● Bended indoor coil with treated aluminum fins and coating for improved
efficiency.
● High COP.
● Pre-Charged units up to the max allowing tubing distance.
● Heating operation at outdoor temperature down to -15ºC
● Advanced test and diagnostics mode.
● M2L diagnostics softwear cable port (for PC)
● Easy access to the interconnecting tubing and wiring connections, so that
during installation removing the front grill or casing is not necessary.
SM DELTA 1-E.2 GB
● Refrigerant pipes can be connected to the indoor unit from 5 different optional
directions.
● Automatic treated air sweep.
● Easy installation and service.
1-1
Page 5
INTRODUCTION
CONTENT
1.3 Indoor Unit
The indoor unit is wall mounted, and can be easily fitted to many types of residential
and commercials applications.
It includes:
● Casing with air inlet and outlet grills.
● A large-diameter tangential fan.
● Bended coil with treated aluminum fins.
● Motorized flaps.
● Variable Speed motor (PG).
● Advanced electronic control box assembly.
● Interconnecting wiring terminal block.
● Mounting plate
.
1.4 Filtration
The Delta series presents several types of air filters:
● Easily accessible, and re-usable pre-filters (mesh)
● Pre-charged electrostatic filter (optional)
● Active carbon filter (optional)
1.5 Control
The microprocessor indoor controller, and an infrared remote control, supplied as
standard, provide complete operating function and programming. For further details
please refer to the Operation Manual, Appendix A.
1.6 Outdoor Unit
The Delta outdoor units can be installed as floor or wall mounted units by using a
wall supporting bracket. The metal sheets are protected by anti- corrosion paint work
allowing long life resistance. All outdoor units are pre-charged. For further information
please refer to the Product Data Sheet, Chapter 2.
1-2
It includes :
● Single DC Rotary Compressor mounted in a soundproofed compartment
● Axial fan.
● Outdoor coil with hydrophilic louver fins.
● Outlet air fan grill.
● Outdoor advanced controller.
● 2 fan speed AC motor
SM DELTA 1-E.2 GB
Page 6
1.7 Tubing Connections
CONTENT
Flare type interconnecting tubing to be produced on site.
For further details please refer to the Installation Manual, Appendix A.
1.8 Inbox Documentation
Each unit is supplied with its own installation and operation manuals.
1.9 Matching Table
OUTDOOR UNITS
INTRODUCTION
INDOOR UNITS
MODELREFR”Delta 22Delta 25Delta 35Delta 50
DCR 22
DCR 25
DCR 35
DCR 50R410A
R410A
√√√
―――
―
√
SM DELTA 1-E.2 GB
1-3
Page 7
PRODUCT DATA SHEET
CONTENT
2. PRODUCT DATA SHEET
2.1 Delta 22 / DCR 22 DCI R410A
Model Indoor UnitDELTA 22 DCI
Model Outdoor UnitDCR 22 R410A
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511.
(2) Airflow in ducted units; at nominal external static pressure.
(3) Sound power in ducted units is measured at air discharge.
(4) Sound pressure level measured at 1 meter distance from unit.
SM DELTA 1-E.2 GB
2-1
Page 8
PRODUCT DATA SHEET
CONTENT
2.2 Delta 25 / DCR 25 DCI R410A
Model Indoor UnitDE LTA 25
Model Outdoor UnitDCR 25
Installation Method of PipeFlared
CharacteristicsUnitsCoolingHeating
Capacity
Power input
EER (Cooling) or COP(Heating)
Energy efficiency classAB
Power supplyV/Ph/Hz220-240V/Single/50Hz
Rated currentA3.2 3.6
Starting currentA10
Circuit breaker ratingA12
Operation control type Remote control
Heating elementskW
Others
(1)
(1)
(1)
Fan type & quantityCrossflow x 1
Fan speedsH/M/LRPM1200/1050/850
DimensionsWxHxDmm680x250x185
Weightkg7
Package dimensionsWxHxDmm740x265x320
Packaged weightkg10
Units per palletunits36 units per pallet
Stacking heightunits9 levels
Refrigerant controlEEV
Compressor type, modelRotary, Panasonic 5RS092XDJ01
Fan type & quantityPropeller(direct) x 1
Fan speedsH/LRPM760
Air flow H/Lm3/hr1390
Sound power levelH/LdB(A)64
Sound pressure level
DimensionsWxHxDmm760x245x545
Weightkg36
Package dimensionsWxHxDmm880x310x610
Packaged weightkg39
Units per palletUnits12 units per pallet
OUTDOOR
Stacking heightunits3 levels
Refrigerant typeR410A
Refrigerant chargless distancekg/m0.85kg/7.5m
Additional charge per 1 meterg/mNo need
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511.
(2) Airflow in ducted units; at nominal external static pressure.
(3) Sound power in ducted units is measured at air discharge.
(4) Sound pressure level measured at 1 meter distance from unit.
2-2
SM DELTA 1-E.2 GB
Page 9
PRODUCT DATA SHEET
CONTENT
2.3 Delta 35 / DCR 35 DCI R410A
Model Indoor UnitDE LTA 35
Model Outdoor UnitDCR 35
Installation Method of PipeFlared
CharacteristicsUnitsCoolingHeating
Capacity
Power input
EER (Cooling) or COP(Heating)
Energy efficiency classAB
Power supplyV/Ph/Hz220-240V/Single/50Hz
Rated currentA4.9 4.8
Starting currentA10.5
Circuit breaker ratingA15
Operation control type Remote control
Heating elementskWNo
Others
(1)
(1)
(1)
Fan type & quantityCrossflow x 1
Fan speedsH/M/LRPM1200/1000/850
DimensionsWxHxDmm840x250x185
Weightkg8
Package dimensionsWxHxDmm930x265x320
Packaged weightkg11
Units per palletunits36 units per pallet
Stacking heightunits9 levels
Refrigerant controlEEV
Compressor type, modelRotary, Panasonic 5RS102XAB
Fan type & quantityPropeller(direct) x 1
Fan speedsH/LRPM760
Air flow H/Lm3/hr1390
Sound power levelH/LdB(A)65
Sound pressure level
DimensionsWxHxDmm760x245x545
Weightkg37
Package dimensionsWxHxDmm880x310x610
Packaged weightkg40
Units per palletUnits12 units per pallet
OUTDOOR
Stacking heightunits3 levels
Refrigerant typeR410A
Refrigerant chargless distancekg/m1.0kg/7.5m
Additional charge per 1 meterg/mNo need
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511.
(2) Airflow in ducted units; at nominal external static pressure.
(3) Sound power in ducted units is measured at air discharge.
(4) Sound pressure level measured at 1 meter distance from unit.
SM DELTA 1-E.2 GB
2-3
Page 10
PRODUCT DATA SHEET
CONTENT
2.4 Delta 50 / DCR 50 DCI R410A
Model Indoor Unit DELTA 50 DCI
Model Outdoor Unit DCR 50 R410A
Installation Method of Pipe Flared
Characteristics Units Cooling Heating
Capacity
Power input
EER (Cooling) or COP(Heating)
Energy efficiency class A B
Power supply V/Ph/Hz 220-240V/Single/50Hz
Rated current A 7.0 6.9
Starting current A 10.5
Circuit breaker rating A 20
Operation control type Remote control
Heating elements kW
Others
(1)
(1)
kW 1.56 1.55
Fan type & quantity Crossflow x 1
Fan speeds H/M/L RPM 1230/1100/900
(2)
Air flow
External static pressure Min-Max Pa
Sound power level
Sound pressure level
Moisture removal l/hr 2
Condensate drain tube I.D mm 16
INDOOR
Dimensions WxHxD mm 900x205x295
Weight kg
Package dimensions WxHxD mm 960x270x360
Packaged weight kg 14
Units per pallet units 24 units per pallet
Stacking height units 8 levels
Refrigerant control EEV
Compressor type, model Scroll, PANASONIC 5CS130XCC03
Fan type & quantity Propeller(direct) x 1
Fan speeds H/L RPM 920
Air flow H/L m3/hr 2160
Sound power level H/L dB(A) 63
Sound pressure level
Dimensions WxHxD mm 795x290x610
Weight kg 38
Package dimensions WxHxD mm 945x395x655
Packaged weight kg 41
OUTDOOR
Units per pallet Units 9 units per pallet
Stacking height units 3 levels
Refrigerant type R410A
Refrigerant chargless distance kg/m 1.26kg/7.5m
Additional charge per 1 meter g/m No need
H/M/L m3/hr 720/620/480
Connections between
units
(1)
W/W 3.21 3.42
(3)
H/M/L dB(A) 56/54/47
(4)
H/M/L dB(A) 44/41/34
(4)
H/L dB(A) 53
Liquid line In.(mm) 1/4"(6.35)
Suction line In.(mm) 1/2"(12.7)
Max.tubing length m. Max.15
Max.height difference m. Max. 10
Btu/hr 17060(4780-18770) 18080(5460-20130)
kW 5.0(1.4-5.5) 5.3(1.6-5.9)
0
11
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511.
(2) Airflow in ducted units; at nominal external static pressure.
(3) Sound power in ducted units is measured at air discharge.
(4) Sound pressure level measured at 1 meter distance from unit.
2-4
SM DELTA 1-E.2 GB
Page 11
3. RATING CONDITIONS
CONTENT
Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units).
Cooling:
Indoor: 27oC DB 19oC WB
Outdoor: 35 oC DB
Heating:
Indoor: 20oC DB
Outdoor: 7oC DB 6oC WB
3.1 Operating Limits
3.1.1 R410A
Cooling
Upper limit
Lower limit
32oC DB 23oC WB46oC DB
21oC DB 15oC WB 10oC DB
RATING CONDITIONS
IndoorOutdoor
Heating
Upper limit
Lower limit
Voltage
27oC DB 24oC DB 18oC WB
10oC DB-15oC DB -16oC WB
198 – 264 V
SM DELTA 1-E.2 GB
3-1
Page 12
4. OUTLINE DIMENSIONS
CONTENT
4.1Indoor Unit: Delta 22, 25 DCI
OUTLINE DIMENSIONS
4.2
Indoor Unit: Delta 35 DCI
SM DELTA 1-E.2 GB
4-1
Page 13
OUTLINE DIMENSIONS
CONTENT
4.3 Indoor Unit: Delta 50 DCI
4.4 Outdoor Unit: DCR 22, 25, 35 DCI
AIR INTAKE
4-2
AIR OUTLET
SM DELTA 1-E.2 GB
Page 14
4.5 Outdoor Unit: DCR 50 DCI
CONTENT
OUTLINE DIMENSIONS
SM DELTA 1-E.2 GB
4-3
Page 15
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5. PERFORMANCE DATA
5.1 Delta 22 DCI
5.1.1 Cooling Capacity (kW) – Run Mode
230[V] : Indoor Fan at High Speed.
OD COIL
ENTERING AIR DB
TEMPERATURE
[oC]
-10 - 20
(protection range)
25
30
35
40
46
ID COIL ENTERING AIR DB/WB TEMPERATURE [oC]
DATA
22/1524/1727/1929/2132/23
TC80 - 110 % of nominal
SC80 - 105 % of nominal
PI25 - 50 % of nominal
TC2.122.262.402.542.68
SC1.621.651.691.721.75
22/15 DB /WB
24/17 DB /WB
27/19 DB /WB
29/21 DB /WB
32/23 DB /WB
SM DELTA 1-E.2 GB
5-19
Page 34
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.6.8 Heating – Test Mode
Suction Pressure VS. Outdoor Temp.
1000
900
800
700
600
500
400
Suction Pressure [kPa]
300
-15-10-5051015
Outdoor WB Temperature [ºC]
15 DB
20 DB
25 DB
Discharge Pressure VS. Outdoor Temp.
4000
3750
3500
3250
3000
2750
2500
2250
2000
Discharge Pressure [kPa]
1750
1500
-15-10-5051015
Outdoor WB Temperature[ºC]
15 DB
20 DB
25 DB
5-20
SM DELTA 1-E.2 GB
Page 35
SOUND LEVEL CHARACTERISTICS
CONTENT
6. SOUND LEVEL CHARACTERISTICS
6.1Sound Pressure Level
Figure 1. Wall MountedFigure 2. Floor Mounted
Figure 3. DuctedFigure 4. Cassette
6.2 Soud Pressure Level Spectrum (Measured as Figure 1)
Delta 22Delta 25
-70NC
-60NC
MICRO AR0. 02 dB re , OCT VE BAN S UN PRES URE L VEL
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
-50NC
-40NC
-30NC
-20NC
VE BAN S UN PRES URE L VEL
MICRO AR0. 02 dB re , OCT
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
-70NC
-60NC
-50NC
-40NC
-30NC
-20NC
FAN SPEEDLINE
SM DELTA 1-E.2 GB
HI
ME
LO
Hz, AND CE TER FREQUENC ES
Hz, AND CE TER FREQUENC ES
6-1
Page 36
SOUND LEVEL CHARACTERISTICS
CONTENT
Delta 35 Delta 50
-70NC
URE L VEL
-70NC
MICRO AR0. 02 dB re , OCT VE BAN S UN PRES URE L VEL
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
Hz, AND CE TER FREQUENC ES
-60NC
-50NC
-40NC
-30NC
-20NC
02 dB re , OCT VE BAN S UN PRES
MICRO AR0.
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
-60NC
-50NC
-40NC
-30NC
-20NC
Hz, AND CE TER FREQUENC ES
FAN SPEEDLINE
6-2
HI
ME
LO
SM DELTA 1-E.2 GB
Page 37
SOUND LEVEL CHARACTERISTICS
CONTENT
6.3 Outdoor units
Microphone Distance from Unit
6.4 Sound Pressure Level Spectrum (Measured as Figure 5)
DCR 22 CoolingDCR 22 Heating
MICRO AR0. 02 dB re , OCT VE BAN S UN PRES URE L VEL
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
-70NC
-60NC
-50NC
-40NC
-30NC
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
Hz, AND CE TER FREQUENC ES
Hz, AND CE TER FREQUENC ES
-20NC
MICRO AR0. 02 dB re , OCT VE BAN S UN PRES URE L VEL
DCR 25 CoolingDCR 25 Heating
-70NC
-70NC
-60NC
-50NC
-40NC
-30NC
-20NC
-70NC
MICRO AR0. 02 dB re , OCT VE BAN S UN PRES URE L VEL
SM DELTA 1-E.2 GB
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
Hz, AND CE TER FREQUENC ES
-60NC
-50NC
-40NC
-30NC
-20NC
MICRO AR0. 02 dB re , OCT VE BAN SUN PRESURE L VEL
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
-60NC
-50NC
-40NC
-30NC
-20NC
Hz, AND CE TER FREQUENC ES
6-3
Page 38
SOUND LEVEL CHARACTERISTICS
CONTENT
DCR 35 CoolingDCR 50 Heating
MICRO AR0. 02 dB re , OCT VE BAN S UN PRES URE L VEL
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
-70NC
-60NC
-50NC
-40NC
-30NC
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
Hz, AND CE TER FREQUENC ES
Hz, AND CE TER FREQUENC ES
-20NC
MICRO AR0. 02 dB re , OCT VE BAN S UN PRES URE L VEL
DCR 50 CoolingDCR 50 Heating
-70NC
-70NC
-60NC
-50NC
-40NC
-30NC
-20NC
-70NC
APPROXIMATE
THRESHOLD OF
MICRO AR0. 02 dB re , OCT VE BAN S UN PRES URE L VEL
HEARING FOR
CONTINUOUS
NOISE
Hz, AND CE TER FREQUENC ES
FAN SPEEDLINE
HI
ME
LO
-60NC
-50NC
-40NC
-30NC
-20NC
MICRO AR0. 02 dB re , OCT VE BAN S UN PRES URE L VEL
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
-60NC
-50NC
-40NC
-30NC
-20NC
Hz, AND CE TER FREQUENC ES
6-4
SM DELTA 1-E.2 GB
Page 39
7. ELECTRICAL DATA
CONTENT
7.1 Single Phase Units
ELECTRICAL DATA
MODEL
Power Supply
Max Current, A5.26.3
Circuit Breaker,A1212
Power Supply Wiring No. X
Cross Section mm
Interconnecting Cable RC
Model No. X Cross Section mm
Power Supply
Max Current, A7.510.3
Circuit Breaker,A1520
Power Supply Wiring No. X
Cross Section mm
Interconnecting Cable RC
Model No. X Cross Section mm
2
2
MODEL
2
2
Delta 22Delta 25
To indoorTo indoor
1PH,220-240V,50Hz1PH,220-240V,50Hz
3x1.0 mm
4x1.0 mm
2
2
3x1.0 mm
4x1.0 mm
2
2
Delta 35Delta 50
To indoorTo indoor
1PH,220-240V,50Hz1PH,220-240V,50Hz
3x1.5 mm
4x1.5 mm
2
2
3x1.5 mm
5x1.5 mm
2
2
(a) The Inrush current is the current when power is up (charging the DC capacitors of
the outdoor unit controller).
(b) Starting current is the current when starting the compressor.
NOTE
Power wiring cord should comply with local lows and electrical regulations
requirements
2. Refrigerant Valve Port (use Allen wrench to open/close)
3. Valve Protection Cap
4. Refrigerant Valve
5. Service Port Cap
6. Flare Nut
7. Unit Back Side
8. Copper Tube
When the outdoor unit is installed above the indoor unit an oil trap is required every 5m along the suction
line at the lowest point of the riser. Incase the indoor unit is installed above the outdoor, no trap is
required.
SM DELTA 1-E.2 GB
10-1
Page 46
CONTROL SYSTEM
CONTENT
11. CONTROL SYSTEM
11.1 General Functions and Operating Rules
The DCI software is fully parametric.All the model dependent parameters are shown in Blue color
and with Italic style [parameter].
The parameters values are given in the last section of this control logic chapter of the service
manual.
11.1.1 System Operation Concept
The control function is divided between indoor and outdoor unit controllers. Indoor unit is the system
‘Master’, requesting the outdoor unit for cooling/heating capacity supply. The outdoor unit is the
system ‘Slave’ and it must supply the required capacity unless it enters into a protection mode
avoiding it from supplying the requested capacity.
The capacity request is transferred via indoor to outdoor communication, and is represented by a
parameter called ‘NLOAD’. NLOAD is an integer number with values between 0 and 127, and it
represents the heat or cool load felt by the indoor unit.
11.1.2 Compressor Frequency Control (NLOAD setting)
The NLOAD setting is done by the indoor unit controller, based on a PI control scheme.
The actual NLOAD to be sent to the outdoor unit controller, is based on the preliminary LOAD
calculation, the indoor fan speed, and the power shedding function.
NLOAD limits as a function of indoor fan speed:
Indoor Fan SpeedMaximum NLOAD CoolingMaximum NLOAD Heating
The compressor target frequency is a function of the NLOAD number sent from the indoor
controller and the outdoor air temperature.
Basic Target Frequency Setting:
NLOADTarget Frequency
127Maximum frequency
10 < NLOAD < 127Interpolated value between minimum and maximum frequency
10Minimum frequency
0Compressor is stopped
SM DELTA 1-E.2 GB
11-1
Page 47
CONTROL SYSTEM
CONTENT
Target frequency limits as a function of outdoor air temperature (OAT):
OAT RangeCool mode limitsHeat mode limits
OAT < 6
6 ≤ OAT < 15MaxFreqAsOAT1H
15 ≤ OAT < 28
28 ≤ OATNo limit
MaxFreqAsOATC
No limit
MaxFreqAsOAT2H
11.1.4 Frequency Changes Control
Frequency change rate is 1 Hz/sec.
11.1.5 Compressor Starting Control
Frequency
Step 3
Step 2
Step 1
1
Minute
1
Minute
Time
Min 10 Minutes
11.1.6 Minimum On and Off Time
3 minutes.
11.1.7 Indoor Fan Control
10 Indoor fan speeds are determined for each model. 5 speeds for cool/dry/fan modes and 5
speeds for heat mode.
When user sets the indoor fan speed to a fixed speed (Low/ Medium/ High), unit will operate
constantly at set speed.
When Auto Fan is selected, indoor unit controller can operate in all speeds. The actual speed is set
according to the cool/heat load.
11.1.8 Turbo Speed
The Turbo speed is activated during the first 30 minutes of unit operation when auto fan speed is
selected and under the following conditions:
• Difference between set point and actual room temperature is bigger then 3 degrees.
• Room temperature > 22 for cooling, or < 25 for heating.
11-2
SM DELTA 1-E.2 GB
Page 48
CONTROL SYSTEM
OFAN Stat
CONTENT
11.1.9 Heating Element Control
Heating element can be started if LOAD > 0.8 * MaximumNLOAD AND Indoor Coil
temperature < 45.
The heating element will be stopped when LOAD < 0.5 * MaximumNLOAD OR if Indoor Coil
temperature > 50.
11.1.10 Outdoor Fan Control
• The OFAN motor is an AC type that operates with 2 speeds (Low/High),
controlled by Relays.
• OFAN speed depends on the compressor Target Frequency, and it’s set according to the
following table and graphs.
• OFAN can change its Speed only if it has been working in the current
speed for
at least 35 seconds:
Compressor
Target Frequency
Freq=0
10 ≤ Freq < OFLowFreqLowLowLowLow
OFLowFreq ≤ Freq< OFMedFreqHighLowLowLow
OFMedFreq≤ FreqHighLowLowHigh
Notes:
Normal cases
State A at cool / Heat
OFFOFFOFFOFF
When OAT is faulty or disabled OFAN will follow ‘Normal cases’ rules (left column).
e
at Cool Mode
A
B
C
3 Degrees
3 Degrees
7
20
OAT
OFAN Speed
State B
at cool
State C
at cool
OAT>15 oC
at heat
Not e : Pe r i o r i t i e s A>B>C
1. OFLowFreq =
2. OFMedFreq =
OFLowFreqC in cool mode, and OFLowFreqH in heat mode.
OFMedFreqC in cool mode, and OFMedFreqH in heat mode.
The OFAN will be off when the compressor is off.
• An exception for the following rule is when compressor was operating in cool
mode before stopped. In this case OFAN will remain on in low speed for 1
minute.
• Whenever the indoor unit is under indoor coil overheating protection, as long as the
protection status is HzD2, the outdoor fan will change to off. It will be enabled to be back on
when the status of this protection becomes normal.
• Upon receiving night mode signal (ON), through communication, the OFAN will be
operating in LOW speed only in Cool. It will be back to its normal operation when receiving
OFF signal.
SM DELTA 1-E.2 GB
11-3
Page 49
CONTROL SYSTEM
CONTENT
11.1.1 EEV (electronic Expansion valve) Control
EEV opening is defined as EEV = EEVOL + EEV
EEVOL is the initial EEV opening as a function of the compressor frequency, operation mode, unit
model and capacity.
EEVCV is a correction value for the EEV opening that is based on the compressor temperature.
During the first 5 minutes of compressor operation EEVCV = 0.
Once the first 5 minutes are over, the correction value is calculated as follow: EEVCV(n) = EEVCV(n-
1) + EEV
EEV
set depending on frequency and outdoor air temperature, and the actual compressor temperature
is compared to the target temperature to set the required correction to the EEV opening.
CTT
is the correction based on the compressor temperature. A target compressor temperature is
CTT
CV
11.1.2 Reversing Valve (RV) Control
Reversing valve is on in heat mode.
Switching of RV state is done only after compressor is off for over 3 minutes.
11.2 Fan Mode
In high/ medium/ low indoor fan user setting, unit will operate fan in selected speed.
In AutoFan user setting, fan speed will be adjusted automatically according to the difference
between actual room temperature and user set point temperature.
11.3 Cool Mode
NLOAD is calculated according to the difference between actual room temperature and user set
point temperature by PI control.
In high/ medium/ low indoor fan user setting, unit will operate fan in selected speed.
In AutoFan user setting, fan speed will be adjusted automatically according to the calculated
NLOAD.
11.4 Heat Mode
NLOAD is calculated according to the difference between actual room temperature and user set
point temperature by PI control.
In high/ medium/ low indoor fan user setting, unit will operate fan in selected speed.
In AutoFan user setting, fan speed will be adjusted automatically according to the calculated
NLOAD.
11.4.1 Temperature Compensation
4 degrees are reduced from RT sensor temperature reading (excluding I-Feel mode), to
compensate for temperature difference between high and low areas in the heated room, and due
to coil heat radiation on RT sensor.
11-4
SM DELTA 1-E.2 GB
Page 50
11.4.2 Indoor Fan Control in Heat Mode
CONTENT
Indoor fan speed depends on the indoor coil temperature:
CONTROL SYSTEM
ICTST
ICTVL ICTT ICTHICTL
11.5 Auto Cool/Heat Mode
When in auto cool heat mode unit will automatically select between cool and heat mode according
to the difference between actual room temperature and user set point temperature (ΔT).
Unit will switch from cool to heat when compressor is off for 3 minutes, and ΔT < -3.
Unit will switch from heat to cool when compressor is off for 5 minutes, and ΔT < -3.
11.6 Dry Mode
As long as room temperature is higher then the set point, indoor fan will work in low speed and
compressor will work between 0 and MaxNLOADIF1C Hz.
When the room temperature is lower than the set point, compressor will be switched OFF and
indoor fan will cycle 3 minutes OFF, 1 minute ON.
11.7 Protections
There are 5 protection codes.
Normal (Norm) – unit operate normally.
Stop Rise (SR) – compressor frequency can not be raised but does not have to be decreased.
HzDown1 (D1) – Compressor frequency is reduced by 2 to 5 Hz per minute.
HzDown2 (D2) – Compressor frequency is reduced by 5 to 10 Hz per minute.
Stop Compressor (SC) – Compressor is stopped.
Compressor temperature can be in one of 5 control zones (4 in protection, and 1 normal),
according to the following chart.
CTT
Stop-Compresor
CTTOH4
CTTOH3
CTTOH2
CTTOH1
Control Status
P1NormSR
P2D1SR
P3D2D1
Compressor
Temperature Increases
P3
P2
P1
Normal
Else
Stop CompressorSC
11-6
SM DELTA 1-E.2 GB
Page 52
11.7.4 Compressor over Current Protection
CONTENT
CCR
Stop-Compresor
CCROC4
CONTROL SYSTEM
CCROC3
HzDown1
CCROC2
CCROC1
Normal
HzDown2
Stop-Rise
11.7.5 Heat Sink Over Heating Protection (NA for DCI 25 and 35)
HST
HST > 90
85 < HST ≤ 90D1D2D2
82 < HST ≤ 85SRD1D2
80 < HST ≤ 82SRSRD1
78 < HST ≤ 80NormNormSR
HST ≤ 78Normal
DecreasingNo ChangeIncreasing
SCSCSC
HST Trend
11.7.6 Outdoor Coil Deicing Protection
Deicing Starting Conditions
Deicing operation will start when either one of the following conditions exist:
• Case 1: OCT < OAT – 8 AND TLD > DI
• Case 2: OCT < OAT – 12 AND TLD > 30 minutes.
• Case 3: OCT is Invalid AND TLD > DI
• Case 4: Unit is just switched to STBY AND OCT < OAT – 8
• Case 5: NLOAD = 0 AND OCT < OAT -8
OCT – Outdoor Coil Temperature
OAT – Outdoor Air Temperature
TLD – Time from Last Deicing
DI – Deicing Interval (Time Interval Between Two Deicing)
Deicing interval time when compressor is first started in heat mode, is 10 minutes if OCT < -2, and
is 40 minutes in other cases.
Deicing interval time is changed (increased/ decreased in 10 minutes steps) as a function of
deicing time. If deicing time is shorter then former deicing time, the deicing interval time will be
increased. If deicing time is longer then former deicing time, the deicing interval time will be
decreased.
SM DELTA 1-E.2 GB
11-7
Page 53
CONTROL SYSTEM
CONTENT
Deicing Protection Procedure
OCT
12
0
Threshold
COMP
RV
OFAN
EEV
ON
HEAT
COOL
ON
OFF
EEVDeicerOpen
Any
T1T2
max. 12 minutes
DT
T3T3
T1 =60 seconds, T2 = 36 seconds, T3 = 6 seconds
T1
11-8
SM DELTA 1-E.2 GB
Page 54
CONTROL SYSTEM
CONTENT
11.8 Operating the Unit from the Mode Button
Forced operation allows to start, stop and operate in Cooling or Heating, in pre-set temperature
according to the following table:
Forced operation ModePre-set Temperature
Cooling200C
Heating280C
11.9 On Unit Controls and Indicators
The following is schematic drawing for the display:
STBY/OPER
Mode/Reset Button
Timer
Filter
Infra Red Receiver
SM DELTA 1-E.2 GB
11-9
Page 55
CONTROL SYSTEM
CONTENT
1. Lights up when the Air Conditioner is connected to power and the
STAND BY
INDICATOR
OPERATION INDICATOR
TIMER INDICATORLights up during Timer and Sleep operation.
FILTER INDICATORLights up when Air Filter needs to be cleaned.
mode is STBY.
2. Blinks for 3 seconds, when the system is switched to Heat Mode
by using the Mode/Reset Switch on the unit (the operation
indicator will be off during this blinking time).
1. Lights up during operation mode (except for item in STBY
indicator).
2. Blinks for 300 msec., to announce that a R/C infrared signal
has been received and stored.
3. Blinks continuously during protections (according to the relevant
spec section).
4. Blinks for 3 seconds when the system is switched to Cool Mode
by using the Mode/Reset Switch on the unit.
As long as the filter Led is off, the Mode/Reset button functions as Mode
switch. Once filter Led is on, the Mode/Reset button functions as Reset
switch.
Mode Function:
Every short pressing , the next operation mode is selected, in this order:
MODE / RESET BUTTON
SB → Cool Mode → Heat Mode → SB → …
In long pressing system enters diagnostic mode (refer to diagnostic mode
Sect.)
Reset Function:
For short pressing:
When Filter LED is on, it turns off the filter indicator.
Notes
1. Pressing time is defined as the time between press and release.
2. If pressing time is one second or less – press is considered as short pressing.
3. If pressing time is three seconds or longer – pressing is considered as long pressing. In
between, pressing is undetermined and system will not respond to pressing.
4. For the LED functionality during diagnostics, refer to the diagnostics Sect.
11-10
SM DELTA 1-E.2 GB
Page 56
CONTROL SYSTEM
CONTENT
11.10 Outdoor Unit Controller Indicators
Unit has three LED’s. SB LED, STATUS LED, FAULT LED.
SB LED is ON when power is ON (230 VAC),
STATUS LED is ON when COMP is ON, and Blinks according to diagnostics mode definitions
when either fault or protection occurs.
FAULT LED Blinks according to diagnostics mode definitions when either fault or protection occurs.
11.11 Test Mode
11.11.1 Entering Test Mode
System can enter Test mode in two ways:
• Automatically when the following conditions exists for 30 minutes continuously:
o Mode = Cool, Set point = 16, Room temperature = 27±1, Outdoor temperature =
35±1
Or
o Mode = Heat, Set point = 30, Room temperature = 20±1, Outdoor temperature =
7±1
• Manually when entering diagnostics with the following settings:
•
o Mode = Cool, Set point = 16
o Mode = Heat, Set point = 30
11.11.2 Unit Operation in Test Mode
In test mode, the unit will operate in fixed settings according to the indoor fan speed setting:
Indoor Fan Speed SettingUnit Setting
LowMinimum Capacity Setting
HighNominal Capacity Setting
AutoMaximum Capacity Setting
During test mode, protections are disabled, except for stop compressor status.
SM DELTA 1-E.2 GB
11-11
Page 57
CONTROL SYSTEM
CONTENT
11.12 SW Parameters
11.12.1 Indoor Units SW Parameters
General Parameters for All Models:
Parameters defining the indoor fan speed as a function of Indoor Coil temperature in heat mode
(ICT):
ICTST Speed ICT to stop indoor fan 25
ICTVLSpeed ICT to go down to very low speed 28
ICTLSpeed ICT to start in very low speed 30
ICTHSpeed ICT to start in increase speed from very low 32
ICTTSpeed ICT to enable Turbo fan speed 40
Parameters for defrost protection:
ICTDef1 ICT to go back to normal 8
ICTDef2 ICT to ‘stop rise’ when ICT decrease 6
ICTDef3 ICT to ‘stop rise’ when ICT is stable 4
ICTDef4 ICT to ‘Hz Down’ when ICT decrease 2
ICTDef5 ICT to ‘Hz Down’ when ICT is stable 0
ICTDef6 ICT to stop compressor -2
Parameters for indoor coil over heating protection:
ICTOH1 ICT to go back to normal 45
ICTOH2 ICT to ‘stop rise’ when ICT increase 48
ICTOH3 ICT to ‘stop rise’ when ICT is stable 52
ICTOH4 ICT to ‘Hz Down’ when ICT increase 55
ICTOH5 ICT to ‘Hz Down’ when ICT is stable 60
ICTOH6 ICT to stop compressor 62
Model Depended Parameters:
Parameter name
NLOAD limits as a function of selected indoor fan speed
When Power Up – the whole outdoor unit controller, including the wiring, is
under HIGH VOLTAGE!!!
Never open the Outdoor unit before turning off the Power!!!
When turned off, the system is still charged (400V)!!!
It takes about 4 Min. to discharge the system.
Touching the controller before discharging may cause an electrical shock!!!
12.1
Single Split system failures and corrective
actions
NoSYMPTOMPROBABLE CAUSE CORRECTIVE ACTION
Power supply indicator
(Red LED) does not light
1
up.
Unit does not respond to
remote control message Remote control message
2
Unit responds to remote
control message but
3
Operate indicator (Green
LED) does not light up
Indoor fan does not start
(louvers are opened and
Green LED does light up)
4
Indoor fan works when
unit is OFF, and indoor
fan speed is not changed
5
by remote control
command.
Compressor does not
6
start
Compressor stops during
operation and Green
7
LED remains on
Compressor is on but
outdoor fan does not
8
work
No power supply
not reached the indoor
unit
Problem with display
PCB
Unit in heat mode and
coil is still not warm.
Problem with PCB or
capacitor
PCB problem
Electronics control
problem or protection
Electronic control or
power supply problem
Problem with outdoor
electronics or outdoor fan
Check power supply. If power supply
is OK, check display and display
wiring. if OK, replace controller.
Check remote control batteries, if
batteries are OK, check display and
display wiring, if OK, replace display
PCB.
If still not OK replace controller.
Replace display PCB.
If still not OK replace controller.
Change to cool mode and check.
Change to high speed and Check
power supply to motor is higher than
130VAC (for triack controlled motor)
or higher than 220VAC for fixed
speed motors, if OK replace
capacitor, if not replace controller
Replace controller
Perform diagnostics , and follow the
actions described.
Perform diagnostics ,and follow the
actions described.
Check outdoor fan motor according
to the procedure in section, if not OK
replace controller
SM DELTA 1-E.2 GB
12-1
Page 61
TROUBLESHOOTING
CONTENT
No
Unit works in wrong
mode (cool instead of
9
heat or heat instead of
cool)
All components are
operating properly but no
10
cooling or no heating
Compressor is over
heated and unit does not
11
generate capacity
Units goes into
protections and
12
compressor is stopped
with no clear reason
Compressor motor is
generating noise and no
13
suction occurs
Water leakage from
14
indoor unit
Freezing of outdoor unit
in heat mode and
15
outdoor unit base is
blocked with ice
Unit operates with wrong
fan speeds or wrong
16
frequency
SYMPTOMPROBABLE CAUSE CORRECTIVE ACTION
Check RV power connections, if OK,
Electronics or power
connection to RV
Refrigerant leak Check refrigeration system.
EEV problem Check EEV
Control problem or
refrigeration system
problem
Phase order to
compressor is wrong
Indoor unit drainage tube
is blocked
Connect base heater.
Wrong jumper settings
Check RV operation with direct
230VAC power supply, if OK,
Replace outdoor controller.
Perform diagnostics and follow the
actions described.
Check compressor phase order.
Check and open drainage tube.
Perform diagnostics, and check if
units is operating by EEPROM
parameters.
12.2 Checking the refrigeration system
Checking system pressures and other thermodynamic measures should be
done when system is in Test Mode (in Test mode, system operates in fixed
settings). The performance curves given in this manual are given for unit
performance in test mode when high indoor fan speed is selected.
Entering test mode:
Set unit to Cool/16 degrees/High indoor fan speed, or Heat/30 degrees/High
indoor fan speed, and enter diagnostics.
12-2
SM DELTA 1-E.2 GB
Page 62
12.3 Judgment by Indoor/Outdoor Unit Diagnostics
CONTENT
Enter diagnostics mode - press for five seconds Mode/Reset button in any
operation mode. Acknowledgment is by 3 short beeps and lights of all Display
LED’s. Then, The units will enter into Indoor and Outdoor unit diagnostic
modes.
During the Outdoor unit diagnostics all three Indoor LED’s (STBY/Operate,
Filter and Timer) are blinking. When Indoor diagnostics is displayed, all three
LED’s (STBY/Operate, Filter and Timer) are ON.
When system enters diagnostics mode, only one fault code is shown. Order
of priority is from the lower to the higher number. Diagnostics is continuously
ON as long as power is ON. The current system operation mode will not be
changed.
If no fault occurred in the system, no fault code will be displayed during
normal operation mode. The last fault code will be displayed even if the
system has recovered from that fault. The last fault will be deleted from
the EEPROM after the system has exit diagnostics mode.
In diagnostics mode, system fault / status will be indicated by blinking of Filter
& Timer LEDs.
The coding method will be as follows:
Filter LED will blink 5 times in 5 seconds, and then will be shut off for the next 5
seconds. Timer LED will blink during the same 5 seconds according to the following
Indoor / Outdoor unit tables:
Note: 0 – OFF, 1-ON
TROUBLESHOOTING
12.3.1 Indoor unit Diagnostics
NoProblem 54321
1
RT-1 is disconnected
2
RT-1 is shorted
3
RT-2 is disconnected
4
RT-2 is shorted
5
Reserved
7
Communication mismatch
8
No Communication
9
No Encoder
10
Reserved 0 1 0 1 0
11
Outdoor Unit Fault 0 1 0 1 1
…
Reserved
17
Defrost protection
18
Deicing Protection
19
Outdoor Unit Protection
20
Indoor Coil HP Protection
21
Reserved
22
Reserved
24
EEPROM Not Updated
25
Bad EEPROM
26
Bad Communication
27
Using EEPROM data
28
Model A
29
Model B
30
Model C
31
Model D
SM DELTA 1-E.2 GB
12-3
Page 63
TROUBLESHOOTING
y
CONTENT
12.3.2 Indoor unit diagnosis and corrective actions
No.FaultProbable Cause Corrective Action
Sensor failures of all
1
types
Communication
2
mismatch
No Communication
3
No Encoder
4
Outdoor Unit Fault
5
EEPROM Not
6
Updated
Bad EEPROM
7
Bad Communication
8
Using EEPROM
9
data
Indoor and Outdoor controllers are
with different versions
Communication or grounding wiring is
not good.
Indoor electronics or motor Check motor wiring, if ok,
Outdoor controller problem Switch to Outdoor diagnostics.
System is using ROM parameters and
not EEPROM parameters
No action, unless special
Communication quality is low reliabilit
No problem. System is using
EEPRRRROM parameters
Check sensor connections or
replace sensor
Replace Indoor controller
Check Indoor to Outdoor wiring
and grounding
replace motor, if still not ok,
replace Indoor controller.
No action, unless special
parameters are required for
unit operation.
parameters are required for
unit operation.
Check Indoor to Outdoor wiring
and grounding
12.3.3 Outdoor unit Diagnostics :
DCR 22/25/35 Diagnostics
NoProblem54321
OCT is disconnected
1
OCT is shorted
2
CTT is disconnected
3
CTT is shorted
4
reserved
5
reserved
6
OAT is disconnected (when enabled)
7
OAT is shorted (when enabled)
8
reserved
9
reserved
10
IPM Fault
11
reserved
12
DC under voltage
13
DC over voltage
14
AC under voltage
15
Indoor / Outdoor unit Communication mismatch
16
No Communication
17
Reserved
18
Reserved
19
Reserved
20
Deicing
21
Compressor Over Heating
22
Compressor Over Current
23
Reserved
24
Reserved
25
Copressor Lock
26
Bad Communication
27
Heat sink Over Heating
20
Deicing
21
Compressor Over Heating
22
Copressor Lock
26
Bad Communication
27
0 0 0 0 1
0 0 0 1 0
0 0 0 1 1
0 0 1 0 0
0 0 1 1 1
0 1 0 0 0
0 1 0 1 1
0 1 1 0 1
0 1 1 1 0
0 1 1 1 1
1 0 0 0 0
1 0 0 0 1
1 0 1 0 1
1 0 1 1 0
1 0 1 1 1
1 1 0 1 0
1 1 0 1 1
1 0 1 0 0
1 0 1 0 1
1 0 1 1 0
1 1 0 1 0
1 1 0 1 1
12-4
SM DELTA 1-E.2 GB
Page 64
TROUBLESHOOTING
CONTENT
DCR50 diagnostics:
NoProblem54321
OCT is disconnected
1
OCT is shorted
2
CTT is disconnected
3
CTT is shorted
4
HST is disconnected (when enabled)
5
HST is shorted (when enabled)
6
OAT is disconnected (when enabled)
7
OAT is shorted (when enabled)
8
TSUC is disconnected (when enabled)
9
TSUC is shorted (when enabled)
10
IPM Fault
11
Bad EEPROM
12
DC under voltage
13
DC over voltage
14
AC under voltage
15
Indoor / Outdoor unit Communication mismatch
16
No Communication
17
Reserved
18
Heat sink Over Heating
20
Deicing
21
Compressor Over Heating
22
Compressor Over Current
23
No OFAN Feedback
24
OFAN Locked
25
Compressor Lock
26
Bad Communication
27
0 0 0 0 1
0 0 0 1 0
0 0 0 1 1
0 0 1 0 0
0 0 1 0 1
0 0 1 1 0
0 0 1 1 1
0 1 0 0 0
0 1 0 0 1
0 1 0 1 0
0 1 0 1 1
0 1 1 0 0
0 1 1 0 1
0 1 1 1 0
0 1 1 1 1
1 0 0 0 0
1 0 0 0 1
1 0 0 1 0
1 0 1 0 0
1 0 1 0 1
1 0 1 1 0
1 0 1 1 1
1 1 0 0 0
1 1 0 0 1
1 1 0 1 0
1 1 0 1 1
SM DELTA 1-E.2 GB
12-5
Page 65
TROUBLESHOOTING
CONTENT
12.3.4 Outdoor unit diagnosis and corrective actions
NO
1
2
3
4
5
6
7
8
9
Fault
Sensors failures of all
types
IPM Fault
Bad EEPROM
DC under/over Voltage
AC under Voltage
Indoor / Outdoor unit
Communication mismatch
No Communication
Compressor Lock
Bad Communication
Probable Cause Corrective Action
Check sensors connections
or replace sensors.
Electronics HW
problem
No action, unless special
Electronics HW
problem
Check outdoor unit power
Indoor and Outdoor
controllers are with
different versions
Communication or
grounding wiring is not
good.
Switch unit to STBY and
Communication quality is
low reliability
Check all wiring and jumper
settings, if OK, replace
electronics.
parameters are required for
unit operation.
Check outdoor unit power
supply voltage
supply voltage
Replace Indoor controller
Check Indoor to Outdoor
wiring and grounding
restart
Check Indoor to Outdoor
wiring and grounding
12.4 Judgment by MegaTool
MegaTool is a special tool to monitor the system states.
Using MegaTool requires:
A computer with RS232C port.
A connection wire for MegaTool.
A special MegaTool software.
Use MegaTool according to following procedure:
Setup MegaTool software: copy the software to the computer.
Connect RS232C port in computer with MegaTool port in
Indoor/Outdoor unit controller by the connection wire.
Run the software and choose the COM port, you can monitor the
A/C system state in monitor tab.
12.5 Simple procedures for checking the Main Parts
12.5.1 Checking Mains Voltage.
Confirm that the Mains voltage is between 198 and 264 VAC. If Mains
voltage is out of this range, abnormal operation of the system is expected. If
in range check the Power (Circuit) Breaker and look for broken or loosed
cable lugs or wiring mistake(s).
12-6
SM DELTA 1-E.2 GB
Page 66
12.5.2Checking Power Input.
CONTENT
If Indoor unit power LED is unlighted, power down the system and check
the fuse of the Indoor unit. If the fuse is OK replace the Indoor unit
controller. If the fuse has blown, replace the fuse and power up again.
Checking Power Input procedure for the Outdoor unit is the same as with
the Indoor unit.
12.5.3 Checking the Outdoor Fan Motor.
Enter Test Mode (where the OFAN speed is high)
Check the voltage between lead wires according to the normal value
as following:
Between red wire and black wire: 310VDC +/- 20V
Between orange wire and black wire: 15VDC +/- 1V
Between yellow wire and black wire: 2-6VDC
12.5.4 Checking the Compressor.
The compressor is brushless permanence magnetic DC motor. Three
coil resistance is same. Check the resistance between three poles.
The normal value should be below 0.5 ohm (TBD).
TROUBLESHOOTING
12.5.5 Checking the Reverse Valve (RV).
Running in heating mode, check the voltage between two pins of
reverse valve connector, normal voltage is 220VAC.
12.5.6 Checking the electrical expansion valve (EEV).
The EEV has two parts, drive part and valve. The drive part is a step motor; it is
ringed on the valve. Check the drive voltage (12VDC). When Outdoor unit is
power on, EEV shall run and have click and vibration.
12.6 Precaution, Advise and Notice Items
12.6.1 High voltage in Outdoor unit controller.
Whole controller, including the wires that are connected to the Outdoor unit
controller may have the potential hazard voltage when power is on. Touching
the Outdoor unit controller may cause an electrical shock.
Advise: Don’t touch the naked lead wire and don’t insert finger,
conductor or anything else into the controller when power is on.
12.6.2 Charged Capacitors
Three large-capacity electrolytic capacitors are used in the Outdoor
unit controller. Therefore, charging voltage (380VDC) remains after
power down. Discharging takes about four minutes after power is off.
Touching the Outdoor unit controller before discharging may cause an
electrical shock.
12.6.3 Additional advises
SM DELTA 1-E.2 GB
When disassemble the controller or the front panel, turn off the power
supply.
When connecting or disconnecting the connectors on the PCB, hold the