Electra Alpha 7, Alpha 12, Alpha 9 DF, Alpha 17, Alpha 9 Service Manual

...
Service Manual
Alpha Series
REFRIGERANT
R410A
COOLING ONLY HEAT PUMP
OCTOBER - 2007
Indoor Units Outdoor Units
Alpha 7 CON 7 (Alpha) Alpha 9 GCN 9 (Alpha) Alpha 9 DF ONG3-9 Alpha 12 GCN 12 (Alpha) Alpha 12 DF ONG3-12 Alpha 17
ONG3-17 (Alpha)
Alpha 17 DF
A
LIST OF EFFECTIVE PAGES
Revision Y05-02
Service Manual - ALPHA
LIST OF EFFECTIVE PAGES
Note: Changes in the pages are indicated by a “Revision#” in the footer of each effected page
(when none indicates no changes in the relevant page). All pages in the following list represent effected/ non effected pages divided by chapters.
Dates of issue for original and changed pages are:
Original ....... 0 ........ 10 December 2004
Total number of pages in this publication is 93 consisting of the following:
Page No.
Revision No. #
Page No.
Revision No. #
Page No.
Revision No. #
Title ....................... 0
A ........................... 0
i ............................. 0
1-1 - 1-3 ................ 1
2-1 - 2-3 ................ 1
3-1 ........................ 1
4-1 - 4-3 ................ 1
5-1 - 5-12 .............. 2
6-1 - 6-3 ................ 1
7-1 ........................ 1
8-1 - 8-3 ................ 1
9-1 ........................ 1
10-1-10-2 .............. 0
11-1 ....................... 0
12-1-12-32 ............ 1
13-1-13-2 .............. 0
14-1-14-23 ............ 1
Appendix -A ........... 1
• Zero in this column indicates an original page.
*Due to constant improvements please note that the data on this service manual can be modified with out notice. **Photos are not contractual
i
TABLE OF CONTENTS
Revision Y05-02Service Manual - ALPHA
Table of Contents
1. INTRODUCTION ...................................................................................................1-1
2. PRODUCT DATA SHEET ......................................................................................2-1
3. RATING CONDITIONS ..........................................................................................3-1
4. OUTLINE DIMENSIONS .......................................................................................4-1
5. PERFORMANCE DATA & PRESSURE CURVES ................................................5-1
6. SOUND LEVEL CHARACTERISTICS ..................................................................6-1
7. ELECTRICAL DATA ..............................................................................................7-1
8. WIRING DIAGRAMS .............................................................................................8-1
9. ELECTRICAL CONNECTIONS .............................................................................9-1
10. REFRIGERATION DIAGRAMS .............................................................................10-1
11. TUBING CONNECTIONS ......................................................................................11-1
12. CONTROL SYSTEM .............................................................................................12-1
13. TROUBLESHOOTING ..........................................................................................13-1
14. EXPLODED VIEWS AND SPARE PARTS LISTS .................................................14-1
15. APPENDIX A .........................................................................................................15-1
1-1
INTRODUCTION
Revision Y05-02Service Manual - ALPHA
1. INTRODUCTION
1.1 General
The new Alpha split wall mounted is based on the compact range. It comprise the ST (cooling only) and RC (heat pump) models, as follows:
Cooling Only Alpha 7 ST/CON 7 ST; Alpha 9 ST/GCN 9 ST;
Alpha 12 ST/GCN 12 ST; Alpha 17 ST/ONG 17 ST;
Heat Pump Alpha 7 RC/CON 7 RC; Alpha 9 RC/GCN 9 RC;
Alpha 12 RC/GCN 12 RC; Alpha 17 RC/ONG 17 RC;
The indoor Alpha units are available as LED display types, featuring esthetic design,
compact dimensions, and low noise operation.
1.2 Main Features
The Alpha series benefits from the most advanced technological innovations, namely:
R410A models
Microprocessor control.
Infrared remote control with liquid crystal display.
Indoor large diameter cross flow fan, allowing low noise level operation.
Bended indoor coil with treated aluminum fins and coating for improved
efficiency.
High COP.
Easy access to the interconnecting tubing and wiring connections, so that
removing the front grill or casing is not necessary.
Refrigerant pipes can be connected to the indoor unit from 5 different optional
directions.
Automatic treated air sweep.
Easy installation and service.
4M length tubing connection kit is provided in the outdoor unit (optional).
1-2
INTRODUCTION
Revision Y05-02 Service Manual - ALPHA
1.3 Indoor Unit
The indoor unit is wall mounted, and can be easily fitted to many types of residential and commercials applications.
It includes:
Casing with air inlet and outlet grills.
A large-diameter tangential fan.
Bended coil with treated aluminum fins.
Motorized flaps
Multi-speed motor with internal protection
Advanced electronic control box assembly
Interconnecting wiring terminal block
Mounting plate
1.4 Filtration
The Alpha series presents several types of air filters:
Easily accessible, and re-usable pre-filters (mesh)
Pre-charged electrostatic filter (optional)
Active carbon filter (optional)
1.5 Control
The microprocessor indoor controller, and an infrared remote control, supplied as standard, provide complete operating function and programming. For further details please refer to the Operation Manual, Appendix A.
1.6 Outdoor Unit
The Alpha outdoor units can be installed as floor or wall mounted units by using a wall supporting bracket. The metal sheets are protected by anti- corrosion paint work allowing long life resistance. All outdoor units are pre-charged. For further information please refer to the Product Data Sheet, Chapter 2.
It includes :
A Rotary compressor mounted in a soundproofed compartment :
Axial fan.
Outdoor coil with hydrophilic louver fins for RC units.
Outlet air fan grill.
Service valves” flare” type connection.
Interconnecting wiring terminal block.
1-3
INTRODUCTION
Revision Y05-02Service Manual - ALPHA
1.7 Tubing Connections
Flare type interconnecting tubing can be produced on site. A connection pipe kit is provided in outdoor package. For further details please refer to the Installation Manual, Appendix A.
1.8 Accessories
ASK (All Season Kit):
For low ambient working conditions in cooling, an ASK can be installed inside the outdoor unit. This kit allows cooling operation down to outdoor temp of -10 ºC by gradually controlling the outdoor fan speed motor.
1.9 Inbox Documentation
Each unit is supplied with its own installation and operation manuals.
1.10 Matching Table
1.10.1 R410A
OUTDOOR UNITS
INDOOR UNITS
MODEL REFRIGER. Alpha 7 Alpha 9 Alpha 12 Alpha 17
CON 7 (Alpha) R410A
GCN 9 (Alpha) R410A
GCN 12 (Alpha) R410A
ONG3 17 (Alpha) R410A
2-1
PRODUCT DATA SHEET
Revision Y05-02Service Manual - ALPHA
2. PRODUCT DATA SHEET
2.1 R410A
Model Indoor Unit Alpha 7 Model Outdoor Unit CON 7 (Alpha) Installation Method of Pipe Flared
Characteristics Units Cooling Only Cooling Heating
Capacity
(1)
Btu/hr 7000 7000 7300
kW 2.05 2.05 2.15
Power input
(1)
kW 0.68 0.68 0.63
EER (Cooling) or COP(Heating)
(1)
W/W 3.01 3.01 3.41
Energy efficiency class
B
B B Power supply V/Ph/Hz 230V/Single/50Hz Rated current A 3.0 3.0 2.8 Starting current A 15 Circuit breaker rating A 10
INDOOR
Fan type & quantity Crossflow x 1 Fan speeds H/M/L RPM 1150/950 Air flow
(2)
H/M/L m3/hr 390/320
External static pressure
Min-Max Pa 0
Sound power level
(3)
H/M/L dB(A) 50/44
Sound pressure level
(4)
H/M/L dB(A) 37/32 Moisture removal l/hr 0.8 Condenstate drain tube I.D mm 16 Dimensions WxHxD mm 680*250*180 Weight
kg 7 Package dimensions WxHxD mm 740*250*310 Packaged weight kg 9.5 Units per pallet units 36 Stacking height units 9 levels
OUTDOOR
Refrigerant control Capillary tube Compressor type, model Rotary,TOSHIBA,PA82X1C-4DZDE Fan type & quantity Propeller(direct) x 1 Fan speeds H/L RPM 850 Air flow H/L m3/hr 1200 Sound power level H/L dB(A) 61 62 Sound pressure level
(4)
H/L dB(A) 52 53 Dimensions WxHxD mm 610*235*490 Weight
kg 27 27.5 Package dimensions WxHxD mm 720*550*360 Packaged weight kg 30/33.5(with kit) 30.5/34(with kit) Units per pallet Units 12 Stacking height units 4 levels Refrigerant type R410A Refrigerant chargless distance Kg/m 0.72kg/7.5m Additional charge kg 4m≤length≤10m,0.72kg; 10m<length≤15m,0.8kg
Connections between
units
Liquid line In.(mm) Ф 1/4”(6.35) Suction line In.(mm) Ф 3/8”(9.53) Max.tubing length m. Max.15
Max.height difference
m. Max.7
Operation control type Remote control Heating elements kW Others
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
2-2
PRODUCT DATA SHEET
Revision Y05-02 Service Manual - ALPHA
Model Indoor Unit Alpha 9 Model Outdoor Unit GCN 9 (Alpha) Installation Method of Pipe Flared
Characteristics Units Cooling Only Cooling Heating
Capacity
(1)
Btu/hr
9000 9000 9650
kW
2.64 2.64 2.83
Power input
(1)
kW
0.87 0.87 0.93
EER (Cooling) or COP(Heating)
(1)
W/W
3.03 3.03 3.04
Energy efficiency class
B
B D
Power supply V/Ph/Hz 230V/Single/50Hz
Rated current A 3.9 3.9 4.1
Starting current A 21.7
Circuit breaker rating A 10
INDOOR
Fan type & quantity Crossflow x 1
Fan speeds H/M/L RPM 1310/1100
Air flow
(2)
H/M/L m3/hr 450/360
External static pressure Min-Max Pa 0
Sound power level
(3)
H/M/L dB(A) 53/49
Sound pressure level
(4)
H/M/L dB(A) 41/35
Moisture removal l/hr 1.2
Condenstate drain tube I.D mm 16
Dimensions WxHxD mm 680*250*180
Weight kg 7
Package dimensions WxHxD mm 740*250*310
Packaged weight kg 9.5
Units per pallet units 36
Stacking height units 9 levels
OUTDOOR
Refrigerant control Capillary tube
Compressor type,model
Rotary,TOSHIBA,PA108X1C-4FZDE
Fan type & quantity Propeller(direct) x 1
Fan speeds H/L RPM 750
Air flow H/L m3/hr 1370
Sound power level H/L dB(A) 59 61
Sound pressure level
(4)
H/L dB(A) 49 51
Dimensions WxHxD mm
830x245x545
Weight kg 32.5 33.5
Package dimensions WxHxD mm 880x320x610
Packaged weight kg 35/38.5(with kit) 36/39.5(with kit)
Units per pallet Units 9
Stacking height units 3levels
Refrigerant type R410A
Refrigerant chargless distance kg/m 0.85kg/7.5m 0.9kg/7.5m
Additional charge kg
4m≤length≤10m,0.85kg
10m<length≤15m,0.93kg
4m≤length≤10m,0.9kg
10m<length≤15m,0.98kg
Connections between
units
Liquid line In.(mm) Ф 1/4”(6.35)
Suction line In.(mm) Ф 3/8”(9.53)
Max.tubing length m. Max.15 Max.height difference
m. Max.7
Operation control type Remote control
Heating elements kW
Others
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units). and EN 14511 (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
2-3
PRODUCT DATA SHEET
Revision Y05-02Service Manual - ALPHA
Units Cooling Onl
y
Btu/hr 8870
kW 2.6
Sensible capacit
y
kW 1940
Moisture removal l/hr 0.98
kW 0.78
W/W 3.34
V/Ph/Hz
A
3.5
A
A
Fan speeds RPM
M
2
Qt
y
mm
External static pressure Nom Pa
amp
dB
(A)dB(A)
-
mm
WxDxH mm
k
g
watt amp
RPM
Qt
y
mm
m3/hr
RPM
watt
M
2
Qt
y
mm
dB
(A)dB(A)
WxDxH mm
k
g
32 / 34.5
kg/m
g
/m
In.
(mm)
In.(mm
)
m. m.
kW -
-
795*610*290 / 970*650*394
R410A
Running Current (Rated)
60 / -
730
20
0.45 2
41/-/35
-
supplied by others
0.13
53/-/49
Max.8
RC7 Remote control
680*250*180 / 740*310*248
9.5
Capillary tube
Flared Max15
1.5
21°C/ 46°C
-9°C / 24°C
Power level (H/L) Pressure level(3) (H/L)
Coil
49 / -
Weight
Air flow
3/8"(9.53)
Speed (H/L)
Motor Type
0.91kg/7.5m
4m
L10m: +0g; 10mL15m: +80g
Sound
Add charge per mtr
Model
Indoor unit Outdoor unit
Cooling Temperature Operating Range (Min/Max)
Fan
Rows
Heating elements (Option) -
Max.tubing length
Connections between units
Suction line
Max.height difference
Operation control type
Liquid line
Type
1/4"(6.35)
Others -
1750
33 / 35.5
Dimensions/(packaged) Weight(packaged)
fixed RPM
Area
400
21°C DB (15 °C WB) / 32°C DB (23°C WB)
Sound
ONG3-9 R410A B1
Motor kW
10°C /27°C
16
Power level (H/M/L) Pressure level(3) (H/M/L
Condenstate drain tube I.D
3
Airflow direction control Air Filter
Cooling Temperature Operating Range (Min/Max)
Type
Model
Heating Temperature Operating Range (Min/Max)
Dimensions/(packaged)
Fin Spacing
Type Blades
Motor output
Diameter
21.7
10
H/M/L
Fan type & quantity
Delta 9RC/ST fixed rpm R410A
Model
Centifugal x1
1310/-/1100
OUTDOOR
Compressor
Motor Speed
Refrigerant
Chargless distance
Heating Temperature Operating Range (Min/Max)
Type Control
Model
Running Current (Rated
)
3.35
Power supply 220-240V/Single/50Hz
INDOOR
Air flow (1)
H
3.8 Starting current Circuit breaker rating
0.850
1940
-
Capacity (4)
Total
8870
9720
2.6
2.85
0.98
EER (Cooling) or COP(Heating) (4) 3.34
Heating
Delta 9RC/ST fixed rpm R410A
ONG3-9 R410A B1
Characteristics Cooling
Running Current (Rated) 3.5
-
Coil
Fin Spacing 1.5
M
Power input (4)
0.78
0
100
2
L
Rows
0.126Area
L/S -
125
Single Rotary
PA103X1C-4DZDE
3000
Propeller(direct) x 1
840/870
3.90/3.80
(1) Airflow in ducted units;at nominal external static pressure.
(2)
Sound power in ducted units is measured at air discharge.
(3)
Sound pressure level measured at 1-meter distance from unit.
(4)
Rating conditions in accordance to AS 3823, ISO 5151 and ISO 13253 (for ducted units).
2-4
PRODUCT DATA SHEET
Revision Y05-02 Service Manual - ALPHA
Model Indoor Unit Alpha 12 Model Outdoor Unit GCN 12 (Alpha)
Installation Method of Pipe Flared
Characteristics Units Cooling Only Cooling Heating
Capacity
(1)
Btu/hr
12000 12000 12900
kW
3.50 3.50 3.78
Power input
(1)
kW
1.16 1.16 1.17
EER (Cooling) or COP(Heating)
(1)
W/W
3.02 3.02 3.23
Energy efficiency class
B
B C
Power supply V/Ph/Hz 230V/Single/50Hz
Rated current A 5.2 5.2 5.2
Starting current A 31.5
Circuit breaker rating A 10
INDOOR
Fan type & quantity Crossflow x 1
Fan speeds H/M/L RPM 1210/950
Air flow
(2)
H/M/L m3/hr 620/460
External static pressure Min-Max Pa 0
Sound power level
(3)
H/M/L dB(A) 53/47
Sound pressure level
(4)
H/M/L dB(A) 40/33
Moisture removal l/hr 1.5
Condenstate drain tube I.D mm 16
Dimensions WxHxD mm 840*250*180
Weight kg 8
Package dimensions WxHxD mm 900*250*310
Packaged weight kg 11
Units per pallet units 36
Stacking height units 9 levels
OUTDOOR
Refrigerant control Capillary tube
Compressor type,model Rotary,TOSHIBA,PA145X2C-4FT
Fan type & quantity Propeller(direct) x 1
Fan speeds H/L RPM 830
Air flow H/L m3/hr 1450
Sound power level H/L dB(A) 65 65
Sound pressure level
(4)
H/L dB(A) 54 54
Dimensions WxHxD mm 830x245x545
Weight kg 37 38
Package dimensions WxHxD mm 880x320x610
Packaged weight kg 39.5/43(with kit) 40.5/44(with kit)
Units per pallet Units 9
Stacking height units 3 levels
Refrigerant type R410A
Refrigerant chargless distance kg/m 0.89kg/7.5m
Additional charge per 1 meter g/m
4m≤length≤10m,0.89kg
10m<length≤15m,0.97kg
Connections between
units
Liquid line In.(mm) Ф1/4”(6.35)
Suction line In.(mm) ø3/8”(9.53)
Max.tubing length m. Max.15 Max.height difference
m. Max.7
Operation control type Remote control
Heating elements kW
Others
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
2-5
PRODUCT DATA SHEET
Revision Y05-02Service Manual - ALPHA
Units Cooling Only
Btu/hr 11260
kW 3.3 Sensible capacity kW 2.585 Moisture removal l/hr 1.05
kW 1.01
W/W 3.26
V/Ph/Hz
A 4.6 A A
Fan speeds RPM
M
2
Qty
mm
External static pressure Nom Pa
amp dB(A) dB(A)
-
mm
WxDxH mm
kg
watt
amp
RPM
Qty
mm m3/hr
RPM
watt
M
2
Qty
mm dB(A) dB(A)
WxDxH mm
kg 33.5 / 36
kg/m
g/m
In.(mm) In.(mm)
m. m.
kW -
-
Model
Indoor unit Delta 12RC/ST fixed rpm R410A Outdoor unit ONG3-12 R410A B1
Characteristics Cooling Heating
Capacity (4)
Total
11260
12280
3.3
3.60
2.585
-
1.05
-
Power input (4)
1.01
1.030 EER (Cooling) or COP(Heating) (4) 3.26 3.47 Power supply 220-240V/Single/50Hz Running Current (Rated) 4.6 4.7 Starting current 24 Circuit breaker rating 10
INDOOR
Model Delta 12RC/ST fixed rpm R410A Fan type & quantity Centifugal x1
H/M/L 1210/-/950
Air flow (1)
H
L/S
172 M ­L 127
Coil
Area 0.167 Rows 2 Fin Spacing 1.5
0 Airflow direction control ­Air Filter supplied by others Running Current (Rated) 0.13
Sound
Power level (H/M/L) 53/-/47
Pressure level(3) (H/M/ 40/-/33 Cooling Temperature Operating Range (Min/Max) 21 °C DB (15°C WB) / 32°C DB (23°C WB) Heating Temperature Operating Range (Min/Max) 10 °C ~27 °C Condenstate drain tube I.D 16 Dimensions/(packaged) 840*250*180 / 900*310*248 Weight 10.5
OUTDOOR
Model ONG3-12 R410A B1
Compressor
Type Single Rotary
Model PANSONIC, 5PS132EAA22
Motor kW 1085/1115
Running Current (Rate
d
5.05/4.85
Motor Speed 3000
Fan
Type Propeller(direct) x 1
Blades 3
Diameter 400
Air flow 1850
Motor Type Fixed RPM
Speed (H/L) 810
Motor output 25
Coil
Area 0.45
Rows 2
Fin Spacing 1.5
Sound
Power level (H/L)
Pressure level(3) (H/L)
61/-
50/­Cooling Temperature Operating Range (Min/Max) 21 °C / 46 °C Heating Temperature Operating Range (Min/Max) -9 °C / 24 °C Dimensions/(packaged) 795*610*290 / 970*650*394 Weight(packaged) 34.5 / 37
Max.height difference
Refrigerant
Type R410A Control Capillary tube Chargless distance 0.93kg/7.5m Add charge per mtr 4m
L10m: +0g; 10mL15m: +80g
Type Flared Max.tubing length Max15
Max.8 Operation control type RC7 Remote control Heating elements (Option)
-
Connections between units
Liquid line 1/4"(6.35) Suction line 3/8"(9.53)
Others
-
(1) Airflow in ducted units;at nominal external static pressure.
(2)
Sound power in ducted units is measured at air discharge.
(3)
Sound pressure level measured at 1-meter distance from unit.
(4)
Rating conditions in accordance to AS 3823, ISO 5151 and ISO 13253 (for ducted units).
2-6
PRODUCT DATA SHEET
Revision Y05-02 Service Manual - ALPHA
Model Indoor Unit Alpha 17 Model Outdoor Unit ONG3 17 (Alpha)
Installation Method of Pipe Flared
Characteristics Units cooling only Cooling Heating
Capacity
(1)
Btu/hr
17570 17570 18250
kW
5.15 5.15 5.35
Power input
(1)
kW
1.70 1.70 1.65
EER (Cooling) or COP(Heating)
(1)
W/W
3.03 3.03 3.24
Energy efficiency class
B
B C
Power supply V/Ph/Hz 230V/Single/50Hz
Rated current A 7.6 7.6 7.4
Starting current A 30
Circuit breaker rating A 15
INDOOR
Fan type & quantity Cross flow x 1
Fan speeds H/M/L RPM 1200/1000
Air flow
(2)
H/M/L m3/hr 720/590
External static pressure Min-Max Pa 0
Sound power level
(3)
H/M/L dB(A) 55-50
Sound pressure level
(4)
H/M/L dB(A) 43-37
Moisture removal l/hr 2.2
Condensate drain tube I.D mm 16
Dimensions WxHxD mm 900x295x200
Weight kg 11
Package dimensions WxHxD mm 955x360x270
Packaged weight kg 14
Units per pallet units 24
Stacking height units 8 levels
OUTDOOR
Refrigerant control Capillary tube
Compressor type, model Rotary,TOSHIBA,PA200X2CS-4KT1
Fan type & quantity Propeller(direct) x 1
Fan speeds H/L RPM 910
Air flow H/L m3/hr 2160
Sound power level H/L dB(A) 64 65
Sound pressure level
(4)
H/L dB(A) 53 54
Dimensions WxHxD mm 795x290x610
Weight
kg 42 43
Package dimensions WxHxD mm 945x395x655
Packaged weight kg 45/49(with kit) 46/50(with kit)
Units per pallet Units 9
Stacking height units 3 levels
Refrigerant type R410A
Refrigerant chargless distance kg/m 1.28/7.5
Additional charge per 1 meter g/m
4m L 10M:0g
10m L 15M:+100g
Connections between units
Liquid line In.(mm) ø1/4”(6.35)
Suction line In.(mm) ø 1/2”(12.7)
Max.tubing length m. Max.15 Max.height difference
m. Max.7
Operation control type Remote Control
Heating elements kW
Others ASK Factory Option
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
2-7
PRODUCT DATA SHEET
Revision Y05-02Service Manual - ALPHA
Model Indoor Unit
Delta 17RC/ST fixed rpm R410A
Model Outdoor Unit ONG3 17 (Alpha)
Installation Method of Pipe Flared
Characteristics Units cooling only Cooling Heating
Capacity
(1)
Btu/hr
17570 17570 18250
kW
5.15 5.15 5.35
Power input
(1)
kW
1.70 1.70 1.65
EER (Cooling) or COP(Heating)
(1)
W/W
3.03 3.03 3.24
Energy efficiency class
B
B C
Power supply V/Ph/Hz 230V/Single/50Hz
Rated current A 7.6 7.6 7.4
Starting current A 30
Circuit breaker rating A 15
INDOOR
Fan type & quantity Cross flow x 1
Fan speeds H/M/L RPM 1200/1000
Air flow
(2)
H/M/L m3/hr 720/590
External static pressure Min-Max Pa 0
Sound power level
(3)
H/M/L dB(A) 55-50
Sound pressure level
(4)
H/M/L dB(A) 43-37
Moisture removal l/hr 2.2
Condensate drain tube I.D mm 16
Dimensions WxHxD mm 900x295x205
Weight kg 11
Package dimensions WxHxD mm 955x360x270
Packaged weight kg 14
Units per pallet units 24
Stacking height units 8 levels
OUTDOOR
Refrigerant control Capillary tube
Compressor type, model Rotary,TOSHIBA,PA200X2CS-4KT1
Fan type & quantity Propeller(direct) x 1
Fan speeds H/L RPM 910
Air flow H/L m3/hr 2160
Sound power level H/L dB(A) 64 65
Sound pressure level
(4)
H/L dB(A) 53 54
Dimensions WxHxD mm 795x290x610
Weight
kg 42 43
Package dimensions WxHxD mm 945x395x655
Packaged weight kg 45/49(with kit) 46/50(with kit)
Units per pallet Units 9
Stacking height units 3 levels
Refrigerant type R410A
Refrigerant chargless distance kg/m 1.28/7.5
Additional charge per 1 meter g/m
4m L 10M:0g
10m L 15M:+100g
Connections between units
Liquid line In.(mm) ø1/4”(6.35)
Suction line In.(mm) ø 1/2”(12.7)
Max.tubing length m. Max.15 Max.height difference
m. Max.7
Operation control type Remote Control
Heating elements kW
Others ASK Factory Option
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511. (2) Airflow in ducted units; at nominal external static pressure. (3) Sound power in ducted units is measured at air discharge. (4) Sound pressure level measured at 1 meter distance from unit.
3-1
RATING CONDITIONS
Revision Y05-02Service Manual - ALPHA
3. RATING CONDITIONS
Standard conditions in accordance with ISO 5151, ISO 13253 (for ducted units) and EN 14511.
Cooling:
Indoor: 27oC DB 19oC WB Outdoor: 35
o
C DB
Heating:
Indoor: 20oC DB Outdoor: 7oC DB 6oC WB
3.1 Operating Limits
3.1.1 R410A
Indoor Outdoor
Cooling
Upper limit 32oC DB 23oC WB 46oC DB Lower limit 21oC DB 15oC WB 10oC DB
Heating
Upper limit 27oC DB 24oC DB 18oC WB
Lower limit 10oC DB -9oC DB -10oC WB
Voltage 198 – 264 V
4-1
OUTLINE DIMENSIONS
Revision Y05-02Service Manual - ALPHA
4. OUTLINE DIMENSIONS
4.1 Indoor Unit: Apha 7, 9 (Omega)
4.2 Indoor Unit: Alpha 12 (Omega)
4-2
OUTLINE DIMENSIONS
Revision Y05-02 Service Manual - ALPHA
4.3 Indoor Unit: Alpha 17
4.4 Indoor Unit: Alpha 9DF
180
680
250
4-3
OUTLINE DIMENSIONS
Revision Y05-02Service Manual - ALPHA
4.5 Indoor Unit: Alpha 12DF
4.6 Indoor Unit Alpha 17DF
180
250
840
4-4
OUTLINE DIMENSIONS
Revision Y05-02 Service Manual - ALPHA
4.5 Outdoor Unit CON 7 (Alpha)
4.5 Outdoor Unit GCN 9, 12 (Alpha)
AI R OUTLET
AI R I NTAKE
4-5
OUTLINE DIMENSIONS
Revision Y05-02Service Manual - ALPHA
4.6 Outdoor Unit ONG3- 9, 12, 17 (Alpha)
5-1
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-02Service Manual - ALPHA
5. PERFORMANCE DATA & PRESSURE CURVES
5.1 Alpha7/CON7
5.1.1 Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR DB OD Coil(oC)
Data
ENTERING AIR WB/DB ID Coil(
o
C)
15/21 17/24 19/27 21/29 23/32
15
(1)
TC
2.16 2.24 2.29 2.34 2.38
SC 1.49 1.55 1.61 1.65 1.68
PI
0.48 0.48 0.48 0.49 0.49
20
(1)
TC
2.09 2.20 2.27 2.33 2.38
SC 1.46 1.54 1.60 1.65 1.68
PI
0.52 0.53 0.53 0.53 0.53
25
TC
1.98 2.14 2.25 2.31 2.37
SC 1.42 1.51 1.59 1.64 1.67
PI
0.57 0.57 0.57 0.58 0.58
30
TC
1.85 2.01 2.18 2.25 2.32
SC 1.38 1.46 1.56 1.60 1.63
PI
0.61 0.62
0.62
0.63 0.64
35
TC
1.71 1.86
2.05
2.15 2.25
SC 1.31 1.40 1.52 1.56 1.59
PI
0.66 0.67
0.68
0.69 0.69
40
TC
1.56 1.70
1.85
2.02 2.13
SC 1.23 1.33 1.44 1.48 1.51
PI
0.71 0.72 0.73 0.74 0.75
46
TC
1.35 1.48 1.62 1.79 1.93
SC 1.14 1.22 1.31 1.36 1.39
PI
0.78 0.79 0.81 0.82 0.83
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C) DB – Dry Bulb Temp., (oC) ID – Indoor OD – Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, an A.S.K Kit is required.
5-2
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-02 Service Manual - ALPHA
5.1.2 Heating
ENTERING AIR DB ID COIL(Oc)
15 20 25
ENTERING
WB OD
COIL(oC)
TH Pl TH Pl TH Pl
-10 1.13 0.50 1.09 0.54 1.04 0.56
-7 1.21 0.52 1.17 0.54 1.13 0.57
-2 1.29 0.52 1.25 0.55 1.20 0.59
2 1.57 0.55
1.51 0.58
1.44 0.62
6 2.21 0.59 2.15 0.63 2.07 0.67
10 2.41 0.62
2.34 0.66
2.28 0.71
15 2.60 0.65 2.54 0.70 2.47 0.74
20 2.74 0.67 2.68 0.72 2.60 0.78
LEGEND
TH – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C) DB – Dry Bulb Temp., (oC) ID – Indoor OD – Outdoor
5-3
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-02Service Manual - ALPHA
5.2 Model: Alpha7/CON7
5.2.1 Cooling
Discharge Pressure VS.Outdoor Temp
16
18
20
22
24
26
28
30
32
34
36
38
15 20 25 30 35 40 46
Outdoor Temp.(DB oC )
Discharge Pressure (Bar[g])
15/21(WB/DB ºC)
17/24(WB/DB ºC)
19/27(WB/DB ºC)
21/29(WB/DB ºC)
23/32(WB/DB ºC)
Suction Pressure VS.Outdoor Temp
6.5
7.0
7.5
8.0
8.5
9.0
9.5
10.0
10.5
11.0
15 20 25 30 35 40 46
Outdoor Temp.(DB oC )
Suction Pressure (Bar[g])
15/21(WB/DB ºC)
17/24(WB/DB ºC)
19/27(WB/DB ºC)
21/29(WB/DB ºC)
23/32(WB/DB ºC)
5-4
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-02 Service Manual - ALPHA
5.2.2 Heating
Discharge Pressure VS.Outdoor Temp
18
20
22
24
26
28
30
32
34
36
-10 -5 0 5 10 15 20
Outdoor Temp.( WB oC )
Discharge Pressure(Bar[g])
25 DB (ºC)
20 DB (ºC)
15 DB (ºC)
Suction Pressure VS.Outdoor Temp
4.0
5.0
6.0
7.0
8.0
9.0
10.0
-10 -5 0 5 10 15 20
Outdoor Temp.( WB oC )
Suction Pressure(Bar[g])
15 DB (ºC)
20 DB (ºC)
25 DB (ºC)
5-5
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-02Service Manual - ALPHA
5.3 Alpha9/GCN9
5.3.1 Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR DB OD Coil(oC)
Data
ENTERING AIR WB/DB ID Coil(
o
C)
15/21 17/24 19/27 21/29 23/32
15
(1)
TC
2.78 2.88 2.95 3.02 3.07
SC 1.78 1.86 1.93 1.98 2.02
PI
0.62 0.62 0.62 0.62 0.62
20
(1)
TC
2.69 2.84 2.93 3.00 3.06
SC 1.75 1.84 1.92 1.97 2.01
PI
0.67 0.67 0.67 0.68 0.68
25
TC
2.55 2.75 2.89 2.98 3.05
SC 1.70 1.81 1.90 1.96 2.00
PI
0.72 0.73 0.73 0.74 0.74
30
TC
2.38 2.59 2.80 2.90 2.99
SC 1.65 1.75 1.86 1.92 1.95
PI
0.78 0.79
0.80
0.81 0.81
35
TC
2.21 2.39
2.64
2.77 2.90
SC 1.57 1.68 1.82 1.87 1.91
PI
0.84 0.86
0.87
0.88 0.88
40
TC
2.01 2.18
2.38
2.60 2.74
SC 1.48 1.59 1.72 1.78 1.81
PI
0.91 0.92 0.94 0.95 0.96
46
TC
1.74 1.90 2.09 2.31 2.49
SC 1.36 1.46 1.57 1.62 1.66
PI
0.99 1.01 1.03 1.04 1.06
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C) DB – Dry Bulb Temp., (
o
C) ID – Indoor OD – Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, an A.S.K Kit is required.
5-6
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-02 Service Manual - ALPHA
5.3.2 Heating
ENTERING AIR DB ID COIL(Oc)
15 20 25
ENTERING
WB OD
COIL(oC)
TH Pl TH Pl TH Pl
-10 1.49 0.74 1.43 0.79 1.37 0.83
-7 1.60 0.76 1.54 0.80 1.49 0.85
-2 1.70 0.77 1.64 0.82 1.58 0.86
2 2.07 0.81
1.98 0.86
1.90 0.91
6 2.91 0.87 2.83 0.93 2.73 0.99
10 3.17 0.92
3.08 0.98
3.00 1.05
15 3.42 0.96 3.34 1.03 3.25 1.10
20 3.61 0.99 3.52 1.07 3.42 1.15
LEGEND
TH – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C) DB – Dry Bulb Temp., (oC) ID – Indoor OD – Outdoor
5-7
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-02Service Manual - ALPHA
5.4 Model: Alpha9/GCN9
5.4.1 Cooling
Discharge Pressure VS.Outdoor Temp
16
18
20
22
24
26
28
30
32
34
36
38
15 20 25 30 35 40 46
Outdoor Temp.(DB oC )
Discharge Pressure (Bar[g])
15/21(WB/DB ºC)
17/24(WB/DB ºC)
19/27(WB/DB ºC)
21/29(WB/DB ºC)
23/32(WB/DB ºC)
Suction Pressure VS.Outdoor Temp
6.5
7.0
7.5
8.0
8.5
9.0
9.5
10.0
10.5
11.0
15 20 25 30 35 40 46
Outdoor Temp.(DB oC )
Suction Pressure (Bar[g])
15/21(WB/DB ºC)
17/24(WB/DB ºC)
19/27(WB/DB ºC)
21/29(WB/DB ºC)
23/32(WB/DB ºC)
5-8
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-02 Service Manual - ALPHA
5.4.2 Heating
Discharge Pressure VS.Outdoor Temp
20
22
24
26
28
30
32
34
36
38
40
-10 -5 0 5 10 15 20
Outdoor Temp.( WB oC )
Discharge Pressure(Bar[g])
25 DB (ºC)
20 DB (ºC)
15 DB (ºC)
Suction Pressure VS.Outdoor Temp
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
-10 -5 0 5 10 15 20
Outdoor Temp.( WB oC )
Suction Pressure(Bar[g])
15 DB (ºC)
20 DB (ºC)
25 DB (ºC)
5-9
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-02Service Manual - ALPHA
5.5 Alpha12/GCN12
5.5.1 Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR DB OD Coil(oC)
Data
ENTERING AIR WB/DB ID Coil(
o
C)
15/21 17/24 19/27 21/29 23/32
15
(1)
TC
3.69 3.82 3.91 4.00 4.06
SC 2.42 2.52 2.62 2.69 2.74
PI
0.82 0.82 0.83 0.83 0.83
20
(1)
TC
3.57 3.76 3.88 3.97 4.06
SC 2.37 2.50 2.60 2.68 2.73
PI
0.89 0.90 0.90 0.90 0.91
25
TC
3.38 3.65 3.83 3.95 4.05
SC 2.31 2.45 2.59 2.66 2.71
PI
0.96 0.97 0.98 0.98 0.99
30
TC
3.16 3.44 3.71 3.85 3.96
SC 2.24 2.38 2.53 2.60 2.65
PI
1.04 1.06
1.07
1.07 1.08
35
TC
2.92 3.17
3.50
3.68 3.85
SC 2.13 2.28 2.47 2.54 2.59
PI
1.12 1.14
1.16
1.17 1.18
40
TC
2.66 2.89
3.16
3.45 3.63
SC 2.01 2.16 2.34 2.41 2.46
PI
1.21 1.23 1.25 1.27 1.28
46
TC
2.31 2.52 2.77 3.06 3.30
SC 1.85 1.98 2.13 2.20 2.25
PI
1.32 1.34 1.37 1.39 1.41
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C) DB – Dry Bulb Temp., (
o
C) ID – Indoor OD – Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, an A.S.K Kit is required
5-10
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-02 Service Manual - ALPHA
5.5.2 Heating
ENTERING AIR DB ID COIL(Oc)
15 20 25
ENTERING
WB OD
COIL(oC)
TH Pl TH Pl TH Pl
-10 1.98 0.94 1.91 1.00 1.83 1.05
-7 2.14 0.96 2.06 1.01 1.98 1.07
-2 2.27 0.97 2.19 1.03 2.12 1.09
2 2.76 1.02
2.65 1.08
2.53 1.15
6 3.89 1.09 3.78 1.17 3.65 1.24
10 4.23 1.15
4.12 1.23
4.01 1.32
15 4.57 1.21 4.46 1.30 4.35 1.38
20 4.82 1.24 4.71 1.35 4.57 1.45
LEGEND
TH – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C) DB – Dry Bulb Temp., (oC) ID – Indoor OD – Outdoor
5-11
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-02Service Manual - ALPHA
5.6 Model: Alpha12/GCN12
5.6.1 Cooling
Discharge Pressure VS.Outdoor Temp
16
18
20
22
24
26
28
30
32
34
36
38
15 20 25 30 35 40 46
Outdoor Temp.(DB oC )
Discharge Pressure (Bar[g])
15/21(W B/DB ºC)
17/24(W B/DB ºC)
19/27(W B/DB ºC)
21/29(W B/DB ºC)
23/32(W B/DB ºC)
Suction Pressure VS.Outdoor Temp
6.0
6.5
7.0
7.5
8.0
8.5
9.0
9.5
10.0
10.5
15 20 25 30 35 40 46
Outdoor Temp.(DB oC )
Suction Pressure (Bar[g])
15/21(WB/DB ºC)
17/24(WB/DB ºC)
19/27(WB/DB ºC)
21/29(WB/DB ºC)
23/32(WB/DB ºC)