● Bended indoor coil with treated aluminum fins and coating for improved efficiency.
● High COP.
● Pre-Charged units up to the max allowing tubing distance.
● Heating operation at outdoor temperature down to -15ºC
● Advanced test and diagnostics mode.
● M2L diagnostics softwear cable port (for PC)
● Easy access to the interconnecting tubing and wiring connections, so that removing
the front grill or casing is not necessary.
● Refrigerant pipes can be connected to the indoor unit from 5 different optional
directions.
● Automatic treated air sweep.
● Easy installation and service.
SM DELTAZ 1-E.0 GB
1-1
Page 5
INTRODUCTION
CONTENTS
1.3 Indoor Unit
The indoor unit is wall mounted, and can be easily fitted to many types of residential and
commercials applications.
It includes:
● Casing with air inlet and outlet grills.
● A large-diameter tangential fan.
● Bended coil with treated aluminum fins.
● Motorized flaps.
● Variable Speed motor (PG).
● Advanced electronic control box assembly.
● Interconnecting wiring terminal block.
● Mounting plate
.
1.4 Filtration
The Delta series presents several types of air filters:
● Easily accessible, and re-usable pre-filters (mesh).
● Pre-charged electrostatic filter (optional).
● Active carbon filter (optional).
1.5 Control
The microprocessor indoor controller, and an infrared remote control, supplied as
standard, provide complete operating function and programming. For further details
please refer to the Operation Manual, Appendix A.
1.6 Outdoor Unit
The Delta outdoor units can be installed as floor or wall mounted units by using a wall
supporting bracket. The metal sheets are protected by anti- corrosion paint work allowing
long life resistance. All outdoor units are pre-charged. For further information please
refer to the Product Data Sheet, Chapter 2.
1-2
It includes :
● Compressor mounted in a soundproofed component.
Single DC Rotary ─ For DCR 25Z, DCR 35Z.
● Axial fan.
● Outdoor coil with hydrophilic louver fins.
● Outlet air fan grill.
● Display (3 LED’s).
● 2 speed AC motor.
SM DELTAZ 1-E.0 GB
Page 6
1.7 Tubing Connections
CONTENTS
Flare type interconnecting tubing to be produced on site.
For further details please refer to the Installation Manual, Outdoor Chapter 9.
1.8 Inbox Documentation
Each unit is supplied with its own installation and operation manuals, one simly remote
control manual.
1.9 Matching Table
OUTDOOR UNITS
INTRODUCTION
INDOOR UNITS
MODELREFR”Delta 25Delta 35
DCR 25ZR410A
DCR 35ZR410A
√
√
SM DELTAZ 1-E.0 GB
1-3
Page 7
2. PRODUCT DATA SHEET
CONTENTS
2.1 Delta 25 / DCR 25Z R410A
PRODUCT DATA SHEET
Model Indoor Unit
Model Outdoor Unit
DELTA 25 DCI
DCR 25 Z R410A
Installation Method of PipeFlared
CharacteristicsUnitsCoolingHeating
Capacity
Power input
(4)
(4)
EER (Cooling) or COP(Heating)
(4)
Btu/hr8530(4090-10240)8530(3410-10910)
kW2.5(1.2-3.0)2.5(1.0-3.2)
kW0.78 0.69
W/W3.213.61
Energy efficiency classAA
Power supplyV/Ph/Hz220-240V ~1Ph 50/60Hz
Rated currentA3.53.1
Starting currentA10.5
Circuit breaker ratingA10
Fan type & quantityCrossflow x 1
Fan speedsH/M/LRPM1200/1050/850
Air flow
(1)
H/M/Lm3/hr420/350/270
External static pressureMin-MaxPa0
Sound power level
DimensionsWxHxDmm680x185x250
Weightkg7
Package dimensionsWxHxDmm740x265x320
Packaged weightkg10
Units per palletunits36 units per pallet
Stacking heightunits9 levels
Refrigerant controlCapillary
Compressor type,modelRotary, TOSHIBA DA89X1C-20FZ3
Fan type & quantityPropeller(direct) x 1
Fan speedsH/LRPM830
Air flow H/Lm3/hr1460
Sound power levelH/LdB(A)65
Sound pressure level
(3)
H/LdB(A)55
DimensionsWxHxDmm760x245x545
Weightkg31
Package dimensionsWxHxDmm880x310x610
Packaged weightkg33
Units per palletUnits12 units per pallet
DimensionsWxHxDmm840x185x250
Weightkg8
Package dimensionsWxHxDmm930x265x320
Packaged weightkg11
Units per palletunits36 units per pallet
Stacking heightunits9 levels
Refrigerant controlCapillary
Compressor type,modelRotary, TOSHIBA DA108X1C-20FZ3
Fan type & quantityPropeller(direct) x 1
Fan speedsH/LRPM830
Air flow H/Lm3/hr1460
Sound power levelH/LdB(A)66
Sound pressure level
(3)
H/LdB(A)56
DimensionsWxHxDmm760x245x545
Weightkg32
Package dimensionsWxHxDmm880x310x610
Packaged weightkg34
Units per palletUnits12 units per pallet
Max.height differencem.Max. 10
Operation control type Remote control
Heating elementskWNo
Others
(1)
(2)
(3)
(4)
2-2
Airflow in ducted units; at nominal external static pressure.
Sound power in ducted units is measured at air discharge.
Sound pressure level measured at 1-meter distance from unit.
Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
SM DELTAZ 1-E.0 GB
Page 9
3. RATING CONDITIONS
CONTENTS
Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units).
2. Refrigerant Valve Port (use Allen wrench to open/close)
3. Valve Protection Cap
4. Refrigerant Valve
5. Service Port Cap
6. Flare Nut
7. Unit Back Side
8. Copper Tube
When the outdoor unit is installed above the indoor unit an oil trap is required every 5m along the suction
line at the lowest point of the riser. Incase the indoor unit is installed above the outdoor, no trap is
required.
SM DELTAZ 1-E.0 GB
10-1
Page 29
CONTROL SYSTEM
CONTENTS
11. CONTROL SYSTEM
11.1 Electronic Control
11.1.1 General Functions and Operating Rules
The DCI software is fully parametric.All the model dependent parameters are shown in Blue color
and with Italic style [parameter].
The parameters values are given in the last section of this control logic chapter of the service
manual.
11.1.2 System Operation Concept
The control function is divided between indoor and outdoor unit controllers. Indoor unit is the system
‘Master’, requesting the outdoor unit for cooling/heating capacity supply. The outdoor unit is the
system ‘Slave’ and it must supply the required capacity unless it enters into a protection mode
avoiding it from supplying the requested capacity.
The capacity request is transferred via indoor to outdoor communication, and is represented
by a parameter called ‘NLOAD’. NLOAD is an integer number with values between 0 and 127,
and it represents the heat or cool load felt by the indoor unit.
11.1.3 Compressor Frequency Control (NLOAD setting)
11.1.3.1 NLOAD setting
The NLOAD setting is done by the indoor unit controller, based on a PI control scheme.
The actual NLOAD to be sent to the outdoor unit controller, is based on the preliminary LOAD
calculation, the indoor fan speed, and the power shedding function.
The compressor target frequency is set by the following table, according to the NLOAD number
received from the indoor unit.
NLOADTarget Frequency [Hz]
00
SM DELTAZ 1-E.0 GB
0<NLOAD≤MinFreqMinFreq
MinFreqMaxFreq
>MinFreq
MinFreqneLoadDeadZo
Definitions
CoolHeat
MinFreqMinFreqCMinFreqH
MaxFreqMaxFreqCMaxFreqH
LoadDeadZoneLoadDeadZoneCLoadDeadZoneH
MinFreqMinFreq}ne)LoadDeadZo(NLOAD,{min
11-1
Page 30
CONTROL SYSTEM
CONTENTS
11.1.3.3 Frequency Changes Control
Frequency change rate is 1 Hz/sec.
11.1.3.4 Compressor Starting Control
Frequency
Step 3
Step 2
Step 1
1
Minute
1
Minute
Time
Min 10 Minutes
11.1.3.5 Minimum On and Off Time
3 minutes.
11.1.4 Indoor Fan Control
10 Indoor fan speeds are determined for each model. 5 speeds for cool/dry/fan modes and 5 speeds
for heat mode.
When user sets the indoor fan speed to a fixed speed (Low/ Medium/ High), unit will operate constantly
at set speed.
When Auto Fan is selected, indoor unit controller can operate in all speeds. The actual speed is set
according to the cool/heat load.
11.1.4.1 Turbo Speed
The Turbo speed is activated during the first 30 minutes of unit operation when auto fan speed is
selected and under the following conditions:
Difference between set point and actual room temperature is bigger then 3 degrees.
Room temperature > 22 for cooling, or < 25 for heating.
11.1.5 Heating Element Control
Heating element can be started if LOAD > 0.8 * MaximumNLOAD AND Indoor Coil temperature
< 45.
The heating element will be stopped when LOAD < 0.5 * MaximumNLOAD OR if Indoor Coil
temperature > 50.
11.1.6 Outdoor Fan Control
11.1.6.1 The following are the speeds types (General Rules):
11-2
MCU
High Speed Output
Low Speed Output
Relay
OFAN
motor
Triac
SM DELTAZ 1-E.0 GB
Page 31
CONTROL SYSTEM
CONTENTS
SpeedControlled by
HighRelay
LowTriac (40% to 95% effective voltage)
11.1.6.2 OFAN Operation in Cooling Mode
With keeping the OFAN general rules above in the highest priority, the operation of the OFAN will be operating
as the following:
OAT
Initial
OAT
Initial
>20
(or Faulty)
OAT
≤20Low(Triac)- Open Loop
Initial
0 – 3min> 3min
High(Relay)
Time After Compressor start up (minutes)
First Time enters the
default is the l ast state
High (Relay)
Low (Triac)- By CDT
1821
Note : OAT faulty , use Hi gh Speed
OAT (cur r ent)
Note:
The OAT
value represents one OAT reading exactly at the moment start up (actual freq>0).
Initial
Low (Triac)- By OMT represents the operation of the Low Fan speed controlled by Triac
according to OMT sensor.
11.1.6.3 OFAN Operation in Heating Mode
Except to the “General rules”, the outdoor fan will always be running at High speed during heating
operation mode.
11.1.7 EEV (electronic Expansion valve) Control
EEV opening is defined as EEV = EEVOL + EEV
EEV
is the initial EEV opening as a function of the compressor frequency, operation
OL
mode, unit model and capacity.
EEV
is a correction value for the EEV opening that is based on the compressor
CV
temperature.
During the first 5 minutes of compressor operation EEV
Once the first 5 minutes are over, the correction value is calculated as follow: EEV
= EEV
EEV
(n-1) + EEV
CV
is the correction based on the compressor temperature. A target compressor
CTT
CTT
temperature is set depending on frequency and outdoor air temperature, and the actual
compressor temperature is compared to the target temperature to set the required
correction to the EEV opening.
CV
CV
= 0.
CV
(n)
SM DELTAZ 1-E.0 GB
11-3
Page 32
CONTROL SYSTEM
CONTENTS
11.1.8 Reversing Valve (RV) Control
Reversing valve is on in heat mode.
Switching of RV state is done only after compressor is off for over 3 minutes.
11.2 Fan Mode
In high/ medium/ low indoor fan user setting, unit will operate fan in selected speed.
In AutoFan user setting, fan speed will be adjusted automatically according to the difference
between actual room temperature and user set point temperature.
11.3 Cool Mode
NLOAD is calculated according to the difference between actual room temperature and user set
point temperature by PI control.
In high/ medium/ low indoor fan user setting, unit will operate fan in selected speed.
In AutoFan user setting, fan speed will be adjusted automatically according to the calculated
NLOAD.
11.4 Heat Mode
NLOAD is calculated according to the difference between actual room temperature and user set
point temperature by PI control.
In high/ medium/ low indoor fan user setting, unit will operate fan in selected speed.
In AutoFan user setting, fan speed will be adjusted automatically according to the calculated
NLOAD.
11.4.1 Temperature Compensation
4 degrees are reduced from RT sensor temperature reading (excluding I-Feel mode), to
compensate for temperature difference between high and low areas in the heated room, and due
to coil heat radiation on RT sensor.
11.4.2 Indoor Fan Control in Heat Mode
Indoor fan speed depends on the indoor coil temperature:
11.5 Auto Cool/Heat Mode
When in auto cool heat mode unit will automatically select between cool and heat mode according
to the difference between actual room temperature and user set point temperature (ΔT).
Unit will switch from cool to heat when compressor is off for 3 minutes, and ΔT < -3.
Unit will switch from heat to cool when compressor is off for 5 minutes, and ΔT < -3.
11-4
ICTST
ICTVL ICTT ICTHICTL
SM DELTAZ 1-E.0 GB
Page 33
CONTROL SYSTEM
CONTENTS
11.6 Dry Mode
As long as room temperature is higher then the set point, indoor fan will work in low speed and
compressor will work between 0 and MaxNLOADIF1C Hz.
When the room temperature is lower than the set point, compressor will be switched OFF and
indoor fan will cycle 3 minutes OFF, 1 minute ON.
11.7 Protections
There are 5 protection codes.
Normal (Norm) – unit operate normally.
Stop Rise (SR) – compressor frequency can not be raised but does not have to be decreased.
HzDown1 (D1) – Compressor frequency is reduced by Down1 Hz/min.
HzDown2 (D2) – Compressor frequency is reduced by Down2 Hz/min.
Stop Compressor (SC) – Compressor is stopped.
(*) Normal (Norm) – No protection status is ON.
Stop-Rise (SR) – System is in protection.
HzDown1 (D1) - System is in protection.
HzDown2 (D2) - System is in protection.
< HSTOH5D1D1D2D2D2
n
< HSTOH4SRSRD1D2D2
n
< HSTOH3SRSRSRD1D1
n
< HSTOH2NormNormNormSRSR
n
< HSTOH1Norm
n
<-1-101>1
HSTn-HST
n-1
11.7.6 Outdoor Coil Deicing Protection
11.7.6.1 Deicing Starting Conditions
Deicing operation will start when either one of the following conditions exist:
Case 1: OCT <-DST – AND TLD > DI
Case 2: OCT < OAT
Case 3: OCT <-1 AND TLD> 100 mnutes.
Case 4: OCT is Invalid AND TLD > DI
Case 5: Unit is just switched to STBY AND OCT <-DST
Case 6: NLOAD = 0 AND OCT <-DST
– 12 AND TLD > 30 minutes.
max
DST Calculation:
When OATmax >0 or OAT is invalid; then DST=8
When OATmax ≤0; then DST= round down (-0.8 * OATmax) + 8
OATmax calculation:
After compressor starts for 3 minutes, OATmax calculation is start.
The OATmax is the moving value of the Maximum OAT during the 1st 10mintues within last
30minutes
OCT – Outdoor Coil Temperature
OAT – Outdoor Air Temperature
TLD – Time from Last Deicing
DI – Deicing Interval (Time Interval Between Two Deicing)
Deicing interval time when compressor is first started in heat mode, is 10 minutes if OCT < -2, and
is 40 minutes in other cases.
Deicing interval time is changed (increased/ decreased in 10 minutes steps) as a function of
deicing time. If deicing time is shorter then former deicing time, the deicing interval time will be
increased. If deicing time is longer then former deicing time, the deicing interval time will be
decreased.
SM DELTAZ 1-E.0 GB
11-7
Page 36
CONTROL SYSTEM
CONTENTS
11.7.6.2 Deicing Protection Procedure
OCT
12
0
Threshold
COMP
RV
OFAN
EEV
ON
HEAT
COOL
ON
OFF
EEVDeicerOpen
Any
T1T2
max. 12 minutes
DT
T3T3
T1 = DEICT1, T2 = DEICT2, T3 = DEICT3
11.7.7 Condensate Water Over Flow Protection
T1
Each of the pins P1, P2, P3 can have two options:
1 – When it is shorted with P4
0 – When it is not shorted to P4
11.7.7.1 3 Levels Logic (used in floor/ceiling models)
11-8
P2P3Level
00L0
10L1
11L2&3
01L4
SM DELTAZ 1-E.0 GB
Page 37
Water Level
CONTENTS
LEVEL4
LEVEL2&3
LEVEL1
Pump
NLOAD
CONTROL SYSTEM
ON
OFF
ANY
0
BLINK
OPER LED
NORMAL
11.7.7.2 1 Level Logic (used in all models except for floor/ceiling models)
P2P3Level
Don’t care1Normal
Don’t care0Overflow
Water Level
OPER
LED
Overflow
Normal
ON
OFF
BLINK
Overflow when
unit is ON
Overflow when
unit is OFF
SM DELTAZ 1-E.0 GB
NLOAD
PUMP
ANY
0
ON
OFF
NLOAD is
forced to 0
8 min8 min
8 min
11-9
Page 38
CONTROL SYSTEM
CONTENTS
11.8 Indoor Unit Dry Contact
Indoor unit Dry contact has two alternative functions that are selected by J8.
Forced operation allows to start, stop and operate in Cooling or Heating, in pre-set temperature
according to the following table:
Forced operation ModePre-set Temperature
Cooling20
Heating28
0
C
0
C
11.10 On Unit Controls and Indicators
11.10.1 Indoor Unit Controller Controls and Indicators Foe All Models
The following is schematic drawing for the display:
STBY/OPER
Mode/Reset Button
Timer
Filter
Infra Red Receiver
11-10
SM DELTAZ 1-E.0 GB
Page 39
1. Lights up when the Air Conditioner is connected to power and the
CONTENTS
STAND BY
INDICATOR
OPERATION INDICATOR
TIMER INDICATORLights up during Timer and Sleep operation.
FILTER INDICATORLights up when Air Filter needs to be cleaned.
mode is STBY.
2. Blinks for 3 seconds, when the system is switched to Heat Mode
by using the Mode/Reset Switch on the unit (the operation
indicator will be off during this blinking time).
1. Lights up during operation mode (except for item in STBY
indicator).
2. Blinks for 300 msec., to announce that a R/C infrared
signal has been received and stored.
3. Blinks continuously during protections (according to the relevant
spec section).
4. Blinks for 3 seconds when the system is switched to Cool Mode
by using the Mode/Reset Switch on the unit.
CONTROL SYSTEM
As long as the filter Led is off, the Mode/Reset button functions as Mode
switch. Once filter Led is on, the Mode/Reset button functions as Reset
switch.
Mode Function:
Every short pressing , the next operation mode is selected, in this order:
MODE / RESET BUTTON
SB → Cool Mode → Heat Mode → SB → …
In long pressing system enters diagnostic mode (refer to diagnostic
mode Sect.)
Reset Function:
For short pressing:
When Filter LED is on, it turns off the filter indicator.
Notes
1. Pressing time is defined as the time between press and release.
2. If pressing time is one second or less – press is considered as short pressing.
3. If pressing time is three seconds or longer – pressing is considered as long pressing. In
between, pressing is undetermined and system will not respond to pressing.
4. For the LED functionality during diagnostics, refer to the diagnostics Sect.
SM DELTAZ 1-E.0 GB
11-11
Page 40
CONTROL SYSTEM
CONTENTS
11.10.2 Outdoor Unit Controller Indicators
Unit has three LED’s. SB LED, STATUS LED, FAULT LED.
SB LED is ON when power is ON (230 VAC),
STATUS LED is ON when COMP is ON, and Blinks according to diagnostics mode definitions
when either fault or protection occurs.
FAULT LED Blinks according to diagnostics mode definitions when either fault or protection occurs.
11.11 Jumper Settings
11.11.1 Indoor Unit Controller
11.11.1.1 Hardware Jumpers
0 = Open Jumper (disconnect jumper).
1 = Close Jumper (connect jumper).
Self test Jumper – J1
OPERATIONJ1
SELF-TEST1
NORMAL0
Family selection Jumper – J2
FamilyJ2
Delta 22/25/350
Delta 501
Model selection Jumper – J3, J4
Model J3 J4
A
B
C
D
11.11.1.2 Software Jumpers
0 0
0 1
1 0
1 1
Property01
EEPROM DATA (J1)Use ROM*Use EEPROM
‘Thermostatic Stop- Heat’ (J2)DeactivatedActivated
‘Heat to STBY’ (J3)DeactivatedActivated
Enable Test Mode (J4)DeactivatedActivated*
* Default values (used in the ROM)
Default SW jumpers according to the family (used in the ROM)
J1 – EEPROM/ROM setting
When J1 is 1, IDU will use model/family/general parameters from EEPROM. If EEPROM is invalid, IDU will
ignore J1 and use/copy the ROM pointed by the selected jumpers (will also set an according fault).
11-12
PropertyDelta 22/25/35Delta 50
‘Thermostatic Stop- Heat’ (J2)11
‘Heat to STBY’ (J3)11
OFFOFFOFFOFFReserved
OFFOFFOFFON A (Single DCR 22- Use Capillary)Toshiba-DA89 (4 Poles)
OFFOFFON OFFB (Single DCR 25- Use Capillary)Toshiba-DA89 (4 Poles)
OFFOFFON ON C (Single DCR 35- Use Capillary)Toshiba- DA108 (4 Poles)
OFFON OFFOFF D (Reserved)
OFFON OFFON E (Single DCR 22- Use EEV)Panasonic-5RS092 (6 Poles)
OFFON ON OFFF (Single DCR 25- Use EEV)Panasonic-5RS092 (6 Poles)
OFFON ON ON G (Single DCR 35- Use EEV)Panasonic-5RS102(6 Poles)
ON OFFOFFOFFH
ON OFFOFFON I
ON OFFON OFFJ
ON OFFON ON K
ON ON OFFOFFL
ON ON OFFON M
ON ON ON OFFN
ON ON ON ON O
PCB JUMPER J1 HEADER
J1 header is used for program flash.
11.11.2.2 Software Jumpers
Property01
EEPROM DATA (J1)Use ROM*Use EEPROM
* Default values (used in the ROM)
J1 – EEPROM/ROM setting
When J1 is 1, ODU will use model/general parameters from EEPROM. If EEPROM is invalid, ODU
will ignore J1 and use/copy the ROM pointed by the selected jumpers (will also set an according
fault).
SM DELTAZ 1-E.0 GB
11-13
Page 42
CONTROL SYSTEM
CONTENTS
11.12 Test Mode
11.12.1 Entering Test Mode
System can enter Test mode in two ways:
Automatically when the following conditions exists for 30 minutes continuously:
o Mode = Cool, Set point = 16, Room temperature = 27±1, Outdoor temperature =
35±1
Or
o Mode = Heat, Set point = 30, Room temperature = 20±1, Outdoor temperature =
7±1
Manually when entering diagnostics with the following settings:
o Mode = Cool, Set point = 16
o Mode = Heat, Set point = 30
11.12.2 Unit Operation in Test Mode
In test mode, the unit will operate in fixed settings according to the indoor fan speed setting:
Indoor Fan Speed SettingUnit Setting
LowMinimum Capacity Setting
HighNominal Capacity Setting
AutoMaximum Capacity Setting
During test mode, protections are disabled, except for stop compressor status.
11.13 SW Parameters
11.13.1 Indoor Units SW Parameters
11.13.1.1 General Parameters for All Models:
Parameters defining the indoor fan speed as a function of Indoor Coil temperature in heat
mode (ICT):
ICTST Speed ICT to stop indoor fan 25
ICTVLSpeed ICT to go down to very low speed 28
ICTLSpeed ICT to start in very low speed 30
ICTHSpeed ICT to start in increase speed from very low 32
ICTTSpeed ICT to enable Turbo fan speed 40
Parameters for defrost protection:
ICTDef1 ICT to go back to normal 8
ICTDef2 ICT to ‘stop rise’ when ICT decrease 6
ICTDef3 ICT to ‘stop rise’ when ICT is stable 4
ICTDef4 ICT to ‘Hz Down’ when ICT decrease 2
ICTDef5 ICT to ‘Hz Down’ when ICT is stable 0
ICTDef6 ICT to stop compressor -2
Parameters for indoor coil over heating protection:
ICTOH1 ICT to go back to normal 45
ICTOH2 ICT to ‘stop rise’ when ICT increase 48
ICTOH3 ICT to ‘stop rise’ when ICT is stable 52
ICTOH4 ICT to ‘Hz Down’ when ICT increase 55
ICTOH5 ICT to ‘Hz Down’ when ICT is stable 60
ICTOH6 ICT to stop compressor 62
11-14
SM DELTAZ 1-E.0 GB
Page 43
11.13.1.2 Model Depended Parameters:
CONTENTS
CONTROL SYSTEM
Parameter name
Models
2535
NLOAD limits as a function of selected indoor fan speed
Frequency limits as a function of outdoor air temperature
MaxFreqAsOATC6578
MaxFreqAsOAT1H5860
MaxFreqAsOAT2H5050
Compressor Over Heating Protection
CTTOH19494
CTTOH29898
CTTOH3102102
CTTOH4105105
CTTOH5120120
Compressor Over Current Protection [A]
CCR013540
CCR023742
CCR033944
CCR044247
Outdoor Fan Speed (RPM)
OFLOWC
OFMEDC
OFMAXC830830
SM DELTAZ 1-E.0 GB
11-15
Page 44
TROUBLESHOOTING
CONTENTS
12 TROUBLESHOOTING
12.1 ELECTRICAL & CONTROL TROUBLESHOOTING
WARNING!!!
When Power Up – the whole outdoor unit controller, including the wiring, is under HIGH
VOLTAGE!!!
Never open the Outdoor unit before turning off the Power!!!
When turned off, the system is still charged (400V)!!!
It takes about 4 Min. to discharge the system.
Touching the controller before discharging may cause an electrical shock!!!
For safe handling of the controller please refer to section 12.3 below.
12.1.1 Single Split system failures and corrective actions
NoSYMPTOMPROBABLE CAUSECORRECTIVE ACTION
Power supply indicator (Red
1
LED) does not light up.
Unit does not respond to
remote control message
2
Unit responds to remote
control message but Operate
3
indicator (Green LED) does
not light up
Indoor fan does not start
(louvers are opened and
Green LED does light up)
4
Indoor fan works when unit is
OFF, and indoor fan speed is
5
not changed by remote control
command.
Compressor does not start
6
Compressor stops during
operation and Green LED
7
remains on
Compressor is on but outdoor
8
fan does not work
Unit works in wrong mode
(cool instead of heat or heat
9
instead of cool)
All components are operating
properly but no cooling or no
10
heating
No power supply
Remote control
message not reached
the indoor unit
Problem with display
PCB
Unit in heat mode and
coil is still not warm.
Problem with PCB or
capacitor
PCB problemReplace controller
Electronics control
problem or protection
Electronic control or
power supply problem
Problem with outdoor
electronics or outdoor
fan
Electronics or power
connection to RV
Refrigerant leakCheck refrigeration system.
Check power supply. If power supply is OK,
check display and display wiring. if OK,
replace controller.
Check remote control batteries, if batteries
are OK, check display and display wiring, if
OK, replace display PCB.
If still not OK replace controller.
Replace display PCB.
If still not OK replace controller.
Change to cool mode and check.
Change to high speed and Check power
supply to motor is higher than 130VAC
(for triack controlled motor) or higher than
220VAC for fixed speed motors, if OK replace
capacitor, if not OK replace controller
Perform diagnostics (See 12.1.3 below), and
follow the actions described.
Perform diagnostics (See 12.1.3 below), and
follow the actions described.
Check outdoor fan motor according to the
procedure in section 12.2.3 below, if not OK
replace controller
Check RV power connections, if OK,
Check RV operation with direct 230VAC
power supply, if OK,
Replace outdoor controller.
SM DELTAZ 1-E.0 GB
12-1
Page 45
TROUBLESHOOTING
CONTENTS
NoSYMPTOMPROBABLE CAUSECORRECTIVE ACTION
Compressor is over heated
and unit does not generate
11
capacity
Units goes into protections
and compressor is stopped
12
with no clear reason
Compressor motor is
generating noise and no
13
suction occurs
Water leakage from indoor
14
unit
Freezing of outdoor unit in
heat mode and outdoor unit
15
base is blocked with ice
EEV problemCheck EEV
Control problem or
refrigeration system
problem
Phase order to
compressor is wrong
Indoor unit drainage
tube is blocked
Perform diagnostics (See 13.1.3 below), and
follow the actions described.
Check compressor phase order.
Check and open drainage tube.
Connect base heater.
Unit operates with wrong fan
16
speeds or wrong frequency
Wrong jumper settings
Perform diagnostics (See 12.1.3 below),
and check if units is operating by EEPROM
parameters.
12.1.2 Checking the refrigeration system
Checking system pressures and other thermodynamic measures should be done when system
is in Test Mode (in Test mode, system operates in fixed settings). The performance curves
given in this manual are given for unit performance in test mode when high indoor fan speed is
selected.
Entering test mode:
Set unit to Cool/16 degrees/High indoor fan speed, or Heat/30 degrees/High indoor fan speed,
and enter diagnostics.
12.1.3 Judgment by Indoor/Outdoor Unit Diagnostics
Enter diagnostics mode - press for five seconds Mode/Reset button in any operation mode.
Acknowledgment is by 3 short beeps and lights of all Display LED’s. Then, The units will enter
into Indoor and Outdoor unit diagnostic modes.
During the Outdoor unit diagnostics all three Indoor LED’s (STBY/Operate, Filter and Timer)
are blinking. When Indoor diagnostics is displayed, all three LED’s (STBY/Operate, Filter and
Timer) are ON.
When system enters diagnostics mode, only one fault code is shown. Order of priority is from
the lower to the higher number. Diagnostics is continuously ON as long as power is ON. The
current system operation mode will not be changed.
If no fault occurred in the system, no fault code will be displayed during normal operation MOde.
The last fault code will be displayed even if the system has recovered from that fault. The last
fault will be deleted from the EEPROM after the system has exit diagnostics mode.
12-2
In diagnostics mode, system fault / status will be indicated by blinking of Filter & Timer LEDs.
The coding method will be as follows:
Filter LED will blink 5 times in 5 seconds, and then will be shut off for the next 5 seconds.
Timer LED will blink during the same 5 seconds according to the following Indoor / Outdoor
unit tables:
Note: 0 – OFF, 1-ON
SM DELTAZ 1-E.0 GB
Page 46
TROUBLESHOOTING
CONTENTS
12.1.3.1 Indoor unit Diagnostics
NoProblem54321
1RT-1 is disconnected00001
2RT-1 is shorted00010
3RT-2 is disconnected00011
4RT-2 is shorted00100
5Reserved00101
7Communication mismatch00111
8No Communication01000
9No Encoder01001
10Reserved01010
11Outdoor Unit Fault01011
…Reserved
17Defrost protection10001
18Deicing Protection10010
19Outdoor Unit Protection10011
20Indoor Coil HP Protection10100
21Reserved10101
22Reserved
24EEPROM Not Updated11000
25Bad EEPROM11001
26Bad Communication11010
27Using EEPROM data11011
28Model A11100
29Model B11101
30Model C 11110
31Model D11111
13.1.3.2 Indoor unit diagnosis and corrective actions
No.FaultProbable CauseCorrective Action
Sensor failures of all
1
types
Communication
mismatch
2
No CommunicationCommunication or grounding
3
No EncoderIndoor electronics or motorCheck motor wiring, if ok, replace motor,
Indoor and Outdoor controllers
are with different versions
wiring is not good.
4
Outdoor Unit FaultOutdoor controller problemSwitch to Outdoor diagnostics.
5
EEPROM Not Updated System is using ROM parameters
6
Bad EEPROMNo action, unless special parameters
and not EEPROM parameters
7
Bad CommunicationCommunication quality is low
8
Using EEPROM dataNo problem. System is using
9
reliability
EEPRRRROM parameters
Check sensor connections or replace
sensor
Replace Indoor controller
Check Indoor to Outdoor wiring and
grounding
if still not ok, replace Indoor controller.
No action, unless special parameters
are required for unit operation.
5OMT shorted/disconnected
…Reserved
11IPM Fault
12Reserved
13DC under voltage
14Reserved
15Zero Crossing detection fault
16Mismatch between IDU & ODU models
17No Communication
…Reserved
20Heat sink Over Heating
21Deicing
22Compressor Over Heating
23Compressor Over Current
…Reserved
26Copressor Lock
27Bad Communication
28Missing ODU configuration
29Undefined ODU Model
30Outdoor Coil Overheating
31Operation condition is exceeded
00001
00010
00011
00100
00101
01011
01100
01101
01110
01111
10000
10001
10100
10101
10110
10111
11010
11011
11100
11101
11110
11111
12.1.3.4 Outdoor unit diagnosis and corrective actions
No.FaultProbable CauseCorrective Action
Sensors failures of all typesCheck sensors connections or
1
IPM FaultElectronics HW problemCheck all wiring and jumper
2
Bad EEPROMNo action, unless special
3
DC under/over VoltageElectronics HW problemCheck outdoor unit power supply
4
AC under VoltageCheck outdoor unit power supply
5
Indoor / Outdoor unit
6
Communication mismatch
No CommunicationCommunication or grounding
7
Compressor LockSwitch unit to STBY and restart
8
Bad CommunicationCommunication quality is low
9
Indoor and Outdoor controllers
are with different versions
wiring is not good.
reliability
replace sensors.
settings, if OK, replace
electronics.
parameters are required for unit
operation.
voltage
voltage
Replace Indoor controller
Check Indoor to Outdoor wiring
and grounding
Check Indoor to Outdoor wiring
and grounding
12.1.4 Judgement by MegaTool
12-4
MegaTool is a special tool to monitor the system states.
Using MegaTool requires:
A computer with RS232C port.
A connection wire for MegaTool.
A special MegaTool software.
SM DELTAZ 1-E.0 GB
Page 48
TROUBLESHOOTING
CONTENTS
Use MegaTool according to following procedure:
Setup MegaTool software: copy the software to the computer.
Connect RS232C port in computer with MegaTool port in Indoor/Outdoor unit controller by
the connection wire.
Run the software and choose the COM port, you can monitor the A/C system state in monitor
tab.
12.2 Simple procedures for checking the Main Parts
12.2.1 Checking Mains Voltage.
Confirm that the Mains voltage is between 198 and 264 VAC. If Mains voltage is out of this range,
abnormal operation of the system is expected. If in range check the Power (Circuit) Breaker and
look for broken or loosed cable lugs or wiring mistake(s).
12.2.2 Checking Power Input.
If Indoor unit power LED is unlighted, power down the system and check the fuse of the Indoor
unit. If the fuse is OK replace the Indoor unit controller. If the fuse has blown, replace the fuse
and power up again.
Checking Power Input procedure for the Outdoor unit is the same as with the Indoor unit.
12.2.3 Checking the Outdoor Fan Motor.
Enter Test Mode (where the OFAN speed is high)
check the voltage between two pins( Hi and N ) of connector Controller OFAN, normal voltage
is 220VAC.
12.2.4 Checking the Compressor.
The compressor is brushless permanence magnetic DC motor. Three coil resistance is same.
Check the resistance between three poles. The normal value should be below 0.5 ohm (TBD).
Pay attention U,V, Ware respective to connect to RED, BROWN, BLACK wires.
12.2.5 Checking the Reverse Valve (RV).
Running in heating mode, check the voltage between two pins of reverse valve connector,
normal voltage is 220VAC.
12.3 Precaution, Advise and Notice Items
12.3.1 High voltage in Ou0tdoor unit controller.
Whole controller, including the wires that are connected to the Outdoor unit controller may have
the potential hazard voltage when power is on. Touching the Outdoor unit controller may cause
an electrical shock.
Advise: Don’t touch the naked lead wire and don’t insert finger, conductor or anything else into
the controller when power is on.
12.3.2 Charged Capacitors
Three large-capacity electrolytic capacitors are used in the Outdoor unit controller. Therefore,
charging voltage (380VDC) remains after power down. Discharging takes about four minutes
after power is off. Touching the Outdoor unit controller before discharging may cause an electrical
shock.
12.3.3 Additional advises
There are sharp fringes and sting on shell. Use gloves when disassemble
SM DELTAZ 1-E.0 GB
When disassemble the controller or the front panel, turn off the power supply.
When connecting or disconnecting the connectors on the PCB, hold the whole housing, don’t
pull the wire.
12-5
Page 49
EXPLODED VIEWS AND SPARE PARTS LISTS
CONTENTS
13. EXPLODED VIEWS AND SPARE PARTS LISTS
13.1 Indoor Unit: Delta 25, Delta 35 DCI
SM DELTAZ 1-E.0 GB
13-1
Page 50
EXPLODED VIEWS AND SPARE PARTS LISTS
CONTENTS
13.2 Indoor Unit: Delta 25 DCI
No.Part No.DescriptionQuan.
1453037000Grill A / DELTA 22,251
2453100500Grill L axis1
3453100600Grill R axis1
4453036500Filter for DELTA 7/92
7465720000Silk-screen front frame for Electra1
84525987SCREW COVER3
9453070701Evap. System Assy./DELTA 22,251
104523526BERAING ASSY FAN1
114523523FAN ASSY PLASTIC1
12452784400IOD-7,9 Air Outlet Assy. (no wire)1
134523693DRAIN HOSE1
144526659REAR PANEL ASSY1
15453027400Mount Bracket Assy./Alfa 7,91
164526000TUBE CLIP1
17412040RRemote controller RC5-RC 975-630-001
184526133Power cord cable1
194523507Step motor1
20453089600Display assy. for DELTA EHK:936-034-001