Electra DELTA 22, DUO 38 DCI, DELTA 25, DELTA 35 Service Manual

Page 1

DUO 38 DCI / DELTA

CONTENT
Indoor Units Outdoor Units
DELTA 22 DELTA 25 DELTA 35
DUO 38 DCI
REFRIGERANT
R410A
SEPTEMBER – 2008
HEAT PUMP
Page 2

LIST OF EFFECTIVE PAGES

CONTENT
LIST OF EFFECTIVE PAGES
Note: Changes in the pages are indicated by a “Revision#” in the footer of each effected page
(when none indicates no changes in the relevant page). All pages in the following list represent effected/ non effected pages divided by chapters.
Dates of issue for original and changed pages are:
Original ....... 0 ........ January 2006
Total number of pages in this publication is 56 consisting of the following:
Page No.
Title ....................... 1
A ........................... 1
i ............................. 1
1-1 ........................ 1
2-1 - 2-4 ................ 1
3-1 - 3-1 ................ 1
4-1 - 4-2 ................ 1
5-1 - 5-9 ................ 1
6-1 - 6-2 ................ 1
7-1 ........................ 1
8-1 ........................ 1
9-1 - 9-2 ................ 1
10-1 ...................... 1
11-1-11-18 ............. 1
12-1-12-6 .............. 1
13-1-13-2 .............. 1
Appendix -A ...........1
Revision No. #
Page No.
Zero in this column indicates an original page.
Revision No. #
Page No.
Revision No. #
*Due to constant improvements please note that the data on this service manual can be modified with out notice. **Photos are not contractual
A
SM DUO38 1-E.1 GB
Page 3

TABLE OF CONTENTS

Table of Contents
1. INTRODUCTION ...................................................................................................1-1
2. PRODUCT DATA SHEET ......................................................................................2-1
3. RATING CONDITIONS ..........................................................................................3-1
4. OUTLINE DIMENSIONS .......................................................................................4-1
5. PERFORMANCE DATA .......................................................................................5-1
6. PRESSURE CURVES ...........................................................................................6-1
7. ELECTRICAL DATA ..............................................................................................7-1
8. WIRING DIAGRAMS .............................................................................................8-1
9. REFRIGERATION DIAGRAMS .............................................................................9-1
10. TUBING CONNECTIONS ......................................................................................10-1
11. CONTROL SYSTEM .............................................................................................11-1
12. TROUBLESHOOTING ..........................................................................................12-1
13. EXPLODED VIEWS AND SPARE PARTS LISTS .................................................13-1
14. APPENDIX A .........................................................................................................14-1
SM DUO38 1-E.1 GB
i
Page 4
1. INTRODUCTION
CONTENT
1.1 General
The new DUO 3.8 DCI Outdoor Unit is a high efficiency multi split inverter unit, supporting Indoor Units capacity range of - 2.2, 2.5 and 3.5 Kw.
1.2 Main Features
DC Inverter
R410A
High COP (A class energy rating)
Pre-Charged
Base heater connection.
Cooling operation at outdoor temperature down to -100C.
Heating operation at outdoor temperature down to -150C.
10 LED’s, shows both indoor and outdoor diagnostics.
Variable Speed DC Inverter outdoor fan.
M2L diagnostics softwear cable Port ( for PC).
Low noise level

INTRODUCTION

1.3 Tubing Connections
Flare type interconnecting tubing to be produced on site. For further details please refer to APPENDIX A on this manual, and to the relevant indoor service Manual,
1.4 Inbox Documentation
Each indoor unit is supplied with its own installation and operation manuals.
1.5 Matching Table
1.5.1 R410A
OUTDOOR UNITS
MODEL REFRIGERANT DELTA 22 DCI DELTA 25 DCI DELTA 35 DCI
INDOOR UNITS
SM DUO38 1-E.1 GB
DUO 38 DCI R410A
√√√
1-1
Page 5

PRODUCT DATA SHEET

CONTENT
2. PRODUCT DATA SHEET
2.1 Outdoor Unit DUO 38 DCI / Delta Specifications.
Model Indoor Unit DELTA 22 25 35 Model Outdoor Unit DCI DUO Delta 38 R410A
Installation Method of Pipe Flared
Characteristics Units Cooling Heating
(4)
Capacity
Power input
EER (Cooling) or COP(Heating)
Energy efficiency class A A
Power supply V/Ph/Hz 220-240V/Single/50Hz
Rated current A 4.8 5.4
Starting current A 10.5
Circuit breaker rating A 15
OUTDOOR
)
(4)
(4)
Refrigerant control EEV
Compressor type,model
Fan type & quantity Propeller(direct) x 1
Fan speeds H/L RPM 920/500
Air flow H/L m3/hr 2160
Sound power level H/L dB(A) 62 63 Sound pressure
(3)
level Dimensions WxHxD mm 795*290*610
Weight kg 38
Package dimensions WxHxD mm 945*395*655
Packaged weight kg 40
Units per pallet Units 9 units per pallet
Stacking height units 3 levels
Refrigerant type R410A
Refrigerant chargless distance kg/m 1.2/7.5
Additional charge per 1 meter g/m No need
Liquid line In.(mm) 1/4"(6.35)
Connections
between units
Suction line In.(mm) 3/8"(9.53)
Max.tubing length m. Max.30
H/L dB(A) 52 53
Btu/hr 13300(4090-18750) 15350(4090-21140)
kW 3.90(1.50-5.50) 4.50(1.20-6.20)
kW 1.1(0.45-1.80) 1.24(0.45-1.80)
W/W 3.55 3.61
Single Rotary DC Inverter,Panasonic
5RS102XAB
Operation control type Remote control
Heating elements kW
Others
(1)Airflow in ducted units;at nominal external static pressure. (2)Sound power in ducted units is measured at air discharge. (3)Sound pressure level measured at 1-meter distance from unit. (4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
SM DUO38 1-E.1 GB
Max.height difference m. Max. 10
2-1
Page 6
PRODUCT DATA SHEET
CONTENT
2.2 Indoor Units Data
2.2.1 DELTA 22 DCI Specifications
Model Indoor Unit / Type DELTA 22 DCI / Wall Mounted
Installation Method FLARE Power Supply V/Ph/Hz 220-240 / 1/ 50
Fan Type & Quantity Crossflow *1
Airflow Cooling / Heating
Sound Power Level Cooling / Heating Sound Pressure Level Cooling / Heating
INDOOR
Condensate Drain Tube I.D. mm 16 Dimensions W/H/D mm 680 250 185 Weight kg 7 Package Dimensions W/H/D mm 740 320 265 Stacking Height Units 9 LEVELS
Heating Elements kW N/A Moisture Removal L/hr 1
(2)
H/M/L m3/hr 400 350 300
(3)
L - H dB (A) 49/46/43
(4)
L - H dB (A) 36/33/30
2.2.2 DELTA 25 DCI Specifications
Model Indoor Unit / Type DELTA 25 DCI / Wall Mounted
Installation Method FLARE Power Supply V/Ph/Hz 220-240 / 1/ 50
Fan Type & Quantity Crossflow *1 Airflow
Cooling / Heating Sound Power Level
Cooling / Heating Sound Pressure Level
Cooling / Heating
INDOOR
Condensate Drain Tube I.D. mm 16 Dimensions W/H/D mm 680 250 185
Weight kg 7 Package Dimensions W/H/D mm 740 320 260
Stacking Height Units 9 LEVELS Heating Elements kW N/A Moisture Removal L/hr 1.0
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
(2)
H/M/L m
(3)
3
/hr 420 350 270
L - H dB (A) 52/48/45
(4)
L - H dB (A) 39/35/32
2-2
SM DUO38 1-E.1 GB
Page 7
PRODUCT DATA SHEET
CONTENT
2.2.3 DELTA 35 DCI Specifications
Model Indoor Unit / Type DELTA 35 DCI / Wall Mounted
Installation Method FLARE
Power Supply V/Ph/Hz 220-240 / 1/ 50
Fan Type & Quantity Crossflow *1
Airflow
Cooling / Heating
Sound Power Level
Cooling / Heating
Sound Pressure Level
Cooling / Heating
INDOOR
Condensate Drain Tube I.D. mm 16
Dimensions W/H/D mm 840 250 185
Weight kg 8.0
Package Dimensions W/H/D mm 930 320 265
Stacking Height Units 9 LEVELS
Heating Elements kW N/A
Moisture Removal L/hr 1.5
(2)
H/M/L m3/hr 550 450 350
(3)
L - H dB (A) 56/46/42
(4)
L - H dB (A) 39/33/29
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
2.3 Indoor Units Combinations
Cooling Heating
Indoor Units
Combinations
22 2200
25 2500
35 3500
22+22 1850 1850
22+25 1850 1950
22+35 1850 3050
25+25 1950 1950
Room A Room B Total Capacity Power Input Room A Room B Total Capacity Power Input
[W] [W] [W] [W] [W] [W] [W] [W]
-
2200 (1500 - 2600) 675 (450 - 850) 2500
-
2500 (1500 - 3000) 750 (450 - 980) 2800
-
3500 (1500 - 4100) 1030 (450 – 1250) 3600
3700 (1500 - 4700) 1000 (450-1800) 2150 2150 4300 (1200 – 5200) 1200 (450 – 1800)
3800 (1500 - 4800) 1050 (450 - 1800) 2150 2250 4400 (1200 – 5300) 1240 (450 – 1800)
4900 (1500 - 5200) 1350 (450 - 1800) 2150 3250 5400 (1200 – 5900) 1520 (450 – 1800)
3900 (1500 - 5500) 1100 (450 - 1800) 2250 2250 4500 (1200 - 6200) 1280 (450 - 1800)
-
2500 (1200 - 3100) 750 (450 - 1000)
-
2800 (1200 – 3500) 910 (450 – 1220)
-
3600 (1200 - 4100) 1030 (450 - 1150)
SM DUO38 1-E.1 GB
25+35 1950 3050
5000 (1500 - 5500) 1400 (450 - 1800) 2250 3250 5500 (1200 - 6200) 1560 (450 - 1800)
2-3
Page 8
3. RATING CONDITIONS
CONTENT
Standard conditions in accordance with ISO 5151, ISO 13253 (for ducted units) and EN 14511.
Cooling:
Indoor: 27oC DB 19oC WB Outdoor: 35 oC DB
Heating:
Indoor: 20oC DB Outdoor: 7oC DB 6oC WB
3.1 Operating Limits
Upper limit
Cooling
Lower limit 21
Upper limit 27
Heating
Lower limit 10

RATING CONDITIONS

Indoor Outdoor
o
C DB 23oC WB 46oC DB
32
o
C DB 15oC WB -10oC DB
o
C DB 24oC DB 18oC WB
o
C DB -15oC DB -16oC WB
Voltage
1PH 198 – 264 V
3PH N/A
SM DUO38 1-E.1 GB
3-1
Page 9
4. OUTLINE DIMENSIONS
µ
CONTENT
4.1 Indoor Unit: DELTA 22, DELTA 25 DCI
MOUNTING TEMPLATE TO BE USED FOR LOCATION OF INDOOR UNIT ON THE WALL
141
58
306

OUTLINE DIMENSIONS

CEILING
INDOOR UNIT OUTLINE
46
Min50
AIR INTAKE
AIR INTAKE
AIR OUTLET
Indoor Unit: DELTA 35 DCI
4.2
185
250
160
41
ŘŞř
52
118
TUBING WALL OPENING (FOR REAR LEFT ROUTING)
Şŗ
40
´¶¼µ»°µ®»¬´·³¨»¬ »¶©¬¼º¬«¶¹³¶ª¨»°¶µ ¶°µ«¶¶¹¼µ°»¶µ»¯¬¾¨³³
380
670
TUBING WALL OPENING
(FOR REAR ROUTING)
680
śŗŝ
ª¬°³°µ®
ŜŠ
244
80
ŗŜòí´
°µ«¶¶¹¼µ°»¶¼»³°
¨°¹°µ»¨²¬
¨°¹°µ»¨²¬
¨°¹¶¼»³¬»
SM DUO38 1-E.1 GB
ŘşŜ
ŗŝ Ř
ŗś
Ŝŗ
ŘŚŞ
ŗŜ ř
řŜ
»¼©°µ®¾¨³³¶·¬µ°µ® ¶¹¹¬¨¹³¬»¹¶¼»°µ®
Ŝŗś
şŚŗ
»¼©°µ®¾¨³³¶·¬µ°µ®
¶¹¹¬¨¹¹¶¼»°µ®
şśŗ
śśř
şŗ
4-1
Page 10
OUTLINE DIMENSIONS
CONTENT
4.3 Outdoor Unit: DUO 38 DCI / Delta
4-2
SM DUO38 1-E.1 GB
Page 11
5. PERFORMANCE DATA
n
CONTENT
5.1 Delta 22+22 DCI
5.1.1 Cooling Capacity (kW) - Run Mode (Unit A or B)
230[V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB/WB TEMPERATURE [0C]

PERFORMANCE DATA

OD COIL ENTERING AIR DB TEMPERATURE [0C]
-10 - 20 (protection range)
25
30
35
40
46
LEGEND
DATA 22/15
24/17 27/19 29/21 32/23
TC 80 - 110 % of nominal SC 80 - 105 % of nominal
PI 25 - 50 % of nominal TC 1.98 2.10 2.22 2.33 2.45 SC 1.53 1.57 1.61 1.64 1.68
PI 0.39 0.40 0.41 0.42 0.43 TC 1.80 1.92 2.03 2.15 2.26 SC 1.46 1.49 1.53 1.56 1.60
PI 0.44 0.45 TC 1.62 1.73
0.45
1.85
0.46 0.47
1.97 2.08
SC 1.38 1.41 1.45 1.49 1.52
PI 0.48 0.49 TC
80%-92% of nominal
0.50
0.51 0.52
SC 80%-92% of nominal
PI 80%-100% of nominal TC 70%-85% of nominal SC 70%-85% of nominal
PI 90%-100% of nominal
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC)
o
DB Dry Bulb Temp., (
C) ID Indoor OD – Outdoor
5.1.2 Capacity Correction Factors
1.2
1.1
1
0.9
0.8
0.7
Capacity Ratio
0.6
0.5
20 25 30 35 40 45
Outdoor Temperature [deg C]
SM DUO38 1-E.1 GB
5-1
Page 12
PERFORMANCE DATA
CONTENT
5.1.3 Heating Capacity (kW) - Run Mode(Unit A or B)
230[V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB TEMPERATURE [C0]
OD COIL ENTERING AIR
DB/WB TEMPERATURE
[C0]
-15/-16
-10/-12
-7/-8
-1/-2
2/1
7/6
10/9
15/12
15-24 TC 85 - 105 % of nominal
(Protection Range) PI 80 - 120 % of nominal
DATA 15 20 25
TC 1.15 1.07 1.00
PI 0.38 0.44 0.49
TC 1.37 1.30 1.23
PI 0.44 0.50 0.55
TC 1.54 1.47 0.55
PI 0.49 0.54 0.60
TC 1.63 1.56 1.49
PI 0.51 0.56 0.62
TC 1.68 1.61 1.54
PI 0.52 0.58 0.63
TC 2.22 2.15 2.08
PI 0.54 0.60 0.66
TC 2.31 2.24 2.17
PI 0.57 0.63 0.68
TC 2.40 2.33 2.26
PI 0.60 0.65 0.71
LEGEND
TC – Total Cooling Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB Dry Bulb Temp., (oC) ID Indoor OD – Outdoor
5.1.4 Capacity Correction Factors
1.2
1.1
1
0.9
0.8
0.7
Capacity Ration
0.6
0.5
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [deg C]
5-2
SM DUO38 1-E.1 GB
Page 13
5.2 Delta 25+25 DCI
CONTENT
5.2.1 Cooling Capacity (kW) - Run Mode (Unit A or B)
230[V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB/WB TEMPERATURE [0C]
OD COIL ENTERING
AIRDB TEMPERATURE
[oC]
-10 - 20 (protection range)
25
30
35
40 (protection range
46 (protection range
DATA 22/15
TC 80 - 110 % of nominal SC 80 - 105 % of nominal
PI 25 - 50 % of nominal TC 2.09 2.21 2.34 2.46 2.58 SC 1.64 1.68 1.72 1.76 1.80
PI 0.43 0.44 0.45 0.46 0.47 TC 1.90 2.02 2.14 2.27 2.39 SC 1.56 1.59 1.63 1.67 1.71
PI 0.48 0.49 TC 1.71 1.83 SC 1.47 1.51 1.55 1.59 1.63
PI 0.53 0.54 TC SC 80%-92% of nominal
PI 80%-100% of nominal TC 70%-85% of nominal SC 70%-85% of nominal
PI 90%-100% of nominal
24/17 27/19 29/21 32/23
80%-92% of nominal
0.50
1.95
0.55
PERFORMANCE DATA
0.51 0.52
2.07 2.19
0.56 0.57
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB Dry Bulb Temp., (oC) ID Indoor OD – Outdoor
5.2.2 Capacity Correction Factors
Cooling Capacity Ratio Vs. Outdoor Temperature
1.2
1.1
1
0.9
0.8
0.7
Capacity Ration
0.6
0.5
20 25 30 35 40 45
Outdoor Temperature [deg C]
SM DUO38 1-E.1 GB
5-3
Page 14
PERFORMANCE DATA
CONTENT
5.2.3 Heating Capacity (kW) - Run Mode(Unit A or B)
230[V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB TEMPERATURE [0C]
OD COIL ENTERING
AIR DB/WB
TEMPERATURE [0C]
DATA 15 20 25
-15/-16
-10/-12
-7/-8
-1/-2
2/1
7/6
10/9
15/12
15-24
(Protection Range)
TC 1.20 1.12 1.05
PI 0.41 0.47 0.53
TC 1.44 1.36 1.29
PI 0.47 0.53 0.59
TC 1.61 1.54 1.47
PI 0.52 0.58 0.64
TC 1.70 1.63 1.55
PI 0.54 0.60 0.66
TC 1.76 1.69 1.61
PI 0.56
TC 2.32
PI 0.58
TC 2.42
PI 0.61 0.67 0.73
TC 2.51 2.43 2.36
PI 0.64 0.69 0.75
TC 85 - 105 % of nominal
PI 80 - 120 % of nominal
LEGEND
TC – Total Cooling Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB Dry Bulb Temp., (oC) ID Indoor OD – Outdoor
0.62
2.25
0.64
2.34
0.68
2.18
0.70
2.27
1.3.4 Capacity Correction Factors
5-4
Heating Capacity Ratio Vs. Outdoor Temperature
1.2
1.1
1
0.9
0.8
0.7
Capacity Ration
0.6
0.5
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [deg C]
SM DUO38 1-E.1 GB
Page 15
5.3 Delta 25+35
CONTENT
5.3.1 Cooling Capacity (kW) - Run Mode(Unit A or B)
230[V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB/WB TEMPERATURE [OC]
OD COIL
ENTERING AIR DB
TEMPERATURE [OC]
DATA 22/15
24/17 27/19 29/21 32/23
PERFORMANCE DATA
-10 - 20 (protection range)
25
30
35
40
46
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB Dry Bulb Temp., (oC) ID Indoor OD – Outdoor
TC 80 - 110 % of nominal SC 80 - 105 % of nominal
PI 25 - 50 % of nominal TC 3.27 3.46 3.65 3.84 4.04 SC 2.22 2.27 2.33 2.38 2.43
PI 0.67 0.68 0.70 0.71 0.72 TC 2.97 3.16 3.35 3.54 3.73 SC 2.11 2.16 2.21 2.27 2.32
PI 0.75 0.76 TC 2.67 2.86
0.77
3.05
0.79 0.80
3.24 3.43
SC 1.99 2.05 2.10 2.15 2.21
PI 0.82 0.84 TC
80%-92% of nominal
0.85
0.86 0.88
SC 80%-92% of nominal
PI 80%-100% of nominal TC 70%-85% of nominal SC 70%-85% of nominal
PI 90%-100% of nominal
5.3.2 Capacity Correction Factors
SM DUO38 1-E.1 GB
Cooling Capacity Ratio Vs. Outdoor Temperature
1.2
1.1
1
0.9
0.8
0.7
Capacity Ration
0.6
0.5
20 25 30 35 40 45
Outdoor Temperature [deg C]
5-5
Page 16
PERFORMANCE DATA
CONTENT
5.3.3 Heating Capacity (kW) - Run Mode(Unit A or B) 230[V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB TEMPERATURE [0C]
OD COIL ENTERING
AIR DB/WB
TEMPERATURE [0C]
DATA 15 20 25
-15/-16
-10/-12
-7/-8
-1/-2
2/1
7/6
10/9
15/12
15-24
(Protection Range)
TC 1.73 1.62 1.52
PI 0.59 0.67 0.76
TC 2.07 1.97 1.86
PI 0.68 0.76 0.85
TC 2.33 2.22 2.12
PI 0.75 0.83 0.91
TC 2.46 2.35 2.25
PI 0.78 0.86 0.95
TC 2.55 2.44 2.33
PI 0.80
TC 3.36
PI 0.84
TC 3.49
PI 0.87 0.96 1.04
TC 3.62 3.52 3.41
PI 0.91 1.00 1.08
TC 85 - 105 % of nominal
PI 80 - 120 % of nominal
LEGEND
TC – Total Cooling Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB Dry Bulb Temp., (oC) ID Indoor OD – Outdoor
0.89
3.25
0.92
3.38
0.97
3.14
1.00
3.28
5.3.4 Capacity Correction Factors
5-6
Cooling Capacity Ratio Vs. Outdoor Temperature
1.2
1.1
1
0.9
0.8
0.7
Capacity Ration
0.6
0.5
20 25 30 35 40 45
Outdoor Temperature [deg C]
SM DUO38 1-E.1 GB
Page 17
PERFORMANCE DATA
CONTENT
5.4 Capacity Correction Factor Due to Tubing Length (OneWay)
5.4.1 Delta 22 / 25 / 35 DCI
5.4.2 Cooling
Capacity Ratio VS.Tubing Length - Cooling
1.02
1.00
0.98
0.96
0.94
0.92
Capacity Ratio
0.90
0.88 4 6 8 1012141618202224262830
Tubing Length [m]
5.4.3 Heating
1.02
1.00
0.98
0.96
0.94
0.92
Capacity Ratio
0.90
0.88
Capacity Ratio VS. Tubing Length - Heating
4 6 8 1012141618202224262830
Tubing Length [m]
SM DUO38 1-E.1 GB
5-7
Page 18
6. PRESSURE CURVES
CONTENT
6.1 Model: Delta 22+22, Delta 25+25 DUO 38 DCI
6.1.1 Cooling – Test Mode
Suction Pressure VS.Outdoor Temp'.
1400

PRESSURE CURVES

Suction Pressure [kPa]
Discharge Pressure [kPa]
1300
1200
1100
1000
900
800
700
10 15 20 25 30 35 40 45
Outdoor DB Temperature [ºC]
Discharge Pressure VS. Outdoor Temp'.
3750 3500 3250 3000 2750 2500 2250 2000 1750 1500
10 15 20 25 30 35 40 45
Outdoor DB Temperature [ºC]
Indoor DB/WB
Temp'.
22/15
24/17
27/19
29/21
32/23
Indoor DB/WB
Temp'.
22/15
24/17
27/19
29/21
32/23
SM DUO38 1-E.1 GB
6-1
Page 19
PRESSURE CURVES
CONTENT
6.1.2 Heading – Test Mode
Suction Pressure VS.Outdoor Temp'.
1100
1000
900
800
700
600
500
Suction Pressure [kPa]
400
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [ºC]
Indoor DB
Temp'.
15
20
25
Discharge Pressure VS. Outdoor Temp'.
3250
3000
2750
2500
2250
2000
1750
Discharge Pressure [kPa]
1500
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [ºC]
Indoor DB
Temp'.
15
20
25
6-2
SM DUO38 1-E.1 GB
Page 20
6.2 Model: Delta 25+35 DUO 38 DCI
CONTENT
6.2.1 Cooling – Test Mode
Suction Pressure VS.Outdoor Temp'.
1200
1100
PRESSURE CURVES
Indoor DB/WB
Temp'.
Suction Pressure [kPa]
Discharge Pressure [kPa]
1000
900
800
700
10 15 20 25 30 35 40 45
Outdoor DB Temperature [ºC]
Discharge Pressure VS. Outdoor Temp'.
4000 3750 3500 3250 3000 2750 2500 2250 2000 1750 1500
10 15 20 25 30 35 40 45
22/15
24/17
27/19
29/21
32/23
Indoor DB/WB
Temp'.
22/15
24/17
27/19
29/21
32/23
SM DUO38 1-E.1 GB
Outdoor DB Temperature [ºC]
6-3
Page 21
PRESSURE CURVES
CONTENT
6.1.2 Heading – Test Mode
Suction Pressure VS.Outdoor Temp'.
1100
Suction Pressure [kPa]
1000
900
800
700
600
500
400
300
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [ºC]
Discharge Pressure VS. Outdoor Temp'.
Indoor DB
Temp'.
15
20
25
Discharge Pressure [kPa]
3250
3000
2750
2500
2250
2000
1750
1500
-15 -10 -5 0 5 10 15 Outdoor WB Temperature [ºC]
Indoor DB
Temp'.
15
20
25
6-4
SM DUO38 1-E.1 GB
Page 22

ELECTRICAL DATA

CONTENT
7. ELECTRICAL DATA
Power Supply 1 PH, 220-240 VAC, 50Hz
Connected to Outdoor
Maximum Current 13.7 A
Inrush Current 35 A
Starting Current 10 A
Circuit breaker 16 A
Power supply wiring - No. x cross section 3 X 2.5 mm
Interconnecting cable - No. x cross section 2 X 4 X 1.5 mm
Note:
Inrush current is the current when power is up. (charging the DC capacitors at outdoor unit controller).
Starting current is the current when starting the compressor
2
2
NOTE
Power wiring cord should comply with local lows and electrical regulations requirements.
7-1
Page 23
8. WIRING DIAGRAMS
CONTENT
8.1 DUO 38 DCI / DELTA Wiring Diagram

WIRING DIAGRAMS

HSTSUCTCTT
Ferrite core
L
N
4/L
5/C
6
N
To metal sheet
L
Red
FUSE
Blue
T 15A/250Vac
Brown
Y/G
~230V 50Hz
Power supply
To metal sheet
Ferrite core
L
UNIT 1
N
4/L
65/C
UNIT 2
Blue
Red
Brown
Y/G
L1
N1
C1
C2
C1
C2
2 1
P5
22 11
P8
N1/2
L1/2
OATOCT
OFAN
OUTDOOR UNIT CIRCUIT DIAGRAM
Base
Choke coil
COMP
heater
valve
Reverse
PG
V
sp=0-6.5V DC
Vcc=15V DC GND
V
m=310V DC
2 1
2 1
64 5
3 2 1
6 5 4 3 2 1
2
1
2 1
W
UV
P20
P19 P2EEV
P7
P15
P1
P4
P14
P13
P11P3 P9
P12
EARTH
To metal sheet
N-COM
COM
P10
N
L
Outdoor unit controller PCB
6
5
4
3
Model Jumper
2
1
JP9
J30
Mega tool
JP60
Jumper
J40
5
3
6
Night
4
J90
P2
P70
P10
P11
E
COM
NL
1
L
N
COM2
COM1
COM
321
2
Alarm
468600029
To metal sheet
E
N
COM
N-F
L-F
EEV1
2
3
1
4 3 2 1
4 3 2 1
RGT1
1
2
J50
6
4
5
RGT2
2
J51
EMI filter PCB
EEV2
2
4
13
J41
Stdby
MSMP PCB
2
1
1
J91
SM DUO38 1-E.1 GB
8-1
Page 24
9. REFRIGERATION DIAGRAMS
CONTENT
9.1 Heat Pump Models
9.1.1 DUO 38 DCI => Cooling Mode

REFRIGERATION DIAGRAMS

IDU1
Brass Jointer
(3/8")
Gas Valve
(3/8")
Brass Jointer
(3/8")
Gas Valve
(3/8")
IDU2
Brass Jointer
(1/4")
Liquid Valve
(1/4")
Strainer
Brass Jointer
(1/4")
Liquid Valve
(1/4")
Strainer
SM DUO38 1-E.1 GB
ODU
Reverse
Valve
ID¦3.0ױ
ID¦3.0ױ
COMP.
EEV1
EEV2
Strainer
ID¦3.0ױ
9-1
Page 25
REFRIGERATION DIAGRAMS
CONTENT
9.1.2 DUO 38 DCI => Heating Mode
IDU1
Brass Jointer
(3/8")
Gas Valve
(3/8")
Brass Jointer
(3/8")
Gas Valve
(3/8")
IDU2
Brass Jointer
(1/4")
Liquid Valve
(1/4")
Strainer
Brass Jointer
(1/4")
Liquid Valve
(1/4")
Strainer
9-2
ODU
Reverse
Valve
ID¦3.0ױ
ID¦3.0ױ
COMP.
EEV1
EEV2
Strainer
ID¦3.0ױ
SM DUO38 1-E.1 GB
Page 26
10. TUBING CONNECTIONS
CONTENT

TUBING CONNECTIONS

TUBE (Inch)
¼” ⅜” ½” ⅝” ¾”
TORQUE (Nm)
Flare Nuts 11-13 40-45 60-65 70-75 80-85 Valve Cap 13-20 13-20 18-25 18-25 40-50
Service Port Cap 11-13 11-13 11-13 11-13 11-13
1. Valve Protection Cap-end
2. Refrigerant Valve Port (use Allen wrench to open/close)
3. Valve Protection Cap
4. Refrigerant Valve
5. Service Port Cap
6. Flare Nut
7. Unit Back Side
8. Copper Tube
When the outdoor unit is installed above the indoor unit an oil trap is required every 5m along the suction line at the lowest point of the riser. Incase the indoor unit is installed above the outdoor, no trap is required.
SM DUO38 1-E.1 GB
10-1
Page 27

CONTROL SYSTEM

CONTENT
11. CONTROL SYSTEM
11.1 General Functions and Operating Rules (for single split models)
The DCI software is fully parametric. All the model dependent parameters are shown in Blue color and with Italic style [parameter]. The parameters values are given in the last section of this control logic chapter of the service manual.
11.2 System Operation Concept
The control function is divided between indoor and outdoor unit controllers. Indoor unit is the system ‘Master’, requesting the outdoor unit for cooling/heating capacity supply. The outdoor unit is the system ‘Slave’ and it must supply the required capacity unless it enters into a protection mode avoiding it from supplying the requested capacity.
The capacity request is transferred via indoor to outdoor communication, and is represented by a parameter called ‘NLOAD’. NLOAD is an integer number with values between 0 and 127, and it represents the heat or cool load felt by the indoor unit.
11.3 Compressor Frequency Control
11.3.1 NLOAD setting
The NLOAD setting is done by the indoor unit controller, based on a PI control scheme. The actual NLOAD to be sent to the outdoor unit controller is based on the preliminary LOAD calculation, the indoor fan speed, and the power shedding function.
NLOAD limits as a function of indoor fan speed:
Indoor Fan Speed Maximum NLOAD Cooling Maximum NLOAD Heating
Low
Medium
High
Turbo
Auto
NLOAD limits as a function of power shedding:
Mode Power Shedding OFF Power Shedding ON
Cool No limit Nominal Cooling
Max NLOADIF1C Max NLOADIF2C Max NLOADIF3C Max NLOADIF4C Max NLOADIF5C
127 127 127 127 127
SM DUO38 1-E.1 GB
Heat No limit Nominal Heating
11-1
Page 28
CONTROL SYSTEM
CONTENT
11.3.2 Target Frequency Setting
The compressor target frequency is a function of the NLOAD number sent from the indoor controller and the outdoor air temperature. Basic Target Frequency Setting:
NLOAD Target Frequency
127
10 < NLOAD < 127 Interpolated value between minimum and maximum frequency
Maximum frequency
10
0 Compressor is stopped
Target frequency limits as a function of outdoor air temperature (OAT):
OAT Range Cool mode limits Heat mode limits
OAT < 6
6 ≤ OAT < 15
15 ≤ OAT < 24
24 ≤ OAT No limit
MaxFreqAsOATC
Minimum frequency
11.3.3 Frequency Changes Control
Frequency change rate is 1 Hz/sec.
11.3.4 Compressor Starting Control
Frequency
Step 3
No limit
MaxFreqAsOAT1H
MaxFreqAsOAT2H
Step 2
Step 1
1
Minute
1
Minute
Min 10 Minutes
\
11.3.5 Minimum On and Off Time 3 minutes
Time
11-2
SM DUO38 1-E.1 GB
Page 29
11.4 Indoor Fan Control
CONTENT
10 Indoor fan speeds are determined for each model. 5 speeds for cool/dry/fan modes and 5 speeds for heat mode. When user sets the indoor fan speed to a fixed speed (Low/ Medium/ High), unit will operate constantly at set speed. When Auto Fan is selected, indoor unit controller can operate in all speeds. The actual speed is set according to the cool/heat load.
11.4.1 Turbo Speed
The Turbo speed is activated during the first 30 minutes of unit operation when auto fan speed is selected and under the following conditions:
Difference between set point and actual room temperature is bigger then 3 degrees.
Room temperature > 22 for cooling, or < 25 for heating.
11.5 Heating Element Control
Heating element can be started if LOAD > 0.8 * MaximumNLOAD AND Indoor Coil temperature < 45. The heating element will be stopped when LOAD < 0.5 * MaximumNLOAD OR if Indoor Coil temperature > 50.
11.6 Outdoor Fan Control
CONTROL SYSTEM
7 outdoor fan speeds are determined for each model. 3 speeds for cool and dry modes, and 3 speeds for heat mode, and a very low speed. Outdoor fan speed is a function of compressor frequency and outdoor air temperature (OAT). 4 routines for fan control are determined. The control routine selection depends on operation mode, compressor speed, and outdoor air temperature (OAT) and heat sink temperature (HST).
Routine Conditions
Heating with OAT < 150C
or
A
B Cooling with 200C > OAT > 70C C Cooling with 7 D Heating with OAT > 15
Compressor Frequency (CF)
CF = 0 OFF OFF OFF OFF
10 ≤ CF < OFLowFreq
OFLowFreq ≤ CF < OFMedFreq
OFMedFreq ≤ CF
Cooling with OAT > 200C, or HST > 500C
or
Faulty OAT
0
C > OAT
0
C
Outdoor Fan Speed
Routine A Routine B Routine C Routine D
Low Low Very Low Low
Medium Low Very Low Low
High Low Low Medium
When compressor is switched to OFF and the heat sink temperature is above 55 degrees, the outdoor fan will remain ON in low speed for up to 3 minutes.
SM DUO38 1-E.1 GB
11-3
Page 30
CONTROL SYSTEM
CONTENT
11.7 EEV (electronic Expansion valve) Control
EEV opening is defined as EEV = EEVOL + EEV
EEVOL is the initial EEV opening as a function of the compressor frequency, operation mode, unit model and capacity.
EEVCV is a correction value for the EEV opening that is based on the compressor temperature.
During the first 10 minutes of compressor operation EEVCV = 0.
Once the first 10 minutes are over, the correction value is calculated as follow: EEVCV(n) =
EEVCV(n-1) + EEV
EEV temperature is set depending on frequency and outdoor air temperature, and the actual compressor temperature is compared to the target temperature to set the required correction to the EEV opening.
is the correction based on the compressor temperature. A target compressor
CTT
CTT
CV
11.8 Reversing Valve (RV) Control
Reversing valve is on in heat mode. Switching of RV state is done only after compressor is off for over 3 minutes.
11.9 Ionizer Control
Ionizer is on when unit is on AND indoor fan is on AND Ionizer power switch (on Ionizer) is on.
11.10 Electro Static Filter (ESF) Control
ESF is on when ESF switch is on, Safety switch is pressed, unit is on, AND indoor fan is on.
11.11 Base Heater Control
When OAT is connected, Base Heater will be on when unit is in heating and OAT<20C. When OAT is disconnected, Base Heater will be on when unit is in heating.
11.12 Fan Mode
In high/ medium/ low indoor fan user setting, unit will operate fan in selected speed. In Auto Fan user setting, fan speed will be adjusted automatically according to the difference between actual room temperature and user set point temperature.
11.13 Cool Mode
NLOAD is calculated according to the difference between actual room temperature and user set point temperature by PI control. In high/ medium/ low indoor fan user setting, unit will operate fan in selected speed. In Auto Fan user setting, fan speed will be adjusted automatically according to the calculated NLOAD.
11-4
SM DUO38 1-E.1 GB
Page 31
11.14 Heat Mode
CONTENT
NLOAD is calculated according to the difference between actual room temperature and user set point temperature by PI control. In high/ medium/ low indoor fan user setting, unit will operate fan in selected speed. In AutoFan user setting, fan speed will be adjusted automatically according to the calculated NLOAD.
11.14.1 Temperature Compensation
In wall mounted, ducted, and cassette models, 3 degrees are reduced from room temperature reading (except when in I-Feel mode), to compensate for temperature difference between high and low areas in the heated room, and for coil heat radiation on room thermistor. The temperature compensation can be enabled/disabled by shortening of J2 on the indoor unit controller.
Model J2 Shorted J2 Opened
Wall mounted Compensation Disabled Compensation Enabled
Cassette Compensation Enabled Compensation Disabled
Ducted Compensation Enabled Compensation Disabled
Floor/Ceiling Compensation Disabled Compensation Enabled
CONTROL SYSTEM
11.14.2 Indoor Fan Control in Heat Mode
Indoor fan speed depends on the indoor coil temperature:
ICTST
ICTVL ICTH ICTL
ICTT
11.15 Auto Cool/Heat Mode
When in auto cool heat mode unit will automatically select between cool and heat mode according to the difference between actual room temperature and user set point temperature (ΔT). Unit will switch from cool to heat when compressor is off for 3 minutes, and ΔT < -3.
Unit will switch from heat to cool when compressor is off for 5 minutes, and ΔT < -3.
SM DUO38 1-E.1 GB
11-5
Page 32
CONTROL SYSTEM
CONTENT
11.16 Dry Mode
As long as room temperature is higher then the set point, indoor fan will work in low speed and compressor will work between 0 and MaxNLOADIF1C Hz. When the room temperature is lower than the set point, compressor will be switched OFF and indoor fan will cycle 3 minutes OFF, 1 minute ON.
11.17 Protections
There are 5 protection codes. Normal (Norm) – unit operate normally. Stop Rise (SR) – compressor frequency can not be raised but does not have to be decreased. HzDown1 (D1) – Compressor frequency is reduced by 2 to 5 Hz per minute. HzDown2 (D2) – Compressor frequency is reduced by 5 to 10 Hz per minute. Stop Compressor (SC) – Compressor is stopped.
11.17.1 Indoor Coil Defrost Protection
ICT
ICT < -2 SC SC SC SC SC
-2 ≤ ICT < 0 D1 D1 D2 D2 D2
0 ≤ ICT < 2 SR SR D1 D2 D2 2 ≤ ICT < 4 SR SR SR D1 D2 4 ≤ ICT < 6 Norm Norm SR SR D1
6 ≤ ICT < 8 Norm Norm Norm SR SR
8 ≤ ICT Normal
Fast
Increasing
Increasing No change Decreasing
ICT Trend
Fast
Decreasing
11.17.2 Indoor Coil over Heating Protection
ICT Trend
ICT
ICT > 55 SC SC SC SC SC 53 < ICT ≤ 55 D1 D1 D2 D2 D2 49 < ICT ≤ 53 SR SR D1 D2 D2 47 < ICT ≤ 49 SR SR SR D1 D2 45 < ICT ≤ 47 Norm Norm SR SR D1
43 < ICT ≤ 45 Norm Norm Norm SR SR
ICT ≤ 43 Normal
Fast
Decreasing
Decreasing No Change Increasing
Fast
Increasing
11-6
SM DUO38 1-E.1 GB
Page 33
11.17.3 Compressor over Heating Protection
CONTENT
Compressor temperature can be in one of 5 control zones (4 in protection, and 1 normal), t.
CTT
Stop-Compresor
CTTOH4
CONTROL SYSTEM
CTTOH3
CTTOH2
CTTOH1
Control Status
P1 Norm SR P2 D1 SR P3 D2 D1
Stop Compressor SC
Compressor Temperature
P3
P2
P1
Normal
Increases
11.17.4 Compressor over Current Protection
CCR
Else
W
Stop-Compresor
CCROC4
HzDown2
CCROC3
HzDown1
CCROC2
Stop-Rise
CCROC1
Normal
SM DUO38 1-E.1 GB
11-7
Page 34
CONTROL SYSTEM
CONTENT
11.17.5 Heat Sink Over Heating Protection (NA for DCI 25 and 35)
HST
HST > 90 SC SC SC 85 < HST ≤ 90 D1 D2 D2 82 < HST ≤ 85 SR D1 D2 80 < HST ≤ 82 SR SR D1 78 < HST ≤ 80 Norm Norm SR
HST ≤ 78 Normal
Decreasing No Change Increasing
HST Trend
11.17.6 Outdoor Coil Deicing Protection
11.17.6.1 Deicing Starting Conditions
Deicing operation will start when either one of the following conditions exist:
Case 1: OCT < OAT – 8 AND TLD > DI
Case 2: OCT < OAT – 12 AND TLD > 30 minutes.
Case 3: OCT is Invalid AND TLD > DI
Case 4: Unit is just switched to STBY AND OCT < OAT – 8
Case 5: NLOAD = 0 AND OCT < OAT -8
OCT – Outdoor Coil Temperature OAT – Outdoor Air Temperature TLD – Time from Last Deicing DI – Deicing Interval (Time Interval between Two Deicing)
Deicing interval time when compressor is first started in heat mode, is 10 minutes if OCT <
-2, and is 40 minutes in other cases. Deicing interval time is changed (increased/ decreased in 10 minutes steps) as a function of deicing time. If deicing time is shorter then former deicing time, the deicing interval time will be increased. If deicing time is longer then former deicing time, the deicing interval time will be decreased.
11-8
SM DUO38 1-E.1 GB
Page 35
11.17.6.2 Deicing Protection Procedure
CONTENT
OCT
12
0
hreshold
CONTROL SYSTEM
COMP
RV
OFAN
EEV
ON
HEAT
COOL
ON
OFF
EEVDeicerOpen
Any
T1 T2
max. 12 minutes
DT
T3 T3
T1 = T2 = 36 seconds, T3 = 6 seconds
11.17.7 Condensate Water Over Flow Protection
T1
Each of the pins P1, P2, P3 can have two options: 1 – When it is shorted with P4 0 – When it is not shorted to P4
11.17.7.1 Levels Logic (used in floor/ceiling models)
SM DUO38 1-E.1 GB
P2 P3 Level
00 L0 10 L1 1 1 L2&3 01 L4
11-9
Page 36
CONTROL SYSTEM
CONTENT
Water Level
LEVEL4
LEVEL2&3
LEVEL1
ON
Pump
OFF
ANY
NLOAD
0
BLINK
OPER LED
NORMAL
11.17.7.2 1 Level Logic (used in all models except for floor/ceiling models)
P2 P3 Level
Water Level
OPER
LED
Don’t
care
Don’t
care
Overflow
Normal
ON
OFF
BLINK
1 Normal
0 Overflow
Overflow when
unit is ON
Overflow when
unit is OFF
11-10
NLOAD
PUMP
ANY
0
ON
OFF
NLOAD is
forced to 0
8 min 8 min
8 min
SM DUO38 1-E.1 GB
Page 37
CONTROL SYSTEM
CONTENT
11.18 Indoor Unit Dry Contact
Indoor unit Dry contact has two alternative functions that are selected
by J8.
Function Contact = Open Contact = Short
J8 = Open Presence Detector Connection No Limit Forced to STBY
J8 = Short Power Shedding Function No Limit Limit NLOAD
11.19 Operating the Unit from the Mode Button
Forced operation allows starting, stopping and operating in Cooling or Heating, in pre­set temperature according to the following table:
Forced operation Mode Pre-set Temperature
Cooling 20
Heating 28
0
C
0
C
11.20 On Unit Controls and Indicators
11.20.1 Indoor Unit Controller Controls and Indicators for All Models Except for Floor/Ceiling model
STAND BY INDICATOR
OPERATION INDICATOR
TIMER INDICATOR Lights up during Timer and Sleep operation.
FILTER INDICATOR Lights up when Air Filter needs to be cleaned.
COOLING INDICATOR
HEATING INDICATOR
Mode SWITCH
(COOL/HEAT/OFF)
1. Lights up when the Air Conditioner is connected to power
and ready to receive the R/C commands
1. Lights up during operation.
2. Blinks for 300 msec., to announce that a R/C infrared
signal has been received and stored.
3. Blinks continuously during protections (according to the
relevant spec section).
Lights up when system is switched to Cool Mode by using the Mode Switch on the unit.
Lights up when system is switched Heat Mode by using the Mode Switch on the unit.
Every short pressing , the next operation mode is selected, in this order : SB → Cool Mode → Heat Mode → SB → … In long pressing system enters diagnostic mode.
SM DUO38 1-E.1 GB
RESET / FILTER SWITCH
For short pressing:
When Filter LED is on - turn off the FILTER INDICATOR after a clean filter has been reinstalled. When Filter LED is off – enable/disable the buzzer announcer, if selected.
11-11
Page 38
CONTROL SYSTEM
CONTENT
11.20.2 Indoor Unit Controls and Indicators for LCD Display
STBY Cool Heat Auto Fan Dry
OFF SPT(1*) SPT(1*) SPT(1*) SPT(1*) SPT(1*)
OFF(2*) ON(2*) ON(2*) ON(2*) ON(2*) ON(2*)
OFF(2*) OFF(2*) OFF(2*) OFF(2*) OFF(2*) OFF(2*)
(Low)
OFF
OFF
(Med)
(High)
(Turbo)
OFF
OFF
User setting IFAN speed
User setting IFAN speed
OFF
(Auto)
Backlight(red) Backlight(green)
OFF OFF ON(3*) ON(3*) ON(3*) OFF
OFF ON(3*) OFF ON(3*) ON(3*) ON(3*)
11.20.3 Outdoor Unit Controller Indicators
Unit has three LED’s. SB LED is ON when power is ON (230 VAC, even when no communication). STATUS LED is ON when COMP is ON, and Blinks according to diagnostics mode definitions when either fault or protection occurs. FAULT LED Blinks according to diagnostics mode definitions when either fault or protection occurs.
User setting IFAN speed
User setting IFAN speed
User setting IFAN speed
11-12
SM DUO38 1-E.1 GB
Page 39
11.21 Jumper Settings
CONTENT
11.21.1 Indoor Unit Controller
0 = Open Jumper (disconnect jumper). 1 = Close Jumper (connect jumper).
Self test Jumper – J1
OPERATION J1 SELF-TEST 1 NORMAL 0
Compensation Jumper – J2
Model J2 (Default) Compensation
Wall Mounted 0 Activated
Floor/Ceiling 1 Deactivated
Ducted/cassette 1 Activated
Family selection Jumper – J3, J4 and J5
CONTROL SYSTEM
Family J5 J4 J3
Reserved Reserved Reserved Wall Mounted (WNG/FLO) Floor/Ceiling (PXD) Reserved Ducted (LS) Cassette (K)
IDU Model
WNG25 000011 WNG35 010011 WNG50 001000 WNG60 011000 WNG80 001001 PXD25 000100 PXD35 010100 PXD50 100100 K25 000111 K35 010111 K50 100111 LS35 010110
J8 J7 J6 J5 J4 J3
0 0 0 0 0 1 0 1 0 0 1 1 1 0 0 1 0 1 1 1 0 1 1 1
Jumper Setting
SM DUO38 1-E.1 GB
For wall mounted units Jumpers j7, j8 can be configured by service. All other jumpers on the above table are factory default (cannot be changed by service). For unit types as Cassettes, floor ceiling, and ducted, jumpers are set by a model plug.
11-13
Page 40
CONTROL SYSTEM
CONTENT
Model selection Jumper – J6, J7
Model J7 J6
9000 Btu/hr 12000 Btu/hr 18000 Btu/hr 24000 Btu/hr
J8- Clock/Power Shedding
Operation J8
Clock 0
Power Shedding 1
J9 – IFAN Cycling Disabling
0 0 0 1 1 0 1 1
Display Mode
(wall mounted units only)
LCD 0 LED 1
J9
11.21.2 Outdoor Unit Controller
11.21.2.1 JP9 JUMPER LAYOUT
Reserved (PIN 9) ODU3 (PIN 7) ODU2 (PIN 5) ODU1 (PIN 3) ODU0 (PIN 1) GND (PIN 10) GND (PIN 8) GND (PIN 6) GND (PIN 4) GND (PIN 2)
11.21.3 ODU MODEL SELECTION
ODU3 ODU2 ODU1 ODU0 ODU Model
OFF OFF OFF OFF Reserved OFF OFF OFF ON (PIN1 & PIN2) A (DCI 25) OFF OFF ON (PIN3 & PIN4) OFF B (DCI 35) OFF OFF ON (PIN3 & PIN4) ON (PIN1 & PIN2) C (DCI 50) OFF ON (PIN5 & PIN6) OFF OFF D OFF ON (PIN5 & PIN6) OFF ON (PIN1 & PIN2) E (Duo) OFF ON (PIN5 & PIN6) ON (PIN3 & PIN4) OFF F
OFF ON (PIN5 & PIN6) ON (PIN3 & PIN4) ON (PIN1 & PIN2) G ON (PIN7 & PIN8) OFF OFF OFF H ON (PIN7 & PIN8) OFF OFF ON (PIN1 & PIN2) I ON (PIN7 & PIN8) OFF ON (PIN3 & PIN4) OFF J ON (PIN7 & PIN8) OFF ON (PIN3 & PIN4) ON (PIN1 & PIN2) K ON (PIN7 & PIN8) ON (PIN5 & PIN6) OFF OFF L ON (PIN7 & PIN8) ON (PIN5 & PIN6) OFF ON (PIN1 & PIN2) M ON (PIN7 & PIN8) ON (PIN5 & PIN6) ON (PIN3 & PIN4) OFF N ON (PIN7 & PIN8) ON (PIN5 & PIN6) ON (PIN3 & PIN4) ON (PIN1 & PIN2) O
11-14
SM DUO38 1-E.1 GB
Page 41
11.22 Test Mode
CONTENT
11.22.1 Entering Test Mode
System can enter Test mode in two ways:
Automatically when the following conditions exists for 30 minutes continuously: o Mode = Cool, Set point = 16, Room temperature = 27±1, Outdoor temperature =
35±1
Or
o Mode = Heat, Set point = 30, Room temperature = 20±1, Outdoor temperature =
7±1
Manually when entering diagnostics with the following settings:
o Mode = Cool, Set point = 16 o Mode = Heat, Set point = 30
11.22.2 Unit Operation in Test Mode
In test mode, the unit will operate in fixed settings according to the indoor fan speed setting :
Indoor Fan Speed Setting Unit Setting
Low Minimum Capacity Setting High Nominal Capacity Setting Auto Maximum Capacity Setting
CONTROL SYSTEM
During test mode, protections are disabled, except for stop compressor status.
11.23 Additional Functions and Operating Rules (for DUAL split models)
The DCI SW is fully parametric. All the model dependent parameters are shown in Blue color and with Italic style [parameter]. The parameters values are given in the last section of this control logic chapter of the service manual.
11.23.1 System Control Concept
All indoor unit related items control remains the same as in single split applications. All outdoor unit related control logic remains the same as in single split applications. The MSMP controller is responsible only for the following control:
Setting of system operation mode (cool/heat)
Setting the NLOAD for the outdoor units
Controlling of the EEV’s
Dry contacts control
11.23.2 Compressor Frequency Control
11.23.3 Outdoor Unit NLOAD setting
The MSMP controller gets the NLOAD from each of the indoor units, and sends a combined NLOAD to the outdoor unit control. The combined NLOAD is a weighted average of the indoor units NLOAD. The weight of the indoor units as a function of their nominal capacity:
SM DUO38 1-E.1 GB
Indoor Unit Capacity [kW] (kBtu/hr) Capacity Code
2.5 (9000) 1
3.5 (12000) 1.5
5.0 (18000) 2
7.2 (24000) 3
11-15
Page 42
CONTROL SYSTEM
CONTENT
11.23.4 EEV (electronic Expansion valve) Control
EEV opening is defined as EEV = EEVOL + EEV
EEVOL is the initial EEV opening as a function of the compressor frequency, operation mode, unit model and capacity.
EEVCV is a correction value for the EEV opening that is based in cooling mode on the relevant indoor unit super heat and compressor temperature.
During the first 10 minutes of compressor operation EEVCV = 0.
CV
11.23.5 System Mode Setting and Reversing Valve (RV) Control
The first indoor unit that is causing the system to be turned ON sets the system mode.
11.23.6 Indoor Units Operation when Indoor Unit Mode is Different than Outdoor Unit Mode
Open louvers according to user selection.
Indoor fan is forced to OFF.
11.24 Dry Contacts Control
Dry Contact Contact = Open Contact = Short
STBY No Limit System is Forced to STBY
Night No Limit Outdoor fan speed reduced to low in cooling mode
A dry contact output for Alarm will be shorted when any failure exists in the system.
11-16
SM DUO38 1-E.1 GB
Page 43
11.25 SW Parameters
CONTENT
11.25.1 Indoor Units SW Parameters
General Parameters for All Models:
Parameters defining the indoor fan speed as a function of Indoor Coil temperature in heat mode (ICT):
ICTST Speed ICT to stop indoor fan 25 ICTVLSpeed ICT to go down to very low speed 28 ICTLSpeed ICT to start in very low speed 30 ICTHSpeed ICT to start in increase speed from very low 32 ICTTSpeed ICT to enable Turbo fan speed 40
Model Depended Parameters:
CONTROL SYSTEM
Parameter name
NLOAD limits as a function of selected indoor fan speed
MaxNLOADIF1C 40 40 MaxNLOADIF2C 53 53 MaxNLOADIF3C 120 120 MaxNLOADIF4C 127 127 MaxNLOADIF5C 127 127
IFVLOWC 700 700 IFLOWC 800 800 IFMEDC 900 950 IFHIGHC 1050 1100 IFTURBOC 1150 1200 IFVLOWH 700 700 IFLOWH 800 850 IFMEDH 950 1000 IFHIGHH 1100 1150 IFTURBOH 1200 1250
Nominal Compressor Frequency
NomLoadC 40 62 NomLoadH 55 67
Parameter Name
NLOAD limits as a function of selected indoor fan speed
MaxNLOADIF1C 40 40 40 40 MaxNLOADIF2C 53 56 56 60 MaxNLOADIF3C 120 90 90 90 MaxNLOADIF4C 127 90 90 90 MaxNLOADIF5C 127 90 90 90
Nominal Compressor Frequency
NomLoadC 40 60 56 63
DCI 25 DCI 35
Indoor Fan speeds
K 25 K 35 K 35S K 50
Wall Mounted Models
Cassette Models
NomLoadH 55 69 73 80
SM DUO38 1-E.1 GB
11-17
Page 44
CONTROL SYSTEM
CONTENT
11.25.2 Outdoor Units SW Parameters:
Parameter Name DCI25 DCI35 DCI 50 DCI50 DUO
Compressor Parameters
MinFreqC 30 33 20 20
MaxFreqC 64 80 85 97
MinFreqH 30 35 20 26
MaxFreqH 81 93 99 106
Step1Freq 60 60 60 60
Step2Freq 70 70 70 80
Step3Freq 90 90 90 90
Frequency limits as a function of outdoor air temperature
MaxFreqAsOATC 50 50 64 62
MaxFreqAsOAT1H 65 75 85 85
MaxFreqAsOAT2H 60 60 60 60
Compressor Over Heating Protection
CTTOH1 949494 90
CTTOH2 989898 95
CTTOH3 102 102 102 102
CTTOH4 105 105 105 105
Compressor Over Current Protection [A]
CCR01 7.1 7.1 10 10
CCR02 7.5 7.5 10.5 10.5
CCR03 7.9 7.9 10.8 10.8
CCR04 8.3 8.3 11.2 11.2
Outdoor Fan Speed (RPM)
VL 200 200 200 200
OFLOWC 550 550 600 600
OFMEDC 700 700 760 830
OFMAXC 830 830 920 920
OFLOWH 550 550 600 600
OFMEDH 700 700 830 920
OFMAXH 830 830 1000 1000
Outdoor Fan Limit Control
OFLowFreq 45 45 40 40
OFMedFreq 57 57 70 70
11-18
SM DUO38 1-E.1 GB
Page 45
12. TROUBLESHOOTING
CONTENT
WARNING!!!
When Power Up – the whole outdoor unit controller, including the wiring, is under HIGH
VOLTAGE!!!
Never open the Outdoor unit before turning off the Power!!!
When turned off, the system is still charged (400V)!!!
It takes about 3 Min. to discharge the system.
Touching the controller before discharging may cause an electrical shock!!!
For safe handling of the controller please refer to section 1.6 below.
1.1 Dual Split System Failures and Corrective Actions

TROUBLESHOOTING

No
1 Power supply indicator at
indoor unit (Red LED) does not light up. Indoor fan does not start (louvers are opened and Green LED does light up)
3 Compressor does not start Jumper settings of
4 One indoor is operating, in
cool mode, with no capacity, and the other unit has water leaks/freezing problems
5 One indoor is operating in
heat mode with a limited capacity, and the coil on the other unit is very hot.
6 Compressor operate but
unit generate no capacity
7 One unit only is operating Communication
8 All others Specific problems of
SYMPTOM PROBABLE CAUSE CORRECTIVE ACTION
No power supply Check power supply from the outdoor. If
Unit in heat mode and coil is still not warm. The outdoor unit is in the opposite mode. Problem with PCB or capacitor
outdoor unit is not correct The communication wires of the two indoor units are switched
EEV is stuck in close position
problems
indoor or outdoor units
power supply is OK, check display and display wiring. If OK, replace controller. Change to cool mode and check. 2
Change operation mode and check if fan starts. Change to high speed and Check power supply to motor is higher than 130VAC (for Triac controlled motor) or higher than 220VAC for fixed speed motors, if OK replace capacitor, if not OK replace controller Use diagnostics (see 1.2 below) information on MSMP board.
Check and correct the communication wires connection
Check EEV
Use diagnostics information on MSMP board (see 1.2 below). Use diagnostics information on MSMP board (see 1.2 below), and perform action items as recommended in single split systems
SM DUO38 1-E.1 GB
12-1
Page 46
TROUBLESHOOTING
CONTENT
1.2 Checking the refrigeration system
Checking system pressures and other thermodynamic measures should be done when system is in Test Mode (in Test mode, system operates in fixed settings). The performance curves given in this manual are given for unit performance in test mode when high indoor fan speed is selected. Entering test mode: Set the two indoor units to Cool/16 degrees/High indoor fan speed, or Heat/30 degrees/High indoor fan speed, and enter diagnostics. Note: the two indoor units should be set to the same mode and fan speed.
1.3 Judgment by MSMP Diagnostics
The MSMP controller has 11 LED’s (1 STBY LED, 5 Unit LEDs and 5 Status/Fault LEDs). STBY LED is ON when power is ON. 5 Unit LEDs refer to four Indoor units and one Outdoor unit. They will turn on one at a time and the corresponding Indoor/Outdoor unit status/fault code will be displayed on the Status/Fault LEDs. If the unit is normal (no fault), the unit LED and the corresponding status will be displayed for 5 seconds and move to the next unit LED. On the other hand, if the unit is in fault, the unit LED and the corresponding fault will be displayed for 10 seconds, and hence more time to read the fault code.
1.3.1 MSMP Fault Code for Outdoor unit:
No Problem 5 4 3 2 1 1 OCT is disconnected 2 OCT is shorted 3 CTT is disconnected 4 CTT is shorted 5 HST is disconnected (when enabled) 6 HST is shorted (when enabled) 7 OAT is disconnected (when enabled) 8 OAT is shorted (when enabled) 9 TSUC is disconnected (when enabled) 10 TSUC is shorted (when enabled) 11 IPM 12 Bad Outdoor unit EEPROM 13 DC under voltage 14 DC over voltage 15 AC under voltage 16 Indoor / Outdoor unit Communication mismatch 17 No Communication 18 Illegal Outdoor unit Model 19 Bad MSMP EEPROM 20 Heat sink Over Heating 21 Deicing 22 Compressor Over Heating 23 Compressor Over Current …. Reserved 27 Bad Communication … Reserved 29 No Fault (Heat Mode) 30 No Fault (Cool, Dry, Fan Mode) 31 No Fault (Stand By)
0 0 0 0 1 0 0 0 1 0 0 0 0 1 1 0 0 1 0 0 0 0 1 0 1 0 0 1 1 0 0 0 1 1 1 0 1 0 0 0 0 1 0 0 1 0 1 0 1 0 0 1 0 1 1 0 1 1 0 0 0 1 1 0 1 0 1 1 1 0 0 1 1 1 1 1 0 0 0 0 1 0 0 0 1 1 0 0 1 0 1 0 0 1 1 1 0 1 0 0 1 0 1 0 1 1 0 1 1 0 1 0 1 1 1
1 1 0 1 1
1 1 1 0 1 1 1 1 1 0 1 1 1 1 1
12-2
SM DUO38 1-E.1 GB
Page 47
1.3.2 Outdoor unit diagnosis by MSMP and corrective actions
CONTENT
TROUBLESHOOTING
No.
Sensors failures of all types Check sensors connections
1
IPM Fault Electronics HW
2
Bad EEPROM No action, unless special
3
DC under/over Voltage Electronics HW
4
AC under Voltage Check outdoor unit power
5
Indoor / Outdoor unit
6
Communication mismatch
No Communication Communication or
7
Compressor Lock Switch unit to STBY and
8
Bad Communication Communication quality is
9
Fault
Probable Cause Corrective Action
or replace sensors. Check all wiring and jumper
problem
problem
Indoor and Outdoor controllers are with different versions
grounding wiring is not good.
low reliability
settings, if OK, replace electronics.
parameters are required for unit operation. Check outdoor unit power supply voltage
supply voltage Replace Indoor controller
Check Indoor to Outdoor wiring and grounding
restart Check Indoor to Outdoor wiring and grounding
SM DUO38 1-E.1 GB
12-3
Page 48
TROUBLESHOOTING
CONTENT
1.3.3 MSMP Fault Code for Indoor unit:
No Problem 5 4 3 2 1
RT-1 is disconnected 0 0 0 0 1
1
RT-1 is shorted 0 0 0 1 0
2
RT-2 is disconnected 0 0 0 1 1
3
RT-2 is shorted 0 0 1 0 0
4
RGT is disconnected 0 0 1 0 1
5
Reserved 0 0 1 1 0
6 7
Communication mismatch 0 0 1 1 1
No Communication 0 1 0 0 0
8
No Encoder 0 1 0 0 1
9
Reserved 0 1 0 1 0
10
Outdoor unit fault 0 1 0 1 1
11
Reserved 0 1 1 0 0
12
Reserved. 0 1 1 0 1
13
Reserved 0 1 1 1 0
14
Reserved 0 1 1 1 1
15
Defrost protection 1 0 0 0 1
17
Deicing Protection 1 0 0 1 0
18
Outdoor Unit Protection 1 0 0 1 1
19
Indoor Coil HP Protection 1 0 1 0 0
20
Overflow Protection 1 0 1 0 1
21
Reserved 1 0 1 1 0
22
Reserved 1 0 1 1 1
23
EEPROM Not Updated 1 1 0 0 0
24
Bad EEPROM 1 1 0 0 1
25
Bad Communication 1 1 0 1 0
26
Using EEPROM data 1 1 0 1 1
27 29 No Fault (Heat Mode) 30 No Fault (Cool, Dry, Fan Mode) 31 No Fault (Stand By)
1 1 1 0 1 1 1 1 1 0 1 1 1 1 1
12-4
SM DUO38 1-E.1 GB
Page 49
1.3.4 Indoor unit diagnosis by MSMP and corrective actions
CONTENT
TROUBLESHOOTING
No.
1 Sensors failures of all
types
2 IPM Fault Electronics HW
3 Bad EEPROM No action, unless special
4 DC under/over Voltage Electronics HW
5 AC under Voltage Check outdoor unit power
6 Indoor / Outdoor unit
Communication mismatch
7 No Communication Communication or
8 Compressor Lock Switch unit to STBY and
9 Bad Communication Communication quality is
Fault
Probable Cause Corrective Action
Check sensors connections
problem
problem
Indoor and Outdoor controllers are with different versions
grounding wiring is not good.
low reliability
1.4 Judgment by MegaTool
MegaTool is a special tool to monitor the system states.
Using MegaTool requires:
A computer with RS232C port. A connection wire for MegaTool. A special MegaTool software.
Use MegaTool according to following procedure:
Setup MegaTool software: copy the software to the computer. Connect RS232C port in computer with MegaTool port in Indoor/Outdoor unit controller by
the connection wire.
Run the software and choose the COM port, you can monitor the A/C system state in monitor
tab.
or replace sensors. Check all wiring and jumper settings, if OK, replace electronics.
parameters are required for unit operation. Check outdoor unit power supply voltage
supply voltage Replace Indoor controller
Check Indoor to Outdoor wiring and grounding
restart Check Indoor to Outdoor wiring and grounding
1.5 Simple procedures for checking the Main Parts
1.5.1 Checking Mains Voltage.
Confirm that the Mains voltage is between 198 and 264 VAC. If Mains voltage is out of this range, abnormal operation of the system is expected. If in range check the Power (Circuit) Breaker and look for broken or loosed cable lugs or wiring mistake(s).
1.5.2 Checking Power Input.
If Indoor unit power LED is unlighted, power down the system and check the fuse of the Indoor unit. If the fuse is OK replace the Indoor unit controller. If the fuse has blown, replace the fuse and power up again. Checking Power Input procedure for the Outdoor unit is the same as with the Indoor unit.
SM DUO38 1-E.1 GB
12-5
Page 50
TROUBLESHOOTING
CONTENT
1.5.3 Checking the PCB.
Appearance inspect: Check discoloration, nick and connection of copper foil, short-circuit and open circuit, component soldering, bulgy and distortion of electrolytic capacitor.
Power circuit check: check voltage of every power level (5V, 12V, 15V) printed on back of PCB.
1.5.4 Checking the Outdoor Fan Motor.
Enter Test Mode (where the OFAN speed is high) Check the voltage between lead wires according to the normal value as following:
Between red wire and black wire: 310VDC +/- 20V  Between orange wire and black wire: 15VDC +/- 1V  Between yellow wire and black wire: 2-6VDC
1.5.5 Checking the Compressor.
The compressor is brushless permanence magnetic DC motor. Three coil resistances are THE same. Check the resistance between three poles.
1.5.6 Checking the Reverse Valve (RV).
Running in heating mode, check the voltage between two pins of reverse valve connector,
normal voltage is 220VAC.
1.5.7 Checking the electrical expansion valve (EEV).
The EEV has two parts, drive part and valve. The drive part is a step motor; it is ringed on the valve. Check the drive voltage (12VDC). When Outdoor unit is power on, EEV shall run and have click and vibration.
1.6 Precaution, Advise and Notice Items
1.6.1 High voltage in Outdoor unit controller.
Whole controller, including the wires, connected to the Outdoor unit controller may have the potential hazard voltage when power is on. Touching the Outdoor unit controller may cause an electrical shock. Advise: Don’t touch the naked lead wire and don’t insert finger, conductor or anything else into the controller when power is on.
1.6.2 Charged Capacitors
Three large-capacity electrolytic capacitors are used in the Outdoor unit controller. Therefore, charging voltage (380VDC) remains after power down. Discharging takes about three minutes after turned off. Touching the Outdoor unit controller before discharging may cause an electrical shock. When open the Outdoor unit controller cover, don’t touch the soldering pin by hand or by any conductive material.
Advise: 1. Open the Outdoor unit controller cover only after five minutes from power down.
2. Measure the electrolytic capacitors voltage before farther checking controller for safety.
1.6.3 Additional advises
12-6
When disassemble the controller or the front panel, turn off the power supply.
When connecting or disconnecting the connectors on the PCB, hold the whole housing, don’t pull the wire.
There are sharp fringes and sting on shell. Use gloves when disassemble the A/C units.
SM DUO38 1-E.1 GB
Page 51

EXPLODED VIEWS AND SPARE PARTS LISTS

CONTENT
13. EXPLODED VIEWS AND SPARE PARTS LISTS
13.1 Outdoor Unit: DUO 38 DCI / DELTA
SM DUO38 1-E.1 GB
13-1
Page 52
EXPLODED VIEWS AND SPARE PARTS LISTS
CONTENT
13.2 Outdoor Unit: DUO 38 DCI / DELTA
No. Part No. Description
1 433218
2 4526340
3 4526476
4 4526475
5 433215
6 464600021
7 4526403 Partition
8 4526774
4526775 Compressor top thermistor(CTT)
9
10 4526776
11 452630201 3/8" Gas Valve(R410A)
452630200 3/8" Gas Valve(R410A)
12 4526301 1/4" Liqiud Valve(R410A)
13 4526403
4527130 terminal block
14
204107 Cable clip Nylon
15
16 4526225 Power lead wire
4526968 Grounding wire with magnetic ring
4526223 AC-IN wire
4526222 Fuse connected wire
4526226 Power lead wire 4526827 Electronical expansion valve
17 18
452682802 EEV coil CAM-MD12FKS-2White connector, 530mm) 452682800 EEV coil CAM-MD12FKS-1 (Red, 530mm)
19 4526344
20 4510677
21 4526221
22 4526204
433230 Valve Cover
23
24 4526429
25 461600010
4522509 4-Way valve coil
26
4518951 4-W valve SHF-4H for R410A
27
433228 Back Side Net
28
29 462000000
30 4519614
4519300 Nut M5 L
31
32 433225
33 4519607
34 4526298
35 433223
36 4526219
37 452823600
38 4526430
39 4526396 Choke assy. 167-021-01
40 4526224 EMI filter board 901-098-00
41 4526774
4526776
4526970
452911100 4526227 MSMP communcation board 906-002-00
43
452823600 Terminal Plate Assy.
44
Front Panel A
Air inlet ring-420
Axial fan OD=401
Resin Motor
Motor Support
Base Painting Assy.
Outdoor air thermistor(OAT)
Outdoor coil thermistor(OCT)
OUTDOOR DC INVERTER CONTROLLER
Comp. Insulation1
Nut With Flange M8
Compressor wire
Compressor Assy
Right side panel (painting plate)
4way valve soldering assy
condensor Soldering assy
Painting Top Cover
Handle
Left Side Panel Painting Plate
Bridge
Painting Insulation Plate
Fuse 6C(15A,230V)EHK:150-007-00
Therminal sheet
Valve Support(painting plate)
Outdoor air thermistor(OAT)
Outdoor coil thermistor(OCT)
Suction tube Thermistor(SUT2)
Sensor/ Suction3
13-2
SM DUO38 1-E.1 GB
Page 53

APPENDIX A

CONTENT
APPENDIX A
INSTALLATION AND OPERATION MANUAL
INSTALLATION MANUAL DUO 38 DCI / DELTA
SM DUO38 1-E.1 GB
14-1
Loading...