T < -3. Unit will switch from heat to cool when compressor is off for 5 minutes, and ∆T < -3.
11.6 Dry Mode
As long as room temperature is higher then the set point, indoor fan will work in low speed and compressor will work between 0 and MaxNLOADIF1C Hz. When the room temperature is lower than the set point, compressor will be switched OFF and indoor fan will cycle 3 minutes OFF, 1 minute ON.
11.7 Protections
There are 5 protection codes. Normal (Norm) – unit operate normally. Stop Rise (SR) – compressor frequency can not be raised but does not have to be decreased. HzDown1 (D1) – Compressor frequency is reduced by 2 to 5 Hz per minute. HzDown2 (D2) – Compressor frequency is reduced by 5 to 10 Hz per minute. Stop Compressor (SC) – Compressor is stopped.
11.7.1 Indoor Coil Defrost Protection
ICT TrendICT
ICT<-2SC SCSC SCSC
Fast Increasing
Increasing No change Decreasing Fast
Decreasing
-2 ≤ ICT < 0 D1 D1 D2 D2 D2 0 ≤ ICT < 2 SR SR D1 D2 D2 2 ≤ ICT < 4 SR SR SR D1 D2 4 ≤ ICT < 6 Norm Norm SR SR D1 6 ≤ ICT < 8 Norm Norm Norm SR SR 8 ≤ ICT Normal
ICTST
ICTVL ICTTICTHICTL
Page 41
11-6
CONTROL SYSTEM
Revision Y05-02 Service Manual -ECF DCI
11.7.2 Indoor Coil over Heating Protection
ICT TrendICT Fast Decreasing
Decreasing No Change Increasing Fast
Increasing ICT55SCSCSCSCSC> 53 <ICT ≤ 55 D1 D1 D2 D2 D2 49 < ICT ≤ 53 SR SR D1 D2 D2 47<ICT49SRSRSRD1D2 45 < ICT ≤ 47 Norm Norm SR SR D1 43 < ICT ≤ 45 Norm Norm Norm SR SR ICT ≤ 43 Normal
11.7.3 Compressor over Heating Protection
Compressor temperature can be in one of 5 control zones )4 in protection, and 1 normal(, according to the following chart.
Normal
P1
P2
Stop-Compresor
CTTOH1
CTTOH2
CTTOH3
CTTOH4
CTT
P3
Control Status Compressor Temperature
Increases
Else
P1 Norm SR P2 D1 SR P3 D2 D1 Stop Compressor SC
11.7.4 Compressor over Current Protection
Normal
Stop-Rise
HzDown1
HzDown2
Stop-Compresor
CCROC1
CCROC2
CCROC3
CCROC4
CCR
Page 42
11-7
CONTROL SYSTEM
Revision Y05-02Service Manual - ECF DCI
11.7.5 Heat Sink Over Heating Protection (NA for DCI 25 and 35)
HST TrendHST
Decreasing No Change Increasing HST SC SC SC>90 85<HST≤90 D1 D2 D2 82 < HST ≤ 85 SR D1 D2 80 < HST ≤ 82 SR SR D1 78 < HST ≤ 80 Norm Norm SR HST ≤ 78 Normal
11.7.6 Outdoor Coil Deicing Protection
11.7.6.1 Deicing Starting Conditions
Deicing operation will start when either one of the following conditions exist: Case 1: OCT OAT – 8 AND TLD<>DI Case 2: OCT OAT – 12 AND TLD 30 minutes.<> Case 3: OCT is Invalid AND TLD DI> Case 4: Unit is ust switched to STBY AND OCTj<OAT-8 Case 5: NLOAD 0 AND OCT OAT -8=<
OCT – Outdoor Coil Temperature OAT – Outdoor Air Temperature TLD – Time from Last Deicing DI – Deicing Interval (Time Interval Between Two Deicing)
Deicing interval time when compressor is first started in heat mode, is 10 minutes if OCT < -2, and is 40 minutes in other cases. Deicing interval time is changed (increased/ decreased in 10 minutes steps) as a function of deicing time. If deicing time is shorter then former deicing time, the deicing interval time will be increased. If deicing time is longer then former deicing time, the deicing interval time will be decreased.
Page 43
11-8
CONTROL SYSTEM
Revision Y05-02 Service Manual - ECF DCI
11.7.6.2 Deicing Protection Procedure
COMP
RV
OFAN
EEV
ON
HEAT
COOL
ON
OFF
EEVDeicerOpen
Any
T1 T2
T3 T3
T1
12
0
Threshold
max. 12 minutes
DT
OCT
T1 = T2 =
36 seconds, T3 nds= 6 seco
11.8 Condensate Water Over Flow Protection
Each of the pins P1, P2, P3 can have two options: 1 – When it is shorted with P4 0 – When it is not shorted to P4
11.8.1 3 Levels Logic (used in floor/ceiling models)
P2 P3 Level
00 L0 1 0 L1 11 L23& 01 L4
Page 44
11-9
CONTROL SYSTEM
Revision Y05-02Service Manual - ECF DCI
Water Level
ANY
0
BLINK
NLOAD
OPER LED
LEVEL1
LEVEL 3
LEVEL4
NORMAL
ON
Pump
OFF
11.8.2 1 Level Logic (used in all models except for floor/ceiling
models)
P2 P3 Level
Don`t care
1 Normal
Don`t care
0 Overflow
ANY
0
ON
NLOAD
PUMP
OFF
ON
OPER
LED
OFF
Overflow
Water Level
Normal
BLINK
NLOAD is
forced to 0
8min 8min
Overflow when
unit is ON
Overflow when
unit is OFF
8min
11.9 Indoor Unit Dry Contact
Indoor unit Dry contact has two alternative functions that are selected by J8.
Function Contact = Open Contact = Short J8 Presence Detector Connection No Limit Forced to STBY= Open J8 Power Shedding Function No Limit Limit NLOAD= Open
Page 45
11-10
CONTROL SYSTEM
Revision Y05-02 Service Manual - ECF DCI
11.10 Operating the Unit from the Mode Button
Forced operation allows to start, stop and operate in Cooling or Heating, in pre-set temperature according to the following table:
Forced operation Mode Pre-set Temperature Cooling 200C Heating 28
0
C
11.11 On Unit Controls and Indicators
11.11.1 Indoor Unit Controller Controls and Indicators For All Models
Except for Floor/Ceiling model
STAND BY
INDICATOR
Lights up when the Air Conditioner is connected to power and ready to
receive the R/C commands
OPERATION INDICATOR
Lights up during operation. Blinks for 300 msec., to announce that a R/C infrared signal has been received and stored. Blinks continuously during protections (according to the relevant spec section).
TIMER INDICATOR Lights up during Timer and Sleep operation.
FILTER INDICATOR Lights up when Air Filter needs to be cleaned.
COOLING INDICATOR
Lights up when system is switched to Cool Mode by using the Mode Switch on the unit.
HEATING INDICATOR
Lights up when system is switched Heat Mode by using the Mode Switch on the unit.
Mode SWITCH
(COOL/HEAT/OFF)
Every short pressing , the next operation mode is selected, in this order : SB → Cool Mode → Heat Mode → SB → In long pressing system enters diagnostic mode.
RESET / FILTER
SWITCH
For short pressing: When Filter LED is on - turn off the FILTER INDICATOR after a clean filter has been reinstalled. When Filter LED is off able/disable the buzzer announcer, if selected.
Page 46
11-11
CONTROL SYSTEM
Revision Y05-02Service Manual - ECF DCI
11.11.2 Indoor Unit Controls and Indicators for LCD Display
STBY Cool Heat Auto Fan Dry OFF SPT(1*)
OFF(2*)
OFF(2*) OFF(2*) OFF(2*) OFF(2*) OFF(2*) OFF(2*)
SPT(1*)
ON(2*)ON(2*) ON(2*) ON(2*) ON(2*)
SPT(1*)SPT(1*) SPT(1*) SPT(1*)
(Low)
OFF
(Med)
OFF
(High)
OFF
(Turbo)
OFF
(Auto)
OFF
User setting IFAN speed
User setting IFAN speed
User setting IFAN speed
User setting IFAN speed
User setting IFAN speed
Backlight(red) OFF OFF ON(3*) ON(3*)
ON(3*)
ON(3*) ON(3*) ON(3*)
OFF
Backlight(green) OFF ON(3*) OFF
Page 47
11-12
CONTROL SYSTEM
Revision Y05-02 Service Manual - ECF DCI
11.11.3 Indoor Unit Controller Controls and Indicators for Floor/Ceiling
Model
STANDBY INDICATOR
Lights up when the Air Conditioner is connected to power and is ready for operation
OPERATE INDICATOR
(4)
1. Lights up during operation.
2. Blinks for 300 msec., to announce that a R/C infrared signal has been received and stored.
3. Blinks continuously during protections (according to the relevant spec section).
TIMER INDICATOR
Lights up during Timer and Sleep operation.
FILTER INDICATOR
1. Lights up when Air Filter needs to be cleaned.
2. Blinks during Water Over Flow in PXD models. (Cf. Sect. 7.3) COOLING INDICATOR
Lights up when system is switched to Cool Mode by using the Mode
Switch on the unit. HEATING INDICATOR
Lights up when system is switched Heat Mode by using the Mode
Switch on the unit. FAN MODE INDICATOR
(4)
Lights up in Fan Mode activated by local switches.
FAN SPEED INDICATORS
L -- Lights up when IFAN setting is Low.
M -- Lights up when IFAN setting is Medium.
H -- Lights up when IFAN setting is High.
A -- Lights up when IFAN setting is Auto. TEMP. SETTING INDICATORS
Each one of the seven indicators indicates the following SPT: 18, 20,
22, 24, 26, 28, 30 ]
o
c[. The odd number temperatures are indicated by
turning on the two adcent indicators. FAN SPEED BUTTON
Press this button to change the speed of the IFAN. Each pressing
change the speed in the sequence of:
..... L → M → H → Auto → L → ...
TEMP. SETTING UP BUTTON
Pressing this button increases the SPT by 1
o
C.
Note: The Max SPT is 30
o
C.
TEMP. SETTING DOWN BUTTON
Pressing this button decreases the SPT by 1
o
C.
Note: The Min SPT is 18
o
C.
MODE BUTTON
Every short pressing , the next operation mode is selected, in this order : SB → Cool Mode → Heat Mode → SB →
In long pressing system enters diagnostic mode. POWER BUTTON
Toggle the unit between OPER & STBY modes.
RESET / FILTER BUTTON
For short pressing:
When Filter LED is on - turn off the FILTER INDICATOR after a clean
filter has been reinstalled.
When Filter LED is off able/disable the buzzer announcer, if
selected.
In long pressing system enters set up mode (if in SB).
11.11.4 Outdoor Unit Controller Indicators
Unit has three LED SB LED is ON when power is ON (230 VAC, even when no communication). STATUS LED is ON when COMP is ON, and Blinks according to diagnostics mode definitions when either fault or protection occurs. FAULT LED Blinks according to diagnostics mode definitions when either fault or protection occurs.
Page 48
11-13
CONTROL SYSTEM
Revision Y05-02Service Manual - ECF DCI
11.1 . Indoor Unit Controller21
11.12 Jumper Setting
0 = Open Jumper (disconnect jumper). 1 = Close Jumper (connect jumper).
Self test Jumper – J1
OPERATION
J1
SELF-TEST
1
NORMAL
0
Compensation Jumper – J2
Model J2 (Default) Compensation
Wall Mounted 0 Activated
Floor/Ceiling 1 Deactivated
Ducted/cassette 1 Activated
Family selection Jumper – J3, J4 and J5
Family J5 J4 J3
Reserved Reserved Reserved Wall Mounted (WNG/FLO) Floor/Ceiling (PXD) Reserved Ducted (LS) Cassette (K)
0 0 0 0 0 1 0 1 0 0 1 1 1 0 0 1 0 1 1 1 0 1 1 1
IDU Model
Jumper Setting
J8 J7 J6 J5 J4 J3 WNG25 000011 WNG35 010011 WNG50 001000 WNG60 011000 WNG80 001001 PXD25 000100 PXD35 010100 PXD50 100100 K25 000111 K35 010111 K50 100111 LS35 010110
For wall mounted units Jumpers j7, j8 can be configured by service. All other jumpers on the above table are factory default (cannot be changed by service). For unit types as Cassettes, floor ceiling, and ducted, jumpers are set by a model plug.
Page 49
11-14
CONTROL SYSTEM
Revision Y05-02 Service Manual - ECF DCI
11.12.2 Outdoor Unit Controller
JP9 JUMPER LAYOUT
Reserved (PIN9)ODU3 (PIN 7) ODU2 (PIN 5) ODU1 (PIN 3) ODU0 (PIN 1)
GND (PIN 10) GND (PIN 8) GND (PIN 6) GND (PIN 4) GND (PIN 2)
ODU MODEL SELECTION
ODU3 ODU2 ODU1 ODU0 ODU Model
OFF OFF OFF OFF Reserved OFF OFF OFF ON (PIN1 & PIN2) A (DCI 25) OFF OFF ON (PIN3 & PIN4) OFF B (DCI 35) OFF OFF ON (PIN3 & PIN4) ON (PIN1 & PIN2) C (DCI 50) OFF ON (PIN5 & PIN6) OFF OFF D OFF ON (PIN5 & PIN6) OFF ON (PIN1 & PIN2) E (Duo) OFF ON (PIN5 & PIN6) ON (PIN3 & PIN4) OFF F
OFF ON (PIN5 & PIN6) ON (PIN3 & PIN4) ON (PIN1 & PIN2) G ON (PIN7 & PIN8) OFF OFF OFF H ON (PIN7 & PIN8) OFF OFF ON (PIN1 & PIN2) I ON (PIN7 & PIN8) OFF ON (PIN3 & PIN4) OFF J ON (PIN7 & PIN8) OFF ON (PIN3 & PIN4) ON (PIN1 & PIN2) K ON (PIN7 & PIN8) ON (PIN5 & PIN6) OFF OFF L ON (PIN7 & PIN8) ON (PIN5 & PIN6) OFF ON (PIN1 & PIN2) M ON (PIN7 & PIN8) ON (PIN5 & PIN6) ON (PIN3 & PIN4) OFF N ON (PIN7 & PIN8) ON (PIN5 & PIN6) ON (PIN3 ? PIN4) ON (PIN1 & PIN2) O
11.13 Test Mode
11.13.1 Entering Test Mode
System can enter Test mode in two ways: Automatically when the following conditions exists for 30 minutes continuously: Mode l, Set point 16, Room temper= Coo = ature = 27±1, Outdoor temperature = 35±1 Or Mode = Heat, Set point = 30, Room temperature = 20±1, Outdoor temperature = 7±1 Manually when entering diagnostics with the following settings: Mode = Cool, Set point = 16 Mode = Heat, Set point = 30
Model selection Jumper – J7, J8
Model J8 J7
A B C D
0 0 0 1 1 0 1 1
J9- Presence Detector/Power Shedding
OPERATION J9
Presence Detector 0 Power Shedding 1
Jumper – J10
OPERATION J10
WNG DCI LCD 0 LED 1
Page 50
11-15
CONTROL SYSTEM
Revision Y05-02Service Manual - ECF DCI
11.13.2 Unit Operation in Test Mode
In test mode, the unit will operate in fixed settings according to the indoor fan speed setting:
Indoor Fan Speed Setting Unit Setting Low Minimum Capacity Setting High Nominal Capacity Setting Auto Maximum Capacity Setting During test mode, protections are disabled, except for stop compressor status.
11.14 SW Parameters
11.14.1 Indoor Units SW Parameters
General Parameters for All Models:
Parameters defining the indoor fan speed as a function of Indoor Coil temperature in heat mode (ICT):
ICTST Speed ICT to stop indoor fan 25 ICTVLSpeed ICT to go down to very low speed 28 ICTLSpeed ICT to start in very low speed 30 ICTHSpeed ICT to start in increase speed from very low 32 ICTTSpeed ICT to enable Turbo fan speed 40
Model Depended Parameters:
Parameter name
Wall Mounted Models
DCI 25 DCI 35
NLOAD limits as a function of selected indoor fan speed
MaxNLOADIF1C 40 40 MaxNLOADIF2C 53 53 MaxNLOADIF3C 120 120 MaxNLOADIF4C 127 127 MaxNLOADIF5C 127 127
Indoor Fan speeds
IFVLOWC 700 700 IFLOWC 800 800 IFMEDC 900 950 IFHIGHC 1050 1100 IFTURBOC 1150 1200 IFVLOWH 700 700 IFLOWH 800 850 IFMEDH 950 1000 IFHIGHH 1100 1150 IFTURBOH 1200 1250
Nominal Compressor Frequency
NomLoadC 40 62 NomLoadH 55 67
Parameter Name
Cassette Models
K 25 K 35 K 35S K 50
NLOAD limits as a function of selected indoor fan speed
MaxNLOADIF1C 40 40 40 40 MaxNLOADIF2C 53 56 56 60 MaxNLOADIF3C 120 90 90 90 MaxNLOADIF4C 127 90 90 90 MaxNLOADIF5C 127 90 90 90
Nominal Compressor Frequency
NomLoadC 40 60 56 63
NomLoadH 55 69 73 80
Page 51
11-16
CONTROL SYSTEM
Revision Y05-02 Service Manual - ECF DCI
11.14.2 Outdoor Units SW Parameters
Parameter Name DCI25 DCI35 DCI 50 DCI50 DUO
Compressor Parameters
MinFreqC 30 33 20 20
MaxFreqC 64 80 85 97
MinFreqH 30 35 20 26
MaxFreqH 81 93 99 106
Step1Freq 60 60 60 60
Step2Freq 70 70 70 80
Step3Freq 90 90 90 90
Frequency limits as a function of outdoor air temperature
MaxFreqAsOATC 50 50 64 62
MaxFreqAsOAT1H 65 75 85 85
MaxFreqAsOAT2H 60 60 60 60
Compressor Over Heating Protection
CTTOH1 94 94 94 90
CTTOH2 98 98 98 95
CTTOH3 102 102 102 102
CTTOH4 105 105 105 105
Compressor Over Current Protection [A]
CCR01 7.1 7.1 10 10
CCR02 7.5 7.5 10.5 10.5
CCR03 7.9 7.9 10.8 10.8
CCR04 8.3 8.3 11.2 11.2
Outdoor Fan Speed (RPM)
VL 200 200 200 200
OFLOWC 550 550 600 600
OFMEDC 700 700 760 830
OFMAXC 830 830 920 920
OFLOWH 550 550 600 600
OFMEDH 700 700 830 920
OFMAXH 830 830 1000 1000
Outdoor Fan Limit Control
OFLowFreq 45 45 40 40
OFMedFreq 57 57 70 70
Page 52
12-1
TROUBLESHOOTING
Revision Y05-02Service Manual -ECF DCI
12. TROUBLESHOOTING
Warning
When Power Up – the whole outdoor unit controller, including the wiring, is under HIGH
VOLTAGE
Never open the Outdoor unit before turning off the PowerHIG
When turned off, the system is still charged (400V)yle
It takes about 4 Min. to discharge the system.
Touching the controller before discharging may cause an electrical shock
For safe handling of the controller please refer to section 12.6 below.
12.1 Single Split system failures and corrective actions
No SYMPTOM PROBABLE
CAUSE
CORRECTIVE ACTION
1 Power supply indicator
(Red LED) does not light up.
No power supply Check power supply. If power supply
is OK, check display and display wiring. if OK, replace controller.
2 Unit does not respond to
remote control message
Remote control message not reached the indoor unit
Check remote control batteries, if batteries are OK, check display and display wiring, if OK, replace display PCB. If still not OK replace controller.
3 Unit responds to remote
control message but Operate indicator (Green LED) does not light up
Problem with display PCB
Replace display PCB. If still not OK replace controller.
Unit in heat mode and coil is still not warm.
Change to cool mode and check.4 Indoor fan does not start (louvers are opened and Green LED does light up)
Problem with PCB or capacitor
Change to high speed and Check
power supply to motor is higher than
130VAC (for triack controlled motor)
or higher than 220VAC for fixed
speed motors, if OK replace
capacitor, if not OK replace
controller
5 Indoor fan works when
unit is OFF, and indoor fan speed is not changed by remote control command.
PCB problem Replace controller
6 Compressor does not
start
Electronics control problem or protection
Perform diagnostics (See 12.3
below), and follow the actions
described.
7 Compressor stops
during operation and Green LED remains on
Electronic control or power supply problem
Perform diagnostics (See 12.3
below), and follow the actions
described.
Page 53
12-2
TROUBLESHOOTING
Revision Y05-02 Service Manual - ECF DCI
No SYMPTOM PROBABLE
CAUSE
CORRECTIVE ACTION
8 Compressor is on but
outdoor fan does not work
Problem with outdoor electronics or outdoor fan
Check outdoor fan motor according to the procedure in section 12.5.3 below, if not OK replace controller
9 Unit works in wrong
mode )cool instead of heat or heat instead of cool(
Electronics or power connection to RV
Check RV power connections, if OK, Check RV operation with direct 230VAC power supply, if OK, Replace outdoor controller.
10 All components are
operating properly but no cooling or no heating
Refrigerant leak Check refrigeration system.
11 Compressor is over
heated and unit does not generate capacity
EEV problem Check EEV
12 Units goes into
protections and compressor is stopped with no clear reason
Control problem or refrigeration system problem
Perform diagnostics )See 12.3 below(, and follow the actions described.
13 Compressor motor is
generating noise and no suction occurs
Phase order to compressor is wrong
Check compressor phase order.
14 Water leakage from
indoor unit
Indoor unit drainage tube is blocked
Check and open drainage tube.
15 Freezing of outdoor unit
in heat mode and outdoor unit base is blocked with ice
Connect base heater.
16 Unit operates with wrong
fan speeds or wrong frequency
Wrong umperj
settings
Perform diagnostics (See 12.3 below), and check if units is operating by EEPROM parameters.
12.2 Checking the refrigeration system
Checking system pressures and other thermodynamic measures should be done when system is in Test Mode (in Test mode, system operates in fixed settings). The performance curves given in this manual are given for unit performance in test mode when high indoor fan speed is selected. Entering test mode: Set unit to Cool/16 degrees/High indoor fan speed, or Heat/30 degrees/High indoor fan speed, and enter diagnostics.
Page 54
12-3
TROUBLESHOOTING
Revision Y05-02Service Manual - ECF DCI
12.3 Judgment by Indoor/Outdoor Unit Diagnostics
Enter diagnostics mode - press for five seconds Mode button in any operation mode. Acknowledgment is by 3 short beeps and lights of COOL and HEAT LEDs. Then, every short pressing of Mode button will scroll between Indoor and Outdoor unit diagnostic modes by the acknowledgment of 3 short beeps and lighting of COOL and HEAT LED s.' During the Outdoor unit diagnostics all four Indoor LED’s, (STBY, Operate, Filter and Timer) are blinking. When Indoor diagnostics is displayed, all four LED’s (STBY, Operate, Filter and Timer) are ON. When system enters diagnostics mode, only one fault code is shown. Order of priority is from the lower to the higher number. Diagnostics is continuously ON as long as power is ON. The current system operation mode will not be changed. If no fault occurred in the system, no fault code will be displayed during normal operation mode. The last fault code will be displayed even if the system has recovered from that fault. The last fault will be deleted from the EEPROM after the system has exit diagnostics mode. In diagnostics mode, system fault / status will be indicated by blinking of Heat d Cool LEDs. The coding method will be as follows: Heat LED will blink 5 times in 5 seconds, and then will be shut off for the next 5 seconds. Cool LED will blink during the same 5 seconds according to the following Indoor / Outdoor unit tables: Note: 0 – OFF, 1-ON
12.3.1 Indoor unit Diagnostics
No Problem 5 4 3 2 1
1 RT-1 is disconnected 00001 2RT-1isshorted 00010 3 RT-2 is disconnected 00011 4RT-2isshorted 00100 5 Reserved 00101 7 Communication mismatch 0 0111
10 Reserved 0 1 0 1 0 11 Outdoor Unit Fault 01011
17 Defrost protection 1 0 0 0 1
19 Outdoor Unit Protection 1 0 0 1 1 20 Indoor Coil HP Protection 10100
21 Overflow Protection 1 0 1 0 1
22 Reserved 24 EEPROM Not Updated 11000 25 Bad EEPROM 1 1 0 0 1 26 Bad Communication 11010 27 Using EEPROM data 11011 28 Model A 11100 29
18
8 No Communication 0 1 0 0 0
No Encoder 0 1 0 0 19
... Reserved
30ModelC 11110 31 Model D 1 1111
Model B 1 1 1 0 1
Deicing Protection 1 0 0 1 0
Page 55
12-4
TROUBLESHOOTING
Revision Y05-02 Service Manual - ECF DCI
12.3.2 Indoor unit diagnosis and corrective actions
No.
Fault
Probable Cause Corrective Action
1
Sensor failures of all types
Check sensor connections or replace sensor.
2
Communication mismatch
Indoor and Outdoor controllers are with different Versions.
Replace Indoor controller.
3
No Communication
Communication or grounding wiring is not good.
Check Indoor to Outdoor wiring and grounding.
4
No Encoder
Indoor electronics or motor Checkmotorwiring,ifok,.
replace motor, if still not ok, replace Indoor controller.
5
Outdoor Unit Fault
Outdoor controller problem Switch to Outdoor.
diagnostics.
6
EEPROM Not Updated
System is using ROM parameters and not EEPROM parameters.
No action, unless special parameters are required for unit operation.
7
Bad EEPROM
No action, unless special parameters are required for unit operation.
8
Bad Communication
Communication quality is low Reliability.
Check Indoor to Outdoor wiring and grounding.
9
Using EEPROM data
No problem. System is using EEPROM parameters.
Page 56
12-5
TROUBLESHOOTING
Revision Y05-02Service Manual - ECF DCI
No Problem 5 4 3 2 1
1 OCT is disconnected
0 0 0 0 1
2 OCT is shorted
0 0 0 1 0
3 CTT is disconnected
0 0 0 1 1
4 CTT is shorted
0 0 1 0 0
5 HST is disconnected (when enabled)
0 0 1 0 1
6 HST is shorted (when enabled)
0 0 1 1 0
7 OAT is disconnected (when enabled)
0 0 1 1 1
8 OAT is shorted (when enabled)
0 1 0 0 0
9 TSUC is disconnected (when enabled)
0 1 0 0 1
10 TSUC is shorted (when enabled)
0 1 0 1 0
11 IPM Fault
0 1 0 1 1
12 Bad EEPROM
0 1 1 0 0
13 DC under voltage
0 1 1 0 1
14 DC over voltage
0 1 1 1 0
15 AC under voltage
0 1 1 1 1
16 IDU/ODU Communication mismatch
1 0 0 0 0
17 No Comm
unication
1 0 0 0 1
18 Reserved
1 0 0 1 0
20 Heat sink Over Heating
1 0 1 0 0
21 Deicing
1 0 1 0 1
22 Compressor Over Heating
1 0 1 1 0
23 Compressor Over Current
1 0 1 1 1
24 No OFAN Feedback
1 1 0 0 0
25 OFAN locked
1 1 0 0 1
26 Compressor Lock
1 1 0 1 0
27 Bad Communication
1 1 0 1 1
1 - ON, 0 - OFF Only one code is shown. Order of priorety is 1-24. Diagnostics is continuously ON as long power is on.
12.3.3 Outdoor Unit Diagnostics
Page 57
12-6
TROUBLESHOOTING
Revision Y05-02 Service Manual -ECF DCI
12.3.4 Outdoor unit diagnosis and corrective actions
o.
Fault
Probable Cause Corrective Action
Sensors failures of all types
Check sensors connections or replace sensors.
IPM Fault Electronics HW
problem
Check all wiring and umper settings, if OK, replace electronics.
Bad EEPROM No action, unless special
parameters are required for unit operation.
DC under/over Voltage Electronics HW
problem
Check outdoor unit power supply voltage
AC under Voltage Check outdoor unit power
supply voltage Indoor / Outdoor unit Communication mismatch
Indoor and Outdoor controllers are with different versions
Replace Indoor controller
No Communication Communication or
grounding wiring is not good.
Check Indoor to Outdoor
wiring and grounding
Compressor Lock Switch unit to STBY and
restart Bad Communication Communication quality is
low reliability
Check Indoor to Outdoor
wiring and grounding
Page 58
12-7
TROUBLESHOOTING
Revision Y05-02Service Manual -ECF DCI
12.4 Judgment by MegaTool
MegaTool is a special tool to monitor the system states.
Using MegaTool requires:
A computer with RS232C port.
A connection wire for MegaTool.
A special MegaTool software. Use MegaTool according to following procedure:
Setup MegaTool software: copy the software to the computer.
Connect RS232C port in computer with MegaTool port in Indoor/Outdoor unit
controller by the connection wire.
Run the software and choose the COM port, you can monitor the A/C system state in monitor tab.
12.5 Simple procedures for checking the Main Parts
12.5.1 Checking Mains Voltage.
Confirm that the Mains voltage is between 198 and 264 VAC. If Mains voltage is out of this range, abnormal operation of the system is expected. If in range check the Power (Circuit) Breaker and look for broken or loosed cable lugs or wiring mistake(s).
12.5.2 Checking Power Input.
If Indoor unit power LED is unlighted, power down the system and check the fuse of the Indoor unit. If the fuse is OK replace the Indoor unit controller. If the fuse has blown, replace the fuse and power up again. Checking Power Input procedure for the Outdoor unit is the same as with the Indoor unit.
12.5.3 Checking the Outdoor Fan Motor.
Enter Test Mode (where the OFAN speed is high) Check the voltage between lead wires according to the normal value as following:
Between red wire and black wire: 310VDC +/- 20V
Between orange wire and black wire: 15VDC +/- 1V
Between yellow wire and black wire: 2-6VDC
12.5.4 Checking the Compressor.
The compressor is brushless permanence magnetic DC motor. Three coil resistance is same. Check the resistance between three poles. The normal value should be below 0.5 ohm (TBD).
12.5.5 Checking the Reverse Valve (RV).
Running in heating mode, check the voltage between two pins of reverse valve
connector, normal voltage is 220VAC.
12.5.6 Checking the electrical expansion valve (EEV).
The EEV has two parts, drive part and valve. The drive part is a step motor the valve. Check the drive voltage (12VDC). When Outdoor unit is power on, EEV shall run and have click and vibration.
Page 59
12-8
TROUBLESHOOTING
Revision Y05-02 Service Manual - ECF DCI
12.6 Precaution, Advise and Notice Items
12.6.1 High voltage in Outdoor unit controller.
Whole controller, including the wires that are connected to the Outdoor unit controller may have the potential hazard voltage when power is on. Touching the Outdoor unit controller may cause an electrical shock. Advise: Don naked lead wire and don t insert finger, conductor or anything''t touch the else into the controller when power is on.
12.6.2 Charged Capacitors
Three large-capacity electrolytic capacitors are used in the Outdoor unit controller. Therefore, charging voltage (380VDC) remains after power down. Discharging takes about four minutes after power is off. Touching the Outdoor unit controller before discharging may cause an electrical shock.
12.6.3 Additional advises
When disassemble the controller or the front panel, turn off the power supply.
When connecting or disconnecting the connectors on the PCB, hold the whole housing, dont pull the wire.
There are sharp fringes and sting on shell. Use gloves when disassemble the A/C units.
Page 60
13-1
EXPLODED VIEWS AND SPARE PARTS LISTS
Revision Y05-02Service Manual - ECF DCI
13. EXPLODED VIEWS AND SPARE PARTS LISTS
13.1 Indoor Unit: ECF 25, 35, 35S, 50 DCI
Page 61
13-2
EXPLODED VIEWS AND SPARE PARTS LISTS
Revision Y05-02 Service Manual - ECF DCI
13.2 Indoor Unit: ECF 25, 35, 35S 50 DCI (page 2)
(Grill B P/N:372231
CASSETTE AUTO LOUVER
Page 62
13-3
EXPLODED VIEWS AND SPARE PARTS LISTS
Revision Y05-02Service Manual -ECF DCI
13.3 Indoor Unit: ECF 25, 35 DCI
No. Part No. Name
Total
Quan.
Version
1 200014 SCREW 4X16 4 1 2 208023 Clip 2 1 3 372273 Flap(White) 4 1 4 4521915 Front(White) 1 1 5 391746 Signal Line 1 1 6 234132 RECEIVER ASSEMBLY 908-081-00 1 1 7 377135 Front EPS I 3 1 8 377138 Front EPS II 1 1
9 4520900 Grill Attachment Assy. 3 1 10 4520923 Drain Pan 1 1 17 232299
Indoor Senso
r BLACK
11 18 4527521 Gas Pipe Assy K9 DCI R410A 1 1 19 4527523 Liquid pipe assy K9 DCI R410A 1 1 20 323436 PUMP PLACEMENT 1 1 21 4522038 Pump assy 1 1 22 369055 DRAIN TUBE 1 1 23 452827401 AUTO-TRANSFORMER 80W FOR K18 DCI 1 1 24 243139 Free Poles terminal block 1 1 25 438413
ROOM Senso
r RED
11 26 323460 CONNECTION SUPPORT 1 1 28 455000000 single patch Capacitor for fan motor 1.5uF (CBB61S) 1 1 31 4526212 STORM DCI CONTROLLER 916-521-00 1 1 32 452908900 MODEL PLUG K-9 DCI R410A 1 1 34 4520925 Rubber Ring 1 1 1 35 4520901 Electrical Plate Assy. 1 1 36 4520927 Rubber Ring 3 3 1 37 4520894 Support Assy. 1 1 39 4520947 Joint for power cord 2 1 40 326196 Install Support 2 1 41 305136 Side Wall Assy. 2 1 42 300323
CHASSIS ASSY
11 43 377131 EPS BLOCK 3 1 44 323432 Corner Support 3 1 45 4520768 Bolt M4x16 4 1 46 4520909 Fresh Air EPS 1 1 47 4520948 Plastical Screw 2 1 48 4527563 coil K9 DCI R410A (2 rows) 1 1 49 4527274 Evaporator Fixing Plate(two rows) K9 R410A 1 1 50 4522157 Rubber Foot for metal-shell motor 3 1 51 261752 MOTOR 36W/4P 230/1/50 1 1 52 4520772 Screw M6x25 3 1 53 293288 Fan 1 1 54 245138 Fan Rubber 1 1 55 4521023 Bolt M5x16 1 1 56 4520898 Fixation Assy. 1 1 57 374152 AIR INTAKE PANEL 1 1 58 4520770 Screw 4.8x40 3 1 59 374019 Drain Plug 1 1 60 221504 FILTER K 1 1 61 4521919 Left Lock (white) 1 1 62 4521920 Right Lock (white) 1 1 63 4521916 Grill A for Cassette (white) 1 1
Page 63
13-4
EXPLODED VIEWS AND SPARE PARTS LISTS
Revision Y05-02 Service Manual -ECF DCI
13.4 Outdoor Unit: ECF 35S DCI
No. Part No. Name
Total
Quan.
Version
1 200014 SCREW 4X16 4 1 2 208023 Clip 2 1 3 372273 Flap(White) 4 1 4 4521915 Front(White) 1 1 5 391746 Signal Line 1 1 6 234132 RECEIVER ASSEMBLY 908-081-00 1 1 7 377135 Front EPS I 3 1 8 377138 Front EPS II 1 1
9 4520900 Grill Attachment Assy. 3 1 10 4520923 Drain Pan 1 1 17 232299
Indoor Senso
r BLACK
11 18 4527517 Gas Pipe Assy K12 DCI R410A 1 1 19 4527518 Liquid pipe assy K12 DCI R410A 1 1 20 323436 PUMP PLACEMENT 1 1 21 4522038 Pump assy 1 1 22 369055 DRAIN TUBE 1 1 23 452827401 AUTO-TRANSFORMER 80W FOR K18 DCI 1 1 24 243139 Free Poles terminal block 1 1 25 438413
ROOM Senso
r RED
11 26 323460 CONNECTION SUPPORT 1 1 28 455000000 single patch Capacitor for fan motor 1.5uF (CBB61S) 1 1 31 4526212 STORM DCI CONTROLLER 916-521-00 1 1 32 452908901 MODEL PLUG K-12 DCI R410A 1 1 34 4520925 Rubber Ring 1 1 1 35 4520901 Electrical Plate Assy. 1 1 36 4520927 Rubber Ring 3 3 1 37 4520894 Support Assy. 1 1 39 4520947 Joint for power cord 2 1 40 326196 Install Support 2 1 41 305136 Side Wall Assy. 2 1 42 300323
CHASSIS ASSY
11 43 377131 EPS BLOCK 3 1 44 323432 Corner Support 3 1 45 4520768 Bolt M4x16 4 1 46 4520909 Fresh Air EPS 1 1 47 4520948 Plastical Screw 2 1 48 4527561 coil K12 DCI R410A (3 rows) 1 1 49 4526909 Evaporator Fixing Plate(three rows) K12 R410A 1 1 50 4522157 Rubber Foot for metal-shell motor 3 1 51 261752 MOTOR 36W/4P 230/1/50 1 1 52 4520772 Screw M6x25 3 1 53 293288 Fan 1 1 54 245138 Fan Rubber 1 1 55 4521023 Bolt M5x16 1 1 56 4520898 Fixation Assy. 1 1 57 374152 AIR INTAKE PANEL 1 1 58 4520770 Screw 4.8x40 3 1 59 374019 Drain Plug 1 1 60 221504 FILTER K 1 1 61 4521919 Left Lock (white) 1 1 62 4521920 Right Lock (white) 1 1 63 4521916 Grill A for Cassette (white) 1 1 64 452864200 Front Plate Assy./Motorized Louver Cassette White Grill A 1 1
Page 64
13-5
EXPLODED VIEWS AND SPARE PARTS LISTS
Revision Y05-02Service Manual - ECF DCI
13.5 Indoor Unit: ECF 50 DCI
No. Part No. Name
Total
Quan.
Version
1 200014 SCREW 4X16 4 1 2 208023 Clip 2 1 5 391746 Signal Line 1 1 6 234132 RECEIVER ASSEMBLY 908-081-00 1 1
9 4520900 Grill Attachment Assy. 3 1 10 4520923 Drain Pan 1 1 17 232299
Indoor Senso
r BLACK
11 18 452783900 Gas Pipe Assy K18 DCI R410A 1 1 19 452784000 Liquid pipe assy K18 DCI R410A 1 1 20 323436 PUMP PLACEMENT 1 1 21 4522038 Pump assy 1 1 22 369055 DRAIN TUBE 1 1 23 452827400 AUTO-TRANSFORMER 80W FOR K18 DCI 1 1 24 243139 Free Poles terminal block 1 1 25 438413
ROOM Senso
r RED
11 26 323460 CONNECTION SUPPORT 1 1 28 455000000 single patch Capacitor for fan motor 1.5uF (CBB61S) 1 1 31 4526212 STORM DCI CONTROLLER 916-521-00 1 1 32 452807400 MODEL PLUG K-18 DCI R410A 1 1 34 4520925 Rubber Ring 1 1 1 35 4520901 Electrical Plate Assy. 1 1 36 4520927 Rubber Ring 3 3 1 37 4520894 Support Assy. 1 1 39 4520947 Joint for power cord 2 1 40 326196 Install Support 2 1 41 305136 Side Wall Assy. 2 1 42 300323
CHASSIS ASS
Y
11 43 377131 EPS BLOCK 3 1 44 323432 Corner Support 3 1 45 4520768 Bolt M4x16 4 1 46 4520909 Fresh Air EPS 1 1 47 4520948 Plastical Screw 2 1 48 452783800 coil k18 DCI R410A (3+1) 1 1 49 4526910 Evaporator Fixing Plate(four rows) K15/K18 R410A 1 1 50 4522157 Rubber Foot for metal-shell motor 3 1 51 261752 MOTOR 36W/4P 230/1/50 1 1 52 4520772 Screw M6x25 3 1 53 293288 Fan 1 1 54 245138 Fan Rubber 1 1 55 4521023 Bolt M5x16 1 1 56 4520898 Fixation Assy. 1 1 57 374152 AIR INTAKE PANEL 1 1 58 4520770 Screw 4.8x40 3 1 59 374019 Drain Plug 1 1 60 221504 FILTER K 1 1 61 4521919 Left Lock (white) 1 1 62 4521920 Right Lock (white) 1 1 63 4521916 Grill A for Cassette (white) 1 1 64 452864200 Front Plate Assy./Motorized Louver Cassette White Grill A 1 1 65 4525353 Step motor 2 1 66 4523557 Automatic Flap / White 1 1 67 4523556 Front Plate / White 1 1 68 4524175-4 EPS 4 1 2 69 4524175-3 EPS 3 1 2 70 4524175-2 EPS 2 1 2 71 4524175-1 EPS 1 1 2 72 4525039 Left Bracket for Motor White 1 1 73 4523563 Shaft Adapter 4 1 74 4523562 Gimbal 4 1 75 4523561 Transmission Shaft 2 1 76 4525041 Right Bracket for Motor White 1 1
Page 65
13-6
EXPLODED VIEWS AND SPARE PARTS LISTS
Revision Y05-02 Service Manual - ECF DCI
13.6 Outdoor Unit: ONG3 25, 35, 35S DCI
2
1
345678
42
41
109
24
26
35
ONG3-9,12 DCI R410AONG3-9,12 DCI R410A
40
38
37
33
34
27
28
32
11 12 13 14 15 16 18 1917
22
21
20
39
36
29
30
31
23
25
Page 66
13-7
EXPLODED VIEWS AND SPARE PARTS LISTS
Revision Y05-02Service Manual - ECF DCI
13.7 Outdoor Unit: ONG3 25, 35, 35S DCI
No. Part No. Description Unit
1 433218
Front panel A
1
2 4526340
Air inlet ring-420
1
3 433223
Painting insulation plate
1
4 4526476
Axial fan OD=401
1
5 4527092
DC motor for DCI25/35
1
6 433215
Motor support
1
7 4523060
Base painting Assy.
1
8 4526299 Partition 1
9 4526403
Outdoor DC inverter controller (English)
1
10 4524177 Gas valve (R410A) 1
11 4524176 Liquid valve(R410A) 1
12 4526224 EMI fliter board 901-098-00 1
13 4526396 Chock Assy. 167-021-01 1
14 4526223 AC-IN connected wire 1
15 4526968 Earthing wire for DCI 1
16 4526222 Fuse connecting wire 1
17 4526300
Therminal sheet
1
18 4526220
Fuse stand JEF-511B(EHK P/N:150-038-00)
1
19 4526219
Fuse 65TS(15A,230)150-031-00
1
20
204107 Cable clip nylon
1
21
4519188 4 poles terminal block
1
22
433229 Value cover
1
23
4522509 4-Way valve coil
1
24 4526367
4-way valve welding Assy. (DCI25)
1
4526393
4-way valve welding Assy. (DCI35)
1
25
4518952 4-way valve (DCI25)
1
4518951 4-way valve (DCI35)
1
26 4526221
Compressor wire
1
27 4526204
DC Inverter compressor Assy. 5RS102XAB
1
28
4526775 Compressor top thermistor(CTT)
1
29 4526774
Outside air thermistor(OAT)
1
30 4526776
Outside coil thermistor(OCT)
1
31 4526969
Suction coil thermistor(SUCT)
1
32 4526828
EEV Coil (CAN-MD 12FKS-1 White)
1
33 4526827
Electronic expansion value (CAMB20YGFKS-1)
1
34 4519606
Right side panel
1
35
433228 Back side net
1
36 4526368
Condenser soldering assy
1
37 4526298
Bridge
1
38 4519614
Painting top cover
1
39 4526480
Gasket for axial fan
1
40
4519300 Nut M5 L
1
41 433225
Handle
1
42 4519607
Left side panel painting plate
1
Page 67
13-8
EXPLODED VIEWS AND SPARE PARTS LISTS
Revision Y05-02 Service Manual - ECF DCI
13.8 Outdoor Unit: ECF 50 DCI
Page 68
13-9
EXPLODED VIEWS AND SPARE PARTS LISTS
Revision Y05-02Service Manual - ECF DCI
13.9 Outdoor Unit: ECF 50 DCI
No. Part No. Description Unit
1 433218
Front panel A
1
2 4526340
Air inlet ring-420
1
3 433223
Painting insulation plate
1
4 4526476
Axial fan OD=401
1
5 4526475
DC motor for DCI 50
1
6 4526457
Motor support
1
7 4527363
Base painting Assy.
1 8 4526459 Partition 1 9 4526203
Outdoor DC inverter controller (English)
1
10 4524595 Gas valve (R410A) 1 11 4524176 Liquid valve(R410A) 1 12 4526224 EMI fliter board 901-098-00 1 13 4526396 Chock Assy. 167-021-01 1 14 4526223 AC-IN connected wire 1 15 4526968 Earthing wire for DCI 1 16 4526222 Fuse connecting wire 1 17 4526300
Therminal sheet
1
18 4526220
Fuse stand JEF-511B(EHK P/N:150-038-00)
1
19 4526533
Fuse 65TS(20A,230)150-031-00
1
20
204107 Cable clip nylon
1
21
4519188 4 poles terminal block
1
22
433229 Value cover
1
23
4522509 4-Way valve coil
1
24 4527327
4-way valve welding Assy.
1
25 4518952 4-way valve 1 26 4526221
Compressor wire
1
27 4523446
DC Inverter compressor Assy. 5CS130XCC03
1
28
4526775 Compressor top thermistor(CTT)
1
29 4526774
Outside air thermistor(OAT)
1
30 4526776
Outside coil thermistor(OCT)
1
31 4526969
Suction coil thermistor(SUCT)
1
32 4526215
Electronic expansion valve ZDPF(L)-1.6C-01-RK for R410A
1
33 4526216
EEV COIL QA(L)12-HR-01A-RK
1
34 4519606
Right side panel
1
35
433228 Back side net
1
36 4526459
Condenser soldering assy
1
37 4526298
Bridge
1
38 4519614
Painting top cover
1
39 4526480
Gasket for axial fan
1
40
4519300 Nut M5 L
1
41 433225
Handle
1
42 4519607
Left side panel painting plate
1
Page 69
1 bis,Avenue du 8 Mai 1945 Saint-Quentin-en-Yvelines 78284 GUYANCOURT Cedex
FRANCEFRANCE
FRANCEFRANCE
FRANCE
: :
: :
:
1 bis,Avenue du 8 Mai 1945 - Saint-Quentin-en-Yvelines - 78284 - GUYANCOURT Cedex - Tél. 33 1 39 44 78 00 - Fax 33 1 39 44 11 55
With a concern for a constant improvement, our products can be modified without notice. Photos non contractual.
Loading...