Electra CN 25 DCI, CN 35 DCI, CN 70 DCI, DCI 25, DCI 35 Service Manual

...
Page 1

CN DC Inverter Series

CONTENT
Indoor Units Outdoor Units
CN 25 DCI DCI 25 CN 35 DCI DCI 35 CN 50 DCI DCI 50 CN 60 DCI DCI 60 CN 70 DCI DCI 72Z
SM CN 1-E.1 GB
REFRIGERANT
R410A
AUGUST – 2008
Page 2

LIST OF EFFECTIVE PAGES

CONTENT
LIST OF EFFECTIVE PAGES
Note: Changes in the pages are indicated by a “Revision#” in the footer of each effected page
(when none indicates no changes in the relevant page). All pages in the following list represent effected/ non effected pages divided by chapters.
Dates of issue for original and changed pages are:
Original ....... 0 ........ December 2007
Total number of pages in this publication is 111 consisting of the following:
Page No.
Title .......................1
A ...........................1
i ............................. 1
1-1 - 1-3 ................1
2-1 - 2-6 ................1
3-1 ........................1
4-1 - 4-3 ................1
5-1 - 5-21 ..............1
6-1 - 6-5 ................1
7-1 ........................1
8-1 - 8-2 ................1
9-1 ........................1
10-1 ......................1
11-1-11-26 .............1
12-1-12-8 .............. 1
13-1-13-15 ............ 1
14-1 ......................1
Revision No. #
Page No.
Revision No. #
Page No.
Revision No. #
*Due to constant improvements please note that the data on this service manual can be modified with out notice. **Photos are not contractual
A
Zero in this column indicates an original page.
SM CN 1- A.1 GB
Page 3

TABLE OF CONTENTS

Table of Contents
1. INTRODUCTION ...................................................................................................1-1
2. PRODUCT DATA SHEET ......................................................................................2-1
3. RATING CONDITIONS ..........................................................................................3-1
4. OUTLINE DIMENSIONS .......................................................................................4-1
5. PERFORMANCE DATA & PRESSURE CURVES ...............................................5-1
6. SOUND LEVEL CHARACTERISTICS ..................................................................6-1
7. ELECTRICAL DATA ..............................................................................................7-1
8. WIRING DIAGRAMS .............................................................................................8-1
9. REFRIGERATION DIAGRAMS .............................................................................9-1
10. TUBING CONNECTIONS ......................................................................................10-1
11. CONTROL SYSTEM .............................................................................................11-1
12. TROUBLESHOOTING ..........................................................................................12-1
13. EXPLODED VIEWS AND SPARE PARTS LISTS .................................................13-1
14. APPENDIX A .........................................................................................................14-1
SM CN 1-E.1 GB
i
Page 4
1. INTRODUCTION
CONTENT
1.1 General
The CN DCI Inverter Cassette type split air conditioner range comprise RC (heat pump) models, as follows:
CN 25
CN 35
CN 50
CN 60
CN 70
1.2 Main Features
The CN DCI series benefits from the most advanced technological innovations, namely:
DC inverter technology.
R410A refrigerant.
High COP.

INTRODUCTION

Precharged refrigerant.
Low Sound level for both Indoor and Outdoor.
60 x60 cm dimension designed for integration in suspended ceilings.
DC Brushless fan motor.
New grille, modern style with elegant lines in line with every interior decor , 2 panels
optional available (hard ceiling / Suspended ceiling).
Motorized air distribution flaps.
Very slim profile 219 mm at size 9-12, and 270 mm at size 18-24.
Option of fresh air intake, and air distribution to adjacent room.
Integrated condensate pump with a lift of 1 m Max.
Connection to Multisplit outdoor units.
Up to 30 m pipe length between indoor and outdoor units.
Up to 15 m vertical high between indoor and outdoor units.
Cooling operation at outdoor temperature down to -10°C.
Heating operation at outdoor temperature down to -15°C.
Built in over-flow protection against the condensate water.
Easy installation and service.
SM CN 1-E.1 GB
Product can have the option of additional function of Ionizer and ESF.
Fan speed can be adjusted by compensation on PCB according to different installation
height (Field option).
1-1
Page 5
INTRODUCTION
CONTENT
1.3 Indoor Unit
The indoor unit is cassette type indoor unit, and can be easily fitted to many types of residential and commercials applications.
It includes:
Coil with hydrophilic aluminum fins.
Motorized flaps (two step motors).
Advanced electronic control box assembly (DCI storm).
Low sound level of the indoor fan.
1.4 Filtration
The CN series presents several types of air filters:
Easily accessible, and re-usable pre-filters.
Easily Static Filter (Field Option).
1.5 Control
The microprocessor indoor controller, and an infrared remote control, supplied as standard, providing complete operating function and programming. For further details please refer to the Operation Manual, Appendix A.
1.6 Outdoor Unit
The CN outdoor units can be installed as floor or wall mounted units by using a wall supporting braCNet. The metal sheets are protected by anti- corrosion paint work allowing long life resistance. All outdoor units are pre-charged. For further information please refer to the Product Data Sheet, Chapter 2.
It includes:
Compressor mounted in a soundproofed compartment:
Single Rotary – for DCI 25 and DCI 35.
Scroll for DCI 50 and DCI 60.
Twin Rotary for DCI 72Z.
Axial fan.
1-2
Outdoor coil with hydrophilic louver fins for RC units.
Outlet air fan grill.
Service valves” flare” type connection.
Interconnecting wiring terminal bloCN.
SM CN 1-E.1 GB
Page 6
1.7 Tubing Connections
CONTENT
Flare type interconnecting tubing to be produced on site. For further details please refer to the Installation Manual, Chapter 10.
1.8 Accessories
Remote Control. Panel 625x625 for gird ceiling. Panel 725x725 for hard ceiling. ESF & Ionizer kit.
1.9 Inbox Documentation
Each unit is supplied with its own installation and operation manuals.
1.10 Matching Table
1.10.1 R410A
INTRODUCTION
INDOOR UNITS
OUTDOOR UNITS
MODEL REFRIGER. CN 25 CN 35 CN 50 CN 60 CN 70
DCI25/35/50 R410A
DCI 60 R410A
DCI 72Z R410A
The above table lists outdoor units and PXD DCI indoor units which can be matched together. In addition the listed outdoor units can be matched with other types of indoor units such as cassettes and wall mounted. For further information please refer to the relevant Service Manual.
√√√
SM CN 1-E.1 GB
1-3
Page 7
2. PRODUCT DATA SHEET
CONTENT
2.1 CN 25 DCI R410A

PRODUCT DATA SHEET

Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Flared
Characteristics Units Cooling Heating
Capacity
Power input EER (Cooling) or COP(Heating) Energy efficiency class A A Power supply V/Ph/Hz 220-240V/Single/50Hz Rated current A 2.6 3.6 Starting current A 10.5 Circuit breaker rating A 15
Operation control type Remote control Heating elements kW NA
(4)
(4)
(4)
Fan type & quantity Centrifugal x 1 Fan speeds H/M/L RPM 550/450/350 600/500/400 Air flow External static pressure Min-Max Pa 0 Sound power level Sound pressure level Moisture removal l/hr 0.7 Condensate drain tube I.D mm 20
INDOOR
Dimensions WxHxD mm 575X575X219 Weight kg 13(2.2/2.8) PaCNage dimensions WxHxD mm 681X681X297 PaCNaged weight kg 15 Units per pallet units 12 StaCNing height units 6 levels Refrigerant control Electronical Expansion Valve Compressor type, model Single Rotary DC Inverter, Panasonic 5RS102XAB Fan type & quantity Propeller x 1 Fan speeds H/L RPM 830 Air flow H/L m3/hr 1780 Sound power level H/L dB(A) 60 61 Sound pressure level Dimensions WxHxD mm 795*290*610 Weight kg 38 PaCNage dimensions WxHxD mm 945*395*655 PaCNaged weight kg 42 Units per pallet Units 9
OUTDOOR
StaCNing height units 3 levels Refrigerant type R410A Refrigerant chargless distance kg/m 1.1kg/7.5m Additional charge g/m No need
(1)
Connections
between units
H/M/L m3/hr 440 460
(2)
(3)
(3)
Liquid line In.(mm) 1/4"(6.35) Suction line In.(mm) 3/8"(9.53) Max.tubing length m. Max.25
Max.height difference m. Max.10
H/M/L dB(A) 49 49 H/M/L dB(A) 32/26 32/26
H/L dB(A) 50 51
Btu/hr 8550(5100-12300) 10900(5100-16400)
kW 2.5(1.5-3.6) 3.2(1.5-4.8) kW 0.59(0.45-1.00) 0.8(0.50-1.40)
W/W 4.24 4.00
CN25 DCI
DCI 25 R410A
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
SM CN 1-E.1 GB
2-1
Page 8
PRODUCT DATA SHEET
CONTENT
2.2 CN 35 DCI R410A
Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Flared
Characteristics Units Cooling Heating
Capacity
Power input EER (Cooling) or COP(Heating) Energy efficiency class A A Power supply V/Ph/Hz 220-240V/Single/50Hz Rated current A 4.3 5.2 Starting current A 10.5 Circuit breaker rating A 15
Operation control type Remote control Heating elements kW NA
(4)
(4)
(4)
Fan type & quantity Centrifugal x 1 Fan speeds H/M/L RPM 600/500/400 650/550/450 Air flow External static pressure Min-Max Pa 0 Sound power level Sound pressure level Moisture removal l/hr 1.38 Condensate drain tube I.D mm 20
INDOOR
Dimensions WxHxD mm 575X575X219 Weight kg 13 PaCNage dimensions WxHxD mm 681X681X297 PaCNaged weight kg 15 Units per pallet units 12 StaCNing height units 6 levels Refrigerant control Electronical Expansion Valve Compressor type, model Single Rotary DC Inverter, Panasonic 5RS102XAB Fan type & quantity Propeller x 1 Fan speeds H/L RPM 830 Air flow H/L m3/hr 1780 Sound power level H/L dB(A) 62 62 Sound pressure level Dimensions WxHxD mm 795*290*610 Weight kg 38.5 PaCNage dimensions WxHxD mm 945*395*655 PaCNaged weight kg 42.5 Units per pallet Units 9
OUTDOOR
StaCNing height units 3 levels Refrigerant type R410A Refrigerant chargless distance kg/m 1.2kg/7.5m Additional charge g/m No need
(1)
Connections
between units
H/M/L m3/hr 490 520
(2)
(3)
(3)
Liquid line In.(mm) 1/4"(6.35) Suction line In.(mm) 3/8"(9.53) Max.tubing length m. Max.25 Max.height difference m. Max.10
H/M/L dB(A) 51 51 H/M/L dB(A) 34/28 34/28
H/L dB(A) 52 52
Btu/hr 11950(5800-14700) 14350(5450-18800)
kW 3.5(1.7-4.3) 4.2(1.6-5.5) kW 0.96(0.50-1.30) 1.16(0.59-1.70)
W/W 3.63 3.64
CN35 DCI
DCI 35 R410A
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
2-2
SM CN 1-E.1 GB
Page 9
2.3 CN 50 DCI R410A
CONTENT
PRODUCT DATA SHEET
Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Flared
Characteristics Units Cooling Heating
Capacity
Power input EER (Cooling) or COP(Heating) Energy efficiency class A A Power supply V/Ph/Hz 220-240V/Single/50Hz Rated current A 7.0 7.2 Starting current A 10.5 Circuit breaker rating A 20
Operation control type Remote control Heating elements kW
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
(4)
(4)
(4)
Fan type & quantity Centrifugal x 1 Fan speeds H/M/L RPM 750/650/550 750/650/550 Air flow
External static pressure Min-Max Pa 0 Sound power level Sound pressure level
Moisture removal l/hr 2.07 Condenstate drain tube I.D mm 20
INDOOR
Dimensions WxHxD mm 575*575*270 Weight kg ??? PaCNage dimensions WxHxD mm 575X575X270 PaCNaged weight kg 15.2 Units per pallet units 681X681X348 StaCNing height units 17.7 Refrigerant control Electronical Expansion Valve Compressor type,model Single Rotary DC Inverter,Panasonic 5RS130XCC03 Fan type & quantity Propeller x 1 Fan speeds H/L RPM 920 Air flow H/L m3/hr 2160 Sound power level H/L dB(A) 62 63
Sound pressure level Dimensions WxHxD mm 795*290*610
Weight kg 39 PaCNage dimensions WxHxD mm 945*395*655 PaCNaged weight kg 43
OUTDOOR
Units per pallet Units 9 StaCNing height units 3 levels Refrigerant type R410A Refrigerant chargless distance kg/m 1.5kg/7.5m Additional charge g/m No need
between units
(1)
Connections
H/M/L m3/hr 700 700
(2)
(3)
(3)
Liquid line In.(mm) 1/4"(6.35) Suction line In.(mm) 1/2"(12.7) Max.tubing length m. Max.30 Max.height difference m. Max.10
H/M/L dB(A) 53 53 H/M/L dB(A) 38/30 38/30
H/L dB(A) 52 53
Btu/hr 17050(4450-20500) 19100(4450-23900)
kW 5.0(1.3-6.0) 5.6(1.3-7.0) kW 1.56(0.46-2.11) 1.55(0.36-2.50)
W/W 3.22 3.62
CN-50 DCI
DCI 50 R410A
SM CN 1-E.1 GB
2-3
Page 10
PRODUCT DATA SHEET
CONTENT
2.4 CN 60 DCI R410A
Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Flared
Characteristics Units Cooling Heating
Capacity
Power input EER (Cooling) or COP(Heating) Energy efficiency class B C Power supply V/Ph/Hz 220-240V/Single/50Hz Rated current A 8.6 9.5 Starting current A 15 Circuit breaker rating A 20
Operation control type Remote control Heating elements (Option) kW
(4)
(4)
(4)
Fan type & quantity Centrifugal x 1 Fan speeds H/M/L RPM 800/7100/600 800/700/600 Air flow External static pressure Min-Max Pa 0 Sound power level Sound pressure level Moisture removal l/hr 2.62 Condenstate drain tube I.D mm 20
INDOOR
Dimensions WxHxD mm 575X575X270 Weight kg 15.2 PaCNage dimensions WxHxD mm 681X681X348 PaCNaged weight kg 17.7 Units per pallet units 12 StaCNing height units 6 levels Refrigerant control EEV Compressor type,model E-Scroll MATSUSHITA 5CS130XCC03 Fan type & quantity Propeller(direct) x 1 Fan speeds H/L RPM 820 Air flow H/L m3/hr 2860 Sound power level H/L dB(A) 65 Sound pressure level Dimensions WxHxD mm 846x690x302 Weight kg 46 PaCNage dimensions WxHxD mm 990x770x430 PaCNaged weight kg 50 Units per pallet Units 9
OUTDOOR
StaCNing height units 3 levels Refrigerant type R410A Refrigerant chargless distance kg/m 1.65kg/7.5m Additional charge per 1 meter g/m No Need
(1)
Connections
between units
H/M/L m3/hr 800 800
(2)
(3)
(3)
Liquid line In.(mm) 1/4"(6.35) Suction line In.(mm) 1/2"(12.7) Max.tubing length m. Max.30 Max.height difference m. Max.15
H/M/L dB(A) 58 58 H/M/L dB(A) 41/33 41/33
H/L dB(A) 55
Btu/hr 19800(4800~22200) 23200(6800~27300)
kW 5.8(1.4-6.5) 6.8(2.0~8.0) kW 1.92(0.44-2.20) 2.11(0.52~2.60)
W/W 3.02 3.22
CN 60 DCI
DCI 60 R410A
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
2-4
SM CN 1-E.1 GB
Page 11
2.5 CN 72(Z) DCI R410A
CONTENT
PRODUCT DATA SHEET
Model Indoor Unit Model Outdoor Unit
CN70 DCI
DCI 72Z R410A
Installation Method of Pipe Flared
Characteristics Units Cooling Heating
Capacity
Power input
(4)
(4)
EER (Cooling) or COP(Heating)
(4)
Btu/hr 23200(5110~25570) 24890(5110~28640)
kW 6.8(1.5-8.0) 7.3(1.5~9.0) kW 2.41(0.5-2.65) 2.27(0.5~2.92)
W/W 2.82 3.22 Energy efficiency class C C Power supply V/Ph/Hz 220-240V/Single/50Hz Rated current A 10.8 10.2 Starting current A 15 Circuit breaker rating A 20
Fan type & quantity Centifugal x 1 Fan speeds H/M/L RPM 850/750/650 850/750/650 Air flow
(1)
H/M/L m3/hr 830 830 External static pressure Min-Max Pa 0 Sound power level
(2)
Sound pressure level
(3)
H/M/L dB(A) 60 60
H/M/L dB(A) 43/35 43/35 Moisture removal l/hr 2.66 Condenstate drain tube I.D mm 20
INDOOR
Dimensions WxDxH mm 575X575X270 Weight( kg 15.5 PaCNage dimensions WxDxH mm 681X681X348 PaCNaged weight kg 18 Units per pallet units 12 StaCNing height units 6 levels Refrigerant control EEV Compressor type,model Two Rotary,Mitsubishi TNB220F Fan type & quantity Propeller(direct) x 1 Fan speeds H/L RPM 850 Air flow H/L m3/hr 3350 Sound power level H/L dB(A) 65 Sound pressure level
(3)
H/L dB(A) 55 Dimensions WxHxD mm 950x412x835 Weight kg 65 PaCNage dimensions WxHxD mm 1080x477x910 PaCNaged weight kg 70 Units per pallet Units 9
OUTDOOR
StaCNing height units 3 levels Refrigerant type R410A Refrigerant chargless distance kg/m 2.045kg/7.5m Additional charge per 1 meter g/m No Need
Liquid line In.(mm) 3/8"(9.53)
Connections
between units
Suction line In.(mm) 5/8"(15.88) Max.tubing length m. Max.30
Max.height difference m. Max.15 Operation control type Remote control Heating elements (Option) kW
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
SM CN 1-E.1 GB
2-5
Page 12
PRODUCT DATA SHEET
CONTENT
2.6 Optional accessory
Panel 625x625(Optional accessory) For all the models
Dimensions (H x L x D) mm 625x625x40 Weight kg 2.2 PaCNage Dimensions (H x L x D) mm 700x700x103 PaCNage Weight kg 3.4 Units per pallet units 20 StaCNing height units 10 levels
Panel 725x725(Optional accessory) For all the models
Dimensions (H x L x D) mm 725x725x40 Weight kg 2.7 PaCNage Dimensions (H x L x D) mm 800x800x103 PaCNage Weight kg 4.2 Units per pallet units 10 StaCNing height units 10 levels
2-6
SM CN 1-E.1 GB
Page 13
3. RATING CONDITIONS
CONTENT
Standard conditions in accordance with ISO 5151, ISO 13253 (for ducted units) and EN 14511.
Cooling:
Indoor: 27oC DB 19oC WB Outdoor: 35 oC DB
Heating:
Indoor: 20oC DB Outdoor: 7oC DB 6oC WB
3.1 Operating Limits R410A DCI (Excluding Delta Units)
o
Cooling
Upper limit Lower limit 21 Upper limit 27
Heating
Lower limit 10oC DB -15oC DB -16oC WB
32
o
o

RATING CONDITIONS

Indoor Outdoor
C DB 23oC WB 46oC DB C DB 15oC WB -10oC DB C DB 24oC DB 18oC WB
Voltage
1PH 198 – 264 V 3PH N/A
3-1SM CN 1-E.1 GB
Page 14
4. OUTLINE DIMENSIONS
CONTENT
4.1 Indoor Unit: CN 25, 35, 50, 60, 70 R410A DCI

OUTLINE DIMENSIONS

25/35 219 2 9 625/725 40 575 230 50/60/70 270 2 9 625/725 40 575 281
SM CN 1-E.1 GB
Unit
Model
Main unit
(A)
Insulation
(B)
Front
Step (C)
Front
width (D)
Front
height (E)
Unit Body Width (W)
Effective
Height (H)
4-1
Page 15
OUTLINE DIMENSIONS
CONTENT
4.2 Outdoor Unit: DCI 50
Outdoor Unit: DCI 60
4.3
4-2
SM CN 1-E.1 GB
Page 16
4.4 Outdoor Unit: DCI 72Z
CONTENT
OUTLINE DIMENSIONS
SM CN 1-E.1 GB
4-3
Page 17

PERFORMANCE DATA & PRESSURE CURVES

o
CONTENT
5. PERFORMANCE DATA
5,1 CN 25 DCI
5.1.1 Cooling Capacity (kW) – Run Mode [230V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB/WB TEMPERATURE [C0]
OD COIL
ENTERING AIR DB
TEMPERATURE [
-10 - 20
(protection range)
25
30
35
40
46
DATA
0
C]
TC 80 - 110 % of nominal SC 80 - 105 % of nominal
PI 25 - 50 % of nominal TC 2.42 2.57 2.73 2.89 3.05 SC 1.72 1.75 1.79 1.82 1.86
PI 0.46 0.47 0.48 0.49 0.50 TC 2.30 2.46 2.62 2.77 2.93 SC 1.67 1.71 1.74 1.78 1.81
PI 0.52 0.53 TC 2.18 2.34 SC 1.63 1.66 1.70 1.74 1.77
PI 0.57 0.58
TC 2.07 2.23
SC 1.59 1.62 1.66 1.69 1.73
PI 0.63 0.64 0.64 0.65 0.66
TC 1.93 2.09 2.24 2.40 2.56
SC 1.53 1.57 1.60 1.64 1.67
PI 0.69 0.70 0.71 0.72 0.73
22/15 24/17 27/19 29/21 32/23
0.54
2.50
0.59
2.38
0.54 0.55
2.66 2.82
0.60 0.61
2.54 2.70
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB – Dry Bulb Temp., (oC) ID Indoor OU – Outdoor
5.1.2 Capacity Correction Factors
Cooling Capacity Ratio Vs. Outdoor Te mperature
1.20
1.10
1.00
0.90
0.80
0.70
Capacity Rati
0.60
0.50 20 25 30 35 40 45
Outdoor Temperature [ºC]
SM CN 1-E.1 GB
5-1
Page 18
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.1.3 Heating Capacity (kW) - Run Mode
[230V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB TEMPERATURE [C0]
OD COIL ENTERING
AIR DB/WB
TEMPERATURE [
-15/-16
-10/-12
-7/-8
-1/-2
2/1
7/6
10/9
15/12
15-24
(Protection Range)
DATA 15 20 25
0
C]
TC 2.04 1.89 1.75
PI 0.48 0.53 0.58
TC 2.27 2.12 1.98
PI 0.58 0.63 0.68
TC 2.44 2.30 2.16
PI 0.65 0.70 0.75
TC 2.53 2.38 2.24
PI 0.69 0.74 0.79
TC 2.58 2.44 2.30
PI 0.71
TC 3.34
PI 0.75
TC 3.53
PI 0.80 0.84 0.89
TC 3.71 3.57 3.43
PI 0.84 0.89 0.94
TC 85 - 105 % of nominal
PI 80 - 120 % of nominal
0.76
3.20
0.80
3.38
0.81
3.06
0.85
3.24
LEGEND
TC – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB – Dry Bulb Temp., (oC) ID Indoor OU – Outdoor
5.1.4 Capacity Correction Factors
Heating Capacity Ratio Vs. Outdoor Temperature
1.20
1.10
1.00
0.90
0.80
0.70
Capacity Ration
0.60
0.50
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [deg C]
5-2
SM CN 1-E.1 GB
Page 19
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.1.5 Model: CN 25 DCI Cooling - Test Mode
Suction Pressure Vs.Outdoor Temp.
1400 1300 1200 1100 1000
900 800 700 600
Suction Pressure [kPa]
500
10 15 20 25 30 35 40 45
Outdoor DB Temperature[ºC ]
Indoor
DB/WB
22/15 24/17 27/19 29/21 32/23
Discharge Pressure [kPa]
Discharge Pressure Vs. Outdoor Temp.
4000 3750 3500 3250 3000 2750 2500 2250 2000 1750 1500 1250 1000
10 15 20 25 30 35 40 45
Outdoor DB Temperature[ºC ]
Indoor
DB/W B
22/15 24/17 27/19 29/21 32/23
SM CN 1-E.1 GB
5-3
Page 20
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.1.6 Heating - Test Mode
Suction Pressure Vs.Outdoor Temp.
1300 1200 1100 1000
900 800 700 600 500 400 300
Suction Pressure [kPa]
200
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [ºC]
15 20 25
Discharge Pressure Vs. Outdoor Temp.
4000 3750 3500 3250 3000 2750 2500 2250 2000 1750 1500 1250
Discharge Pressure [kPa]
1000
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [ºC]
Indoor DB
15 20 25
5-4
SM CN 1-E.1 GB
Page 21
PERFORMANCE DATA & PRESSURE CURVES
o
CONTENT
5.2 CN 35 DCI
5.2.1 Cooling Capacity (kW) - Run Mode [230V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB/WB TEMPERATURE [C0]
OD COIL
ENTERING AIR DB
TEMPERATURE [
-10 - 20
(protection range)
25
30
35
40
46
0
C]
TC 80 - 110 % of nominal SC 80 - 105 % of nominal
PI 25 - 50 % of nominal TC 3.38 3.60 3.83 4.05 4.27 SC 2.40 2.45 2.50 2.55 2.60
PI 0.75 0.77 0.78 0.80 0.81 TC 3.22 3.44 3.66 3.88 4.11 SC 2.34 2.39 2.44 2.49 2.54
PI 0.84 0.86 TC 3.06 3.28 SC 2.28 2.33 2.38 2.43 2.48
PI 0.93 0.95 TC 2.89 3.12 SC 2.22 2.27 2.32 2.37 2.42
PI 1.02 1.03 1.05 1.06 1.08 TC 2.70 2.92 3.14 3.36 3.58 SC 2.15 2.20 2.25 2.30 2.34
PI 1.13 1.14 1.15 1.17 1.18
DATA
22/15 24/17 27/19 29/21 32/23
0.87
3.50
0.96
3.34
0.89 0.90
3.72 3.94
0.97 0.99
3.56 3.78
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB – Dry Bulb Temp., (oC) ID Indoor OU – Outdoor
5.2.2 Capacity Correction Factor
Cooling Capacity Ratio Vs. Outdoor Te mperature
1.20
1.10
1.00
0.90
0.80
0.70
Capacity Rati
0.60
0.50 20 25 30 35 40 45
Outdoor Temperature [ºC]
SM CN 1-E.1 GB
5-5
Page 22
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.2.3 Heating Capacity (kW) - Run Mode [230V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB TEMPERATURE [C0]
OD COIL ENTERING
AIR DB/WB
TEMPERATURE [
-15/-16
-10/-12
-7/-8
-1/-2
2/1
7/6
10/9
15/12
15-24
(Protection Range)
DATA 15 20 25
0
C]
TC 2.67 2.49 2.30
PI 0.70 0.77 0.84
TC 2.98 2.79 2.60
PI 0.84 0.91 0.98
TC 3.20 3.02 2.83
PI 0.95 1.02 1.09
TC 3.32 3.13 2.94
PI 1.00 1.07 1.14
TC 3.39 3.20 3.02
PI 1.04
TC 4.39
PI 1.09
TC 4.63
PI 1.15 1.23 1.30
TC 4.87 4.68 4.50
PI 1.22 1.29 1.36
TC 85 - 105 % of nominal
PI 80 - 120 % of nominal
1.11
4.20
1.16
4.44
1.18
4.01
1.23
4.26
LEGEND
TC – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB – Dry Bulb Temp., (oC) ID Indoor OU – Outdoor
5.2.4 Capacity Correction Factors
Heating Capacity Ratio Vs. Outdoor Temperature
1.20
1.10
1.00
0.90
0.80
0.70
Capaci ty Ration
0.60
0.50
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [deg C]
5-6
SM CN 1-E.1 GB
Page 23
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.2.5 Model: CN 35 DCI Cooling - Test Mode
Suction Pressure VS.Outdoor Temp.
1400
1300
1200
1100
1000
900
800
700
Suction Pressure [kPa]
600
500
10 15 20 25 30 35 40 45
Outdoor DB Temperature[ºC ]
Indoor DB/WB
22/15 24/17 27/19 29/21 32/23
Discharge Pressure VS. Outdoor Temp.
4000 3750 3500 3250 3000 2750 2500 2250 2000 1750 1500
Discharge Pressure [kPa]
1250 1000
10 15 20 25 30 35 40 45
Outdoor DB Temperature[ºC ]
Indoor
DB/WB
22/15 24/17 27/19 29/21 32/23
SM CN 1-E.1 GB
5-7
Page 24
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.2.6 Heating - Test Mode
Suction Pressure VS.Outdoor Temp.
1300 1200 1100 1000
900 800 700 600 500 400
Suction Pressure [kPa]
300 200
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [ºC]
15 20 25
Discharge Pressure VS. Outdoor Temp.
4000 3750 3500 3250 3000 2750 2500 2250 2000 1750 1500
Discharge Pressure [kPa]
1250 1000
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [ºC]
Indoor DB
15 20 25
5-8
SM CN 1-E.1 GB
Page 25
PERFORMANCE DATA & PRESSURE CURVES
o
CONTENT
5.3 CN 50 DCI
5.3.1 Cooling Capacity (kW) - Run Mode [230V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB/WB TEMPERATURE [C0]
OD COIL
ENTERING AIR DB
TEMPERATURE [
-10 - 20
(protection range)
25
30
35
40
46
DATA
0
C]
TC 80 - 110 % of nominal
SC 80 - 105 % of nominal
PI 25 - 50 % of nominal
TC 4.83 5.15 5.47 5.78 6.10
SC 3.43 3.50 3.57 3.64 3.71
PI 1.23 1.25 1.27 1.30 1.32
TC 4.60 4.92 5.23 5.55 5.86
SC 3.35 3.42 3.49 3.56 3.63
PI 1.37 1.39
TC 4.37 4.68
SC 3.26 3.33 3.40 3.47 3.54
PI 1.51 1.54
TC 4.14 4.45
SC 3.17 3.24 3.31 3.38 3.45
PI 1.66 1.68 1.70 1.73 1.75
TC 3.86 4.17 4.49 4.80 5.12
SC 3.07 3.14 3.21 3.28 3.35
PI 1.83 1.85 1.88 1.90 1.92
22/15 24/17 27/19 29/21 32/23
1.42
5.00
1.56
4.77
1.44 1.46
5.32 5.63
1.58 1.61
5.08 5.40
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB – Dry Bulb Temp., (oC) ID Indoor OU – Outdoor
5.3.2 Capacity Correction Factors
Cooling Capacity Ratio Vs . Outdoor Temperature
1.20
1.10
1.00
0.90
0.80
0.70
Capacity Rati
0.60
0.50
20 25 30 35 40 45
Outdoor Temperature [ºC]
SM CN 1-E.1 GB
5-9
Page 26
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.3.3 Heating Capacity (kW) - Run Mode [230V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB TEMPERATURE [C0]
OD COIL ENTERING
AIR DB/WB
TEMPERATURE [
-15/-16
-10/-12
-7/-8
-1/-2
2/1
7/6
10/9
15/12
15-24
(Protection Range)
DATA 15 20 25
0
C]
TC 3.69 3.43 3.18
PI 0.96 1.06 1.16
TC 4.11 3.85 3.59
PI 1.16 1.26 1.35
TC 4.42 4.16 3.91
PI 1.31 1.40 1.50
TC 4.58 4.32 4.06
PI 1.38 1.48 1.57
TC 4.68 4.43 4.17
PI 1.43
TC 6.06
PI 1.50
TC 6.39
PI 1.59 1.69 1.79
TC 6.73 6.47 6.21
PI 1.68 1.78 1.88
TC 85 - 105 % of nominal
PI 80 - 120 % of nominal
1.53
5.80
1.60
6.13
1.62
5.54
1.70
5.88
LEGEND
TC – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB – Dry Bulb Temp., (oC) ID Indoor OU – Outdoor
5.3.4 Capacity Correction Factors
Heating Capacity Ratio Vs. Outdoor Temperature
1.20
1.10
1.00
0.90
0.80
0.70
Capaci ty Ration
0.60
0.50
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [deg C]
5-10
SM CN 1-E.1 GB
Page 27
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.3.5 Model: CN 50 DCI Cooling - Test Mode
Suction Pressure VS.Outdoor Temp.
1400
1300
1200
1100
1000
900
800
700
Suction Pressure [kPa]
600
500
10 15 20 25 30 35 40 45
Outdoor DB Temperature[ºC ]
Indoor
DB/WB
22/15 24/17 27/19 29/21 32/23
4250
Discharge Pressure VS. Outdoor Temp.
4000 3750 3500 3250 3000 2750 2500 2250 2000 1750 1500
Discharge Pressure [kPa]
1250 1000
10 15 20 25 30 35 40 45
Outdoor DB Temperature[ºC ]
Indoor
DB/WB
22/15 24/17 27/19 29/21 32/23
SM CN 1-E.1 GB
5-11
Page 28
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.3.6 Heating - Test Mode
Suction Pressure VS.Outdoor Temp.
1100 1000
900
800 700 600 500
400
Suction Pressure [kPa]
300 200
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [ºC]
15 20 25
Discharge Pressure VS. Outdoor Temp.
4000 3750 3500 3250 3000 2750 2500 2250 2000 1750 1500
Discharge Pressure [kPa]
1250 1000
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [ºC]
Indoor DB
15 20 25
5-12
SM CN 1-E.1 GB
Page 29
PERFORMANCE DATA & PRESSURE CURVES
o
CONTENT
5.4 CN 60 DCI
5.4.1 Cooling Capacity (kW) - Run Mode [230V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB/WB TEMPERATURE [C0]
OD COIL
ENTERING AIR DB
TEMPERATURE [
-10 - 20
(protection range)
25
30
35
40
46
DATA
0
C]
TC 80 - 110 % of nominal
SC 80 - 105 % of nominal
PI 25 - 50 % of nominal
TC 5.61 5.97 6.34 6.71 7.07
SC 3.98 4.06 4.15 4.23 4.31
PI 1.51 1.54 1.57 1.60 1.62
TC 5.34 5.70 6.07 6.44 6.80
SC 3.88 3.96 4.04 4.13 4.21
PI 1.69 1.71
TC 5.07 5.43
SC 3.78 3.86 3.94 4.03 4.11
PI 1.86 1.89
TC 4.80 5.16
SC 3.68 3.76 3.84 3.92 4.01
PI 2.04 2.07 2.10 2.13 2.15
TC 4.47 4.84 5.21 5.57 5.94
SC 3.56 3.64 3.72 3.80 3.89
PI 2.25 2.28 2.31 2.34 2.37
22/15 24/17 27/19 29/21 32/23
1.74
5.80
1.92
5.53
1.77 1.80
6.17 6.53
1.95 1.98
5.90 6.26
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB – Dry Bulb Temp., (oC) ID Indoor OU – Outdoor
5.4.2 Capacity Correction Factors
Cooling Capacity Ratio Vs . Outdoor Temperature
1.20
1.10
1.00
0.90
0.80
0.70
Capacity Rati
0.60
0.50 20 25 30 35 40 45
Outdoor Temperature [ºC]
SM CN 1-E.1 GB
5-13
Page 30
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.4.3 Heating Capacity (kW) - Run Mode [230V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB TEMPERATURE [C0]
OD COIL ENTERING
AIR DB/WB
TEMPERATURE [
-15/-16
-10/-12
-7/-8
-1/-2
2/1
7/6
10/9
15/12
15-24
(Protection Range)
DATA 15 20 25
0
C]
TC 4.33 4.03 3.72
PI 1.27 1.40 1.52
TC 4.82 4.52 4.21
PI 1.53 1.66 1.78
TC 5.19 4.88 4.58
PI 1.72 1.85 1.98
TC 5.37 5.07 4.76
PI 1.82 1.95 2.08
TC 5.49 5.19 4.89
PI 1.88
TC 7.10
PI 1.98
TC 7.49
PI 2.10 2.23 2.36
TC 7.89 7.58 7.28
PI 2.22 2.35 2.48
TC 85 - 105 % of nominal
PI 80 - 120 % of nominal
2.01
6.80
2.11
7.19
2.14
6.50
2.24
6.89
LEGEND
TC – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB – Dry Bulb Temp., (oC) ID Indoor OU – Outdoor
5.4.4 Capacity Correction Factors
Heating Capacity Ratio Vs. Outdoor Temperature
1.20
1.10
1.00
0.90
0.80
0.70
Capaci ty Ration
0.60
0.50
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [deg C]
5-14
SM CN 1-E.1 GB
Page 31
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.4.5 Model: CN 60 DCI Cooling – Test Mode
Suction Pressure Vs.Outdoor Temp.
1100 1050 1000
950 900 850 800 750 700 650
Suction Pressure [kPa]
600
4000 3750 3500 3250 3000 2750 2500 2250 2000 1750 1500 1250
Discharge Pressure [kPa]
1000
Indoor DB/WB
22/15 24/17 27/19 29/21 32/23
10 15 20 25 30 35 40 45
Outdoor DB Temperature[oC]
Discharge Pressure Vs.Outdoor Temp.
Indoor DB/WB
22/15 24/17 27/19 29/21 32/23
10 15 20 25 30 35 40 45
Outdoor DB Temperature[oC]
SM CN 1-E.1 GB
5-15
Page 32
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.4.6 Heating – Test Mode
Suction Pressure Vs.Outdoor Temp.
1200 1100 1000
900 800 700 600 500 400 300
Suction Pressure [kPa]
200
-15 -10 -5 0 5 10 15
Outdoor WB Temperature[
Indoor DB
1 5
2 0
2
o
C]
Discharge Pressure [kPa]
Discharge Pressure Vs. Outdoor Temp.
3750 3500 3250 3000 2750 2500 2250 2000 1750 1500
-15 -10 -5 0 5 10 15
Outdoor WB Temperature[
o
C]
Indoor DB
15
20
25
5-16
SM CN 1-E.1 GB
Page 33
PERFORMANCE DATA & PRESSURE CURVES
o
CONTENT
5.5 CN 70 DCI
5.5.1 Cooling Capacity (kW) - Run Mode [230V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB/WB TEMPERATURE [C0]
OD COIL
ENTERING AIR DB
TEMPERATURE [
-10 - 20
(protection range)
25
30
35
40
46
DATA
0
C]
TC 80 - 110 % of nominal
SC 80 - 105 % of nominal
PI 25 - 50 % of nominal
TC 6.57 7.00 7.43 7.86 8.29
SC 4.67 4.76 4.86 4.96 5.05
PI 1.89 1.93 1.97 2.00 2.04
TC 6.26 6.69 7.12 7.55 7.98
SC 4.55 4.65 4.74 4.84 4.93
PI 2.12 2.15
TC 5.94 6.37
SC 4.43 4.53 4.62 4.72 4.81
PI 2.34 2.37
TC 5.62 6.05
SC 4.32 4.41 4.51 4.60 4.70
PI 2.56 2.60 2.63 2.67 2.70
TC 5.24 5.67 6.10 6.53 6.96
SC 4.17 4.27 4.36 4.46 4.56
PI 2.83 2.86 2.90 2.93 2.97
22/15 24/17 27/19 29/21 32/23
2.19
6.80
2.41
6.48
2.22 2.26
7.23 7.66
2.45 2.48
6.91 7.34
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB – Dry Bulb Temp., (oC) ID Indoor OU – Outdoor
5.5.2 Capacity Correction Factors
Cooling Capacity Ratio Vs . Outdoor Temperature
1.20
1.10
1.00
0.90
0.80
0.70
Capacity Rati
0.60
0.50 20 25 30 35 40 45
Outdoor Temperature [ºC]
SM CN 1-E.1 GB
5-17
Page 34
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.5.3 Heating Capacity (kW) - Run Mode [230V] : Indoor Fan at High Speed
ID COIL ENTERING AIR DB TEMPERATURE [C0]
OD COIL ENTERING
AIR DB/WB
TEMPERATURE [
-15/-16
-10/-12
-7/-8
-1/-2
2/1
7/6
10/9
15/12
15-24
(Protection Range)
DATA 15 20 25
0
C]
TC 4.65 4.32 4.00
PI 1.36 1.50 1.64
TC 5.17 4.85 4.52
PI 1.64 1.78 1.92
TC 5.57 5.24 4.92
PI 1.85 1.99 2.13
TC 5.76 5.44 5.11
PI 1.96 2.10 2.23
TC 5.89 5.57 5.25
PI 2.03
TC 7.62
PI 2.13
TC 8.05
PI 2.26 2.40 2.54
TC 8.47 8.14 7.82
PI 2.39 2.52 2.66
TC 85 - 105 % of nominal
PI 80 - 120 % of nominal
2.17
7.30
2.27
7.72
2.30
6.98
2.41
7.40
LEGEND
TC – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (oC) DB – Dry Bulb Temp., (oC) ID Indoor OU – Outdoor
5.5.4 Capacity Correction Factors
Heating Capacity Ratio Vs. Outdoor Temperature
1.20
1.10
1.00
0.90
0.80
0.70
Capaci ty Ration
0.60
0.50
-15 -10 -5 0 5 10 15
Outdoor WB Temperature [deg C]
5-18
SM CN 1-E.1 GB
Page 35
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.5.5 Model: CN 70 DCI Cooling – Test Mode
Suction Pressure Vs. Outdoor Temp.
1000
960 920 880 840 800 760 720 680
Suction Pressure [kPa]
640 600
10 15 20 25 30 35 40 45
Outdoor DB Temperature[OC]
Indoor DB/WB
22/15
24/17
27/19
29/21
32/23
Discharge Pressure [kPa]
Discharge Pressure Vs. Temp.
3900 3700 3500 3300 3100 2900 2700 2500 2300 2100 1900 1700 1500
10 15 20 25 30 35 40 45
Outdoor DB Temperature[OC]
Indoor DB/WB
22/15
24/17
27/19
29/21
32/23
SM CN 1-E.1 GB
5-19
Page 36
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.5.6 Heating – Test Mode
Suction Pressure Vs. Outdoor Temp.
1050
950 850 750 650 550 450 350
Suction Pressure [kPa]
250
-15 -10 -5 0 5 10 15 Outdoor WB Temperature[
Indoor DB
15
20
25
O
C]
3700 3500 3300 3100 2900 2700 2500 2300 2100
Discharge Pressure [kPa]
1900 1700
Discharge Pressure Vs. Outdoor Temp.
-15 -10 -5 0 5 10 15 Outdoor WB Temperature[
O
C]
Indoor DB
15
20
25
5-20
SM CN 1-E.1 GB
Page 37
PERFORMANCE DATA & PRESSURE CURVES
CONTENT
5.6 Capacity Correction Factor Due to Tubing Length
5.6.1 Cooling
TOTAL TUBING LENGTH
Model
ז
3m
1.02
7.5m 1
10m 15m 20m 25m 30m 40m 50m
0.98 0.96 0.95 0.95 0.93 --- ---
* Minimum recommended tubing length between indoor and outdoor units is 3m.w
5.6.2 Heating
TOTAL TUBING LENGTH
Model
3m
1.02
7.5m 1
10m 15m 20m 25m 30m 40m 50m
0.98 0.96 0.95 0.95 0.93 --- ---
* Minimum recommended tubing length between indoor and outdoor units is 3m.
5.7 Fresh air volume to the external static pressure (Field option)
KnoCN-down opening :φ100mm on the casing for the fresh duct Fresh air control: by external booster fan Select the fresh air volume according to required external static pressure.
Fresh air volume Vs. ESP
)h/3m(emuloVriAhserF
70.0
60.0
50.0
40.0
30.0
20.0
10.0
0.0 10 15 20 25 30 35 40
ESP(Pa)
5.8 Conditioned air supply to adjacent room (Field option) (To be finished)
SM CN 1-E.1 GB
5-21
Page 38

SOUND LEVEL CHARACTERISTICS

CONTENT
6. SOUND LEVEL CHARACTERISTICS
6.1 Sound Pressure Level
1.5m
Unit
Mic.
Figure 1
6.2 Soud Pressure Level Spectrum (Measured as Figure 1)
CN 25 CN 35
NC-70
NC-60
NC-50
NC-70
NC-60
NC-50
APPROXIMATE THRESHOLD OF
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
HEARING FOR CONTINUOUS NOISE
BAND CENTER FREQUENCIES, Hz
FAN SPEED LINE
HI
ME
LO
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-40
NC-30
NC-20
BAND CENTER FREQUENCIES, Hz
SM CN 1-E.1 GB
6-1
Page 39
SOUND LEVEL CHARACTERISTICS
CONTENT
CN 50 CN 60
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
BAND CENTER FREQUENCIES, Hz
CN 70
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
BAND CENTER FREQUENCIES, Hz
APPROXIMATE THRESHOLD OF
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR
HEARING FOR CONTINUOUS NOISE
BAND CENTER FREQUENCIES, Hz
FAN SPEED LINE
HI
ME
LO
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
6-2
SM CN 1-E.1 GB
Page 40
6.3 Outdoor units
CONTENT
MODEL SPL dB(A) SPW dB(A)
Indoor Outdoor Cooling/Heating Cooling/Heating
CN 25 DCI 25 50/51 60/61 CN 35 DCI 35 52/52 62/62 CN 50 DCI 50 52/53 62/63 CN 60 DCI 60 55/55 65/65 CN 70 DCI 72Z 56/56 66/66
SOUND LEVEL CHARACTERISTICS
Unit
Mic.
Ground
Figure 2
6.4 Sound Pressure Level Spectrum (Measured as Figure 2)
DCI 25 Cooling DCI 25 Heating
SM CN 1-E.1 GB
6-3
Page 41
SOUND LEVEL CHARACTERISTICS
CONTENT
DCI 35 Cooling DCI 35 Heating
DCI 50 Cooling DCI 50 Heating
FAN SPEED LINE
6-4
HI
ME
LO
SM CN 1-E.1 GB
Page 42
SOUND LEVEL CHARACTERISTICS
CONTENT
DCI 60 Cooling DCI 60 Heating
DCI 72 Cooling DCI 72 Heating
FAN SPEED LINE
SM CN 1-E.1 GB
HI
ME
LO
6-5
Page 43

ELECTRICAL DATA

CONTENT
7. ELECTRICAL DATA
7.1 Single Phase Units
MODEL CN 25 DCI CN 35 DCI CN 50 DCI CN 60 DCI CN 70 DCI
To indoor To indoor To indoor To indoor To outdoor
Power Supply
Max Current, A 10 10 12 13 14 Inrush Current A 35 35 35 35 45 Starting Current A 10.5 10.5 10.5 10.5 10.5
Circuit Breaker A 16 16 20 20 20 Power Supply Wiring No.X Cross
Section mm Interconnecting Cable No.X Cross
Section mm
2
2
Power wiring cord should comply with local lows and electrical regulations requirements.
1PH-230V-50Hz 1PH-230V-50Hz 1PH-230V-50Hz 1PH-230V-50Hz 1PH-230V-50Hz
3 x 1.5 mm
4 x 1.5 mm
2
2
3 x 1.5 mm
4 x 1.5 mm
2
2
3 x 2.5 mm
4 x 2.5 mm
2
2
3 x 2.5 mm
4 x 2.5 mm
2
2
3 x 2.5 mm
4 x 2.5 mm
NOTE
2
2
SM CN 1-E.1 GB
7-1
Page 44
8. WIRING DIAGRAMS
CONTENT
8.1 CN 25, 35, 50, 60, 70 DCI

WIRING DIAGRAMS

SM CN 1-E.1 GB
8-1
Page 45
WIRING DIAGRAMS
CONTENT
8.2 Outdoor Unit: DCI 72Z
RED
U
3P
L
N
PMOC
BLK
BRN
V
W
9P
11P
01P
MOC
CORE
FERRITE
WHITE
31P
MOC-N
KCALB
DER
EULB
NWORB
EKOHC
LIOC
BLUE
41P
G/Y
ESREVER
EVLAV
ESAB
RETAEH
)LANOITPO(
NAFO
TTCTCO
TSHTAOTMO
143562
2
1
4P
21
1P
1
112
6P
ABCPRELLORTNOCUDO
21P
9PJ
321HTRAE
654
65
2 02P
91P
7P
342
12
2211
2P
5P
8P
1
VEE
SNIAMCA
ABCPRETLIFIME
HTRAE
MOCN
MOC
F-N
F-L
HTRAE
MOC
N
L
L
ESUF
N
DER
NWORB
EULB
DER
NWORB
EULB
EROCETIRREF
CNLNL
OT
UDI
8-2
SM CN 1-E.1 GB
Page 46
9. REFRIGERATION DIAGRAMS
CONTENT
9.1 CN 25, 35, 50, 60, 70 DCI Cooling Mode
VEE

REFRIGERATION DIAGRAMS

Heating Mode
EEV
SM CN 1-E.1 GB
9-1
Page 47
10. TUBING CONNECTIONS
CONTENT

TUBING CONNECTIONS

TUBE (Inch)
¼” ⅜” ½” ⅝” ¾”
TORQUE (Nm)
Flare Nuts 11-13 40-45 60-65 70-75 80-85 Valve Cap 13-20 13-20 18-25 18-25 40-50
Service Port Cap 11-13 11-13 11-13 11-13 11-13
1. Valve Protection Cap-end
2. Refrigerant Valve Port (use Allen wrench to open/close)
3. Valve Protection Cap
4. Refrigerant Valve
5. Service Port Cap
6. Flare Nut
7. Unit BaCN Side
8. Copper Tube
When the outdoor unit is installed above the indoor unit an oil trap is required every 5m along the suction line at the lowest point of the riser. Incase the indoor unit is installed above the outdoor, no trap is required.
SM CN 1-E.1 GB
10-1
Page 48

CONTROL SYSTEM

CONTENT
11. CONTROL SYSTEM
11.1 General Functions and Operating RulesThe DCI software is fully parametric.
All the model dependent parameters are shown in Blue color and with Italic style [parameter]. The parameters values are given in the last section of this control logic chapter of the service man­ual.
11.1.1 System Operation Concept
The control function is divided between indoor and outdoor unit controllers. Indoor unit is the system ‘Master’, requesting the outdoor unit for cooling/heating capacity supply. The outdoor unit is the system ‘Slave’ and it must supply the required capacity unless it enters into a protection mode avoiding it from supplying the requested capacity. The capacity request is transferred via indoor to outdoor communication, and is represented by a parameter called ‘NLOAD’. NLOAD is an integer number with values between 0 and 127, and it represents the heat or cool load felt by the indoor unit.
11.1.2 Compressor Frequency Control
11.1.2.1 NLOAD setting
The NLOAD setting is done by the indoor unit controller, based on a PI control scheme. The actual NLOAD to be sent to the outdoor unit controller is based on the preliminary LOAD calculation, the indoor fan speed, and the power shedding function. NLOAD limits as a function of indoor fan speed:
Indoor Fan Speed Maximum NLOAD Cooling Maximum NLOAD Heating
Indoor Fan Speed Maximum NLOAD Cooling Maximum NLOAD Heating
Low MaxNLOADIF1C MaxNLOADIF1H Medium MaxNLOADIF2C MaxNLOADIF2H High MaxNLOADIF3C MaxNLOADIF3H Turbo MaxNLOADIF4C MaxNLOADIF4H Auto MaxNLOADIF5C MaxNLOADIF5H
NLOAD limits as a function of power shedding:
Mode Power Shedding OFF Power Shedding ON Cooling No limit Nominal Cooling
Heating No limit Nominal heating
11.1.3 Target Frequency Setting
11.1.3.1 Target Frequency Setting for DCI 25/35/50/60/72Z
The compressor target frequency is a function of the NLOAD number sent from the indoor controller and the outdoor air temperature.
Basic Target Frequency Setting: Up to SW 35V12
SM CN 1-E.1 GB
NLOAD Target Frequency [Hz]
<10 0 10 MinFreqC in cool OR MinFreqH in heat mode
11-126
127 MaxFreqC in cool OR MaxFreqH in heat mode.
NLOAD (as long it is in the allowed range, if not, the MinFreqC or Max FreqC in cool mode OR MinFreqH or MaxFreqH in heat mode will be selected).
11-1
Page 49
CONTROL SYSTEM
CONTENT
SW 35V14 and above
NLOAD Target Frequency [Hz]
0 0
0 < NLOAD ≤ MinFreq MinFreq
MinFreqMaxFreq
> MinFreq
MinFreqneLoadDeadZo
MinFreqMinFreq}ne)LoadDeadZo(NLOAD,{min
Differences between Old and New ODU DCI/DCR software
Unit Current software New software
DCI 35V12 35V14
Comment: there is no use for 35V13 software. This software is used in the past for Nordic countries. However, currently
it’s stopped completely from being used.
Graphical Illustration:
Target Frequency
LoadDeadZone allowed in this range
MaxFreq
MinFreq
MaxFreq
MinFreq
LoadDeadZone
Minimum Allowed Linearization
Maximum Allowed Linearization
NLOAD
(Run Phase)
MinFreq
Mode
(
MaxFreq
During initial period
(Start Phase)
)
127LoadDeadZone
After initial period
Cool MaxFreqC MaxFreqCRunPhase Heat MaxFreqH MaxFreqHRunPhase Cool MinFreqC Heat MinFreqH Cool LoadDeadZoneC Heat LoadDeadZoneH
#NameASingle
1 MinFreqC 30 33 20 20 20 20 38 20 20 2 MaxFreqC 64 80 85 95 97 77 93 100 77 3 MaxFreqCRunPhase 64 80 85 95 97 77 85 95 77 4 MinFreqH 30 35 20 26 26 26 38 25 26 5 MaxFreqH 81 93 95 94 106 79 100 100 79 6 MaxFreqHRunPhase 81 93 95 94 106 79 90 95 79 7 LoadDeadZoneC 90 95 95 111 97 90 93 127 90 8 LoadDeadZoneH 127 127 127 127 106 127 100 100 127
11-2
DCI-25
B
Single
DCI-35
C Single DCI-50
D Single DCI 60
E
Duo
50
F
DCR
50
G
Duo
Delta38
Trio
Delta52
SM CN 1-E.1 GB
H
I
DCR
50T
Page 50
CONTROL SYSTEM
CONTENT
Target frequency limits as a function of outdoor air temperature (OAT):
OAT Range Cooling Mode limits Heating Mode limits OAT < 6 6 ≤ OAT < 15 MaxFreqAsOAT1H
MaxFreqAsOATC
No limit
15≤ OAT<28
MaxFreqAsOAT2H
28≤ OAT No limit
11.1.4 Frequency Changes Control
When the unit is running normally , the compressor frequency change rate is 1 Hz/sec.
11.1.5 Compressor Starting Control
11.1.5.1 Compressor starting control for DCI25/35/50/60
Step3
Step2
Step1
1
1
Minute
11.1.5.2 Compressor starting control for DCI72Z
Step 1
Minute
Min 10 Minutes
Time
Whenever the compressor starts up, after it has been off for more than 45 minutes, the compressor frequency cannot go below Step1RPS for 3 continuous minutes (this rule comes to ensure oil return to the compressor).
Step 2
The compressor speed cannot go above Step2RPS once after each compressor start up for 3 continuous minutes (this rule comes to prevent oil exit from the compressor after its start up).
Step 3
The speed cannot go higher than Step3RPS unless it was operating for more than 1 continuous minutes between Step3RPS – 5 and Step3RPS . After passing above Step3RPS, this rule is re-applied when passing below Step3RPS-5.
SM CN 1-E.1 GB
11-3
Page 51
CONTROL SYSTEM
CONTENT
11.1.6 Minimum On and Off Time
3 minutes
11.1.7 Indoor Fan Control
8 Indoor fan speeds are determined for each model. 4 speeds for cool/dry/fan modes and 4speeds for heat mode. When user sets the indoor fan speed to a fixed speed (Low/ Medium/ High), unit will operate constantly at set speed. When Auto Fan is selected, indoor unit controller can operate in all speeds. The actual speed is set according to the cool/heat load.
11.1.7.1 Turbo Speed
The Turbo speed is activated during the first 30 minutes of unit operation when auto fan speed is selected and under the following conditions: Difference between set point and actual room temperature is bigger then 3 degrees. Room temperature > 22 for cooling, or < 25 for heating.
11.1.8 Outdoor Fan Control
11.1.8.1 Outdoor Fan Control for DCI25/35/50/60
7 outdoor fan speeds are determined for each model. 3 speeds for cool and dry modes, and 3speeds for heat mode, and a very low speed. Outdoor fan speed is a function of compressor frequency and outdoor air temperature (OAT). 4 routines for fan control are determined. The control routine selection depends on operation mode, compressor speed, outdoor air temperature (OAT) and heat sink temperature (HST).
Routine Conditions
A
Heating with OAT < 15 or Cooling with OAT > 20ഒ, or Faulty OAT
B Cooling with 20 > OAT > 7 C Cooling with 7 > OAT D Heating with OAT > 15
OFAN Speed
Compressor
Target Frequency
Freq=0 OFF OFF OFF OFF
10 ≤ Freq < OFLowFreq Low Low VL Low
OFLowFreq ≤ Freq< OFMedFreq
OFMedFreq≤ Freq High Low Low Medium
Routin
A
Medium Low VL Low
Routin
B
Routin
C
Routin
D
11-4
SM CN 1-E.1 GB
Page 52
CONTROL SYSTEM
CONTENT
OFAN State at Cool Mode
$
%
&
Note: Periorities A>B>C
3 Degrees
3 Degrees

2$ 7
HST
Change To Higher
OFAN Cool state (*1)
50
45
Change To lower OFAN Cool state
(*1) If State C, change to B
If State B, change to A
When compressor is switched to OFF and the heat sink temperature is above 55 degrees, the outdoor fan will remain ON in low speed for up to 3 minutes.
11.1.8.2 Outdoor Fan Control for DCI72Z
OFAN operates between OFMinRPM to OFMaxRPM. Min time for speed change of OFAN OFMinTimeReduce (60 seconds). There are 4 defined speeds – High, Med, Low, and Very Low. The actual OFAN speeds in cool mode are defined according to the following table:
Freq
15 25 130 140 160 190 250 380 600 610 670 730 740 750 35 160 180 210 250 330 470 730 730 730 730 780 800 45 205 230 260 320 440 600 730 730 730 730 800 850 55 250 280 310 390 550 730 730 730 730 730 800 850 65 275 315 355 470 640 730 730 730 730 730 800 850 75
85 95
-10-5 0 5 1015 202530354046
0
00000 0 000000
80 100 120 130 220 340 460 580 600 730 730 730
300 350 400 550 730 730 730 730 730 730 800 850
325 395 445 630 730 730 730 730 730 730 800 850 350 440 490 710 730 730 730 730 730 730 800 850
Outdoor air temperature (OAT)
The actual OFAN speeds in heat mode are defined according to the following table
Freq
0 15 25 850 850 750 750 520 370 320 35 850 850 750 750 540 390 340 45 850 850 750 750 560 410 360 55 850 850 750 750 580 430 380 65 850 850 750 750 600 450 400 75 850 850 750 750 620 470 420 85 850 850 750 750 640 490 440 95
Outdoor air temperature (OAT)
-15 -7 0 7 14 21 24
000000 0
850 850 750 750 500 350 300
850 850 750 750 650 500 450
The fan speed is also related to protections and OMT value.
SM CN 1-E.1 GB
11-5
Page 53
CONTROL SYSTEM
CONTENT
11.1.9 EEV (Electronic Expansion Valve) Control
11.1.9.1 EEV Control for DCI25/35/50/60
EEV opening is defined as EEV = EEV EEV
is the initial EEV opening as a function of the compressor frequency, operation mode, unit
OL
+ EEV
OL
CV
model and capacity. EEV During the first 5 minutes of compressor operation EEV
is a correction value for the EEV opening that is based on the compressor temperature.
CV
CV
= 0.
Once the first 5 minutes are over, the correction value is calculated as follow: EEVCV(n) = EEVCV(n-1) + EEV EEV
CTT
is the correction based on the compressor temperature. A target compressor temperatureзs
CTT
set depending on frequency and outdoor air temperature, and the actual compressor temperature is compared to the target temperature to set the required correction to the EEVopening.
11.1.9.2 EEV Control for DCI72Z
The target EEV value is the sum of open loop value (OL) and a result of the accumulative correction values (CV).
EEVEEVEEV
CVOL
Initial EEV value is set according to compressor frequency and according to indoor and outdoor model The corrective value is calculate every 30 sec the EEV corrective value is set to keep the discharged super heat temperature between 20º to 30º in cooling and 12º to 20º in heating.
11-6
SM CN 1-E.1 GB
Page 54
CONTROL SYSTEM
CONTENT
11.1.10 RV(Reversing Valve) Control
Reversing valve is on in heat mode. Switching of RV state is done only after compressor is off for over 3 minutes.
11.1.10.1 Ioniser Control
Ioniser is on when unit is on ,AND indoor fan is on ,AND Ioniser power switch (on grille) is on.
11.1.10.2 Base Heater Control
The base heater will be working only when RV is “ON” according to the following graph:
Base
Heater
OFF
ON
0
2
OAT
When OAT is faulty the base heater will be “ON” continuously in HEAT mode.
11.1.11 Fan Mode
In high/ medium/ low indoor fan user setting, unit will operate fan in selected speed. In AutoFan user setting, fan speed will be adjusted automatically according to the difference between actual room temperature and user set point temperature.
11.1.12 Cool Mode
NLOAD is calculated according to the difference between actual room temperature and user set point temperature by fuzzy control. In high/ medium/ low indoor fan user setting, unit will operate fan in selected speed. In AutoFan user setting, fan speed will be adjusted automatically according to the calculated NLOAD.
11.1.13 Heat Mode
NLOAD is calculated according to the difference between actual room temperature and user set point temperature by fuzzy control. In high/ medium/ low indoor fan user setting, unit will operate fan in selected speed. In AutoFan user setting, fan speed will be adjusted automatically according to the calculated NLOAD.
11.1.11.1 Temperature Compensation
In ducted and cassette models, 3 degrees are reduced from room temperature reading (except when in I-Feel mode), to compensate for temperature difference between high and low areas in the heated room, and for coil heat radiation on room thermistor. The temperature compensation can be enabled/disabled by shortening of J2 on the indoor unit
Controller
SM CN 1-E.1 GB
Model J2 Shorted J2 Opened Cassette Compensation Enabled Compensation Disabled
Ducted Compensation Enabled Compensation Disabled
11-7
Page 55
CONTROL SYSTEM
CONTENT
11.1.11.2 Indoor Fan Control in Heating Mode
Indoor fan speed depends on the indoor coil temperature:
11.1.14 Auto Cool/Heat Mode
When in auto cool heat mode unit will automatically select between cool and heat mode according to the difference between actual room temperature and user set point temperature (.T). Unit will switch from cool to heat when compressor is off for 3 minutes, and .T < -3. Unit will switch from heat to cool when compressor is off for 5 minutes, and .T < -3.
11.1.15 Dry Mode
As long as room temperature is higher then the set point, indoor fan will work in low speed and compressor will work between 0 and MaxNLOADIF1C Hz. When the room temperature is lower than the set point, compressor will be switched OFF and indoor fan will cycle 3 minutes OFF, 1 minute ON.
11.1.16 Protections
There are 5 protection codes. Normal (Norm) – unit operate normally. Stop Rise (SR) – compressor frequency can not be raised but does not have to be decreased. HzDown1 (D1) – Compressor frequency is reduced by 2 to 5 Hz per minute. HzDown2 (D2) – Compressor frequency is reduced by 5 to 10 Hz per minute. Stop Compressor (SC) – Compressor is stopped.
11.1.16.1 Indoor Coil Defrost Protection — CN
Min(ICT,ICTE)
Fast Increasing Increasing No Change Decreasing Fast Decreasing
< -2 SC SC SC SC SC [-2, 0) D1 D1 D2 D2 D2 [0, 2) SR SR D1 D2 D2 [2, 4) SR SR SR D1 D2 [4, 6) Norm Norm SR SR D1 [6, 8] Norm Norm Norm SR SR > 8 Norm
Trend
11-8
SM CN 1-E.1 GB
Page 56
11.1.16.2 Indoor Coil Defrost Protection — CN
p
r
CONTENT
CONTROL SYSTEM
ICT
Fast Increasing Increasing No Change Decreasing Fast Decreasing
< -2 SC SC SC SC SC [-2, 0) D1 D1 D2 D2 D2 [0, 2) SR SR D1 D2 D2 [2, 4) SR SR SR D1 D2 [4, 6) Norm Norm SR SR D1 [6, 8] Norm Norm Norm SR SR > 8 Norm
11.1.16.3 Indoor Coil Overheating Protection
ICT
Fast Decreasing Decreasing No Change Increasing Fast Increasing
>62 SC SC SC SC SC [60, 62) D1 D1 D2 D2 D2 [55, 60) SR SR D1 D2 D2 [52, 55) SR SR SR D1 D2 [48, 52) Norm Norm SR SR D1 [45, 48) Norm Norm Norm SR SR I<45 Norm
Trend
ICT Trend
11.1.17 Compressor Overheating Protection
11.1.17.1 Compressor Overheating Protection for DCI25/35/50/60/72Z
Compressor temperature can be in one of 5 control zones (4 in protection, and 1 normal), according to the following chart.
CTT
-Compresso
Sto
105
P3
102
P2
98
P1
94
Normal
Control Status Compressor Temperature Increases Else
P1 Normal Stop Rise P2 HzDown 1 Stop Rise P3 HzDown 2 HzDown 1 Stop Compressor Stop Compressor
SM CN 1-E.1 GB
11-9
Page 57
CONTROL SYSTEM
CONTENT
11.1.17.2 Compressor Over Current Protection Only For DCI25/35/50/60/72Z
CCR
Stop-Compresor
CCROC4
CCROC3
HzDown1
CCROC2
CCROC1
Normal
HzDown2
Stop-Rise
11.1.18 Heat Sink Overheating Protection
11.1.08.1 Heat Sink Overheating Protection For DCI25/35/50/60/72Z
HST
Fast Decreasing Decreasing No Change Increasing Fast Increasing
90 SC SC SC SC SC [85, 90) D1 D1 D2 D2 D2 [82, 85) SR SR D1 D2 D2 [80, 82) SR SR SR D1 D1 [78 , 80) Norm Norm Norm SR SR < 78 Norm
HST Trend
11.1.19 Outdoor Coil Deicing Protection
11.1.19.1 Outdoor coil Deicing Protection For DCI25/35/50/60/72Z
Entering Deicing Conditions
Deicing operation will start when either one of the following conditions exist: Case 1: OCT < OAT – 8 AND TLD > DI Case 2: OCT < OAT – 12 AND TLD > 30 minutes. Case 3: OCT is Invalid AND TLD > DI Case 4: Unit is just switched to STBY AND OCT < OAT – 8 Case 5: NLOAD = 0 AND OCT < OAT -8 Case 6: OCT<-19 AND TLD>60 minutes All this condition will exist during 10 seconds OCT – Outdoor Coil Temperature OAT – Outdoor Air Temperature TLD – Time from Last Deicing DI – Deicing Interval (Time Interval Between Two Deicing) Deicing interval time when compressor is first started in heat mode, is 10 minutes if OCT < -2, and is 40 minutes in other cases. Deicing interval time is changed (increased/ decreased in 10 minutes steps) as a function of deicing time. If deicing time is shorter then former deicing time, the deicing interval time will be increased. If deicing time is longer then former deicing time, the deicing interval time will be decreased.
11-10
SM CN 1-E.1 GB
Page 58
Deicing Operation Procedure
CONTENT
OCT
12
0
Threshold
CONTROL SYSTEM
COMP
DeiceFreqChRV
RV
OFAN
EEV
ON
HEAT
COOL
ON
OFF
EEVDeicerOpen
Any
T1 T2
DT
max. 12 minutes
T3 T3
T1=60 secondes;T2=36 secondes;T3=6 secondes T1=50 secondes;T2=36 secondes;T3=6 secondes
11.1.20 Condensate Water Over Flow Protection
P1 P4P2 P3
T1
Level Connector Top View
Each of the pins P1, P2, P3 can have two options: 1 – When it is shorted with P4 0 – When it is not shorted to P4
P1 P2 P3 Level
Don’t care Don’t care 1 Normal Don’t care Don’t care 0 Overflow
(*) 1- Pin P1, P2, or P3 is connected to P4.
0- Pin P1, P2 or P3 is not connected to P4.
For CN unit:
In case of vertical installation, change dipswitch 7 to OFF position to cancel Water Pump operation.
SM CN 1-E.1 GB
11-11
Page 59
CONTROL SYSTEM
CONTENT
Water Level
OPER
LED
NLOAD
PUMP
Overflow
Normal
ON
OFF
BLINK
ANY
0
ON
OFF
Overflow when
unit is ON
NLOAD is
forced to 0
8 min 8 min
Overflow when
unit is OFF
8 min
11.1.21 Operating the Unit from Mode Button (On display)
Forced operation allows to start, stop and operate in Cooling or Heating, in pre-set temperature according to the following table:
Forced operation Mode Pre-set Temperature
Cooling 20 Heating 28
11.1.22 On Unit Controls and Indicators
11.1.22.1 Indoor Unit controller Controls and Indicatiors for All Models Except for Floor/Ceiling model
During OFF, Fan, Cool, Heat, Dry, and Auto modes (for operation in other modes, see at the relevant spec paragraph):
Lights up when the Air Conditioner is connected to power and ready
STAND BY/OPERATION INDICATOR
ESF/INOIZER INDICATOR TIMER INDICATOR FILTER INDICATOR
MODE/RESET BUTTON
to receive the R/C commands
Lights up during operations. Blinks when compressor is stopped as
a result of a thermodynamic protection.
Lights up during ESF/ ionizer operation.Lights up during Timer and Sleep operation.Lights up when Air Filter needs to be cleaned.Every short pressing , the next operation mode is selected, in this
order : SB → Cool Mode → Heat Mode → SB → …
Press to turn off the filter indicator and to reset the filter function,
after the cleaned filter has been reinstalled.
11-12
In long pressing the system enters into diagnostic mode.
SM CN 1-E.1 GB
Page 60
CONTROL SYSTEM
r
r
r
A
p
CONTENT
11.1.22.2 Outdoor Unit controller Indicatiors
Unit has three LED’s. SB LED is ON when power is ON (230 VAC, even when no communication). STATUS LED is ON when COMP is ON, and Blinks according to diagnostics mode definitions when either fault or protection occurs. FAULT LED Blinks according to diagnostics mode definitions when either fault or protection occurs.
11.1.23 DIP switch settings
Indoor Unit Controller
11.1.23.1 Power PCB - CN
11.1.23.2 Main PCB - CN
12Pin Displayer Cable
larm Output
Unit On Out
RC-W Power
ut
RC-W
PD/PS
PUMP
Wire to Main PCB
DC Motor Cable
Self Test Jumper
DIP Switch
M2L Port
MCU Flash Port
Safety switch Terminals
SM CN 1-E.1 GB
Inoizer
ESF
Swing Motor
ICTE Senso ICT Senso RAT Senso Water Level
11-13
Page 61
CONTROL SYSTEM
CONTENT
11.1.23.3 Main PCB − CN
ICTE sensor
ICT sensor
RAT sensor
M2L Port
DIP Switch
WATER level
Unit On output
ALARM output
MCU Flash Port
IF Motor
RCW Power
RCW
16 Pins Display (not used)
To Display
Water Pump
11-14
Fresh Air
SM CN 1-E.1 GB
Page 62
11.1.24 Self Test Jumper(J1))
CONTENT
Jumper for production line only, never install jumper on site!
11.1.25 DIP Switch and Jumper Settings
CN - Dip switch default setting for each model
CONTROL SYSTEM
DIP
MODEL
2.5 KW ON OFF OFF OFF OFF OFF ON OFF
3.5 KW ON OFF OFF ON OFF OFF ON OFF
5.0 KW ON ON OFF OFF OFF OFF ON OFF
6.0 KW ON ON OFF ON OFF OFF ON OFF
7.0 KW ON ON OFF OFF ON OFF ON OFF
J
12345678
J2 J3 J6 J7 J8 J9 J12 J13
CN - Dip switch default setting for each model
DIP
MODEL
2.5 KW ON OFF OFF ON OFF OFF ON OFF
3.5 KW ON OFF OFF OFF ON OFF ON OFF
5.0 KW ON OFF OFF ON ON OFF ON OFF
6.0 KW ON ON OFF OFF OFF OFF ON OFF
7.0 KW ON ON OFF ON OFF OFF ON OFF
J
*Water pump and float switch setting In case of vertical installation, change dipswitch 7 to OFF position to cancel their operation.
1234567*8**
J2 J3 J5 J7 J8 J9 J10 J12
**High external static pressure There is an option of increasing the airflow if the ESP (external static pressure) is higher than planned. To increase the speed change dipswitch 8 to ON position.
● Compensation setting (Factory setting)
This setting activates the compensation to the return air temperature in heating mode. For indoor unit like cassette, the DIP switch J2 should be ON.
Compensation J2
Activated(factory setting) ON Deactivated OFF
● Unit model setting (Factory setting)
The unit model setting should be in accordance with the unit model on the nameplate. The unit operating parameters will be improper with wrong settings.
Unit model(Capacity) J3 J6 J7 J8
2.5kW model OFF OFF OFF OFF
3.5kW model OFF OFF ON OFF
5.0kW model ON OFF OFF OFF
6.0kW model ON OFF ON OFF
7.0kW model ON OFF OFF ON
SM CN 1-E.1 GB
11-15
Page 63
CONTROL SYSTEM
CONTENT
Presence Detector/Power Shedding Selection
Select the functions of dry contact PD/PS by setting the Dip switch J9
Selection J9 Presence Detector OFF Power Shedding ON
Installation of height compensation settings (By installer)
The compensation settings according to installation height should be set by using the dip switch J12, J13 on the controller PCB
Installation Height J12 J13 Installation height H0 OFF OFF 2.1-2.7m
H1(Factory setting) ON OFF 2.7-3.3m H2 OFF ON >3.3m H3 ON ON Reserved
Compensation data according to the installation height
Installation
Height
H0 -50 0 -50 0 42 H1 0 150 0 150 4 2 H2 100 150 100 150 6 2 H3 150 150 150 150 7 2
Speed Compensation for
Heating Mode
CN CN CN CN CN CN
Speed Compensation for
other Modes
Temperature compensation
in heating mode
11-16
SM CN 1-E.1 GB
Page 64
CONTROL SYSTEM
CONTENT
IDU Diagnostic Table.
Alarm Output
The Alarm Output dry contact will be on (closed), when a predefined set faults occur. The fault set is defined under diagnostics section. The alarm output will be off (open), when the predefined fault is cleared. The indoor alarm outputs are defined according to the following IDU Diagnostic Table:
No Problem AO 54321
1 ICT is disconnected Yes 0 0 0 0 1 2 ICT is shorted Yes 0 0 0 1 0 3 RAT is disconnected Yes 0 0 0 1 1 4 RAT is shorted Yes 0 0 1 0 0 5 Reserved (for MSMP used as RGT fault) No 0 0 1 0 1
*6
ICTE shorted/disconnected (when enabled) Yes 0 0 1 1 0 7 Undefined IDU family/model Yes 0 0 1 1 1 8 No Communication Yes 0 1 0 0 0 9 No Encoder No 0 1 0 0 1
10 Reserved No 0 1 0 1 0
11 Outdoor Unit Fault No 0 1 0 1 1
Reserved No 17 Defrost protection No 1 0 0 0 1 18 Deicing Protection No 1 0 0 1 0 19 Outdoor Unit Protection No 1 0 0 1 1 20 Indoor Coil HP Protection No 1 0 1 0 0 21 Overflow Protection Yes 1 0 1 0 1 22 Reserved No 24 EEPROM Not Updated No 1 1 0 0 0 25 Bad EEPROM No 1 1 0 0 1 26 Bad Communication No 1 1 0 1 0 27 Using EEPROM data No 1 1 0 1 1 28 Model A No 1 1 1 0 0 29 Model B No 1 1 1 0 1 30 Model C No 1 1 1 1 0 31 Model D No 1 1 1 1 1
* CN Unit only
SM CN 1-E.1 GB
11-17
Page 65
CONTROL SYSTEM
CONTENT
OUD Diagnostic Table
AO - Alarm output
No Problem AO 5 4 3 2 1
1 OCT is disconnected Yes 0 0 0 0 1 2 OCT is shorted Yes 0 0 0 1 0 3 CTT is disconnected Yes 0 0 0 1 1 4 CTT is shorted Yes 0 0 1 0 0 5 HST is disconnected (when enabled) Yes 0 0 1 0 1 6 HST is shorted (when enabled) Yes 0 0 1 1 0 7 OAT is disconnected (when enabled) Yes 0 0 1 1 1 8 OAT is shorted (when enabled) Yes 0 1 0 0 0
9 TSUC is disconnected (when enabled) Yes 0 1 0 0 1 10 TSUC is shorted (when enabled) Yes 0 1 0 1 0 11 IPM Fault Yes 0 1 0 1 1 12 Bad EEPROM No 0 1 1 0 0 13 DC under voltage Yes 0 1 1 0 1 14 DC over voltage Yes 0 1 1 1 0 15 AC under voltage Yes 0 1 1 1 1 16 Mismatch IDU & ODU models 17 No Communication Yes 1 0 0 0 1 18 Reserved No 1 0 0 1 0 20 Heat sink Over Heating No 1 0 1 0 0 21 Deicing No 1 0 1 0 1 22 Compressor Over Heating No 1 0 1 1 0 23 Compressor Over Current No 1 0 1 1 1 24 No OFAN FeedbaCN No 1 1 0 0 0 25 OFAN loCNed Yes 1 1 0 0 1 26 Compressor LoCN Yes 1 1 0 1 0 27 Bad Communication No 1 1 0 1 1 28 Missing ODU configuration 29 Undefined ODU Model 30 For future use No 1 1 1 1 0 31 Operation condition is exceeded
(*SW 35V14 and above) Yes11101
(*SW 35V14 and above) Yes10000
(*SW 35V14 and above) Yes11100
(*SW 35V14 and above) Yes11111
*Alarm Output - is on SW 35V14 and above. There is no alarm on SW 35V12 and below/
The ‘On/Off status’ dry contact will be on (closed), when the indoor mode is not STBY. If the indoor mode is STBY mode, the ‘On/Off status’ will be off (open).
J9=open Presence Detector Connection Last Mode Force to STBY J9=short Power Shedding Function No limit Limit NLOAD
11-18
Unit ON Output
PD/PS(Presence Detector/Power Shedding)
Function Contact=open Contact=short
SM CN 1-E.1 GB
Page 66
CONTROL SYSTEM
CONTENT
11.1.25 Outdoor Unit Controller
11.1.25.1 Outdoor Unit Controller - Jumper setting
JP9 Jumper Layout
Reserved (PIN 9) ODU3 (PIN 7) ODU2 (PIN 5) ODU1 (PIN 3) ODU0 (PIN 1) GND (PIN 10) GND (PIN 8) GND (PIN 6) GND (PIN 4) GND (PIN 2)
11.1.26 ODU Model Selection
ODU3 ODU2 ODU1 ODU0 ODU Model
OFF OFF OFF ON A (Single DCI 25) OFF OFF ON OFF B (Single DCI 35) OFF OFF ON (PIN3 & PIN4) ON (PIN1 & PIN2) C (Single DCI 50) OFF ON (PIN5 & PIN6) OFF OFF D (Single DCI 60) ON (PIN7 & PIN8) ON (PIN5 & PIN6) OFF OFF L (Single DCI 72Z)
11.1.27 Outdoor Unit Controller
11.1.27.1 Outdoor Unit Controller - DIP Switch setting
ODU0
ODU1
ODU2
ODU3
N.A.
N.A.
ON
123456
DIP
ODU MODEL SETTING
ODU3 ODU2 ODU1 ODU0 ODU MODEL
OFF OFF OFF ON DCI 25 OFF OFF ON OFF DCI 35 OFF OFF ON ON DCI 50 OFF ON OFF OFF DCI 60 ON ON OFF OFF DCI 72Z
11.2 Test Mode
11.2.1 Entering Test Mode
System can enter Test mode in two ways: Automatically when the following conditions exists for 30 minutes continuously: Mode = Cool, Set point = 16, Room temperature = 27(+1/-2), Outdoor temperature = 35(+2/-1) Or Mode = Heat, Set point = 30, Room temperature = 20±1, Outdoor temperature = 7±(+1/-2) Manually when entering diagnostics with the following settings: Mode = Cool, Set point = 16 Mode = Heat, Set point = 30
SM CN 1-E.1 GB
11-19
Page 67
CONTROL SYSTEM
CONTENT
11.2.3 Unit Operation in Test Mode
In test mode, the unit will operate in fixed settings according to the indoor fan speed setting:
Indoor FAN Speed Setting Unit Setting
Low Minimum Capacity Setting Turbo Nominal Capacity Setting Auto Maximum Capacity Setting
During test mode, protections are disabled, except for stop compressor status.
11.3 Parameters
11.3.1 General Parameters for all models
# Name Values(Factory Setting)
1 CVStep 0 2 Cool2Heat 3 3 Heat2Cool 3 4 ICTDef1 8 5 ICTDef2 6 6 ICTDef3 4 7 ICTDef4 2 8 ICTDef5 0 9 ICTDef6 -2
10 ICTDeltaDef1 1 11 ICTDeltaDef2 -1 12 ICTDeltaOH1 -1 13 ICTDeltaOH2 1 14 FLTRTime 1023 15 PITconst 30 16 STARTTIMETURBOH 10 17 IFANOffTimeDry 3 18 IFANOnTimeDry 1 19 ICTLowLimitDry 10 20 ICTHighLimitDry 12 21 ExtraNLOADDry 20 22 IFANMAXTimeH 150 23 IFANOffTimeH 4 24 IFANOnTimeH 3 25 IFANTimeHeat2STBY 30 26 MAXTURBOTIMEF 30 27 MAXTURBOTIMEC 30 28 MAXTURBOTIMEH 30
11-20
SM CN 1-E.1 GB
Page 68
11.3.2 Family Dependent Parameter
CONTENT
CONTROL SYSTEM
# Name CN
1 BasicCV1 4422 2 BasicCV2 4422 3 BasicCV3 6622 4 BasicCV4 7722 5 Max_Swg 40 40 NA NA 6 Min_H_Angle 5 5 NA NA 7 Max_H_Angle 40 40 NA NA 8 Min_C_Angle 5 5 NA NA 9 Max_C_Angle 40 40 NA NA
10 MTR_Cls_Dir C C NA NA
11 MTR_Cls_Dir_V C C NA NA 12 Max_Angle_V NA NA NA NA 13 Min_Angle_V NA NA NA NA 14 Max_Swg_V NA NA NA NA 15 IFSPCHNA 10 10 10 10 16 IFSPCHND 4 4 10 10
A
CN
B
CN
A
CN
B
17 IFSPCHAA 6 6 6 6 18 IFSPCHAD 4 4 6 6 19 IFSTARTSPEED 670 670 670 670 20 ICTSTSpeed 25 25 25 25 21 ICTVLSpeed 28 28 28 28 22 ICTLSpeed 30 30 30 30 23 ICTHSpeed 32 32 32 32 24 ICTTSpeed 40 40 35 35 25 NLOADHForcedValue 60 60 60 60 26 ICTOH1 45 45 49 49 27 ICTOH2 48 48 51 51 28 ICTOH3 52 52 53 53 29 ICTOH4 55 55 55 55 30 ICTOH5 60 60 60 60 31 ICTOH6 62 62 62 62 32 ICTEEnable 1 1 0 0
SM CN 1-E.1 GB
11-21
Page 69
CONTROL SYSTEM
CONTENT
11.3.3 Indoor Model Parameters:
Indoor Family CN
A
CN
B
CN
A
CN
B
Indoor Model
Parameter
IFVLOWC 250 300 450 500 550 670 690 800 900 900
IFLOWC 450 450 550 600 650 740 730 860 960 980
IFMEDC 500 520 620 660 700 810 860 980 1050 1050
IFHIGHC 550 600 680 720 750 920 980 1100 1170 1200
IFTURBOC 650 700 800 900 1000 960 1060 1170 1240 1280
IFVLOWH 250 300 450 500 550 670 690 800 900 900
IFLOWH 450 450 550 600 650 740 730 860 960 980
IFMEDH 520 550 620 660 700 810 860 980 1050 1050
IFHIGHH 600 650 680 720 750 920 980 1100 1170 1200
IFTURBOH 650 700 850 950 1000 960 1060 1220 1240 1280
Cap .Group 0133 4 0 1 3 3 4
A (CN25)
B (CN 35)
A (CN50)
B (CN 60)
C (CN72)
A (CN25)
B (CN35)
C (CN50)
A (CN60)
B (CN72)
NomLoadC 40 62 66 81 62 40 60 64 79 54
NomLoadH 52 67 67 81 57 57 70 73 82 57
MaxNLOADIF1C 47 42 55 56 50 127 127 127 127 127
MaxNLOADIF2C 70 60 78 81 70 127 127 127 127 127
MaxNLOADIF3C 127 127 127 127 127 127 127 127 127 127
MaxNLOADIF4C 127 127 127 127 127 127 127 127 127 127
MaxNLOADIF5C 127 127 127 127 127 127 127 127 127 127
IFAN_SPEED_COMP0_C -50 -50 -50 -50 -50 0 0 0 0 0
IFAN_SPEED_COMP1_C 0 0 0 0 0 150 150 150 150 150
IFAN_SPEED_COMP2_C 100 100 100 100 100 150 150 150 150 150
IFAN_SPEED_COMP3_C 150 150 150 150 150 150 150 150 150 150
IFAN_SPEED_COMP0_H -50 -50 -50 -50 -50 0 0 0 0 0
IFAN_SPEED_COMP1_H 0 0 0 0 0 150 150 150 150 150
IFAN_SPEED_COMP2_H 100 100 100 100 100 150 150 150 150 150
IFAN_SPEED_COMP3_H 150 150 150 150 150 150 150 150 150 150
ModelEnable 1111 1 1 1 1 1 1
11-22
SM CN 1-E.1 GB
Page 70
11.3.4 Outdoor Parameters
CONTENT
General Parameters ( for every software):
# Name Default Value
1 MinOFFTime 3 2 MinONTime 3 3 OFSPCH 4 4 Down1 3 5 Down2 10 6 DImin 30 7 DImax 120 8 TimeD 1 9 DTmin 2
10 DTmax 12
11 DIT 10
12 CTMRUP 15
CONTROL SYSTEM
13 DIF 30 14 TCT 10 15 HSTOH1 78 17 HSTOH2 80 18 HSTOH3 82 19 HSTOH4 85 20 HSTOH5 90 21 HSTOHDelta1 -1 22 HSTOHDelta2 1 23 EEVCVTConst 30 24 BalanceTime 5 25 EEVInitOpen 300
SM CN 1-E.1 GB
11-23
Page 71
CONTROL SYSTEM
CONTENT
11.3.5 ODU Model Dependent Parameters ( 35V12 )
#
1 MinFreqC 30 33 20 20 2 MaxFreqC 64 80 85 95 3 MinFreqH 30 35 20 26 4 MaxFreqH 81 93 95 94 5 NormAccel 11 1 1 6 NormDecel 11 1 1 7 Step1Freq 60 60 60 60 8 Step2Freq 70 70 70 70
9 Step3Freq 90 90 90 90 10 OFVL 20 20 20 20 11 OFLOWC 55 55 60 55 12 OFMEDC 70 70 76 70 13 OFMAXC 83 83 92 79 14 OFLOWH 55 55 60 55 15 OFMEDH 70 70 83 70 16 OFMAXH 83 83 100 79 17 OFANTESTMODEC 83 83 92 83 18 OFANTESTMODEH 83 83 100 83 19 OFDelTestMode 20 20 28 28 20 CTTOH1 94 94 94 94 21 CTTOH2 98 98 98 98 22 CTTOH3 102 102 102 102 23 CTTOH4 105 105 105 105 24 CCROC1 7.1 7.1 10 11.4 25 CCROC2 7.5 7.5 10.5 11.8 26 CCROC3 7.9 7.9 10.8 12.2 27 CCROC4 8.3 8.3 11.2 12.6 28 DEICT1 60 60 60 60 29 DEICT2 36 36 36 36 30 DEICT3 66 6 6 31 ProtFreqLimit 60 60 60 60 32 EEVDecierOpen 180 180 100 180 33 OptimDeicFreq 90 90 90 90 34 EEVMinOperOpenC 35 EEVMaxOperOpenC 380 380 380 380 36 EEVMinOperOpenH 50 50 50 60 37 EEVMaxOperOpenH 300 300 380 300 38 EEVNormRate 33 33 33 33 39 EEVHighRate 12 12 12 12 40 EEVMaxOpen 500 500 500 500 41 OFLowFreqC 45 45 40 35 42 OFMedFreqC 57 57 70 55 43 OFLowFreqH 45 45 40 40 44 OFMedFreqH 57 57 86 60 45 HeaterDisableFlag 00 0 0 46 DeiceFreqChRV 00 0 0 47 OATRefC 35 35 35 35 48 SUCT Enable 00 0 0 49 HST Enable 00 1 1 50 OAT Enable 11 1 1 51 OATRefH 77 7 7 52 MinTargCTTC 30 30 30 30 53 MaxTargCTTC 95 95 95 90 54 MinTargCTTH 40 40 40 45 55 MaxTargCTTH 95 95 95 90 56 DST 88 8 8 57 DSTF 12 12 12 12 58 OATLimitC 24 24 28 28 59 OATLimit1H 66 6 6 60 OATLimit2H 15 15 15 15 61 MaxFreqAsOATC 50 50 64 85 62 MaxFreqAsOAT1H 65 75 85 80 63 MaxFreqAsOAT2H 60 60 60 60
Parameter
Outdoor Model
A
Single
DCI-25
50 50 50 80
B
Single
DCI-35
C
Single
DCI-50
D
Single
DCI 60
11-24
SM CN 1-E.1 GB
Page 72
11.3.6 ODU Model Dependent Parameters ( 35V14 )
CONTENT
CONTROL SYSTEM
#
Parameter
1 MinFreqC 30 33 20 20 2 MaxFreqC 64 80 85 95 3 MaxFreqCRunPhase 64 80 85 95 4 MinFreqH 30 35 20 26 5 MaxFreqH 81 93 95 94 6 MaxFreqHRunPhase 81 93 95 94 7 LoadDeadZoneC 90 95 95 111 8 LoadDeadZoneH 127 127 127 127
9 NormAccel 1111 10 NormDecel 1111 11 Step1Freq 60 60 60 60 12 Step2Freq 70 70 70 70 13 Step3Freq 90 90 90 90 14 OFVL 20 20 20 20 15 OFLOWC 55 55 60 55 16 OFMEDC 70 70 76 70 17 OFMAXC 83 83 92 79 18 OFLOWH 55 55 60 55 19 OFMEDH 70 70 83 70 20 OFMAXH 83 83 100 79 21 OFANTESTMODEC 83 83 92 83 22 OFANTESTMODEH 83 83 100 83 23 OFDelTestMode 20 20 28 28 24 CTTOH1 94 94 94 94 25 CTTOH2 98 98 98 98 26 CTTOH3 102 102 102 102 27 CTTOH4 105 105 105 105 28 CCROC1 7.1 7.1 10 11.4 29 CCROC2 7.5 7.5 10.5 11.8 30 CCROC3 7.9 7.9 10.8 12.2 31 CCROC4 8.3 8.3 11.2 12.6 32 DEICT1 60 60 60 60 33 DEICT2 36 36 36 36 34 DEICT3 35 ProtFreqLimit 60 60 60 60 36 EEVDecierOpen 180 180 100 180 37 OptimDeicFreq 90 90 90 90 38 OCTExitDeicer 12 12 12 12 39 MaxDeicerTime 12 12 12 12 40 EEVMinOperOpenC 50 50 50 80 41 EEVMaxOperOpenC 380 380 380 380 42 EEVMinOperOpenH 50 50 50 60 43 EEVMaxOperOpenH 300 300 380 300 44 EEVNormRate 33 33 33 33 45 EEVHighRate 12 12 12 12 46 EEVMaxOpen 500 500 500 500 47 OFLowFreqC 45 45 40 35 48 OFMedFreqC 57 57 70 55 49 OFLowFreqH 45 45 40 40 50 OFMedFreqH 57 57 86 60 51 HeaterDisableFlag 0000 52 DeiceFreqChRV 0000 53 OATRefC 35 35 35 35 54 SUCT Enable 0000 55 HST Enable 1111 56 OAT Enable 1111 57 OATRefH 7777 58 MinTargCTTC 30 30 30 30 59 MaxTargCTTC 95 95 95 90 60 MinTargCTTH 40 40 40 45 61 MaxTargCTTH 95 95 95 90 62 DST 8888 63 DSTF 12 12 12 12 64 OATLimitC 24 24 28 28 65 OATLimit1H 6666 66 OATLimit2H 15 15 15 15 67 MaxFreqAsOATC 50 50 64 85 68 68 MaxFreqAsOAT2H 60 60 60 60 69 EnableExceedCond 0 0 0 0
MaxFreqAsOAT1H 65 75 85 80
Outdoor Model
A
Single
DCI-25
6666
B
Single
DCI-35
C
Single
DCI-50
D Single DCI 60
SM CN 1-E.1 GB
11-25
Page 73
CONTROL SYSTEM
CONTENT
11.3.7 ODU Model Dependent Parameters ( 36V1-S01 )
Outdoor Model
#
Parameter
1 MinFreqC 15 2 MaxFreqC 70 3 MinFreqH 15 4 MaxFreqH 90 7 Step1Freq 35 8 Step2Freq 55
9 Step3Freq 90 10 OFMinRPM 8 11 OFMaxRPM 90 12 NightRPM 65 13 OFNNoiseMaxRPM 78 14 CTTOH1 90 15 CTTOH2 95 16 CTTOH3 100 17 CTTOH4 105 18 CCROC1 12.5 19 CCROC2 11.3 20 CCROC3 14.1 21 CCROC4 14.9 22 ProtFreqLimit 60 23 EEVMinOperOpenC 50 24 EEVMaxOperOpenC 480 25 EEVMinOperOpenH 50 26 EEVMaxOperOpenH 480 27 HeaterDisableFlag 0 28 HST Enable 1 29 OATLimitC 25 30 OATLimit1H 4 31 OATLimit2H 15 32 MaxFreqAsOATC 60 33 MaxFreqAsOAT1H 68 34 MaxFreqAsOAT2H 57 35 NormAccel 1 36 NormDecel 1 37 OCTExitDeicer 12 38 MaxDeicerTime 15
L
Single
DCI-72Z
11-26
SM CN 1-E.1 GB
Page 74

TROUBLESHOOTING

CONTENT
12. TROUBLESHOOTING
WARNING!!!
When Power Up – the whole outdoor unit controller, including the wiring, is under
HIGH VOLTAGE!!!
Never open the Outdoor unit before turning off the Power!!!
When turned off, the system is still charged (400V)!!!
It takes about 3 Min. to discharge the system.
Touching the controller before discharging may cause an electrical shoCN!!!
For safe handling of the controller please refer to section 12.6 below.
12.1 General DCI Single Split System failures and Corrective Actions
No SYMPTOM
1
2
3
4
Power supply indicator (Red LED) does not light up.
Unit does not respond to remote control message
Unit responds to remote control message but Operate indicator (Green LED) does not light up
Indoor fan does not start (louvers are opened and Green LED does light up)
PROBABLE
CAUSE
CheCN power supply. If power supply
No power supply
Remote control message not reached the indoor unit
Problem with display PCB
Unit in heat mode and coil is still not warm.
Problem with PCB or capacitor
is OK, cheCN display and display wiring. if OK, replace controller.
CheCN remote control batteries, if batteries are OK, cheCN display and display wiring, if OK, replace display PCB. If still not OK replace controller.
Replace display PCB. If still not OK replace controller.
Change to cool mode and cheCN.
Change to high speed and CheCN power supply to motor is higher than 130VAC (for triaCN controlled motor) or higher than 220VAC for fixed speed motors, if OK replace capacitor, if not OK replace controller
CORRECTIVE ACTION
SM CN 1-E.1 GB
Indoor fan works when unit
5
6 Compressor does not start
7
is OFF, and indoor fan speed is not changed by remote control command.
Compressor stops during operation and Green LED remains on
PCB problem Replace controller
Electronics control problem or protection
Electronic control or power supply problem
Perform diagnostics (See 12.3), and follow the actions described.
Perform diagnostics (See 12.3), and follow the actions described.
12-1
Page 75
TROUBLESHOOTING
CONTENT
No SYMPTOM
8
9
10
11
12
Compressor is on but outdoor fan does not work
Unit works in wrong mode (cool instead of heat or heat instead of cool)
All components are operating properly but no cooling or no heating
Compressor is over heated and unit does not generate capacity
Units goes into protections and compressor is stopped with no clear reason
PROBABLE
CAUSE
Problem with outdoor electronics or outdoor fan
Electronics or power connection to RV
Refrigerant leak CheCN refrigeration system.
EEV problem CheCN EEV
Control problem or refrigeration system problem
CORRECTIVE ACTION
CheCN outdoor fan motor according to the procedure in section 12.5.3 , if not OK replace controller
CheCN RV power connections, if OK, CheCN RV operation with direct 230VAC power supply, if OK, Replace outdoor controller.
Perform diagnostics (See 12.3), and follow the actions described.
13
14
15
16
Compressor motor is generating noise and no suction occurs
Water leakage from indoor unit
Freezing of outdoor unit in heat mode and outdoor unit base is bloCNed with ice
Unit operates with wrong fan speeds or wrong frequency
Phase order to compressor is wrong
Indoor unit drainage tube is bloCNed
Wrong jumper settings
CheCN compressor phase order.
CheCN and open drainage tube.
Connect base heater.
Perform diagnostics (See 12.3), and cheCN if units is operating by EEPROM parameters.
12.2 CheCNing the refrigeration system
CheCNing system pressures and other thermodynamic measures should be done when system is in Test Mode (in Test mode, system operates in fixed settings). The performance curves given in this manual are given for unit performance in test mode when high indoor fan speed is selected. Entering test mode: Set unit to Cool/16 degrees/High indoor fan speed, or Heat/30 degrees/High indoor fan speed, and enter diagnostics.
12.3 Judgment by Indoor/Outdoor Unit Diagnostics
12-2
Enter diagnostics mode - press for five seconds Mode button in any operation mode. ACNnowledgment is by 3 short beeps and lights of COOL and HEAT LED’s. Then, every short pressing of Mode button will scroll between Indoor and Outdoor unit diagnostic modes by the aCNnowledgment of 3 short beeps and lighting of COOL and HEAT LED’s. During the Outdoor unit diagnostics all four Indoor LED’s (STBY, Operate, Filter and Timer) are blinking. When Indoor diagnostics is displayed, all four LED’s (STBY, Operate, Filter and Timer) are ON.
SM CN 1-E.1 GB
Page 76
TROUBLESHOOTING
CONTENT
When system enters diagnostics mode, only one fault code is shown. Order of priority is from the lower to the higher number. Diagnostics is continuously ON as long as power is ON. The current system operation mode will not be changed. If no fault occurred in the system, no fault code will be displayed during normal operation mode. The last fault code will be displayed even if the system has recovered from that fault. The last fault will be deleted from the EEPROM after the system has exit diagnostics mode.
In diagnostics mode, system fault / status will be indicated by blinking of Heat & Cool LEDs. The coding method will be as follows: Heat LED will blink 5 times in 5 seconds, and then will be shut off for the next 5 seconds. Cool LED will blink during the same 5 seconds according to the following Indoor / Outdoor unit tables: Note: 0 – OFF, 1-ON
12.3.1 Indoor Unit Diagnostics
Alarm Output
The Alarm Output dry contact will be on (closed), when a predefined set faults occur. The fault set is defined under diagnostics section. The alarm output will be off (open), when the predefined fault is cleared. The indoor alarm outputs are defined according to the following table:
No Problem AO 54321
1 ICT is disconnected Yes 0 0 0 0 1 2 ICT is shorted Yes 0 0 0 1 0 3 RAT is disconnected Yes 0 0 0 1 1 4 RAT is shorted Yes 0 0 1 0 0 5 Reserved (for MSMP used as RGT fault) No 0 0 1 0 1
*6 *7
ICTE shorted/disconnected (when enabled) Yes 0 0 1 1 0 Undefined IDU family/model Yes 0 0 1 1 1
8 No Communication Yes 0 1 0 0 0 9 No Encoder No 0 1 0 0 1
10 Reserved No 0 1 0 1 0
11 Outdoor Unit Fault No 0 1 0 1 1
Reserved No 17 Defrost protection No 1 0 0 0 1 18 Deicing Protection No 1 0 0 1 0 19 Outdoor Unit Protection No 1 0 0 1 1 20 Indoor Coil HP Protection No 1 0 1 0 0
SM CN 1-E.1 GB
21 Overflow Protection Yes 1 0 1 0 1 22 Reserved No 24 EEPROM Not Updated No 1 1 0 0 0 25 Bad EEPROM No 1 1 0 0 1 26 Bad Communication No 1 1 0 1 0 27 Using EEPROM data No 1 1 0 1 1
12-3
Page 77
TROUBLESHOOTING
CONTENT
No Problem AO 54321
28 Model A No 1 1 1 0 0 29 Model B No 1 1 1 0 1 30 Model C No 1 1 1 1 0 31 Model D No 1 1 1 1 1
* CN / LSN Units only
12.3.2 Indoor Unit Diagnostics and Corrective Actions
No. Fault Probable Cause Corrective Action
1
2
3
4 No Encoder
5
6
7 Bad EEPROM
8
9
Sensor failures of all types
Communication mismatch
No Communication
Outdoor Unit Fault
EEPROM Not Updated
Bad Communication
Using EEPROM data
Indoor and Outdoor controllers are with different versions
Communication or grounding wiring is not good.
Indoor electronics or motor
Outdoor controller problem
System is using ROM parameters and not EEPROM parameters
Communication quality is low reliability
No problem. System is using EEPRRRROM parameters
CheCN sensor connections or replace sensor
Replace Indoor controller
CheCN Indoor to Outdoor wiring and grounding
CheCN motor wiring, if ok, replace motor, if still not ok, replace Indoor controller.
Switch to Outdoor diagnostics.
No action, unless special parameters are required for unit operation.
No action, unless special parameters are required for unit operation.
CheCN Indoor to Outdoor wiring and grounding
12.3.3 Outdoor Unit Diagnostics
The outdoor alarm outputs are defined in the following way:
No Problem AO 5 4 3 2 1
12-4
1 OCT is disconnected Yes 0 0 0 0 1 2 OCT is shorted Yes 0 0 0 1 0 3 CTT is disconnected Yes 0 0 0 1 1 4 CTT is shorted Yes 0 0 1 0 0 5 HST is disconnected (when enabled) Yes 0 0 1 0 1 6 HST is shorted (when enabled) Yes 0 0 1 1 0 7 OAT is disconnected (when enabled) Yes 0 0 1 1 1 8 OAT is shorted (when enabled) Yes 0 1 0 0 0 9 OMT is disconnected (DCI72 / 72Z / 80) Yes 0 1 0 0 1
SM CN 1-E.1 GB
Page 78
TROUBLESHOOTING
CONTENT
No Problem AO 5 4 3 2 1
10 OMT is shorted (DCI72 / 72Z / 80) Yes 0 1 0 1 0 11 IPM Fault Yes 0 1 0 1 1 12 Bad EEPROM No 0 1 1 0 0 13 DC under voltage Yes 0 1 1 0 1 14 DC over voltage Yes 0 1 1 1 0 15 AC under voltage Yes 0 1 1 1 1 16 Mismatch IDU & ODU models 17 No Communication Yes 1 0 0 0 1 18 Reserved No 1 0 0 1 0 20 Heat sink Over Heating No 1 0 1 0 0 21 Deicing No 1 0 1 0 1 22 Compressor Over Heating No 1 0 1 1 0 23 Compressor Over Current No 1 0 1 1 1 24 No OFAN FeedbaCN No 1 1 0 0 0 25 OFAN loCNed Yes 1 1 0 0 1 26 Compressor LoCN Yes 1 1 0 1 0 27 Bad Communication No 1 1 0 1 1 28 Missing ODU configuration 29 Undefined ODU Model 30 For future use No 1 1 1 1 0 31 Operation condition is exceeded
(*SW 35V14 and above) Yes11101
(*SW 35V14 and above) Yes10000
(*SW 35V14 and above) Yes11100
(*SW 35V14 and above) Yes11111
*Alarm Output - is on SW 35V14 and above. There is no alarm on SW 35V12 and below/
12.3.4 Outdoor Unit Diagnostics and Corrective Actions
No. Fault Probable Cause Corrective Action
1
Sensors failures of all types
2 IPM Fault Electronics HW problem
3 Bad EEPROM
4 DC under/over Voltage Electronics HW problem
5 AC under Voltage
Indoor / Outdoor unit
6
Communication mis­match
Indoor and Outdoor controllers are with different versions
Communication or
7 No Communication
grounding wiring is not good.
CheCN sensors connections or replace sensors.
CheCN all wiring and jumper settings, if OK, replace electronics.
No action, unless special parameters are required for unit operation.
CheCN outdoor unit power supply voltage
CheCN outdoor unit power supply voltage
Replace Indoor controller
CheCN Indoor to Outdoor wiring and grounding
SM CN 1-E.1 GB
12-5
Page 79
TROUBLESHOOTING
CONTENT
No. Fault Probable Cause Corrective Action
Switch unit to STBY and restart If still not ok cheCN
8 Compressor LoCN
compressor (12.5.4) If comp is ok replace OU controller If compressor is not ok replace compressor
9 Bad Communication
Communication quality is low reliability
CheCN Indoor to Outdoor wiring and grounding
12.4 Judgment by MegaTool
MegaTool is a special tool to monitor the system states. Using MegaTool requires:
A computer with RS232C port.
A connection wire for MegaTool.
A special MegaTool software.
Use MegaTool according to following procedure:
Setup MegaTool software: copy the software to the computer.
Connect RS232C port in computer with MegaTool port in Indoor/Outdoor unit controller by
the connection wire.
Run the software and choose the COM port, you can monitor the A/C system state in
monitor tab.
12.5 Simple procedures for cheCNing the Main Parts
12.5.1 CheCNing Mains Voltage.
Confirm that the Mains voltage is between 198 and 264 VAC. If Mains voltage is out of this range, abnormal operation of the system is expected. If in range cheCN the Power (Circuit) Breaker and look for broken or loosed cable lugs or wiring mistake(s).
12.5.2 CheCNing Power Input.
If Indoor unit power LED is unlighted, power down the system and cheCN the fuse of the Indoor unit. If the fuse is OK replace the Indoor unit controller. If the fuse has blown, replace the fuse and power up again. CheCNing Power Input procedure for the Outdoor unit is the same as with the Indoor unit.
12.5.3 CheCNing the Outdoor Fan Motor.
Enter Test Mode (where the OFAN speed is high) CheCN the voltage between lead wires according to the normal value as following:
Between red wire and blaCN wire: 310VDC +/- 20V
Between orange wire and blaCN wire: 15VDC +/- 1V
Between yellow wire and blaCN wire: 2-6VDC
12-6
SM CN 1-E.1 GB
Page 80
TROUBLESHOOTING
CONTENT
12.5.4 CheCNing the Compressor.
The compressor is brushless permanence magnetic DC motor. Three coil resistance is same. CheCN the resistance between three poles. The normal value should be below 0.5 ohm (TBD).
12.5.5 CheCNing the Reverse Valve (RV).
Running in heating mode, cheCN the voltage between two pins of reverse valve connector, normal voltage is 220VAC.
12.5.6 CheCNing the electrical expansion valve (EEV).
The EEV has two parts, drive part and valve. The drive part is a step motor; it is ringed on the valve. CheCN the drive voltage (12VDC). When Outdoor unit is power on, EEV shall run and have cliCN and vibration.
12.6 Precaution, Advise and Notice Items
12.6.1 High voltage in Outdoor unit controller.
Whole controller, including the wires that are connected to the Outdoor unit controller may have the potential hazard voltage when power is on. Touching the Outdoor unit controller may cause an electrical shoCN. Advise: Don’t touch the naked lead wire and don’t insert finger, conductor or anything else into the controller when power is on.
12.6.2 Charged Capacitors
Three large-capacity electrolytic capacitors are used in the Outdoor unit controller. Therefore, charging voltage (380VDC) remains after power down. Discharging takes about four minutes after power is off. Touching the Outdoor unit controller before discharging may cause an electrical shoCN.
12.6.3 Additional advises
When disassemble the controller or the front panel, turn off the power supply.
When connecting or disconnecting the connectors on the PCB, hold the whole housing,
don’t pull the wire.
w
There are sharp fringes and sting on shell. Use gloves when disassemble the A/C units.
SM CN 1-E.1 GB
12-7
Page 81

EXPLODED VIEWS AND SPARE PARTS LISTS

CONTENT
13. EXPLODED VIEWS AND SPARE PARTS LISTS
13.1 Indoor Unit: CN 25, 35. 50, 60, 70 DCI
SM CN 1-E.1 GB
13-1
Page 82
EXPLODED VIEWS AND SPARE PARTS LISTS
CONTENT
13.2 Indoor Unit: CN 25, 35 DCI
No. Part No. Description Unit
1 453189500 Grille 1 2 453189900 Filter Assy. 1 3 453192700 Water-Level Switch 1 4 465720163 Front Plate Assy (625x625) 1 4 465720169 Front Plate Assy (725x725) ION/CN Airwell 1 5 465080003 Display Cover 1 6 462350078 Evaporator Assy/CN DCI 25/35 R410A 1 7 453192600 Pump CN 1 8 465800084 Drain Pipe Assy/CN 1
9 453189700 Horizontal Flap 4 10 453191300 Drain pan Assy 1 11 465360021 Support/Grill Clasp 2 12 466010002 Centrifugal Fan Low (CN60X60) 1 13 453191600 EPS 1 / Front Frame 3 14 453191700 EPS 2 / Front Frame 4 14 470250017 EPS /Air outlet/Front Frame 4 15 470250004 EPS 3/Front Frame 1 16 466130010R DC Motor 40W/ CN60x60 1 17 465020104 Front Frame (625x625) 1 17 465020105 Front Frame (725x725) (Airwell)./CN 1 18 433050 Step Motor 2 19 4520278R power cord 1 20 464250066 Fixing Plate/Pump Assy. 1 21 467300128R Display Board/CN 1 22 467300122R Filter Board/CN DCI 1 23 467300121R Control Board/CN DCI 1 24 232299 Indoor Sensor BLACN 1 24 467400032 Coil Air Temperature Sensor-Thermister EVAP(Φ6)./CN 1 25 4519813 Thermistor room 1 26 470250006 EPS/Air Housing assy.(Low) 1 27 453193600 ESF(option) 1 28 464750006 control Box assay1 1 29 453042500R Remote controller/RC4-I-1 EHK P/N 974-710-00 1 30 464750003 Cover/Controll Box 1 1 31 464750002 Controll Box 2/CN 1 32 464750004 Cover/Controll Box 2 1 33 467420016 7 Poles Terminal BloCN 1 34 453189600 Grille Clasp 2 35 465340022 Cover1 /Front Plate 1 36 453190600 Cover2 /Front Plate 1 37 465340040 Cover3 /Front Plate 1 38 465080002 Cover4 /Front Plate 1 39 465800089 Support 1/lever Assy/CN 4
13-2
SM CN 1-E.1 GB
Page 83
EXPLODED VIEWS AND SPARE PARTS LISTS
CONTENT
No. Part No. Description Unit
40 453193500 Ionizer(option) 1 41 465800090 Support 2/lever Assy/CN 4 42 465360028 Orienting Support/Lever 6 43 464000020 Base Plate Assy./CN DCI 1 49 463750123 Liquid Pipe Assy. /6.35 1 50 463750122 Gas Pipe Assy./9.53 1 51 464250047 Fixing Plate/Evaporator (Low height) 2 52 470100003 Cushion Rubber 3 57 465120005 Air Intake Panel (Low) 1 59 453195100 Drain Jam 1 61 465800091 Linkage Assy./Flap/CN 2 62 465440018 connect Shaft/Motor 2 63 453190000 Linkage /Flap 2 64 465360022 Support/Step Motor 1 64 465360032 Support/Step Moter 2 1
SM CN 1-E.1 GB
13-3
Page 84
EXPLODED VIEWS AND SPARE PARTS LISTS
CONTENT
13.3 Indoor Unit: CN 50, 60 DCI
No. Part No. Description Unit
1 453189500 Grille 1 2 453189900 Filter Assy. 1 3 453192700 Water-Level Switch 1 4 465720163 Front Plate Assy. 625x625 1 4 465720169 Front Plate Assy. 725x725 ION/CN Airwell 1 5 465080003 Display Cover 1 6 462350077 Evaporator Assy./CN DCI 50/60 R410A 1 7 453192600 Pump CN 1 8 465800084 Drain Pipe Assy/CN. 1 9 453189700 Horizontal Flap 4
10 453191300 Drain pan Assy 1
11 465360021 Support/Grill Clasp 2 12 453189300 Centrifugal Fan High)CN60X60 1 13 453191600 EPS 1 / Front Frame 3 14 453191700 EPS 2 / Front Frame 4 14 470250017 EPS /Air outlet/Front Frame 4 15 470250004 EPS 3/Front Frame 1 16 466130009R DC Motor 40W/ CN60x60 1 17 465020104 Front Frame (625x625) 1 17 465020105 Front Frame (725x725) (Airwell)./CN 1 18 433050 Step Motor 2 19 453232400R Power Cord Without Plug/ EU 1 20 464250066 Fixing Plate/Pump Assy. 1 21 467300128R Display Board/CN 1 22 467300122R Filter Board/CN DCI 1 23 467300121R Control Board/CN DCI 1 24 232299 Indoor Sensor BLACN 1 24 467400032 Coil Air Temperature Sensor-Thermister EVAP(Φ6)./CN 1 25 4519813 Thermistor room 1 26 453191800 EPS/Air Housing (high) 1 27 453193600 ESF(option) 1 28 464750006 control Box assay1 1 29 453042500R Remote controller/RC4-I-1 EHK P/N 974-710-00 1 30 464750003 Cover/Controll Box 1 1 31 464750002 Controll Box 2/CN 1 32 464750004 Cover/Controll Box 2 1 33 467420016 7 Poles Terminal BloCN 1 34 453189600 Grille Clasp 2 35 465340022 Cover1 /Front Plate 1 36 453190600 Cover2 /Front Plate 1 37 465340040 Cover3 /Front Plate 1 38 465080002 Cover4 /Front Plate 1 39 465800089 Support 1/lever Assy/CN 4
13-4
SM CN 1-E.1 GB
Page 85
EXPLODED VIEWS AND SPARE PARTS LISTS
CONTENT
No. Part No. Description Unit
40 453193500 Ionizer(option) 1 41 465800090 Support 2/lever Assy/CN 4 42 465360028 Orienting Support/Lever 6 43 464000020 Base Plate Assy./CN DCI 1 49 463750124 Liquid Pipe Assy. /6.35 1 50 463750120 Gas Pipe Assy./12.7 1 51 453188400 Fixing Plate/Evaporator high) 2 52 470100003 Cushion Rubber 3 57 453190900 Air Intake Panel (high) 1 59 453195100 Drain Jam 1 61 465800091 Linkage Assy./Flap/CN 2 62 465440018 connect Shaft/Motor 2 63 453190000 Linkage /Flap 2 64 465360022 Support/Step Motor 1 64 465360032 Support/Step Motor 2 1
SM CN 1-E.1 GB
13-5
Page 86
EXPLODED VIEWS AND SPARE PARTS LISTS
CONTENT
13.4 Indoor Unit: CN 70 DCI
No. Part No. Description Unit
1 453189500 Grille 1 2 453189900 Filter Assy. 1 3 453192700 Water-Level Switch 1 4 465720163 Front Plate Assy. 625x625 1 4 465720169 Front Plate Assy. 725x725 ION/CN Airwell 1 5 465080003 Display Cover 1 6 462350079 Evaporator Assy./CN DCI 70 R410A 1 7 453192600 Pump CN 1 8 465800084 Drain Pipe Assy/CN. 1 9 453189700 Horizontal Flap 4
10 453191300 Drain pan Assy 1
11 465360021 Support/Grill Clasp 2 12 453189300 Centrifugal Fan High(CN60X60) 1 13 453191600 EPS 1 / Front Frame 3 14 453191700 EPS 2 / Front Frame 4 14 470250017 EPS /Air outlet/Front Frame 4 15 470250004 EPS 3/Front Frame 1 16 466130009R Motor 40W/ CN60x60 1 17 465020104 Front Frame (625x625) 1 17 465020105 Front Frame (725x725) (Airwell)./CN 1 18 433050 Step Motor 2 20 464250066 Fixing Plate/Pump Assy. 1 21 467300128R Display Board/CN 1 22 467300122R Filter Board/CN DCI 1 23 467300121R Control Board/CN DCI 1 24 232299 Indoor Sensor BLACN 1 24 467400032 Coil Air Temperature Sensor-Thermister EVAP(Φ6)./CN 1 25 4519813 Thermistor room 1 26 453191800 EPS/Air Housing (high) 1 27 453193600 ESF(option) 1 28 464750006 control Box assay1 1 29 453042500R Remote controller/RC4-I-1 EHK P/N 974-710-00 1 30 464750003 Cover/Controll Box 1 1 31 464750002 Controll Box 2/CN 1 32 464750004 Cover/Controll Box 2 1 33 467420016 7 Poles Terminal BloCN 1 34 453189600 Grille Clasp 2 35 465340022 Cover1 /Front Plate 1 36 453190600 Cover2 /Front Plate 1 37 465340040 Cover3 /Front Plate 1 38 465080002 Cover4 /Front Plate 1 39 465800089 Support 1/lever Assy/CN 4 40 453193500 Ionizer(option) 1
13-6
SM CN 1-E.1 GB
Page 87
EXPLODED VIEWS AND SPARE PARTS LISTS
CONTENT
No. Part No. Description Unit
41 465800090 Support 2/lever Assy/CN 4 42 465360028 Orienting Support/Lever 6 43 464000020 Base Plate Assy./CN DCI 1 49 453194200 Liquid Pipe Assy. /9.53 1 50 453194500 Gas Pipe Assy./15.88 1 51 453188400 Fixing Plate/Evaporator (high) 2 52 470100003 Cushion Rubber 3 57 453190900 Air Intake Panel (high) 1 59 453195100 Drain Jam 1 61 465800091 Linkage Assy./Flap/CN 2 62 465440018 connect Shaft/Motor 2 63 453190000 Linkage /Flap 2 64 465360022 Support/Step Motor 1 64 465360032 Support/Step Moter 2 1
SM CN 1-E.1 GB
13-7
Page 88
EXPLODED VIEWS AND SPARE PARTS LISTS
CONTENT
13.5 Outdoor Unit: ONG3 25, 35 DCI
34
32
33
31
30
29
28
27
26
25
24
23
22
21
20
1 2 34 85 67 9
35
3637
13-8
38
39
40
41
42
SM CN 1-E.1 GB
Page 89
EXPLODED VIEWS AND SPARE PARTS LISTS
CONTENT
13.6 Outdoor Unit: ONG3 25, 35 DCI
No. Part No. Description Unit
1 433218 Front panel A 1 2 4526340 Air inlet ring-420 1 3 433223 Painting insulation plate 1 4 4526476 Axial fan OD=401 1 5 4527092 DC motor for DCI25/35 1 6 433215 Motor support 1 7 4523060 Base painting Assy. 1 8 4526299 Partition 1
9 4526403 Outdoor DC inverter controller (English) 1 10 4524177 Gas valve (R410A) 1 11 4524176 Liquid valve(R410A) 1 12 4526224 EMI fliter board 901-098-00 1 13 4526396 ChoCN Assy. 167-021-01 1 14 4526223 AC-IN connected wire 1 15 4526968 Earthing wire for DCI 1 16 4526222 Fuse connecting wire 1 17 4526300 Therminal sheet 1 18 4526220 Fuse stand JEF-511B(EHK P/N:150-038-00) 1 19 4526219 Fuse 65TS(15A,230)150-031-00 1 20 204107 Cable clip nylon 1 21 4519188 4 poles terminal bloCN 1 22 433229 Value cover 1 23 4522509 4-Way valve coil 1 24 4526367 4-way valve welding Assy. (DCI25) 1
25 4518952 4-way valve (DCI25) 1
26 4526221 Compressor wire 1 27 4526204 DC Inverter compressor Assy. 5RS102XAB 1 28 4526775 Compressor top thermistor(CTT) 1 29 4526774 Outside air thermistor(OAT) 1 30 4526776 Outside coil thermistor(OCT) 1 31 4526969 Suction coil thermistor(SUCT) 1 32 4526828 EEV Coil (CAN-MD 12FKS-1 White) 1 33 4526827 Electronic expansion value (CAMB20YGFKS-1) 1 34 4519606 Right side panel 1 35 433228 BaCN side net 1 36 4526368 Condenser soldering assy 1 37 4526298 Bridge 1 38 4519614 Painting top cover 1 39 4526480 Gasket for axial fan 1 40 4519300 Nut M5 L 1 41 433225 Handle 1 42 4519607 Left side panel painting plate 1
4526393 4-way valve welding Assy. (DCI35) 1
4518951 4-way valve (DCI35) 1
SM CN 1-E.1 GB
13-9
Page 90
EXPLODED VIEWS AND SPARE PARTS LISTS
CONTENT
13.9 Outdoor Unit: ONG3 50 DCI
13-10
SM CN 1-E.1 GB
Page 91
EXPLODED VIEWS AND SPARE PARTS LISTS
CONTENT
13.10 Outdoor Unit: ONG3 50 DCI
No. Part No. Description Unit
1 433218 Front panel A 1 2 4526340 Air inlet ring-420 1 3 433223 Painting insulation plate 1 4 4526476 Axial fan OD=401 1 5 4526475 DC motor for DCI 50 1 6 4526457 Motor support 1 7 4527363 Base painting Assy. 1 8 4526459 Partition 1
9 4526203 Outdoor DC inverter controller (English) 1 10 4524595 Gas valve (R410A) 1 11 4524176 Liquid valve(R410A) 1 12 4526224 EMI fliter board 901-098-00 1 13 4526396 ChoCN Assy. 167-021-01 1 14 4526223 AC-IN connected wire 1 15 4526968 Earthing wire for DCI 1 16 4526222 Fuse connecting wire 1 17 4526300 Therminal sheet 1 18 4526220 Fuse stand JEF-511B(EHK P/N:150-038-00) 1 19 4526533 Fuse 65TS(20A,230)150-031-00 1 20 204107 Cable clip nylon 1 21 4519188 4 poles terminal bloCN 1 22 433229 Value cover 1 23 4522509 4-Way valve coil 1 24 4527327 4-way valve welding Assy. 1 25 4518952 4-way valve 1 26 4526221 Compressor wire 1 27 4523446 DC Inverter compressor Assy. 5CS130XCC03 1 28 4526775 Compressor top thermistor(CTT) 1 29 4526774 Outside air thermistor(OAT) 1 30 4526776 Outside coil thermistor(OCT) 1 31 4526969 Suction coil thermistor(SUCT) 1 32 4526215 Electronic expansion valve ZDPF(L)-1.6C-01-RK for R410A 1 33 4526216 EEV COIL QA(L)12-HR-01A-RK 1 34 4519606 Right side panel 1 35 433228 BaCN side net 1 36 4526459 Condenser soldering assy 1 37 4526298 Bridge 1 38 4519614 Painting top cover 1 39 4526480 Gasket for axial fan 1 40 4519300 Nut M5 L 1 41 433225 Handle 1 42 4519607 Left side panel painting plate 1
SM CN 1-E.1 GB
13-11
Page 92
EXPLODED VIEWS AND SPARE PARTS LISTS
CONTENT
13.11 Outdoor Unit: DCI 60
13-12
SM CN 1-E.1 GB
Page 93
EXPLODED VIEWS AND SPARE PARTS LISTS
CONTENT
13.12 Outdoor Unit: DCI 60
No. Part No Description Unit
1 4517144 FAN COVER PP+UV 1 2 452795700 PAINTED LEFT CABINET ASSY 1 3 4521642 Painted Right Cabinet and Isolation Assy. 1 4 4523141 M10 Hexagon loCNed nut M10 1 5 4526841 cusion for fan 1 6 4526510 FAN D=460mm (3 blade) 1 7 453026500 DC Motor SIC-71FW-F170-2 1 8 453036400 Motor Support 1
9 453238900 Sensor/OAT 1 10 4526775 Compressor top thermistor(CTT) 1 11 4526776 Outdoor coil thermistor(OCT) 1 12 453035800 Partition Plate 1 13 453036100 Base Plate Paint Assy. 1 14 4526221 Compressor wire 1 15 453041900 Liquid Accumulator 1 16 452882900 Condenser and distributor welding assy. 1 17 4523446 Liquid Accumulator 1 18 453034000 4-way Valve System Assy. 1 19 4522509 4-Way valve coil 1 20 4516766 PAINTED VALVE PLATE ASSY 1 21 4526301 High pressure stop valve R410a 1 22 4524595 1/2" Gas Valve for ONG R410A 1 23 4526215 Electronic expansion valve ZDPF(L)-1.6C-01-RK for R410A 1 24 4526216 EEV COIL QA(L)12-MD-02 1 25 4518952 4-W valve SHF-7H for R410A 1 26 4525938 PAINTED RIGHT-BACN CABINET ASSY 1 27 4523145 R.lifter 1 28 4517028 PAINTED LEFT-BACN GRILL 1 29 4516758 SMALL HANDLE 1 30 452841100 Earth wire 3 31 453238800 Ground Wire 1 32 453238700 Wire UL1007 16AWG/COM 1 33 4519188 4 poles terminal bloCN 1 34 453238600 Wire 1015 16#/Power Input 1 35 204107 Cable clip Nylon 1 36 453048500 DCI 2.8kW EMI Filter Board 901-107-00 1 37 453052900 Therminal Plate Assy. 1 38 4526585 connect for motor baCNet 1 39 453030500 Outdoor DCI Controller/2.8kW(English) 906-105-00 1 40 4516788 PAINTED TOP COVER ASSY 1
SM CN 1-E.1 GB
13-13
Page 94
EXPLODED VIEWS AND SPARE PARTS LISTS
CONTENT
13.13 Outdoor Unit: DCI 72Z
13-14
SM CN 1-E.1 GB
Page 95
13.14 Outdoor Unit: DCI 72Z
CONTENT
No. Item Description Quan.
1 465100000 Grill/ DCI Trio 1 2 4523652 PAINTED LEFT CABINET ASSY 1 3 4523758 Nut M8 left 1 4 452960400 Outdoor Fan 1 5 461600023 4-Way Valve Assy. 1 6 4522509 4-way Valve Coil 1 7 4526522 FOUR-WAY VALVE R410A 1 8 466130002R DC Motor 70W 8P 1
9 4522601 Right Handle 1 10 4523653 PAINTED RIGHT CABINET ASSY 1 11 4526775 Compressor Top Thermistor(CTT) 1 12 452956500 OMT Thermistor(OMT) 1 13 452677601 Outdoor Coil Thermistor(OCT) 1 14 452809900 Base Plate Painting Assy. 1 15 460080000R Compressor Assy./ C-7RVN153H0W SANYO ShenYang) 1 16 452783600 Oil Separator Assy. 1 17 452783200 Liquid-gas Separator 1 18 453256100 Support Painting Support Assy./Gas-Liquid Separator 1 19 4526080 Valve plate paint assy 1 20 4526513 LOW PRESS VALVE (R410A) 1 21 4526514 Hight press valve(R410A) 1 22 4523654 PAINTED RIGHT BACN CABINET ASSY 1 23 4522602 Valve Cover 1 24 4518950 Filter Drier BFK-053S 1 26 204107 Cable clip Nylon 2 27 467420003 7 Poles Terminal BloCN 1 28 464280001 Terminal Plate/ DCI 72Z 1 29 4526215 Electronic expansion valve ZDPF(L)-1.6C-01-RK for R410A 1 30 4526216 EEV COIL QA(L)12-MD-02 1 31 462300002 Condenser Assy. 1 32 453175500 Guard Net Painting Assy. 1 33 453083800 Support/OAT 1 34 4526396 Choke Assy.167-021-01 1 35 464730006 Partition Plate Assy./DCI 72Z 1 36 467300082R Controller/Outdoor Unit DCI 3.0KW(English) 906A-361-00 1 37 452888500 Motor Support 1 38 464250044 Connect Plate/Controller DCI 72Z 1 39 452841100 Earth wire 3 39 4516540 Earth wire 2 40 453238900 Sensor/OAT 1 41 4523657 PAINTED TOP COVER ASSY 1 42 4522600 Left Handle 1 43 467300114R DCI 3.0KW EMI Fillter Board 901A-574-00 1
EXPLODED VIEWS AND SPARE PARTS LISTS
SM CN 1-E.1 GB
13-15
Page 96

APPENDIX A

CONTENT
APPENDIX A
INSTALLATION AND OPERATION MANUAL
OPERATION MANUAL RC4 ► OPERATION MANUAL CN DCI ► INSTALLATION MANUAL CN DCI
SM CN 1-E.1 GB
14-1
Loading...