Electra Delta 25, DCR 22, Delta 35, DCR 35, DCR 25 Service Manual

...
Service Manual
DC Inverter Delta Series
REFRIGERANT
R410A
HEAT PUMP
JUNY 2005
Delta 22 DCR 22 Delta 25 DCR 25 Delta 35 DCR 35 Delta 50 DCR 50
A
LIST OF EFFECTIVE PAGES
Revision Y05-02 Service Manual - Delta DCI
LIST OF EFFECTIVE PAGES
Note: Changes in the pages are indicated by a “Revision#” in the footer of each effected page
(when none indicates no changes in the relevant page). All pages in the following list represent effected/ non effected pages divided by chapters.
Dates of issue for original and changed pages are:
Original ....... 0 ........ 15 March 2005
Total number of pages in this publication is 79 consisting of the following:
Page No.
Revision No. #
Page No.
Revision No. #
Page No.
Revision No. #
Title ....................... 1
A ........................... 1
i ............................. 0
1-1 - 1-3 ................ 1
2-1 - 2-4 ................ 1
3-1 ........................ 0
4-1 - 4-3 ................ 1
5-1 - 5-20 .............. 1
6-1 - 6-4 ................ 1
7-1 ........................ 1
8-1 ........................ 1
9-1 ........................ 1
10-1 ...................... 1
11-1-11-14 ............. 0
12-1-12-7 .............. 2
13-1-13-11 ............ 1
Appendix -A ...........0
• Zero in this column indicates an original page.
*Due to constant improvements please note that the data on this service manual can be modified with out notice. **Photos are not contractual
i
TABLE OF CONTENTS
Revision Y05-02Service Manual - Delta DCI
Table of Contents
1. INTRODUCTION ...................................................................................................1-1
2. PRODUCT DATA SHEET ......................................................................................2-1
3. RATING CONDITIONS ..........................................................................................3-1
4. OUTLINE DIMENSIONS .......................................................................................4-1
5. PERFORMANCE DATA & PRESSURE CURVES ...............................................5-1
6. SOUND LEVEL CHARACTERISTICS ..................................................................6-1
7. ELECTRICAL DATA ..............................................................................................7-1
8. WIRING DIAGRAMS .............................................................................................8-1
9. REFRIGERATION DIAGRAMS .............................................................................9-1
10. TUBING CONNECTIONS ......................................................................................10-1
11. CONTROL SYSTEM .............................................................................................11-1
12. TROUBLESHOOTING ..........................................................................................12-1
13. EXPLODED VIEWS AND SPARE PARTS LISTS .................................................13-1
14. APPENDIX A .........................................................................................................14-1
1-1
INTRODUCTION
Revision Y05-01Service Manual - Delta DCI
1. INTRODUCTION
1.1 General
The new Delta DC Inverter split wall mounted series comprise RC (heat pump) models, as follows:
Delta 22
Delta 25
Delta 35
Delta 50
The indoor Delta units are available as LED display types only, featuring esthetic design, compact dimensions, and low noise operation.
1.2 Main Features
The Delta series benefits from the most advanced innovations, namely:
DC Inverter Technology
● R410A
● Microprocessor control.
● Infrared remote control with liquid crystal display.
● Indoor large diameter cross flow fan, allowing low noise level operation.
● Bended indoor coil with treated aluminum fins and coating for improved efficiency.
● High COP.
● Pre-Charged units up to the max allowing tubing distance.
● Heating operation at outdoor temperature down to -15ºC
● Advanced test and diagnostics mode.
● M2L diagnostics softwear cable port (for PC)
● Easy access to the interconnecting tubing and wiring connections, so that during installation removing the front grill or casing is not necessary.
● Refrigerant pipes can be connected to the indoor unit from 5 different optional directions.
● Automatic treated air sweep.
● Easy installation and service.
1-2
INTRODUCTION
Revision Y05-01 Service Manual - Delta DCI
1.3 Indoor Unit
The indoor unit is wall mounted, and can be easily fitted to many types of residential and commercials applications.
It includes:
● Casing with air inlet and outlet grills.
A large-diameter tangential fan.
● Bended coil with treated aluminum fins.
● Motorized flaps.
● Variable Speed motor (PG).
● Advanced electronic control box assembly.
● Interconnecting wiring terminal block.
● Mounting plate
.
1.4 Filtration
The Delta series presents several types of air filters:
Easily accessible, and re-usable pre-filters (mesh)
Pre-charged electrostatic filter (optional)
Active carbon filter (optional)
1.5 Control
The microprocessor indoor controller, and an infrared remote control, supplied as standard, provide complete operating function and programming. For further details please refer to the Operation Manual, Appendix A.
1.6 Outdoor Unit
The Delta outdoor units can be installed as floor or wall mounted units by using a wall supporting bracket. The metal sheets are protected by anti- corrosion paint work allowing long life resistance. All outdoor units are pre-charged. For further information please refer to the Product Data Sheet, Chapter 2.
It includes :
● Single DC Rotary Compressor mounted in a soundproofed compartment
● Axial fan.
● Outdoor coil with hydrophilic louver fins.
● Outlet air fan grill.
● Outdoor advanced controller.
● 2 fan speed AC motor
1-3
INTRODUCTION
Revision Y05-01Service Manual - Delta DCI
1.7 Tubing Connections
Flare type interconnecting tubing to be produced on site. For further details please refer to the Installation Manual, Appendix A
1.8 Inbox Documentation
Each unit is supplied with its own installation and operation manuals,
1.9 Matching Table
OUTDOOR UNITS
INDOOR UNITS
MODEL REFR” Delta 25 Delta 35
DCR 25 R410A
DCR 35 R410A
2-1
PRODUCT DATA SHEET
Revision Y05-01Service Manual - Delta DCI
2.1 R410A
Model Indoor Unit DELTA 22 DCI Model Outdoor Unit DCR 22 R410A Installation Method of Pipe
Flared
Characteristics Units Cooling Heating
Capacity
(1)
Btu/hr 7500(4440-8870) 8530(4440-10580)
kW 2.2(1.3-2.6) 2.5(1.3-3.1)
Power input
(1)
kW 0.66 0.73
EER (Cooling) or COP(Heating)
(1)
W/W 3.33 3.42 Energy efficiency class A B Power supply V/Ph/Hz 220-240V/Single/50Hz Rated current A 3.0 3.3 Starting current A 10.5 Circuit breaker rating A 10
INDOOR
Fan type & quantity Crossflow x 1 Fan speeds H/M/L RPM 1100/950/800 Air flow
(2)
H/M/L m3/hr 400/350/300 External static pressure Min-Max Pa 0 Sound power level
(3)
H/M/L dB(A) 49/46/43 Sound pressure level
(4)
H/M/L dB(A) 36/33/30 Moisture removal l/hr 1 Condensate drain tube I.D mm 16 Dimensions WxHxD mm 680x250x185 Weight kg 7 Package dimensions WxHxD mm 740x265x320 Packaged weight kg 10 Units per pallet units 36 units per pallet Stacking height units 9 levels
OUTDOOR
Refrigerant control EEV Compressor type, model Rotary, Panasonic 5RS092XDJ01 Fan type & quantity Propeller(direct) x 1 Fan speeds H/L RPM 770 Air flow H/L m3/hr 1400 Sound power level H/L dB(A) 64 Sound pressure level
(4)
H/L dB(A) 54 Dimensions WxHxD mm 760x245x545 Weight kg 35 Package dimensions WxHxD mm 880x310x610 Packaged weight kg 38 Units per pallet Units 12 units per pallet Stacking height units 3 levels Refrigerant type R410A Refrigerant chargless distance kg/m 0.7kg/7.5m Additional charge per 1 meter g/m No need
Connections between
units
Liquid line In.(mm) 1/4”(6.35) Suction line In.(mm) 3/8”(9.53) Max.tubing length m. Max.15
Max.height difference m. Max. 10 Operation control type Remote control Heating elements kW Others
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
2. PRODUCT DATA SHEET
2-2
PRODUCT DATA SHEET
Revision Y05-01 Service Manual - Delta DCI
Model Indoor Unit DE LTA 25 Model Outdoor Unit DCR 25 Installation Method of Pipe Flared
Characteristics Units Cooling Heating
Capacity
(1)
Btu/hr 8530(4440-10240) 9550(4774-11940)
kW 2.5(1.3-3.0) 2.8(1.4-3.5)
Power input
(1)
kW 0.75 0.82
EER (Cooling) or COP(Heating)
(1)
W/W 3.33 3.41 Energy efficiency class A B Power supply V/Ph/Hz 220-240V/Single/50Hz Rated current A 3.2 3.6 Starting current A 10 Circuit breaker rating A 12
INDOOR
Fan type & quantity Crossflow x 1 Fan speeds H/M/L RPM 1200/1050/850 Air flow
(2)
H/M/L m3/hr 420/350/270 External static pressure Min-Max Pa 0 Sound power level
(3)
H/M/L dB(A) 52/48/45 Sound pressure level
(4)
H/M/L dB(A) 39/35/32 Moisture removal l/hr 1 Condensate drain tube I.D mm 16 Dimensions WxHxD mm 680x250x185 Weight kg 7 Package dimensions WxHxD mm 740x265x320 Packaged weight kg 10 Units per pallet units 36 units per pallet Stacking height units 9 levels
OUTDOOR
Refrigerant control EEV Compressor type, model Rotary, Panasonic 5RS092XDJ01 Fan type & quantity Propeller(direct) x 1 Fan speeds H/L RPM 760 Air flow H/L m3/hr 1390 Sound power level H/L dB(A) 64 Sound pressure level
(4)
H/L dB(A) 54 Dimensions WxHxD mm 760x245x545 Weight kg 36 Package dimensions WxHxD mm 880x310x610 Packaged weight kg 39 Units per pallet Units 12 units per pallet Stacking height units 3 levels Refrigerant type R410A Refrigerant chargless distance kg/m 0.85kg/7.5m Additional charge per 1 meter g/m No need
Connections between
units
Liquid line In.(mm) 1/4”(6.35) Suction line In.(mm) 3/8”(9.53) Max.tubing length m. Max.15
Max.height difference
m. Max. 10
Operation control type Remote control Heating elements kW Others
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
2-3
PRODUCT DATA SHEET
Revision Y05-01Service Manual - Delta DCI
Model Indoor Unit DE LTA 35 Model Outdoor Unit DCR 35 Installation Method of Pipe Flared
Characteristics Units Cooling Heating
Capacity
(1)
Btu/hr 11940(4440-13990) 12280(5115-13990)
kW 3.5(1.3-4.1) 3.6(1.65-4.1)
Power input
(1)
kW 1.03 1.05
EER (Cooling) or COP(Heating)
(1)
W/W 3.39 3.43 Energy efficiency class A B Power supply V/Ph/Hz 220-240V/Single/50Hz Rated current A 4.9 4.8 Starting current A 10.5 Circuit breaker rating A 15
INDOOR
Fan type & quantity Crossflow x 1 Fan speeds H/M/L RPM 1200/1000/850 Air flow
(2)
H/M/L m3/hr 550/450/350 External static pressure Min-Max Pa 0 Sound power level
(3)
H/M/L dB(A) 56/46/42 Sound pressure leve
l
(4)
H/M/L dB(A) 39/33/29 Moisture removal l/hr 1.5 Condensate drain tube I.D mm 16 Dimensions WxHxD mm 840x250x185 Weight kg 8 Package dimensions WxHxD mm 930x265x320 Packaged weight kg 11 Units per pallet units 36 units per pallet Stacking height units 9 levels
OUTDOOR
Refrigerant control EEV Compressor type, model Rotary, Panasonic 5RS102XAB Fan type & quantity Propeller(direct) x 1 Fan speeds H/L RPM 760 Air flow H/L m3/hr 1390 Sound power level H/L dB(A) 65 Sound pressure level
(4)
H/L dB(A) 55 Dimensions WxHxD mm 760x245x545 Weight kg 37 Package dimensions WxHxD mm 880x310x610 Packaged weight kg 40 Units per pallet Units 12 units per pallet Stacking height units 3 levels Refrigerant type R410A Refrigerant chargless distance kg/m 1.0kg/7.5m Additional charge per 1 meter g/m No need
Connections between units
Liquid line In.(mm) 1/4”(6.35) Suction line In.(mm) 3/8”(9.53) Max.tubing length m. Max.15
Max.height difference
m. Max. 10
Operation control type Remote control Heating elements kW No Others
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
2-4
PRODUCT DATA SHEET
Revision Y05-01 Service Manual - Delta DCI
Model Indoor Unit DELTA 50 DCI Model Outdoor Unit DCR 50 R410A Installation Method of Pipe Flared
Characteristics Units Cooling Heating
Btu/hr 17060(4780-18770) 18080(5460-20130)
Capacity
(1)
kW 5.0(1.4-5.5) 5.3(1.6-5.9)
Power input
(1)
kW 1.56 1.55
EER (Cooling) or COP(Heating)
(1)
W/W 3.21 3.42 Energy efficiency class A B Power supply V/Ph/Hz 220-240V/Single/50Hz Rated current A 7.0 6.9 Starting current A 10.5 Circuit breaker rating A 20
Fan type & quantity Crossflow x 1 Fan speeds H/M/L RPM 1230/1100/900 Air flow
(2)
H/M/L m3/hr 720/620/480
External static pressure Min-Max Pa
0
Sound power level
(3)
H/M/L dB(A) 56/54/47
Sound pressure level
(4)
H/M/L dB(A) 44/41/34 Moisture removal l/hr 2 Condensate drain tube I.D mm 16 Dimensions WxHxD mm 900x205x295 Weight kg
11 Package dimensions WxHxD mm 960x270x360 Packaged weight kg 14 Units per pallet units 24 units per pallet
INDOOR
Stacking height units 8 levels Refrigerant control EEV Compressor type, model Scroll, PANASONIC 5CS130XCC03 Fan type & quantity Propeller(direct) x 1 Fan speeds H/L RPM 920 Air flow H/L m3/hr 2160 Sound power level H/L dB(A) 63 Sound pressure level
(4)
H/L dB(A) 53 Dimensions WxHxD mm 795x290x610 Weight kg 38 Package dimensions WxHxD mm 945x395x655 Packaged weight kg 41 Units per pallet Units 9 units per pallet Stacking height units 3 levels Refrigerant type R410A Refrigerant chargless distance kg/m 1.26kg/7.5m Additional charge per 1 meter g/m No need
Liquid line In.(mm) 1/4"(6.35) Suction line In.(mm) 1/2"(12.7) Max.tubing length m. Max.15
OUTDOOR
Connections between
units
Max.height difference m. Max. 10 Operation control type Remote control Heating elements kW Others
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
3-1
RATING CONDITIONS
Revision Y05-01Service Manual - Delta DCI
3. RATING CONDITIONS
Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units).
Cooling:
Indoor: 27
o
C DB 19oC WB
Outdoor: 35
o
C DB
Heating:
Indoor: 20
o
C DB
Outdoor: 7
o
C DB 6oC WB
3.1 Operating Limits
3.1.1 R410A
Indoor Outdoor
Cooling
Upper limit
32oC DB 23oC WB 46oC DB
Lower limit
21oC DB 15oC WB 10oC DB
Heating
Upper limit
27oC DB 24oC DB 18oC WB
Lower limit
10oC DB -15oC DB -16oC WB
Voltag e
198 – 264 V
4-1
OUTLINE DIMENSIONS
Revision Y05-01Service Manual - Delta DCI
4. OUTLINE DIMENSIONS
4.1 Indoor Unit: Delta 22, 25 DCI
4.2
Indoor Unit: Delta 35 DCI
185
250
680
AIR OUTLET
AIR INTAKE
AIR INTAKE
INDOOR UNIT OUTLINE
244
160
118
TUBING WALL OPENING (FOR REAR LEFT ROUTING)
670
41
40
TUBING WALL OPENING
(FOR REAR ROUTING)
380
52
80
141
MOUNTING TEMPLATE TO BE USED FOR LOCATION OF INDOOR UNIT ON THE WALL
58
Min50
306
46
CEILING
185
250
840
AIR OUTLET
AIR INTAKE
830
160
AIR INTAKE
TUBING WALL OPENING
(FOR REAR ROUTING)
TUBING WALL OPENING (FOR REAR LEFT ROUTING)
504
137
50
40
52
MOUNTING TEMPLATE TO BE USED FOR LOCATION OF INDOOR UNIT ON THE WALL
CEILING
406
172
70
59
Min50
244
80
INDOOR UNIT OUTLINE
4-2
OUTLINE DIMENSIONS
Revision Y05-01 Service Manual - Delta DCI
4.3 Indoor Unit: 50 DCI
4.4 Outdoor Unit: DCR 22, 25, 35 DCI
TUBING WALL OPENING
(FOR REAR ROUTING)
205
AIR OUTLET
AIR INTAKE
AIR INTAKE
295
900
TUBING WALL OPENING (FOR REAR LEFT ROUTING)
295
80
900
40
440
50
INDOOR UNIT OUTLINE
CEILING
MOUNTING TEMPLATE TO BE USED FOR LOCATION OF INDOOR UNIT ON THE WALL
483
65
Min50
65
AI R OUTL E T
AI R I NTAKE
4-3
OUTLINE DIMENSIONS
Revision Y05-01Service Manual - Delta DCI
4.5 Outdoor Unit: DCR 50 DCI
5-1
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-02Service Manual - Delta DCI
5. PERFORMANCE DATA
5.1 Delta 22 DCI
5.1.1 Cooling Capacity (kW) – Run Mode
230[V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB/WB TEMPERATURE [
o
C]
OD COIL
ENTERING AIR DB
TEMPERATURE
[
o
C]
DATA
22/15 24/17 27/19 29/21 32/23
-10 - 20
(protection range)
TC 80 - 110 % of nominal SC 80 - 105 % of nominal
PI 25 - 50 % of nominal
25
TC 2.12 2.26 2.40 2.54 2.68 SC 1.62 1.65 1.69 1.72 1.75
PI 0.52 0.53 0.54 0.55 0.56
30
TC 2.02 2.16 2.30 2.44 2.58 SC 1.58 1.61 1.65 1.68 1.71
PI 0.58 0.59
0.60
0.61 0.62
35
TC 1.92 2.06
2.20
2.34 2.48
SC 1.54 1.58 1.61 1.64 1.68
PI 0.64 0.65
0.66
0.67 0.68
40
TC 1.82 1.96
2.10
2.24 2.38
SC 1.50 1.54 1.57 1.60 1.64
PI 0.70 0.71 0.72 0.73 0.74
46
TC 1.70 1.84 1.98 2.12 2.26 SC 1.46 1.49 1.52 1.56 1.59
PI 0.77 0.78 0.79 0.80 0.81
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB – Dry Bulb Temp., (oC) ID – Indoor OD – Outdoor
5.1.2 Capacity Correction Factors
Coo ling Cap acity Ratio Vs . Outdoor T emperatu re
0.50
0.60
0.70
0.80
0.90
1.00
1.10
1.20
20 25 30 35 40 45
Outdoor Temperature [deg C]
Capacity Ratio
5-2
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-02 Service Manual - Delta DCI
5.1.3 Heating Capacity (kW) - Run Mode
230[V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB TEMPERATURE [oC]
OD COIL
ENTERING
AIR DB/WB
TEMPERATURE
[
o
C]
DATA 15 20 25
-15/-16
TC 1.59 1.48 1.37
PI 0.44 0.48 0.53
-10/-12
TC 1.77 1.66 1.55
PI 0.53 0.57 0.62
-7/-8
TC 1.91 1.80 1.68
PI 0.60 0.64 0.68
-1/-2
TC 1.97 1.86 1.75
PI 0.63 0.67 0.72
2/1
TC 2.02 1.91 1.80
PI 0.65
0.70
0.74
7/6
TC 2.61
2.50
2.39
PI 0.69
0.73
0.77
10/9
TC 2.75
2.64
2.53
PI 0.73 0.77 0.82
15/12
TC 2.90 2.79 2.68
PI 0.77 0.81 0.86
15-24
TC 85 - 105 % of nominal
(Protection Range)
PI 80 - 120 % of nominal
LEGEND
TC – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB – Dry Bulb Temp., (oC) ID – Indoor OU – Outdoor
5.1.4 Capacity Correction Factors
Hea ting C apacity R atio Vs. Outdoo r Tem pera ture
0.50
0.60
0.70
0.80
0.90
1.00
1.10
1.20
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [deg C]
Capacit y Ration
5-3
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-02Service Manual - Delta DCI
5.2 Delta 25 DCI
5.2.1 Cooling Capacity (kW) – Run Mode
230[V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB/WB TEMPERATURE [
o
C]
OD COIL
ENTERING AIR DB
TEMPERATURE
[
o
C]
DATA
22/15 24/17 27/19 29/21 32/23
-10 - 20
(protection range)
TC 80 - 110 % of nominal SC 80 - 105 % of nominal
PI 25 - 50 % of nominal
25
TC 2.41 2.57 2.73 2.89 3.05 SC 1.67 1.71 1.74 1.77 1.81
PI 0.59 0.60 0.61 0.62 0.63
30
TC 2.30 2.46 2.62 2.77 2.93 SC 1.63 1.67 1.70 1.73 1.77
PI 0.66 0.67
0.68
0.69 0.70
35
TC 2.18 2.34
2.50
2.66 2.82
SC 1.59 1.63 1.66 1.69 1.73
PI 0.73 0.74
0.75
0.76 0.77
40
TC 2.07 2.23
2.39
2.54 2.70
SC 1.55 1.59 1.62 1.65 1.69
PI 0.80 0.81 0.82 0.83 0.84
46
TC 1.93 2.09 2.25 2.41 2.56 SC 1.50 1.54 1.57 1.61 1.64
PI 0.88 0.89 0.90 0.91 0.92
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB – Dry Bulb Temp., (oC) ID – Indoor OD – Outdoor
5.2.2 Capacity Correction Factors
Coo ling Cap acity Ratio Vs . Outdoor T emperatu re
0.50
0.60
0.70
0.80
0.90
1.00
1.10
1.20
20 25 30 35 40 45
Outdoor Temperature [deg C]
Capacity Ratio
5-4
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-02 Service Manual - Delta DCI
5.2.3 Heating Capacity (kW) - Run Mode
230[V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB TEMPERATURE [oC]
OD COIL
ENTERING
AIR DB/WB
TEMPERATURE
[
o
C]
DATA 15 20 25
-15/-16
TC 1.78 1.66 1.53
PI 0.49 0.54 0.59
-10/-12
TC 1.98 1.86 1.73
PI 0.59 0.64 0.69
-7/-8
TC 2.14 2.01 1.89
PI 0.67 0.72 0.77
-1/-2
TC 2.21 2.09 1.96
PI 0.71 0.76 0.81
2/1
TC 2.26 2.14 2.01
PI 0.73
0.78
0.83
7/6
TC 2.92
2.80
2.68
PI 0.77
0.82
0.87
10/9
TC 3.09
2.96
2.84
PI 0.82 0.87 0.92
15/12
TC 3.25 3.12 3.00
PI 0.86 0.91 0.96
15-24
TC 85 - 105 % of nominal
(Protection Range)
PI 80 - 120 % of nominal
LEGEND
TC – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB – Dry Bulb Temp., (oC) ID – Indoor OU – Outdoor
5.2.4 Capacity Correction Factors
Hea ting C apacity R atio Vs. Outdoo r Tem pera ture
0.50
0.60
0.70
0.80
0.90
1.00
1.10
1.20
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [deg C]
Capacit y Ration
5-5
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-02Service Manual - Delta DCI
5.3 Delta 35 DCI
5.3.1 Cooling Capacity (kW) - Run Mode
230[V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB/WB TEMPERATURE [
o
C]
OD COIL
ENTERING AIR DB
TEMPERATURE [
o
C]
DATA
22/15 24/17 27/19 29/21 32/23
-10 - 20
(protection range)
TC 80 - 110 % of nominal SC 80 - 105 % of nominal
PI 25 - 50 % of nominal
25
TC 3.38 3.60 3.82 4.04 4.26 SC 2.54 2.59 2.64 2.69 2.74
PI 0.81 0.83 0.84 0.86 0.87
30
TC 3.22 3.44 3.66 3.88 4.10 SC 2.48 2.53 2.58 2.63 2.68
PI 0.90 0.92
0.94
0.95 0.97
35
TC 3.06 3.28
3.50
3.72 3.94
SC 2.42 2.47 2.52 2.57 2.62
PI 1.00 1.01
1.03
1.05 1.06
40
TC 2.90 3.12
3.34
3.56 3.78
SC 2.36 2.41 2.46 2.51 2.56
PI 1.09 1.11 1.12 1.14 1.16
46
TC 2.70 2.92 3.15 3.37 3.59 SC 2.28 2.34 2.39 2.44 2.49
PI 1.21 1.22 1.24 1.25 1.27
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB – Dry Bulb Temp., (oC) ID – Indoor OD – Outdoor
5.3.2 Capacity Correction Factors
Coo ling Cap acity Ratio Vs . Outdoor T emperatu re
0.50
0.60
0.70
0.80
0.90
1.00
1.10
1.20
20 25 30 35 40 45
Outdoor Temperature [deg C]
Capacity Ratio
5-6
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-02 Service Manual - Delta DCI
5.3.3 Heating Capacity (kW) - Run Mode
230[V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB TEMPERATURE [oC]
OD COIL
ENTERING
AIR DB/WB
TEMPERATURE
[oC]
DATA 15 20 25
-15/-16
TC 2.29 2.13 1.97
PI 0.63 0.69 0.76
-10/-12
TC 2.55 2.39 2.23
PI 0.76 0.82 0.89
-7/-8
TC 2.75 2.58 2.42
PI 0.86 0.92 0.98
-1/-2
TC 2.84 2.68 2.52
PI 0.91 0.97 1.03
2/1
TC 2.91 2.75 2.59
PI 0.94
1.00
1.07
7/6
TC 3.76
3.60
3.44
PI 0.99
1.05
1.11
10/9
TC 3.97
3.81
3.65
PI 1.04 1.11 1.17
15/12
TC 4.17 4.01 3.85
PI 1.10 1.17 1.23
15-24
TC 85 - 105 % of nominal
(Protection Range)
PI 80 - 120 % of nominal
LEGEND
TC – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB – Dry Bulb Temp., (oC) ID – Indoor OU – Outdoor
5.3.4 Capacity Correction Factors
Hea ting C apacity R atio Vs. Outdoo r Tem pera ture
0.50
0.60
0.70
0.80
0.90
1.00
1.10
1.20
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [deg C]
Capacit y Ration
5-7
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-02Service Manual - Delta DCI
5.4 Delta 50 DCI
5.4.1 Cooling Capacity (kW) – Run Mode
230[V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB/WB TEMPERATURE [
o
C]
OD COIL
ENTERING AIR DB
TEMPERATURE
[oC]
DATA
22/15 24/17 27/19 29/21 32/23
-10 - 20
(protection range)
TC 80 - 110 % of nominal SC 80 - 105 % of nominal
PI 25 - 50 % of nominal
25
TC 4.93 5.22 5.51 5.80 6.09 SC 3.68 3.73 3.79 3.84 3.90
PI 1.18 1.21 1.23 1.26 1.29
30
TC 4.67 4.96 5.25 5.54 5.83 SC 3.53 3.59 3.64 3.70 3.75
PI 1.34 1.37
1.40
1.42 1.45
35
TC 4.42 4.71
5.00
5.29 5.58
SC 3.39 3.45 3.50 3.55 3.61
PI 1.51 1.53
1.56
1.59 1.61
40
TC 4.17 4.46
4.75
5.04 5.33
SC 3.25 3.30 3.36 3.41 3.47
PI 1.67 1.70 1.72 1.75 1.78
46
TC 3.86 4.15 4.44 4.73 5.02 SC 3.08 3.13 3.18 3.24 3.29
PI 1.87 1.89 1.92 1.95 1.97
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB – Dry Bulb Temp., (oC) ID – Indoor OD – Outdoor
5.4.2 Capacity Correction Factors
Coo ling Cap acity Ratio Vs . Outdoor T emperatu re
0.50
0.60
0.70
0.80
0.90
1.00
1.10
1.20
20 25 30 35 40 45
Outdoor Temperature [deg C]
Capacity Ratio
5-8
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-02 Service Manual - Delta DCI
5.4.3 Heating Capacity (kW) - Run Mode
230[V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB TEMPERATURE [oC]
OD COIL
ENTERING
AIR DB/WB
TEMPERATURE
[
o
C]
DATA 15 20 25
-15/-16
TC 3.37 3.14 2.90
PI 0.93 1.02 1.12
-10/-12
TC 3.76 3.52 3.28
PI 1.12 1.22 1.31
-7/-8
TC 4.04 3.81 3.57
PI 1.26 1.36 1.45
-1/-2
TC 4.18 3.95 3.71
PI 1.34 1.43 1.53
2/1
TC 4.28 4.04 3.81
PI 1.38
1.48
1.57
7/6
TC 5.54
5.30
5.06
PI 1.46
1.55
1.64
10/9
TC 5.84
5.60
5.37
PI 1.54 1.64 1.73
15/12
TC 6.14 5.91 5.67
PI 1.63 1.72 1.82
15-24
TC 85 - 105 % of nominal
(Protection Range)
PI 80 - 120 % of nominal
LEGEND
TC – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB – Dry Bulb Temp., (oC) ID – Indoor OU – Outdoor
5.4.4 Capacity Correction Factors
Hea ting C apacity R atio Vs. Outdoo r Tem pera ture
0.50
0.60
0.70
0.80
0.90
1.00
1.10
1.20
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [deg C]
Capacit y Ration
5-9
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-02Service Manual - Delta DCI
5.5
Capacity Correction Factor Due to Tubing Length
5.5.1 Delta 22 DCI : Cooling
5.5.2 Heating
0.93
0.94
0.95
0.96
0.97
0.98
0.99
1.00
1.01
3579111315
Tubing Length[m]
Capacity Ratio
0.92
0.93
0.94
0.95
0.96
0.97
0.98
0.99
1.00
1.01
3579111315
Tubing Length[m]
Capacity Ratio
5-10
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-02 Service Manual - Delta DCI
5.5.3 Delta 25 DCI : Cooling
5.5.4 Heating
0.90
0.91
0.92
0.93
0.94
0.95
0.96
0.97
0.98
0.99
1.00
1.01
3 5 7 9 11 13 15
Tubing Length[m]
Capacity Ratio
0.84
0.86
0.88
0.90
0.92
0.94
0.96
0.98
1.00
1.02
3579111315
Tubing Length[m]
Capacity Ratio