Electra IOD 7, CON 12, IOD 9 Service Manual

Service Manual
Compact Series
REFRIGERANT
R407C R22
COOLING ONLY HEAT PUMP
SEPTEMBER - 2005
Indoor Units Outdoor Units
IOD 7 CON 7 IOD 9 CON 9
IOD 12 CON 12
A
LIST OF EFFECTIVE PAGES
Revision Y05-01 Service Manual - COMPACT
LIST OF EFFECTIVE PAGES
Note: Changes in the pages are indicated by a “Revision#” in the footer of each effected page
(when none indicates no changes in the relevant page). All pages in the following list represent effected/ non effected pages divided by chapters.
Dates of issue for original and changed pages are:
Original ....... 0 ........ 15 December 2004
Total number of pages in this publication is 108 consisting of the following:
Page No.
Revision No. #
Page No.
Revision No. #
Page No.
Revision No. #
Title ....................... 0
A ........................... 0
i ............................. 0
1-1 - 1-4 ................ 0
2-1 - 2-6 ................ 0
3-1 - 3-2 ................ 0
4-1 - 4-2 ................ 0
5-1 - 5-24 .............. 1
6-1 - 6-2 ................ 0
7-1 - 7-2 ................ 0
8-1 - 8-2 ................ 0
9-1 - 9-2 ................ 0
10-1-10-4 .............. 0
11-1-11-2 ............... 0
12-1-12-32 ............ 0
13-1-13-2 .............. 0
14-1-14-20 ............ 0
15-1-15-6 .............. 0
Appendix -A ...........0
• Zero in this column indicates an original page.
*Due to constant improvements please note that the data on this service manual can be modified with out notice. **Photos are not contractual
i
TABLE OF CONTENTS
Revision Y05-01Service Manual - COMPACT
Table of Contents
1. INTRODUCTION ...................................................................................................1-1
2. PRODUCT DATA SHEET ......................................................................................2-1
3. RATING CONDITIONS ..........................................................................................3-1
4. OUTLINE DIMENSIONS .......................................................................................4-1
5. PERFORMANCE DATA & PRESSURE CURVES ................................................5-1
6. SOUND LEVEL CHARACTERISTICS ..................................................................6-1
7. ELECTRICAL DATA ..............................................................................................7-1
8. WIRING DIAGRAMS .............................................................................................8-1
9. ELECTRICAL CONNECTIONS .............................................................................9-1
10. REFRIGERATION DIAGRAMS .............................................................................10-1
11. TUBING CONNECTIONS ......................................................................................11-1
12. CONTROL SYSTEM .............................................................................................12-1
13. TROUBLESHOOTING ..........................................................................................13-1
14. EXPLODED VIEWS AND SPARE PARTS LISTS .................................................14-1
15. OPTIONAL ACCESSORIES .................................................................................15-1
16. APPENDIX A
1-1
INTRODUCTION
Revision Y05-01Service Manual - COMPACT
1. INTRODUCTION
1.1 General
The new COMPACT split wall mounted range comprise the ST (cooling only) and RC (heat pump) models, as follows:
Cooling Only COMPACT 7 ST, COMPACT 9 ST, COMPACT 12 ST
Heat Pump COMPACT 7 RC, COMPACT 9 RC, COMPACT 12 RC
The indoor COMPACT units are available as LED display types only, featuring esthetic design, compact dimensions, and low noise operation.
1.2 Main Features
R22 and R407C models
Microprocessor control.
Infrared remote control with liquid crystal display.
Cross flow fan, allowing low noise level operation.
Indoor coil with treated aluminum fins and coating for improved efficiency.
Easy access to the interconnecting tubing and wiring connections, so that
removing the front grill or casing is not necessary.
Refrigerant pipes can be connected to the indoor unit from 6 different optional
directions.
Automatic treated air sweep.
Low indoor and outdoor noise levels.
Easy installation and service.
1-2
INTRODUCTION
Revision Y05-01 Service Manual - COMPACT
1.3 Indoor Unit
The indoor unit is wall mounted, and can be easily fitted to many types of residential and commercials applications.
It includes:
Casing with air inlet and outlet grills.
tangential fan.
Coil with treated aluminum fins.
Motorized flaps
Multi-speed motor with internal protection
Advanced electronic control box assembly
Interconnecting wiring terminal block
Mounting plate
1.4 Filtration
The COMPACT series presents several types of air filters:
Easily accessible, and re-usable pre-filters (mesh)
Pre-charged electrostatic filter (disposable) – optional
Active carbon filter (disposable) – optional
1.5 Control
The microprocessor indoor controller, and an infrared remote control, supplied as standard, provides complete operating function and programming. For further details please refer to the Operation Manual, Appendix A.
1.6 Outdoor Unit
The COMPACT outdoor units can be installed as floor or wall mounted units by using a wall supporting bracket. The metal sheets are protected by anti- corrosion paint work allowing long life resistance. All outdoor units are pre-charged. For further information please refer to the Product Data Sheet, Chapter 2.
It includes :
A Rotary Compressor mounted in a soundproofed compartment :
Axial fan.
Outdoor coil with hydrophilic louver fins for RC units.
Outlet air fan grill.
Service valves” flare” type connection.
Interconnecting wiring terminal block.
1-3
INTRODUCTION
Revision Y05-01Service Manual - COMPACT
1.7 Tubing Connections
Flare type interconnecting tubing to be produced on site. For further details please refer to the Installation Manual, Appendix A.
1.8 Accessories
ASK (All Season Kit):
For low ambient working conditions in cooling, an ASK can be installed inside the outdoor unit. This kit allows cooling operation down to outdoor temp of -10 ºC by gradually controlling the outdoor fan speed motor.
RCW Wall Mounted Remote Control
The RCW remote control is mounted on the wall, and controls the unit either as an infrared remote control or as a wired controller. The wired controller can control up to 10 Indoor units with the same program settings and adjustments. For further details please refer to Optional Accessories, Chapter 15.
1.9 Inbox Documentation
Each unit is supplied with its own installation and operation manuals.
1.10 Matching Table
1.10.1 R407C / R22
OUTDOOR UNITS
INDOOR UNITS
MODEL REF’ IOD 7 IOD 9 IOD 12
CON 7 ST/ RC R407C/R22
CON 9 ST/ RC R407C/R22
CON 12 ST/ RC R407C/R22
2-1
PRODUCT DATA SHEET
Revision Y05-01Service Manual - COMPACT
2. PRODUCT DATA SHEET
2.1 R407C
Model Indoor Unit IOD-7 Model Outdoor Unit CON-7 Installation Method of Pipe Flared
Characteristics Units Cooling Only Cooling Heating
Capacity
(1)
Btu/hr 7230 7230 7400
kW 2.12 2.12 2.17
Power input
(1)
kW 0.83 0.83 0.73
EER (Cooling) or COP(Heating)
(1)
W/W 2.55 2.55 2.97
Energy efficiency class
E
ED Power supply V/Ph/Hz 230V/Single/50Hz Rated current A 3.7 3.7 3.3 Starting current A 18 Circuit breaker rating A 10
INDOOR
Fan type & quantity Cross flow x 1 Fan speeds H/M/L RPM 1150/950 Air flow
(2)
H/M/L m3/hr 400/320 External static pressure Min-Max Pa 0 Sound power level
(3)
H/M/L dB(A) 50/45
Sound pressure level
(4)
H/M/L dB(A) 37/31 Moisture removal l/hr 0.7 Condensate drain tube I.D mm 16 Dimensions WxHxD mm 680*250*180 Weight kg 7 Package dimensions WxHxD mm 770*265*325 Packaged weight kg 9.5 Units per pallet units 36 Stacking height units 9 levels
OUTDOOR
Refrigerant control Capillary tube Compressor type, model Rotary, HITACHI CG433EG1UC Fan type & quantity Propeller(direct) x 1 Fan speeds H/L RPM 850 Air flow H/L m3/hr 1200 Sound power level H/L dB(A) 61 62 Sound pressure level
(4)
H/L dB(A) 51 52 Dimensions WxHxD mm 610*520*240 Weight kg 24 24.5 Package dimensions WxHxD mm 730*560*350 Packaged weight kg 26.5 26.5 Units per pallet Units 12 Stacking height units 4 levels Refrigerant type R407C Refrigerant chargless distance kg/m 0.58kg/m Additional charge per 1 meter g/m 4m<Lin<8m:+5g/m Lin>8m:+9g/m
Connections between
units
Liquid line In.(mm) Ф 1/4”(6.35) Suction line In.(mm) Ф 3/8”(9.53) Max.tubing length m. Max.10
Max.height difference
m. Max.7
Operation control type Remote control Heating elements kW Others
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
2-2
PRODUCT DATA SHEET
Revision Y05-01 Service Manual - COMPACT
Model Indoor Unit IOD-9 Model Outdoor Unit CON-9 Installation Method of Pipe Flared
Characteristics Units Cooling Only Cooling Heating
Capacity
(1)
Btu/hr 8530 8530 9080
kW 2.5 2.5 2.66
Power input
(1)
kW 1.03 1.03 0.93
EER (Cooling) or COP(Heating)
(1)
W/W 2.43 2.43 2.86
Energy efficiency class
E
ED
Power supply V/Ph/Hz 230V/Single/50Hz Rated current A 4.5 4.5 4.0 Starting current A 20 Circuit breaker rating A 10
INDOOR
Fan type & quantity Cross flow x 1 Fan speeds H/M/L RPM 1250/1050 Air flow
(2)
H/M/L m3/hr 450/350 External static pressure Min-Max Pa 0 Sound power level
(3)
H/M/L dB(A) 52/47 Sound pressure level
(4)
H/M/L dB(A) 40/36 Moisture removal l/hr 1 Condensate drain tube I.D mm 16 Dimensions WxHxD mm 680*250*180 Weight kg 7 Package dimensions WxHxD mm 770*265*325 Packaged weight kg 9.5 Units per pallet units 36 Stacking height units 9 levels
OUTDOOR
Refrigerant control Capillary tube Compressor type, model Rotary, TOSHIBA PG170X1C-4DZ3 Fan type & quantity Propeller(direct) x 1 Fan speeds H/L RPM 900 Air flow H/L m3/hr 1265 Sound power level H/L dB(A) 62 63 Sound pressure level
(4)
H/L dB(A) 52 53 Dimensions WxHxD mm 610*520*240 Weight kg 26 26.5 Package dimensions WxHxD mm 730*560*350 Packaged weight kg 29 29 Units per pallet Units 12 Stacking height units 4 levels Refrigerant type R407C Refrigerant chargless distance kg/m 0.63kg/m Additional charge per 1 meter g/m 4m<Lin<8m:+5g/m Lin>8m:+15g/m
Connections between
units
Liquid line In.(mm) Ф 1/4”(6.35) Suction line In.(mm) Ф 3/8”(9.53) Max.tubing length m. Max.12
Max.height difference
m. Max.7
Operation control type Remote control Heating elements kW Others
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
2-3
PRODUCT DATA SHEET
Revision Y05-01Service Manual - COMPACT
Model Indoor Unit IOD-12 Model Outdoor Unit CON-12 Installation Method of Pipe Flared
Characteristics Units Cooling Only Cooling Heating
Capacity
(1)
Btu/hr 12620 12450 12620
kW 3.7 3.65 3.7
Power input
(1)
kW 1.29 1.26 1.25
EER (Cooling) or COP(Heating)
(1)
W/W 2.87 2.90 2.96
Energy efficiency class
C
CD
Power supply V/Ph/Hz 230V/Single/50Hz Rated current A 5.7 5.7 6.0 Starting current A 30 Circuit breaker rating A 15
INDOOR
Fan type & quantity Cross flow x 1 Fan speeds H/M/L RPM 1250/1000 Air flow
(2)
H/M/L m3/hr 600/450 External static pressure Min-Max Pa 0 Sound power level
(3)
H/M/L dB(A) 54/47
Sound pressure level
(4)
H/M/L dB(A) 42/36 Moisture removal l/hr 1.7 Condensate drain tube I.D mm 16 Dimensions WxHxD mm 840*250*180 Weight kg 8 Package dimensions WxHxD mm 930*265*325 Packaged weight kg 11 Units per pallet units 36 Stacking height units 9 levels
OUTDOOR
Refrigerant control Capillary tube Compressor type, model Rotary, TOSHIBA PG215X2C-4FS Fan type & quantity Propeller(direct) x 1 Fan speeds H/L RPM 735 Air flow H/L m3/hr 1550 Sound power level H/L dB(A) 66 67 Sound pressure level
(4)
H/L dB(A) 56 57 Dimensions WxHxD mm 760*545*245 Weight kg 37 38 Package dimensions WxHxD mm 880*610*310 Packaged weight kg 40.5 40.5 Units per pallet Units 12 Stacking height units 4 levels Refrigerant type R407C Refrigerant chargless distance kg/m 1.015kg/m Additional charge per 1 meter g/m 4m<Lin<7.5m:+10g/m 7.5M>Lin>15m:+15g/m
Connections between
units
Liquid line In.(mm) Ф 1/4”(6.35) Suction line In.(mm) Ф 1/2”(12.7) Max.tubing length m. Max.15
Max.height difference
m. Max.7
Operation control type Remote control Heating elements kW Others
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
2-4
PRODUCT DATA SHEET
Revision Y05-01 Service Manual - COMPACT
1.2 R22
Model Indoor Unit IOD-7 Model Outdoor Unit CON-7 Installation Method of Pipe Flared
Characteristics Units cooling only Cooling Heating
Capacity
(1)
Btu/hr 7230 7230 7340
kW 2.12 2.12 2.15
Power input
(1)
kW 0.75 0.75 0.67
EER (Cooling) or COP(Heating)
(1)
W/W 2.83 2.83 3.21
Energy efficiency class
C
CC Power supply V/Ph/Hz 230V/Single/50Hz Rated current A 3.4 3.4 3.1 Starting current A 16 Circuit breaker rating A 10
INDOOR
Fan type & quantity Cross flow x 1 Fan speeds H/M/L RPM 1150/950 Air flow
(2)
H/M/L m3/hr 400/320 External static pressure Min-Max Pa 0 Sound power level
(3)
H/M/L dB(A) 50/45 Sound pressure level
(4)
H/M/L dB(A) 37/31 Moisture removal l/hr 0.7 Condensate drain tube I.D mm 16 Dimensions WxHxD mm 680*180*250 Weight kg 7 Package dimensions WxHxD mm 770*325*265 Packaged weight kg 9.5 Units per pallet units 36 Stacking height units 9 levels
OUTDOOR
Refrigerant control Capillary tube Compressor type, model Rotary, HITACHI SD134CV-H6AU Fan type & quantity Propeller(direct) x 1 Fan speeds H/L RPM 850 Air flow H/L m3/hr 1200 Sound power level H/L dB(A) 61 62 Sound pressure level
(4)
H/L dB(A) 51 52 Dimensions WxHxD mm 610*240*520 Weight kg 23 Package dimensions WxHxD mm 730*350*560 Packaged weight kg 26.5 26.5 Units per pallet Units 12 Stacking height units 4 levels Refrigerant type R22 Refrigerant chargless distance kg/m 0.5kg/m Additional charge per 1 meter g/m 4m<Lin<8m:+5g/m Lin>8m:+9g/m
Connections between
units
Liquid line In.(mm) 1/4”(6.35) Suction line In.(mm) 3/8”(9.53) Max.tubing length m. Max.10
Max.height difference
m. Max.7
Operation control type Remote control Heating elements kW Others
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
2-5
PRODUCT DATA SHEET
Revision Y05-01Service Manual - COMPACT
Model Indoor Unit IOD-9 Model Outdoor Unit CON-9 Installation Method of Pipe Flared
Characteristics Units cooling only Cooling Heating
Capacity
(1)
Btu/hr 8630 8630 9140
kW 2.53 2.53 2.68
Power input
(1)
kW 0.97 0.97 0.88
EER (Cooling) or COP(Heating)
(1)
W/W 2.61 2.61 3.05
Energy efficiency class
D
DD
Power supply V/Ph/Hz 230V/Single/50Hz Rated current A 4.2 4.2 3.9 Starting current A 26 Circuit breaker rating A 10
INDOOR
Fan type & quantity Cross flow x 1 Fan speeds H/M/L RPM 1250/1050 Air flow
(2)
H/M/L m3/hr 450/350 External static pressure Min-Max Pa 0 Sound power level
(3)
H/M/L dB(A) 52/48 Sound pressure level
(4)
H/M/L dB(A) 40/35 Moisture removal l/hr 1 Condensate drain tube I.D mm 16 Dimensions WxHxD mm 680*180*250 Weight kg 7 Package dimensions WxHxD mm 770*325*265 Packaged weight kg 9.5 Units per pallet units 36 Stacking height units 9 levels
OUTDOOR
Refrigerant control Capillary tube Compressor type, model Rotary, TOSHIBA PH170X1C 4DZ2 Fan type & quantity Propeller(direct) x 1 Fan speeds H/L RPM 900 Air flow H/L m3/hr 1265 Sound power level H/L dB(A) 62 63 Sound pressure level
(4)
H/L dB(A) 52 53 Dimensions WxHxD mm 610*240*520 Weight kg 26 26.5 Package dimensions WxHxD mm 730*350*560 Packaged weight kg 29 29 Units per pallet Units 12 Stacking height units 4 levels Refrigerant type R22 Refrigerant chargless distance kg/m 0.63kg/m Additional charge per 1 meter g/m 4m<Lin<8m:+5g/m Lin>8m:+15g/m
Connections between
units
Liquid line In.(mm) 1/4”(6.35) Suction line In.(mm) 3/8”(9.53) Max.tubing length m. Max.12
Max.height difference
m. Max.7
Operation control type Remote control Heating elements kW Others
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
2-6
PRODUCT DATA SHEET
Revision Y05-01 Service Manual - COMPACT
Model Indoor Unit IOD-12 Model Outdoor Unit CON-12 Installation Method of Pipe Flared
Characteristics Units cooling only Cooling Heating
Capacity
(1)
Btu/hr 13140 13140 13310
kW 3.85 3.85 3.90
Power input
(1)
kW 1.27 1.27 1.25
EER (Cooling) or COP(Heating)
(1)
W/W 3.03 3.03 3.12
Energy efficiency class
B
BD
Power supply V/Ph/Hz 230V/Single/50Hz Rated current A 5.7 5.7 6.0 Starting current A 30 Circuit breaker rating A 15
INDOOR
Fan type & quantity Cross flow x 1 Fan speeds H/M/L RPM 1250/1000 Air flow
(2)
H/M/L m3/hr 600/450 External static pressure Min-Max Pa 0 Sound power level
(3)
H/M/L dB(A) 54/47
Sound pressure level
(4)
H/M/L dB(A) 42/36 Moisture removal l/hr 1.77 Condensate drain tube I.D mm 16 Dimensions WxHxD mm 840*180*250 Weight kg 8 Package dimensions WxHxD mm 930*325*265 Packaged weight kg 11 Units per pallet units 36 Stacking height units 9 levels
OUTDOOR
Refrigerant control Capillary tube Compressor type, model Rotary, TOSHIBA PH225X2C-4FS Fan type & quantity Propeller(direct) x 1 Fan speeds H/L RPM 735 Air flow H/L m3/hr 1550 Sound power level H/L dB(A) 65 Sound pressure level
(4)
H/L dB(A) 55 Dimensions WxHxD mm 760*245*545 Weight kg 37 38 Package dimensions WxHxD mm 880*310*610 Packaged weight kg 40.5 40.5 Units per pallet Units 12 Stacking height units 4 levels Refrigerant type R22 Refrigerant chargless distance kg/m 1.005kg/m
Additional charge per 1 meter g/m
4m<Lin<7.5m:+10g/m 7.5M>Lin>15m:+15g/
m
Connections between
units
Liquid line In.(mm) 1/4”(6.35) Suction line In.(mm) 1/2”(12.7) Max.tubing length m. Max.15
Max.height difference
m. Max.7
Operation control type Remote control Heating elements kW Others
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
3-1
RATING CONDITIONS
Revision Y05-01Service Manual - COMPACT
3. RATING CONDITIONS
Standard conditions in accordance with ISO 5151, ISO 13253 (for ducted units) and EN 14511.
Cooling:
Indoor: 27oC DB 19oC WB Outdoor: 35 oC DB
Heating:
Indoor: 20oC DB Outdoor: 7oC DB 6oC WB
3.1 Operating Limits
3.1.1 R407C
Indoor Outdoor
Cooling
Upper limit 32oC DB 23oC WB 46oC DB Lower limit 21oC DB 15oC WB 10oC DB
Heating
Upper limit
27oC DB 24oC DB 18oC WB
Lower limit 10oC DB -9oC DB -10oC WB
Voltage
1PH 198 – 264 V 3PH 360 – 440 V
3.1.2 R22
Indoor Outdoor
Cooling
Upper limit
32oC DB 23oC WB 46oC DB
Lower limit 21oC DB 15oC WB 10oC DB
Heating
Upper limit
27oC DB 24oC DB 18oC WB
Lower limit 10oC DB -5oC DB -6oC WB
Voltage
1PH
198 – 264 V
3PH 360 – 440 V
4-1
OUTLINE DIMENSIONS
Revision Y05-01Service Manual - COMPACT
4. OUTLINE DIMENSIONS
4.1 Indoor Unit IOD 7, 9
85
150mm
4.2 Indoor Unit IOD 12
150mm
4-2
OUTLINE DIMENSIONS
Revision Y05-01 Service Manual - COMPACT
4.3 Outdoor Unit CON 7, 9
4.4 Outdoor Unit CON 12
AI R OUTL E T
AI R I NTAKE
5-1
PERFORMANCE DATA
Revision Y05-01Service Manual - COMPACT
5. PERFORMANCE DATA & PRESSURE CURVES
5.1 IOD7/CON7 R407C
5.1.1 Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR DB OD Coil(
o
C)
Data
ENTERING AIR WB/DB ID Coil(
o
C)
15/21 17/24 19/27 21/29 23/32
15
(1)
TC
2.23 2.31 2.37 2.42 2.46
SC 1.49 1.55 1.61 1.65 1.68
PI
0.59 0.59 0.59 0.59 0.60
20
(1)
TC
2.16 2.28 2.35 2.41 2.46
SC 1.46 1.54 1.60 1.65 1.68
PI
0.64 0.64 0.64 0.65 0.65
25
TC
2.05 2.21 2.32 2.39 2.45
SC 1.42 1.51 1.59 1.64 1.67
PI
0.69 0.70 0.70 0.70 0.71
30
TC
1.91 2.08 2.25 2.33 2.40
SC 1.38 1.46 1.56 1.60 1.63
PI
0.74 0.76
0.76
0.77 0.78
35
TC
1.77 1.92
2.12
2.23 2.33
SC 1.31 1.40 1.52 1.56 1.59
PI
0.80 0.82
0.83
0.84 0.84
40
TC
1.61 1.75
1.91
2.09 2.20
SC 1.23 1.33 1.44 1.48 1.51
PI
0.87 0.88 0.89 0.91 0.91
46
TC
1.40 1.53 1.68 1.86 2.00
SC 1.14 1.22 1.31 1.36 1.39
PI
0.95 0.96 0.98 1.00 1.01
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C) DB – Dry Bulb Temp., (oC) ID – Indoor OD – Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, an A.S.K Kit is required.
5-2
PERFORMANCE DATA
Revision Y05-01 Service Manual - COMPACT
5.1.2 Heating Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR DB ID COIL ( qC)
15 20 25
ENTERING AIR
WB OU COIL ( qC)
TH PI TH PI TH PI
-10
1.14 0.58 1.10 0.62 1.05 0.65
-7
1.23 0.60 1.18 0.63 1.14 0.67
-2
1.30 0.61 1.26 0.64 1.22 0.68
2
1.58 0.64 1.52 0.68 1.45 0.72
6
2.24 0.68
2.17 0.73
2.09 0.78
10
2.43 0.72 2.37 0.77 2.30 0.82
15
2.63 0.75 2.56 0.81 2.50 0.86
20
2.77 0.77 2.70 0.84 2.63 0.91
* the above chart includes the weighted deicing infleuence.
LEGEND
TH – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C) ID – Indoor OU – Outdoor
5.2 Capacity Correction Factor Due to Tubing Length
5.2.1 Cooling
TOTAL TUBING LENGTH
3m
7.5m
10m 15m 20m 25m 30m 40m 50m
1.03
1
0.961 --- --- --- --- --- ---
* Minimum recommended tubing length between indoor and outdoor units is 3m.
5.2.2 Heating
TOTAL TUBING LENGTH
3m
7.5m
10m 15m 20m 25m 30m 40m 50m
1.06
1
0.982 --- --- --- --- --- ---
* Minimum recommended tubing length between indoor and outdoor units is 3m.
5-3
PERFORMANCE DATA
Revision Y05-01Service Manual - COMPACT
5.3 Pressure Curves.
5.3.1 Cooling.
Suction Pressure VS.Outdoor Temp
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
15 20 25 30 35 40 46
Outdoor Temp.(DB oC )
Suction Pressure (Bar[g])
15/21(WB/DB ºC) 17/24(WB/DB ºC) 19/27(WB/DB ºC) 21/29(WB/DB ºC) 23/32(WB/DB ºC)
Discharge Pressure VS.Outdoor Temp
8
10
12
14
16
18
20
22
24
26
28
30
15 20 25 30 35 40 46
Outdoor Temp.(DB oC )
Discharge Pressure (Bar[g])
15/21(WB/DB ºC) 17/24(WB/DB ºC) 19/27(WB/DB ºC) 21/29(WB/DB ºC) 23/32(WB/DB ºC)
5-4
PERFORMANCE DATA
Revision Y05-01 Service Manual - COMPACT
5.3.2 Heating.
Suction Pressure VS.Outdoor Temp
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
-10 -5 0 5 10 15 20
Outdoor Temp.( WB oC )
Suction Pressure(Bar[g])
15 DB (ºC) 20 DB (ºC) 25 DB (ºC)
Discharge Pressure VS.Outdoor Temp
10
12
14
16
18
20
22
24
-10 -5 0 5 10 15 20
Outdoor Temp.( WB oC )
Discharge Pressure(Bar[g])
25 DB (ºC) 20 DB (ºC) 15 DB (ºC)
5-5
PERFORMANCE DATA
Revision Y05-01Service Manual - COMPACT
5.4 IOD9/CON9 R407C
5.4.1 Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR DB OD Coil(
o
C)
Data
ENTERING AIR WB/DB ID Coil(
o
C)
15/21 17/24 19/27 21/29 23/32
15
(1)
TC
2.63 2.73 2.79 2.86 2.90
SC 1.65 1.72 1.78 1.83 1.86
PI
0.73 0.73 0.73 0.73 0.74
20
(1)
TC
2.55 2.69 2.77 2.84 2.90
SC 1.61 1.70 1.77 1.82 1.86
PI
0.79 0.80 0.80 0.80 0.80
25
TC
2.41 2.60 2.74 2.82 2.89
SC 1.57 1.67 1.76 1.81 1.84
PI
0.86 0.86 0.87 0.87 0.88
30
TC
2.26 2.46 2.65 2.75 2.83
SC 1.52 1.62 1.72 1.77 1.80
PI
0.92 0.94
0.95
0.95 0.96
35
TC
2.09 2.27
2.50
2.63 2.75
SC 1.45 1.55 1.68 1.73 1.76
PI
1.00 1.01
1.03
1.04 1.04
40
TC
1.90 2.07
2.26
2.47 2.59
SC 1.36 1.47 1.59 1.64 1.67
PI
1.08 1.09 1.11 1.12 1.14
46
TC
1.65 1.80 1.98 2.19 2.36
SC 1.26 1.35 1.45 1.50 1.53
PI
1.17 1.19 1.22 1.24 1.25
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C) DB – Dry Bulb Temp., (oC) ID – Indoor OD – Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, an A.S.K Kit is required.
5-6
PERFORMANCE DATA
Revision Y05-01 Service Manual - COMPACT
5.4.2 Heating Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR DB ID COIL ( qC)
15 20 25
ENTERING AIR
WB OU COIL (qC)
TH PI TH PI TH PI
-10
1.40 0.74 1.34 0.79 1.29 0.83
-7
1.50 0.76 1.45 0.80 1.40 0.85
-2
1.60 0.77 1.54 0.82 1.49 0.86
2
1.94 0.81 1.86 0.86 1.78 0.91
6
2.74 0.87
2.66 0.93
2.57 0.99
10
2.98 0.92 2.90 0.98 2.82 1.05
15
3.22 0.96 3.14 1.03 3.06 1.10
20
3.39 0.99 3.31 1.07 3.22 1.15
* the above chart includes the weighted deicing infleuence.
LEGEND
TH – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C) ID – Indoor OU – Outdoor
5.5 Capacity Correction Factor Due to Tubing Length
5.5.1 Cooling
TOTAL TUBING LENGTH
3m
7.5m
10m 12m 20m 25m 30m 40m 50m
1.03
1
0.978 0.961 --- --- --- --- ---
* Minimum recommended tubing length between indoor and outdoor units is 3m.
5.5.2 Heating
TOTAL TUBING LENGTH
3m
7.5m
10m 12m 20m 25m 30m 40m 50m
1.05
1
0.981 0.965 --- --- --- --- ---
* Minimum recommended tubing length between indoor and outdoor units is 3m.
5-7
PERFORMANCE DATA
Revision Y05-01Service Manual - COMPACT
5.6 Pressure Curves.
5.6.1 Cooling.
Suction Pressure VS.Outdoor Temp
3.0
3.5
4.0
4.5
5.0
5.5
6.0
15 20 25 30 35 40 46
Outdoor Temp.(DB oC )
Suction Pressure (B ar[g])
15/21(WB/DB ºC) 17/24(WB/DB ºC) 19/27(WB/DB ºC) 21/29(WB/DB ºC) 23/32(WB/DB ºC)
Discharge Pressure VS.Outdoor Temp
8
10
12
14
16
18
20
22
24
26
28
30
15 20 25 30 35 40 46
Outdoor Temp.(DB oC )
Discharge Pressure (Bar[g])
15/21(WB/DB ºC) 17/24(WB/DB ºC) 19/27(WB/DB ºC) 21/29(WB/DB ºC) 23/32(WB/DB ºC)
5-8
PERFORMANCE DATA
Revision Y05-01 Service Manual - COMPACT
5.6.2 Heating.
Suction Pressure VS.Outdoor Temp
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
-10 -5 0 5 10 15 20
Outdoor Temp.( WB oC )
Suction Pressure(Bar[g])
15 DB (ºC) 20 DB (ºC) 25 DB (ºC)
Discharge Pressure VS.Outdoor Temp
10
12
14
16
18
20
22
24
26
28
-10 -5 0 5 10 15 20
Outdoor Temp.( WB oC )
Discharge Pressure(Bar[g])
25 DB (ºC) 20 DB (ºC) 15 DB (ºC)
5-9
PERFORMANCE DATA
Revision Y05-01Service Manual - COMPACT
5.7 IOD12/CON12 R407C
5.7.1 Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR DB OD Coil(
o
C)
Data
ENTERING AIR WB/DB ID Coil(
o
C)
15/21 17/24 19/27 21/29 23/32
15
(1)
TC
3.90 4.04 4.13 4.23 4.30
SC 2.43 2.53 2.63 2.70 2.75
PI
0.91 0.92 0.92 0.92 0.93
20
(1)
TC
3.77 3.98 4.10 4.20 4.29
SC 2.38 2.51 2.62 2.69 2.74
PI
0.99 1.00 1.00 1.01 1.01
25
TC
3.57 3.85 4.05 4.18 4.28
SC 2.32 2.46 2.60 2.67 2.72
PI
1.07 1.08 1.09 1.09 1.10
30
TC
3.34 3.64 3.93 4.07 4.19
SC 2.25 2.39 2.54 2.61 2.66
PI
1.16 1.17
1.18
1.19 1.21
35
TC
3.09 3.35
3.70
3.89 4.07
SC 2.14 2.29 2.48 2.55 2.60
PI
1.25 1.27
1.29
1.30 1.31
40
TC
2.81 3.06
3.34
3.65 3.84
SC 2.01 2.17 2.35 2.42 2.47
PI
1.35 1.37 1.39 1.41 1.42
46
TC
2.44 2.67 2.93 3.24 3.49
SC 1.85 1.99 2.14 2.21 2.26
PI
1.47 1.49 1.53 1.55 1.57
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C) DB – Dry Bulb Temp., (oC) ID – Indoor OD – Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, an A.S.K Kit is required.
5-10
PERFORMANCE DATA
Revision Y05-01 Service Manual - COMPACT
5.7.2 Heating Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR DB ID COIL ( qC)
15 20 25
ENTERING AIR
WB OU COIL (qC)
TH PI TH PI TH PI
-10
1.94 1.00 1.87 1.07 1.79 1.12
-7
2.09 1.03 2.02 1.08 1.94 1.14
-2
2.22 1.04 2.15 1.10 2.07 1.16
2
2.70 1.09 2.59 1.16 2.48 1.23
6
3.81 1.17
3.70 1.25
3.57 1.33
10
4.14 1.23 4.03 1.32 3.92 1.41
15
4.48 1.29 4.37 1.39 4.26 1.48
20
4.72 1.33 4.61 1.44 4.48 1.55
* the above chart includes the weighted deicing infleuence.
LEGEND
TH – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C) ID – Indoor OU – Outdoor
5.8 Capacity Correction Factor Due to Tubing Length
5.8.1 Cooling
TOTAL TUBING LENGTH
3m
7.5m
10m 15m 20m 25m 30m 40m 50m
1.04
1
0.974 0.922 --- --- --- --- ---
* Minimum recommended tubing length between indoor and outdoor units is 3m.
5.8.2 Heating
TOTAL TUBING LENGTH
3m
7.5m
10m 15m 20m 25m 30m 40m 50m
1.05
1
0.976 0.935 --- --- --- --- ---
* Minimum recommended tubing length between indoor and outdoor units is 3m.
5-11
PERFORMANCE DATA
Revision Y05-01Service Manual - COMPACT
5.9 Pressure Curves.
5.9.1 Cooling.
Suction Pressure VS.Outdoor Temp
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
15 20 25 30 35 40 46
Outdoor Temp.(DB oC )
Suction Pressure (B ar[g])
15/21(WB/DB ºC) 17/24(WB/DB ºC) 19/27(WB/DB ºC) 21/29(WB/DB ºC) 23/32(WB/DB ºC)
Discharge Pressure VS.Outdoor Temp
8
10
12
14
16
18
20
22
24
26
28
30
15 20 25 30 35 40 46
Outdoor Temp.(DB oC )
Discharge Pressure (Bar[g])
15/21(WB/DB ºC) 17/24(WB/DB ºC) 19/27(WB/DB ºC) 21/29(WB/DB ºC) 23/32(WB/DB ºC)
5-12
PERFORMANCE DATA
Revision Y05-01 Service Manual - COMPACT
5.9.2 Heating.
Suction Pressure VS.Outdoor Temp
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
-10-5 0 5 101520
Outdoor Temp.( WB oC )
Suction Pressure(Bar[g])
15 DB (ºC) 20 DB (ºC) 25 DB (ºC)
Discharge Pressure VS.Outdoor Temp
10
12
14
16
18
20
22
24
26
28
-10 -5 0 5 10 15 20
Outdoor Temp.( WB oC )
Discharge Pressure(Bar[g])
25 DB (ºC) 20 DB (ºC) 15 DB (ºC)
5-13
PERFORMANCE DATA
Revision Y05-01Service Manual - COMPACT
5.10 IOD7/CON7 R22
5.10.1 Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR DB OD Coil(
o
C)
Data
ENTERING AIR WB/DB ID Coil(
o
C)
15/21 17/24 19/27 21/29 23/32
15
(1)
TC
2.23 2.31 2.37 2.42 2.46
SC 1.57 1.63 1.70 1.74 1.77
PI
0.53 0.53 0.53 0.53 0.54
20
(1)
TC
2.16 2.28 2.35 2.41 2.46
SC 1.54 1.62 1.69 1.74 1.77
PI
0.58 0.58 0.58 0.58 0.59
25
TC
2.05 2.21 2.32 2.39 2.45
SC 1.50 1.59 1.67 1.72 1.75
PI
0.62 0.63 0.63 0.64 0.64
30
TC
1.91 2.08 2.25 2.33 2.40
SC 1.45 1.54 1.64 1.69 1.72
PI
0.67 0.68
0.69
0.69 0.70
35
TC
1.77 1.92
2.12
2.23 2.33
SC 1.38 1.48 1.60 1.65 1.68
PI
0.73 0.74
0.75
0.76 0.76
40
TC
1.61 1.75
1.91
2.09 2.20
SC 1.30 1.40 1.51 1.56 1.59
PI
0.78 0.80 0.81 0.82 0.83
46
TC
1.40 1.53 1.68 1.86 2.00
SC 1.20 1.28 1.38 1.43 1.46
PI
0.86 0.87 0.89 0.90 0.91
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C) DB – Dry Bulb Temp., (oC) ID – Indoor OD – Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, an A.S.K Kit is required.
5-14
PERFORMANCE DATA
Revision Y05-01 Service Manual - COMPACT
5.10.2 Heating Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR DB ID COIL ( qC)
15 20 25
ENTERING AIR
WB OU COIL (qC)
TH PI TH PI TH PI
-10
1.13 0.54 1.09 0.57 1.04 0.60
-7
1.21 0.55 1.17 0.58 1.13 0.61
-2
1.29 0.56 1.25 0.59 1.20 0.62
2
1.57 0.58 1.51 0.62 1.44 0.66
6
2.21 0.63
2.15 0.67
2.07 0.71
10
2.41 0.66 2.34 0.71 2.28 0.76
15
2.60 0.69 2.54 0.74 2.47 0.79
20
2.74 0.71 2.68 0.77 2.60 0.83
* the above chart includes the weighted deicing infleuence.
LEGEND
TH – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C) ID – Indoor OU – Outdoor
5.11 Capacity Correction Factor Due to Tubing Length
5.11.1 Cooling
TOTAL TUBING LENGTH
3m
7.5m
10m 15m 20m 25m 30m 40m 50m
1.04
1
0.949 --- --- --- --- --- ---
* Minimum recommended tubing length between indoor and outdoor units is 3m.
5.11.2 Heating
TOTAL TUBING LENGTH
3m
7.5m
10m 15m 20m 25m 30m 40m 50m
1.03
1
0.973 --- --- --- --- --- ---
* Minimum recommended tubing length between indoor and outdoor units is 3m.
5-15
PERFORMANCE DATA
Revision Y05-01Service Manual - COMPACT
5.12 Pressure Curves.
5.12.1 Cooling.
Suction Pressure VS.Outdoor Temp
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
15 20 25 30 35 40 46
Outdoor Temp.(DB oC )
Suction Pressure (B ar[g])
15/21(WB/DB ºC) 17/24(WB/DB ºC) 19/27(WB/DB ºC) 21/29(WB/DB ºC) 23/32(WB/DB ºC)
Discharge Pressure VS.Outdoor Temp
8
10
12
14
16
18
20
22
24
26
28
30
15 20 25 30 35 40 46
Outdoor Temp.(DB oC )
Discharge Pressure (Bar[g])
15/21(WB/DB ºC) 17/24(WB/DB ºC) 19/27(WB/DB ºC) 21/29(WB/DB ºC) 23/32(WB/DB ºC)