Elecro Engineering Cygnet Aquatic Heater 1-kW, Cygnet Aquatic Heater 3-kW, Cygnet Aquatic Heater 4-kW, Cygnet Aquatic Heater 2-kW Installation & Operating Manual

Cygnet Aquatic Heater
Installation & Operating Manual
ENGLISH
Contents
Page
ENGLISH ........................................................................................................ 1 - 9
ESPAOL ....................................................................................................... 10 - 19
DEUTSCH ...................................................................................................... 30 - 39
www.elecro.co.uk
Important Notes!
Thank you for purchasing the CYGNET Aquatic Heater manufactured in England to the highest standards.
To ensure your new heater will give years of trouble free service please
carefully read the following instructions.
Incorrect installation will aect your warranty.
Do not discard this manual, please retain for future reference.
The appliance is not to be used by children. The appliance is not to be used by persons with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction.
Product Overview
Thermal safety
Cut-out
re-set switch
Heater ‘ON’
Indicator (red)
Temperature
set
point dial
Top cover
Flow switch
ENGLISH
LH End tting
Foot /Carrier – A
Fig 1.
Flow tube
Foot / Carrier—B
www.elecro.co.uk
RH End Fitting
Hosetail Stepped
Connector
1¼” (32mm) or
1½” (38mm)
1
ENGLISH
Positioning
POND
WATER
TREATMENT
VALVE
NON RETURN
YES
For vertical wall
mounting water
must always enter
at the bottom
2
PUMP
FILTER
Flow switch
at top
CYGNET AQUATIC HEATER
Fig 2.
NO
NO
NO
NO
Fig 3.
www.elecro.co.uk
Positioning (continued)
Your heater should be horizontally or vertically sited allowing sucient space for pipe connections and wiring, it should be screw xed securely to a rm base or wall.
The heater should be installed at a low point in the ltration system. It must be positioned downstream of (after) the lter and upstream of (before) any dosing or other water treatment plant. (see Fig.2)
Pipe Work
It is essential that the pipe work connecting to and from the heater has a minimum bore (internal diameter) of 1¼” (32mm).
To assist correct air purging and to ensure the heater remains completely full of water during operation, the return pipe which carries the water back to the pond must incorporate a safety loop or ‘kick-up’ in the pipe as close as possible to the heater (see g 3).
NOTE: When coupling to a exible pipe a safety loop can simply be created by routing the pipe up and over an obstacle. Remember to use pipe clips to securely fasten all hose connections.
ENGLISH
Weather Protection
The heater must be installed within a dry weather proof enclosure.
CAUTION! If the heater is not used during winter months it must be drained to prevent frost damage.
Electrical Connection
The heater has been supplied pre-wired with a power lead. Sizes 1-kW to 3-kW also have a plug; 4-kW models must be installed by a qualied electrician.
www.elecro.co.uk
3
ENGLISH
requirements and regulations. In any event the work must be carried out by a qualied electrician, who will provide a certicate of conformity upon completion of the work.
It is essential that the power supply to the heater is protected by a 30mA RCD (Residual Current Device). If in doubt consult a qualied Electrician.
Power Requirements
The heater must be installed in accordance with the country / regional
230V 1 Phase­Power Output
1-kW
Load
5-Amp
2-kW 9-Amp
3-kW
4-kW*
13-Amp 18-Amp
*4-kW MUST BE HARDWIRED BY A QUALIFIED ELECTRICIAN
Flow Requirements
The ow rate of water into the heater must not exceed 17,000 litres per hour (17m/h / 3,740 UK gallons/hour) A higher ow rate will require the
installation of a bypass to prevent damage to the heater elements. The heater will not operate with a ow rate below 1,000 litres / hour (1m/h or 220 UK gallons/hour)
Water Quality
The water quality must be within the following limits:
PH 6.8 - 8.0 TA (Total alkalinity) 80—140ppm (parts per million) TDS (Total Dissolved Solids) / Calcium hardness 200 - 1,000ppm
The Cygnet Aquatic heaters are suitable for use with salt water ponds with a salt concentration up to 8000ppm (8g/litre).
Water chemistry is complicated if in doubt seek expert advise.
4
www.elecro.co.uk
Operating Instructions
Upon completion of the installation, run the water-circulating pump to purge the system and heater of air (i.e. remove any trapped air in the system and heater). TIP: You can encourage air out of the heater ow tube by gently elevating the exit port of the heater when the pump is running. The heater will only switch ‘On’ (red light indicator illuminated) when the following criteria are met ie:
· Water circulating pump is ‘On’ delivering in excess of 1,000 litres / hour (1m/h or 220 UK gallons/hour)
· Required temperature is set to a higher value than the water temperature.
Useful advice: To reduce running costs and speed up the heating process, insulate the pond wherever possible.
Quick Function Test
Observe the main electricity meter when the heater is on (ie: red light ‘On’) and then observe it again when the red light is o. The test should show that the meter is recording more electricity being used by the heater when the red light is ‘On’.
ENGLISH
It is impossible for an electric heater to waste energy, if it is drawing power then that power will be turned into heat that will be transferred to the water.
Accurate Function Test
If a more accurate test is required to conrm that your heater is delivering the specied heat output, two electricity meter readings will need to be taken from the properties main electricity meter, with an exact one hour interval (ie: take one meter reading and then a second reading exactly one hour later) then by subtracting the rst reading from the second reading the number of units (kilowatts / kW) consumed can be calculated.
www.elecro.co.uk
5
ENGLISH
Note that your heater is also rated in kW hours. The pond pump and heater will need to be running continuously during the test (ie: with the heater red light ’On’) To avoid inaccurate results when performing this test, it is important to refrain from using other high current consuming appliances in the property (such as tumble dryer, showers, cookers etc).
A large aquatic pump of 1 horsepower will draw less than 1-kW in a one hour period. The conclusion of the test should prove that for example a 3-kW heater and a ½ horsepower pump will draw between 3.3-kW ~
3.5-kW in one hour. It is impossible for an electric heater to waste energy, if it is drawing power then that power will be turned into heat that will be transferred to the water.
Trouble Shooting
HEATER WILL NOT SWITCH ‘ON’
In most cases this will be the result of one of the following points not being met.
Possible cause 1: The required temperature has been achieved. To conrm: increase the set point value by turning the temperature set point dial to a value greater than the current water temperature.
Possible cause 2: The ‘Thermal safety cut-out’ has tripped. Remedy: Remove button cover and press red button to re-set (see g 4) If a positive click is felt, the cause of the tripping must be investigated and could be caused by a debris build-up or air pocket trapped inside the ow tube of the heater.
6
www.elecro.co.uk
Fig 4.
Possible cause 3: Insucient ow.
If using a cartridge lter: Conrm this by running the system with the cartridge removed from your pump and lter unit, this will supply the heater with the maximum ow rate your unit is capable of. If the heater then switches ’On’ (ie: red light ’On’) a blocked cartridge can be conrmed to be the cause. The cartridge should be cleaned or replaced. If using a sand lter: Check the pressure indicator on your sand lter and back wash if necessary.
Note: In some cases the ‘Thermal safety cut-out’ tripping and a low ow rate can be linked ie: when a lter becomes choked air can be drawn into the ltration system and become trapped inside the heater, so causing the thermal cut-out to trip.
General Trouble Shooting
THE FLOW TUBE DOES NOT FEEL WARM
Due to the high eciency of your electric heater no warmth should be detectable from the ow tube of the heater.
The most likely causes of the ow tube feeling warm are:-
ENGLISH
Possible cause 1: The heater has been positioned in direct sunlight. Possible cause 2: An air pocket is trapped inside the heater particularly if the
ow tube feels warmer at the highest point (as air rises).
THE WATER ENTERING MY POND DOES NOT FEEL MUCH WARMER
The temperature gain of the water after it has passed through the heater will be directly proportional to the volume of water being pumped in relationship to the power output of the heater.
For example: A 6-kW heater, when connected to a 4,000 litre / hour (4m/h) pump, will produce a lift in temperature of approximately 1.2°C (almost undetectable to the human hand) however, as the water being heated is re-circulated from a single body of water, the time required to heat it remains unaected by the volume of ow. A popular misconception is that slowing down the ow rate will speed up the heating process.
www.elecro.co.uk
7
ENGLISH
RoHS Compliance Statement
Elecro Engineering Limited certify that our Electric Swimming Pool Heater Range/Heat Exchanger Range complies in accordance with RoHS Directive 2011/65/EU on the restriction of hazardous substances.
Waste of Electrical / Electronic Equipment
This product complies with EU directive 2012/19/EU
Do Not dispose of this product as unsorted municipal waste.
This symbol on the product or on its packaging indicates that this product should not be treated as household waste. Instead it should be handed over to the applicable collection point for the recycling of electrical and electronic equipment.
By ensuring this product is disposed of correctly you will help prevent potential negative consequences for the environment and human health, which could otherwise be caused by inappropriate waste handling of this product. The recycling of materials will help to conserve natural resources. For more information please contact your local Civic oce, your household waste disposal service or the retailer where you purchased the product.
Guarantee
Your heater is guaranteed for 3 years from the date of purchase against faulty workmanship and materials.
The manufacturer will replace or repair, at it’s discretion, any faulty units or components returned to the company for inspection. Proof of purchase may be required.
The manufacturer will not be liable in cases of incorrect installation of the heater, inappropriate use or neglect of the heater.
8
www.elecro.co.uk
ENGLISH
www.elecro.co.uk
9
Notas importantes
Gracias por adquirir el calentador para estanques CYGNET, fabricado en
ESPAŇOL
Inglaterra según los niveles de calidad más altos.
Para que su nuevo calentador funcione sin problemas durante años, lea
atentamente las siguientes instrucciones.
Una instalación incorrecta afectará a la garantía de su producto.
Conserve este manual para futura referencia.
Visión general del producto
Interruptor de
reinicio para
seguridad térmica
Indicador (rojo) de
calentador en
marcha
Conexión extremo
izquierdo
Pie / Soporte - A
Fig 1.
Dial de
ajuste de
temperatura
Tubería de paso
Pie / Soporte - B
Cubierta superior
Controlador de
caudal
Conexión
extremo derecho
Conexión
escalonada para
mangueras
1¼’’ (32mm) ó
1½” (38mm)
10
www.elecro.co.uk
Ubicación
ESTANQUE
ESPAŇOL
DEL AGUA
TRATAMIENTO
VÁLVULA
ANTIRETORNO
BOMBA
Si se ja
verticalmente a
la pared, el agua
siempre debe
entrar por la parte
inferior
FILTRO
Controlador
de caudal
en la parte
superior
CALENTADOR CYGNET
NO
www.elecro.co.uk
Fig 2.
NO
NO
NO
Fig 3.
11
Ubicación (continuación)
El calentador debería colocarse en posición horizontal o vertical, dejando
ESPAŇOL
suciente espacio para las conexiones de las tuberías y el cableado. Además, debería atornillarse bien a una base sólida o a una pared.
El calentador debería instalarse en un punto bajo del sistema de ltrado y colocarse (en el sentido del uir del agua) en una posición posterior al ltro y anterior a cualquier sistema de dosicación u otro sistema de tratamiento del agua (véase Fig.2)
Tuberías
Es fundamental que el diámetro interno de las tuberías que transportan el agua hacia y desde el calentador sea de 1¼” (32mm) como mínimo.
Para contribuir a que la purga del aire se realice correctamente y garantizar que el calentador esté constantemente lleno de agua mientras esté en marcha, la tubería de retorno que lleva el agua de vuelta al estanque debe disponer de una curva de seguridad o un eyector lo más cerca posible del calentador (véase Fig. 3).
NOTA: Si el calentador se conecta a una tubería exible, la curva de seguridad puede crearse simplemente haciendo que la tubería pase por encima de un obstáculo. Acuérdese de utilizar abrazaderas para jar bien todas las conexiones de las tuberías.
Protección contra la intemperie
El calentador debe instalarse dentro de un espacio cerrado, seco y resistente a los elementos.
ATENCIÓN: Si el calentador no se utiliza durante los meses de invierno, el agua del interior del mismo debe drenarse para evitar daños causados por las heladas.
12
www.elecro.co.uk
Loading...
+ 30 hidden pages