Electra WNG 50 DCI, WNG 80 DCI, DCI 50, DCI 60, DCI 72 Service Manual

...

WNG DC Inverter Series

CONTENTS
Indoor Units Outdoor Units
WNG 50 DCI DCI 50 WNG 60 DCI DCI 60
WNG 72 DCI
WNG 80 DCI DCI 80
DCI 72 DCI 72 Z
SM WNGDCI 2-E.4 GB
REFRIGERANT
NOVEMBER − 2008
HEAT PUMP

LIST OF EFFECTIVE PAGES

CONTENTS
LIST OF EFFECTIVE PAGES
Note: Changes in the pages are indicated by a “Revision#” in the footer of each effected page
(when none indicates no changes in the relevant page). All pages in the following list represent effected/ non effected pages divided by chapters.
Dates of issue for original and changed pages are:
Original ....... 0 ........September 2006
Total number of pages in this publication is 107 consisting of the following:
Page No.
Title ....................... 4
A ........................... 4
i ............................. 4
1-1 - 1-4 ................ 4
2-1 - 2-4 ................ 4
3-1 ........................ 4
4-1 - 4-3 ................ 4
5-1 - 5-17 .............. 4
6-1 - 6-3 ................ 4
7-1 ........................ 4
8-1-8-3 .................. 4
9-1-9-2 .................. 4
10-1-10-2 .............. 4
11-1 ....................... 4
12-1-12-23 ............ 4
13-1-13-18 ............ 4
14-1-14-12 ............ 4
15-1-15-10 ............ 4
Appendix -A ...........4
Revision No. #
Page No.
Revision No. #
Page No.
Revision No. #
● Zero in this column indicates an original page.
*Due to constant improvements please note that the data on this service manual can be modified with out notice. **Photos are not contractual
A
SM WNGDCI 2-E.4 GB

TABLE OF CONTENTS

Table of Contents
1. INTRODUCTION ...................................................................................................1-1
2. PRODUCT DATA SHEET ......................................................................................2-1
3. RATING CONDITIONS ..........................................................................................3-1
4. OUTLINE DIMENSIONS .......................................................................................4-1
5. PERFORMANCE DATA & PRESSURE CURVES ...............................................5-1
6. SOUND LEVEL CHARACTERISTICS ..................................................................6-1
7. ELECTRICAL DATA ..............................................................................................7-1
8. WIRING DIAGRAMS .............................................................................................8-1
9. REFRIGERATION DIAGRAMS .............................................................................9-1
10. ELECTRICAL CONNECTIONS .............................................................................10-1
11. TUBING CONNECTIONS ......................................................................................11-1
12. CONTROL SYSTEM .............................................................................................12-1
13. TROUBLESHOOTING ..........................................................................................13-1
14. EXPLODED VIEWS AND SPARE PARTS LISTS .................................................14-1
15. APPENDIX A .........................................................................................................15-1
SM WNGDCI 2-E.4 GB
i
1. INTRODUCTION
CONTENTS
1.1 General
The new WNG DCI INVERTER split wall mounted range has expanded, comprising the following RC (heat pump) models:
WNG 50
WNG 60
WNG 72
WNG 80
The indoor WNG units are available as LED or LCD display types, featuring esthetic design, compact dimensions, and low noise operation.
1.2 Main Features

INTRODUCTION

The WNG DCI series benefits from the most advanced technological innovations, namely:
● DC inverter technology.
● R410A.
● High COP.
● Pre-Charged units up to the max’ allowing tubing distance.
● Networking system connectivity.
● A dry contact for clock or power shedding functions (configurable).
● Base heater connection.
● Cooling operation at outdoor temperature down to -10°C.
● Heating operation at outdoor temperature down to -15°C.
● Supports Indoor Air Quality features, such as – Ionizer and Active Electrostatic Filter.
● Indoor large diameter cross flow fan, allowing low noise level operation.
● Bended indoor coil with treated aluminum fins and coating for improved efficiency.
● Easy access to the interconnecting tubing and wiring connections, so that removing the front grill or casing is not necessary.
SM WNGDCI 2-E.4 GB
● Refrigerant pipes can be connected to the indoor unit from 5 different optional directions.
● Automatic treated air sweep.
● Low indoor and outdoor noise levels.
● Easy installation and service.
1-1
INTRODUCTION
CONTENTS
1.3 Indoor Unit
The indoor unit is wall mounted, and can be easily fitted to many types of residential and commercials applications.
Indoor Unit features:
Feature WNG 50 WNG 60 WNG 72 / 80
Display LCD or LED LCD
Ionizer YES
ESF YES
Fresh air YES NO
Indoor fan motor Variable speed (PG)
Horizontal motorized louver YES
Vertical motorized louver YES
Heating element NO
M2L Cable port YES
Dry contact Presence detector or (jumper selected) power shedding
1.4 Filtration
The WNG DCI INV series presents several types of air filters:
Easily accessible, and re-usable pre-filters (mesh)
Pre-charged electrostatic filter (disposable)
Active carbon filter (disposable)
ESF. Active Electro Static re-usable filter (optional)
1.5 Ionizer (Optional)
A special design Ionizer protected by unique patents integrated into the indoor unit, generating negative ions to the room providing comfort and upgraded indoor air quality.
1.6 Control
The microprocessor indoor controller, and an infrared remote control, supplied as standard, provides complete operating function and programming. Remote controllers: RC-2/3/4/5/7, RC-4i-1, RCW, μBMS. Networking system Airconet version 4.2 and up, MIU SW version H8 and up.
1-2
SM WNGDCI 2-E.4 GB
1.7 Outdoor Unit
CONTENTS
The WNG DCI INV outdoor units can be installed as floor or wall mounted units by using a wall supporting bracket. The metal sheets are protected from corrosion paint work allowing long life resistance. All outdoor units are pre-charged. For further information please refer to the Product Data Sheet, Chapter 2.
Outdoor Unit Feature
Feature DCI 50 DCI 60 DCI 72 / 72Z / 80
Display 3 LED’s
Base Heater Optional Outdoor Fan Variable speed DC Inverter
M2L cable Port No Yes
Night No Yes
STBY No Yes
INTRODUCTION
Power Shedding No Yes
Alarm No Yes
1.8 Tubing Connections
Flare type interconnecting tubing to be produced on site. For further details please refer to the Installation Manual, Appendix A.
1.9 Accessories
Item Description
MIU (WNG) MODBUS interface unit
RS485 Adapter
Base Heater
M2L cable Port
To be used as an interface
with RCW or μBMS remote
controllers
1.10 Inbox Documentation
SM WNGDCI 2-E.4 GB
Each unit is supplied with its own installation and operation manuals.
1-3
INTRODUCTION
CONTENTS
1.11 Matching Table
1.11.1 R410A
OUTDOOR UNITS
INDOOR UNITS
MODEL REFR”
DCI 50 R410A
DCI 60 R410A
DCI 72
R410A
DCI 72Z
DCI 80 R410A
WNG 50 DCI WNG 60 DCI WNG 72 DCI WNG 80 DCI
1-4
SM WNGDCI 2-E.4 GB

PRODUCT DATA SHEET

CONTENTS
2. PRODUCT DATA SHEET
2.1 WNG 50 DCI
Model Indoor Unit WNG 50
Model Outdoor Unit DCI 50 Installation Method of Pipe Flared
Characteristics Units Cooling Heating
Capacity
Power input EER (Cooling) or COP(Heating)
(1)
(1)
(1)
Energy efficiency class A A Power supply V/Ph/Hz 220-240V/Single/50Hz Rated current A 6.6 7.5 Starting current A 10.5 Circuit breaker rating A 20
Fan type & quantity Crossflow x 1 Fan speeds H/M/L RPM 1200/1050/900 Air flow
(2)
H/M/L m3/hr 850/760/620 External static pressure Min-Max Pa 0 Sound power level Sound pressure level
(3)
(4)
H/M/L dB(A) 55/51/47
H/M/L dB(A) 43/39/34 Moisture removal l/hr 2 Condenstate drain tube I.D mm 16
INDOOR
Dimensions WxHxD mm 1060x295x210 Weight kg 15 Package dimensions WxHxD mm 1125x360x280 Packaged weight kg 18 Units per pallet units 16 units per pallet Stacking height units 8 levels Refrigerant control EEV Compressor type,model Scroll,Panasonic 5CS130XCC03 Fan type & quantity Propeller(direct) x 1 Fan speeds H/L RPM 920 Air flow H/L m3/hr 2160 Sound power level H/L dB(A) 63 Sound pressure level
(4)
H/L dB(A) 53 Dimensions WxHxD mm 795x610x290 Weight kg 39 Package dimensions WxHxD mm 945x655x395 Packaged weight kg 43 Units per pallet Units 9 units per pallet
OUTDOOR
Stacking height units 3 levels Refrigerant type R410A Refrigerant chargless distance kg/m 1.50/7.5 Additional charge per 1 meter g/m No need
Liquid line In.(mm) 1/4”(6.35)
Connections between units
Suction line In.(mm) 1/2”(12.7) Max.tubing length m. Max.30
Max.height difference m. Max. 10 Operation control type Remote control Heating elements kW Others
Btu/hr 17060(5120-20470) 20470(5120-25930)
kW 5.00(1.50-6.00) 6.00(1.50-7.60) kW 1.46(0.50-2.00) 1.66(0.45-2.20)
W/W 3.42 3.61
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
SM WNGDCI 2-E.4 GB
2-1
PRODUCT DATA SHEET
CONTENTS
2.2 WNG 60 DCI
Model Indoor Unit WNG-60 Model Outdoor Unit DCI60
Installation Method of Pipe Flared
Characteristics Units Cooling Heating
Capacity
Power input EER (Cooling) or COP(Heating)
(1)
(1)
(1)
Energy efficiency class B B Power supply V/Ph/Hz 220-240V/Single/50Hz Rated current A 8.9 8.6 Starting current A 10.5 Circuit breaker rating A 20
Fan type & quantity Crossflow x 1 Fan speeds H/M/L RPM 1250/1100/1000 Air flow
(2)
H/M/L m3/hr 900/760/620 External static pressure Min-Max Pa 0 Sound power level
(3)
Sound pressure level
(4)
H/M/L dB(A) 56/53/48
H/M/L dB(A) 45/40/34 Moisture removal l/hr 2 Condenstate drain tube I.D mm 16
INDOOR
Dimensions WxHxD mm 1060x295x210 Weight kg 15 Package dimensions WxHxD mm 1125x360x280 Packaged weight kg 18 Units per pallet units 16 units per pallet Stacking height units 8 levels Refrigerant control EEV Compressor type,model Scroll,Panasonic 5CS130XCC03 Fan type & quantity Propeller(direct) x 1 Fan speeds H/L RPM 820 Air flow H/L m3/hr 2860 Sound power level H/L dB(A) 65 Sound pressure level
(4)
H/L dB(A) 55 Dimensions WxHxD mm 846x690x302 Weight kg 46 Package dimensions WxHxD mm 990x770x430 Packaged weight kg 50 Units per pallet Units 9 units per pallet
OUTDOOR
Stacking height units 3 levels Refrigerant type R410A Refrigerant chargless distance kg/m 1.65/7.5 Additional charge per 1 meter g/m No need
Liquid line In.(mm) 1/4”(6.35) Suction line In.(mm) 1/2”(12.7)
Connections between units
Max.tubing length m. Max.30
Max.height difference m. Max. 10
Operation control type Remote control Heating elements kW Others
Btu/hr 20470(5120-22860) 22180(5120-26950)
kW 6.00(1.50-6.70) 6.50(1.80-7.90) kW 1.99(0.50-2.20) 1.90(0.45-2.30)
W/W 3.02 3.42
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
2-2
SM WNGDCI 2-E.4 GB
PRODUCT DATA SHEET
CONTENTS
2.3 WNG 72 DCI
Model Indoor Unit WNG-DCI 72 Model Outdoor Unit GC-DCI 72
Installation Method of Pipe Flared
Characteristics Units Cooling Heating
Capacity
Power input EER (Cooling) or COP(Heating)
(1)
(1)
(1)
Energy efficiency class B C Power supply V/Ph/Hz 220-240V/Single/50Hz Rated current A 9.8 10.3 Starting current A 15 Circuit breaker rating A 20
Fan type & quantity Crossflow x 1 Fan speeds H/M/L RPM 1300/1150/1000 1350/1200/1050 Air flow
(2)
H/M/L m3/hr 950/800/650 1000/850/700 External static pressure Min-Max Pa 0 Sound power level Sound pressure level
(3)
(4 )
H/M/L dB(A) 60/54/47
H/M/L dB(A) 47/41/34 Moisture removal l/hr 2.5 Condenstate drain tube I.D mm 16
INDOOR
Dimensions WxHxD mm 1060x295x210 Weight kg 15 Package dimensions WxHxD mm 1115x350x260 Packaged weight kg 18 Units per pallet units 16 Stacking height units 8 levels Refrigerant control EEV Compressor type,model Two Rotary,Mitsubishi TNB220F Fan type & quantity Propeller(direct) x 1 Fan speeds H/L RPM 850 Air flow H/L m3/hr 3600 Sound power level H/L dB(A) 66 Sound pressure level
(4)
H/L dB(A) 56 Dimensions WxHxD mm 950x835x412 Weight kg 65.5 Package dimensions WxHxD mm 1080x910x477 Packaged weight kg 73 Units per pallet Units 2
OUTDOOR
Stacking height units 2 levels Refrigerant type R410A Refrigerant chargless distance kg/m 2.4kg/30m Additional charge per 1 meter g/m No Need
Liquid line In.(mm) 3/8"(9.53) Suction line In.(mm) 5/8"(15.88)
Connections between units
Max.tubing length m. Max.30 Max.height difference m. Max.15
Operation control type Remote control Heating elements (Option) kW Others
Btu/hr 23188(5100~25575) 25916(5100~30000)
kW 6.8(1.5-7.5) 7.6(1.5~8.8) kW 2.25(0.5-2.8) 2.35(0.45~3.0)
W/W 3.01 3.23
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
SM WNGDCI 2-E.4 GB
2-3
PRODUCT DATA SHEET
CONTENTS
2.4 WNG 72 / DCI 72Z
Model Indoor Unit WNG 72 DCI Model Outdoor Unit DCI 72 Z R410A
Installation Method of Pipe Flared
Characteristics Units Cooling Heating
Capacity
Power input EER (Cooling) or COP(Heating)
(4)
(4)
(4)
Energy efficiency class B C
Power supply
Rated current A 10.0 10.3 Power factor 0.97 0.97 Prated (IDU) W 60 Prated (IDU+ODU) W 3000 Starting current A 15 Circuit breaker rating A 20
Fan type & quantity Crossflow x 1 Fan speeds H/M/L RPM 1350/1150/1000 Air flow
(1)
H/M/L m3/hr 960/800/670 External static pressure Min Pa 0 Sound power level
(2)
Sound pressure level
(3)
H/M/L dB(A) 60/56/51
H/M/L dB(A) 47/43/38 Moisture removal l/hr 2.5 Condenstate drain tube I.D mm 16
INDOOR
Dimensions WxHxD mm 1060x295x210 Net Weight kg 15 Package dimensions WxHxD mm 1125x360x280 Packaged weight kg 18 Units per pallet units 16 Stacking height units 8 levels Refrigerant control EEV Compressor type,model Two Rotary,Sanyo(Sheny) C-7RVN153H0W Fan type & quantity Propeller(direct) x 1 Fan speeds H RPM 850 Air flow H m3/hr 3600 Sound power level H dB(A) 66 Sound pressure level
(3)
H dB(A) 56 Dimensions WxHxD mm 950x835x412 Net Weight kg 64.5 Package dimensions WxHxD mm 1080x910x477 Packaged weight kg 72 Units per pallet Units 4
OUTDOOR
Stacking height units 2 levels Refrigerant type R410A Standard charge kg(7.5m) 2.3kg
Additional charge
Liquid line In.(mm) 3/8”(9.53)
Connections between units
Suction line In.(mm) 5/8”(15.88) Max.tubing length m. 30
Max.height difference m. 15 Operation control type Remote control Heating elements(Option) kW Others
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
Btu/hr 23200(5120-25590) 24050(5120-30030)
kW 6.80(1.50-7.50) 7.05(1.50-8.80) kW 2.25(0.5-2.8) 2.19(0.45-3.0)
W/W 3.01 3.23
V 220-240 Ph Single Hz 50
7.5m≤Length≤20m:+0g;
20m≤Length≤30m:+300g
2-4
SM WNGDCI 2-E.4 GB
PRODUCT DATA SHEET
CONTENTS
2.5 WNG 80 DCI
Model Indoor Unit WNG- 80 Model Outdoor Unit DCI 80
Installation Method of Pipe Flared
Characteristics Units Cooling Heating
Capacity
Power input EER (Cooling) or COP(Heating)
(1)
(1)
(1)
Energy efficiency class B C Power supply V/Ph/Hz 220-240V/Single/50Hz Rated current A 11.3 11.5 Starting current A 15 Circuit breaker rating A 20
Fan type & quantity Crossflow x 1 Fan speeds H/M/L RPM 1350/1150/1000 1350/1200/1050 Air flow
(2)
H/M/L m3/hr 1250/1050/900 1250/1100/950 External static pressure Min-Max Pa N/A Sound power level Sound pressure level
(3)
(4)
H/M/L dB(A) 66/61/57
H/M/L dB(A) 51/48/44 Moisture removal l/hr 3 Condensate drain tube I.D mm 16
INDOOR
Dimensions WxHxD mm 1200x340x236 Weight kg 18.5 Package dimensions WxHxD mm 1305x430x325 Packaged weight kg 24 Units per pallet units 12 units per pallet Stacking height units 6 levels Refrigerant control EEV Compressor type, model Twin Rotary DC Inverter Mitsubishi TNB220F Fan type & quantity Propeller(direct) x 1 Fan speeds H/L RPM 850 Air flow H/L m3/hr 3600 Sound power level Sound pressure level
(3)
(4)
H/L dB(A) 66
H/L dB(A) 56 Dimensions WxHxD mm 950x412x835 Weight kg 66 Package dimensions WxHxD mm 1080x477x910 Packaged weight kg 73.5 Units per pallet Units 2 units per pallet
OUTDOOR
Stacking height units 3 levels Refrigerant type R410A Refrigerant chargless distance kg/m 2.75/30 Additional charge per 1 meter g/m No need
Liquid line In.(mm) 3/8”(9.53) Suction line In.(mm) 5/8”(15.88)
Connections between units
Max. tubing length m. Max.30
Btu/hr 26620(5100~30035) 29010 (5100~32420)
kW 7.8 (1.50~8.8) 8.5 (1.5~9.5) kW 2.59 (0.50~3.1) 2.65 (0.5~3.2)
W/W 3.01 3.21
Operation control type Remote control Heating elements kW Others
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
SM WNGDCI 2-E.4 GB
Max. height difference m. Max. 15
2-5
3. RATING CONDITIONS
CONTENTS
Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units).
Cooling:
Indoor: 27oC DB 19oC WB Outdoor: 35 oC DB
Heating:
Indoor: 20oC DB Outdoor: 7oC DB 6oC WB
3.1 Operating Limits
3.1.1 R410A

RATING CONDITIONS

Indoor Outdoor
Cooling
Heating
Upper limit
32oC DB 23oC WB 46oC DB
Lower limit 21oC DB 15oC WB -10oC DB Upper limit 27 Lower limit 10
Volta ge
o
C DB 24oC DB 18oC WB
o
C DB -15oC DB -16oC WB
198 – 264 V
SM WNGDCI 2-E.4 GB
3-1
4. OUTLINE DIMENSIONS
CONTENTS
4.1 Indoor Unit: WNG 50 / 60 / 72 DCI

OUTLINE DIMENSIONS

4.2
Outdoor Unit: DCI 50
SM WNGDCI 2-E.4 GB
4-1
OUTLINE DIMENSIONS
CONTENTS
4.3 Outdoor Unit: DCI 60
4.4 Indoor Unit: WNG 80
4-2
SM WNGDCI 2-E.4 GB
4.5 Outdoor Unit: DCI 72 / 72 Z / 80
CONTENTS
OUTLINE DIMENSIONS
SM WNGDCI 2-E.4 GB
4-3

PERFORMANCE DATA & PRESSURE CURVES

CONTENTS
5. PERFORMANCE DATA
5.1 WNG 50 / DCI 50
5.1.1 Cooling Capacity (kW) - Run Mode
230[V] : Indoor Fan at High Speed.
OD COIL
ENTERING AIR DB
TEMPERATURE [0C]
DATA
ID COIL ENTERING AIR DB/WB TEMPERATURE [0C]
22/15 24/17 27/19 29/21 32/23
-10 - 20
(protection range)
TC 80 - 110 % of nominal SC 80 - 105 % of nominal
PI 25 - 50 % of nominal
TC 4.93 5.22 5.51 5.80 6.09
25
SC 4.10 4.16 4.22 4.28 4.34
PI 1.10 1.13 1.15 1.18 1.20
TC 4.67 4.96 5.25 5.54 5.83
30
SC 3.94 4.00 4.06 4.12 4.18
PI 1.26 1.28
TC 4.42 4.71
35
SC 3.78 3.84 3.90 3.96 4.02
PI 1.41 1.44
TC 4.17 4.46
40
SC 3.62 3.68 3.74 3.80 3.86
PI 1.56 1.59 1.61 1.64 1.66
TC 3.86 4.15 4.44 4.73 5.02
46
SC 3.43 3.49 3.55 3.61 3.67
PI 1.75 1.77 1.80 1.82 1.85
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB Dry Bulb Temp., (oC) ID Indoor OD – Outdoor
1.31
5.00
1.46
4.75
1.33 1.36
5.29 5.58
1.48 1.51
5.04 5.53
5.1.2 Capacity Correction Factors
SM WNGDCI 2-E.4 GB
Cool ing Ca pacity Ratio Vs. Outdoor Temp era ture
1.20
1.10
1.00
0.90
0.80
0.70
Capaci ty Ration
0.60
0.50 20 25 30 35 40 45
Outdoor DB Temperature [ºC]
5-1
PERFORMANCE DATA & PRESSURE CURVES
CONTENTS
5.1.3 Heating Capacity (kW) - Run Mode)
230[V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB TEMPERATURE [0C]
OD COIL ENTERING
AIR DB/WB
TEMPERATURE [0C]
DATA 15 20 25
-15/-16
-10/-12
-7/-8
-1/-2
2/1
7/6
10/9
15/12
15-24
(Protection Range)
TC 2.73 2.34 1.94
PI 1.16 1.24 1.33
TC 3.60 3.21 2.82
PI 1.31 1.40 1.48
TC 4.26 3.87 3.47
PI 1.43 1.51 1.59
TC 4.59 4.19 3.80
PI 1.48 1.57 1.65
TC 4.81 4.41 4.02
PI 1.52
TC 6.39
PI 1.58
TC 6.72
PI 1.61 1.69 1.77
TC 7.06 6.66 6.27
PI 1.64 1.72 1.80
TC 85 - 105 % of nominal
PI 80 - 120 % of nominal
LEGEND
TC – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB Dry Bulb Temp., (oC) ID Indoor OD – Outdoor
1.60
6.00
1.66
6.33
1.69
5.61
1.74
5.94
5.1.4 Capacity Correction Factors
5-2
1.20
1.10
1.00
0.90
0.80
0.70
0.60
Capaci ty Rati on
0.50
0.40
Hea ti ng Ca pacity Ra tio Vs. Outdoor Te mpera ture
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [ºC]
SM WNGDCI 2-E.4 GB
PERFORMANCE DATA & PRESSURE CURVES
CONTENTS
5.2 WNG 60 / DCI 60
5.2.1 Cooling Capacity (kW) - Run Mode
230[V] : Indoor Fan at High Speed.
OD COIL
ENTERING AIR DB
TEMPERATURE [0C]
-10 - 20
(protection range)
25
30
35
40
(Protection Range)
46
(Protection Range)
ID COIL ENTERING AIR DB/WB TEMPERATURE [0C]
DATA
22/15 24/17 27/19 29/21 32/23
TC 80 - 110 % of nominal SC 80 - 105 % of nominal
PI 25 - 50 % of nominal TC 5.91 6.26 6.61 6.95 7.30 SC 4.64 4.71 4.78 4.85 4.92
PI 1.50 1.54 1.57 1.61 1.64 TC 5.61 5.96 6.30 6.65 7.00 SC 4.46 4.53 4.60 4.67 4.74
PI 1.71 1.75 TC 5.30 5.65
1.78
6.00
1.81 1.85
6.35 6.70
SC 4.28 4.35 4.42 4.49 4.56
PI 1.92 1.96 TC 5.00 5.35
1.99
5.70
2.02 2.06
6.05 6.39
SC 4.10 4.17 4.24 4.31 4.38
PI 2.13 2.17 2.20 2.23 2.27 TC 4.64 4.99 5.33 5.68 6.03 SC 3.88 3.95 4.02 4.09 4.16
PI 2.38 2.42 2.45 2.48 2.52
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB Dry Bulb Temp., (oC) ID Indoor OD – Outdoor
5.2.2 Capacity Correction Factors
Cool in g Ca pa ci ty Ra ti o Vs. Outdo or T emp era ture
1.20
1.10
1.00
0.90
0.80
0.70
Capaci ty Ration
0.60
0.50
20 25 30 35 40 45
Outdoor DB Temperature [ºC]
SM WNGDCI 2-E.4 GB
5-3
PERFORMANCE DATA & PRESSURE CURVES
CONTENTS
5.2.3 Heating Capacity (kW) - Run Mode
230[V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB TEMPERATURE [0C]
OD COIL ENTERING
AIR DB/WB
TEMPERATURE [0C]
DATA
15 20 25
-15/-16
-10/-12
-7/-8
-1/-2
2/1
7/6
10/9
15/12
15-24
(Protection Range)
TC 2.96 2.53 2.11
PI 1.33 1.42 1.52
TC 3.90 3.48 3.05
PI 1.50 1.60 1.69
TC 4.61 4.19 3.76
PI 1.63 1.73 1.82
TC 4.97 4.54 4.12
PI 1.70 1.79 1.82
TC 5.21 4.78 4.35
PI 1.74
TC 6.93
PI 1.81
TC 7.28
PI 1.84 1.93 2.03
TC 7.64 7.22 6.79
PI 1.87 1.97 2.06
TC 85 - 105 % of nominal
PI 80 - 120 % of nominal
LEGEND
TC – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB Dry Bulb Temp., (oC) ID Indoor OD – Outdoor
1.84
6.50
1.90
6.86
1.93
6.07
2.00
6.43
5.2.4 Capacity Correction Factors
5-4
1.20
1.10
1.00
0.90
0.80
0.70
0.60
Capacity Rati on
0.50
0.40
Heating Capa city Ratio Vs. Outdoor Tempera ture
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [ºC]
SM WNGDCI 2-E.4 GB
PERFORMANCE DATA & PRESSURE CURVES
CONTENTS
5.3 WNG 72 / DCI 72
5.3.1 Cooling Capacity (kW) - Run Mode
230[V] : Indoor Fan at High Speed.
OD COIL
ENTERING AIR DB
TEMPERATURE [0C]
-10 - 20
(protection range)
25
30
35
40
(Protection Range)
46
(Protection Range)
ID COIL ENTERING AIR DB/WB TEMPERATURE [0C]
DATA
TC
22/15 24/17 27/19 29/21 32/23
80 - 110 % of nominal
SC 80 - 105 % of nominal
PI 25 - 50 % of nominal
TC 6.70 7.09 7.49 7.88 8.28
SC 5.04 5.12 5.19 5.27 5.34
PI 1.70 1.74 1.78 1.82 1.85
TC 6.35 6.75 7.14 7.54 7.93
SC 4.85 4.92 5.00 5.07 5.15
PI 1.94 1.98 2.01 2.05 2.09
TC 6.01 6.41 6.80 7.19 7.59
SC 4.65 4.73 4.80 4.87 4.95
PI 2.17 2.21 2.25 2.29 2.33
TC 5.67 6.06 6.46 6.85 7.25
SC 4.45 4.53 4.60 4.68 4.75
PI 2.41 2.45 2.49 2.52 2.56
TC 5.26 5.65 6.04 6.44 6.83
SC 4.22 4.29 4.37 4.44 4.52
PI
2.69 2.73 2.77 2.81 2.85
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB Dry Bulb Temp., (oC) ID Indoor
OD – Outdoor
5.3.2 Capacity Correction Factors
Cool ing Ca pacity Ratio Vs. Outdoor Tempe ra ture
1.20
1.10
1.00
0.90
0.80
0.70
Capaci ty Ration
0.60
0.50
20 25 30 35 40 45
Outdoor DB Temperature [ºC]
SM WNGDCI 2-E.4 GB
5-5
PERFORMANCE DATA & PRESSURE CURVES
CONTENTS
5.3.3 Heating Capacity (kW) - Run Mode
230[V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB TEMPERATURE [0C]
OD COIL ENTERING
AIR DB/WB
TEMPERATURE [0C]
-15/-16
-10/-12
-7/-8
-1/-2
2/1
7/6
10/9
15/12
15-24
(Protection Range)
DATA
TC
PI 1.64 1.76 1.88
TC 4.57 4.07 3.57
PI 1.86 1.98 2.09
TC 5.40 4.90 4.40
PI 2.02 2.14 2.25
TC 5.81 5.31 4.81
PI 2.10 2.22 2.33
TC 6.09 5.59 5.09
PI 2.15 2.27 2.39
TC 8.10 7.60 7.10
PI 2.23 2.35 2.47
TC 8.52 8.02 7.52
PI 2.28 2.39 2.51
TC 8.94 8.44 7.94
PI 2.32 2.44 2.55
TC 85 - 105 % of nominal
PI
15 20 25
3.46 2.96 2.46
80 - 120 % of nominal
LEGEND
TC – Total Heating Capacity, kW PI – Power Input, kW
o
WB – Wet Bulb Temp., ( DB Dry Bulb Temp., (
o
C)
C) ID Indoor OD – Outdoor
5.3.4 Capacity Correction Factors
1.20
1.10
1.00
0.90
0.80
0.70
0.60
Capacity Rati on
0.50
0.40
Heating Capa city Ratio Vs. Outdoor Tempera ture
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [ºC]
5-6
SM WNGDCI 2-E.4 GB
PERFORMANCE DATA & PRESSURE CURVES
CONTENTS
5.4 WNG 72 / DCI 72Z
5.4.1 Cooling Capacity (kW) - Run Mode
230[V] : Indoor Fan at High Speed.
OD COIL
ENTERING AIR DB
TEMPERATURE [0C]
-10 - 20
(protection range)
25
30
35
40
(Protection Range)
46
(Protection Range)
ID COIL ENTERING AIR DB/WB TEMPERATURE [0C]
DATA
TC
22/15 24/17 27/19 29/21 32/23
80 - 110 % of nominal
SC 80 - 105 % of nominal
PI 25 - 50 % of nominal
TC 6.70 7.09 7.49 7.88 8.28
SC 5.04 5.12 5.19 5.27 5.34
PI 1.70 1.74 1.78 1.82 1.85
TC 6.35 6.75 7.14 7.54 7.93
SC 4.85 4.92 5.00 5.07 5.15
PI 1.94 1.98 2.01 2.05 2.09
TC 6.01 6.41 6.80 7.19 7.59
SC 4.65 4.73 4.80 4.87 4.95
PI 2.17 2.21 2.25 2.29 2.33
TC 5.67 6.06 6.46 6.85 7.25
SC 4.45 4.53 4.60 4.68 4.75
PI 2.41 2.45 2.49 2.52 2.56
TC 5.26 5.65 6.04 6.44 6.83
SC 4.22 4.29 4.37 4.44 4.52
PI
2.69 2.73 2.77 2.81 2.85
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB Dry Bulb Temp., (oC) ID Indoor
OD – Outdoor
5.4.2 Capacity Correction Factors
Cool ing Ca pacity Ratio Vs. Outdoor Tempe ra ture
1.20
1.10
1.00
0.90
0.80
0.70
Capaci ty Ration
0.60
0.50
20 25 30 35 40 45
Outdoor DB Temperature [ºC]
SM WNGDCI 2-E.4 GB
5-7
PERFORMANCE DATA & PRESSURE CURVES
CONTENTS
5.4.3 Heating Capacity (kW) - Run Mode
230[V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB TEMPERATURE [0C]
OD COIL ENTERING
AIR DB/WB
TEMPERATURE [0C]
-15/-16
-10/-12
-7/-8
-1/-2
2/1
7/6
10/9
15/12
15-24
(Protection Range)
DATA
TC
PI 1.53 1.64 1.75
TC 4.23 3.77 3.31
PI 1.73 1.84 1.95
TC 5.00 4.54 4.08
PI 1.88 1.99 2.10
TC 5.39 4.93 4.47
PI 1.96 2.07 2.17
TC 5.65 5.18 4.72
PI 2.01 2.12 2.22
TC 7.51 7.05 6.59
PI 2.08 2.19 2.30
TC 7.90 7.44 6.98
PI 2.12 2.23 2.34
TC 8.28 7.83 7.37
PI 2.16 2.27 2.38
TC 85 - 105 % of nominal
PI
15 20 25
3.21 2.75 2.28
80 - 120 % of nominal
LEGEND
TC – Total Heating Capacity, kW PI – Power Input, kW
o
WB – Wet Bulb Temp., ( DB Dry Bulb Temp., (
o
C)
C) ID Indoor OD – Outdoor
5.4.4 Capacity Correction Factors
1.20
1.10
1.00
0.90
0.80
0.70
0.60
Capacity Rati on
0.50
0.40
Heating Capa city Ratio Vs. Outdoor Tempera ture
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [ºC]
5-8
SM WNGDCI 2-E.4 GB
PERFORMANCE DATA & PRESSURE CURVES
CONTENTS
5.5 WNG 80 DCI / DCI 80
5.5.1 Cooling Capacity (kW) - Run Mode
230[V] : Indoor Fan at High Speed.
OD COIL
ENTERING AIR DB
TEMPERATURE [0C]
-10 - 20
(protection range)
25
30
35
40
(Protection Range)
46
(Protection Range)
ID COIL ENTERING AIR DB/WB TEMPERATURE [0C]
DATA
22/15 24/17 27/19 29/21 32/23
TC 80 - 110 % of nominal SC 80 - 105 % of nominal
PI 25 - 50 % of nominal TC 7.68 8.14 8.59 9.04 9.49 SC 6.41 6.51 6.60 6.70 6.79
PI 1.96 2.00 2.05 2.09 2.13 TC 7.29 7.74 8.19 8.65 9.10 SC 6.16 6.25 6.35 6.45 6.54
PI 2.23 2.27 TC 6.90 7.35
2.32
7.80
2.36 2.41
8.25 8.70
SC 5.91 6.00 6.10 6.20 6.29
PI 2.50 2.55 TC 6.50 6.95
2.59
7.41
2.63 2.68
7.86 8.31
SC 5.66 5.75 5.85 5.95 6.04
PI 2.77 2.82 2.86 2.91 2.95 TC 6.03 6.48 6.93 7.39 7.84 SC 5.36 5.45 5.55 5.64 5.74
PI
3.10 3.14 3.19 3.23 3.28
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB Dry Bulb Temp., (oC) ID Indoor OD – Outdoor
5.5.2 Capacity Correction Factors
Cool in g Ca pa ci ty Ra ti o Vs. Outdo or T emp era ture
1.20
1.10
1.00
0.90
0.80
0.70
Capaci ty Ration
0.60
0.50
20 25 30 35 40 45
Outdoor DB Temperature [ºC]
SM WNGDCI 2-E.4 GB
5-9
PERFORMANCE DATA & PRESSURE CURVES
CONTENTS
5.5.3 Heating Capacity (kW) - Run Mode
230[V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB TEMPERATURE [0C]
OD COIL
ENTERING
AIR DB/WB
TEMPERATURE
[0C]
-15/-16
-10/-12
-7/-8
-1/-2
2/1
7/6
10/9
15/12
15-24
(Protection Range)
DATA
TC 3.87 3.31 2.75
PI 1.85 1.99 2.12
TC 5.11 4.55 3.99
PI 2.09 2.23 2.36
TC 6.03 5.48 4.92
PI 2.28 2.41 2.54
TC 6.50 5.94 5.38
PI 2.37 2.50 2.63
TC 6.81 6.25 5.69
PI 2.43
TC 9.06
PI 2.52
TC 9.53
PI 2.57 2.70 2.83
TC 10.00 9.44 8.88
PI 2.61 2.75 2.88
TC 85 - 105 % of nominal
PI 80 - 120 % of nominal
15 20 25
2.56
8.50
2.65
8.97
2.69
7.94
2.78
8.41
LEGEND
TC – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB Dry Bulb Temp., (oC) ID Indoor OD – Outdoor
5.5.4 Capacity Correction Factors
1.20
1.10
1.00
0.90
0.80
0.70
0.60
Capacity Rati on
0.50
0.40
Heating Capa city Ratio Vs. Outdoor Tempera ture
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [ºC]
5-10
SM WNGDCI 2-E.4 GB
PERFORMANCE DATA & PRESSURE CURVES
CONTENTS
5.6 Capacity Correction Factor Due to Tubing Length
5.6.1 WNG 50/60/72/80 DCI: Cooling
1.02
1.00
0.98
0.96
0.94
0.92
0.90
Capacity ratio
0.88
0.86 4 6 8 101214161820 2224262830
Tubing length(m)
5.6.2 Heating
1.02
1.00
0.98
0.96
0.94
0.92
0.90
0.88
Capaci ty ratio
0.86
0.84
4 6 8 101214161820 222426 2830
Tubing Length(m)
SM WNGDCI 2-E.4 GB
5-11
PERFORMANCE DATA & PRESSURE CURVES
CONTENTS
5.7 Pressure Curves
5.7.1. Model: WNG 50 DCI / DCI 50 Cooling — Test Mode
Suction Pressure VS.Outdoor Temp.
1100
1000
900
800
700
600
Suction Pressure [kPa]
500
10 15 20 25 30 35 40 45
Outdoor DB Temperature[ºC ]
Discharge Pressure VS. Outdoor Temp.
4000
3500
3000
2500
2000
1500
Discharge Pressure [kPa]
1000
10 15 20 25 30 35 40 45
Indoor
DB/WB Te m p '
22/15
24/17
27/19
29/21
32/23
Indoor
DB/WB T e m p'
22/15
24/17
27/19
29/21
32/23
5-12
Outdoor DB Temperature[ºC ]
SM WNGDCI 2-E.4 GB
5.7.2. Heating — Test Mode
CONTENTS
Suction Pressure VS.Outdoor Temp.
1100
1000
900
800
700
600
500
400
Suction Pressure [kPa]
300
200
-15 -10 -5 0 5 10 15
Outdoor WB Temperature[ºC ]
PERFORMANCE DATA & PRESSURE CURVES
Indoor DB
15
20
25
Discharge Pressure VS. Outdoor Temp.
4000
3500
3000
2500
2000
1500
Discharge Pressure [kPa]
1000
-15 -10 -5 0 5 10 15
Outdoor WB Temperature
Indoor DB
15
20
25
SM WNGDCI 2-E.4 GB
5-13
PERFORMANCE DATA & PRESSURE CURVES
CONTENTS
5.7.3 Model: WNG 60 DCI / DCI 60 Cooling — Test Mode.
Suction Pressure VS.Outdoor Temp.
1100
1000
900
800
700
600
Suction Pressure [kPa]
500
10 15 20 25 30 35 40 45
Outdoor DB Temperature[ºC ]
Indoor
DB/WB T e m p '
22/15 24/17
27/19 29/21
32/23
Discharge Pressure VS. Outdoor Temp.
4000
3500
3000
2500
2000
1500
Discharge Pressure [kPa]
1000
10 15 20 25 30 35 40 45
Outdoor DB Tempe rature
Indoor
DB/WB T e m p '
22/15 24/17
27/19 29/21
32/23
5-14
SM WNGDCI 2-E.4 GB