Elcon SA10A User Manual

www.elcon.se
2018-03-21
Rev 1
USER MANUAL
Page 2 (40)
Rev 1 2018-03-21 www.elcon.se Go to INDEX.
IN DEX.
INDEX. ........................................................................................................................................... 2
1 General description. .................................................................................................................... 4
2 Safety regulations Important! .............................................................................................. 5
2.1 General safety regulations. ..................................................................................................................................... 5
2.2 Connection of SA10A to mains power. .................................................................................................................... 7
3.0 Connections .............................................................................................................................. 7
3.1 Connections for time measurement. ...................................................................................................................... 7
3.1.1 Safety regulations. .................................................................................................................................................. 7
3.1.2 Principals for connections to SA10A. ...................................................................................................................... 7
3.1.3 Connections for one breaking unit per phase. ........................................................................................................ 7
3.1.4 Connections for two or more breaking units per phase. ........................................................................................ 8
3.1.5 Connection for a breaking unit with a pre-insertion resistor. ................................................................................. 8
3.2 Connections for a resistance measurement of a breaking unit. .............................................................................. 9
3.2.1 Safety regulations. .................................................................................................................................................. 9
3.2.2 Connection. ............................................................................................................................................................. 9
3.3 Connections for resistance measurement of a pre-insertion resistor. ................................................................... 10
3.3.1 Safety regulations. ................................................................................................................................................ 10
3.3.2 Principal of measurement. .................................................................................................................................... 10
3.3.3 Connection. ........................................................................................................................................................... 10
3.4 Connection of the breaker operating mechanism. ................................................................................................ 11
3.4.1 Safety regulations. ................................................................................................................................................ 11
3.4.2 Connection of operating coils. .............................................................................................................................. 11
3.4.3 Connection of motor. ............................................................................................................................................ 11
3.5 Connection of transducers. ................................................................................................................................... 12
3.6 Connection to windows PC ................................................................................................................................... 12
4 Using SA10A stand alone ........................................................................................................... 13
4.1 Before operation Important! ........................................................................................................................ 13
4.2 Standalone operation of SA10A ............................................................................................................................ 13
5 Technical Specification............................................................................................................... 15
6 Maintenance. ............................................................................................................................ 18
6.1 Before use. ........................................................................................................................................................... 18
6.2 After use. .............................................................................................................................................................. 18
Page 3 (40)
Rev 1 2018-03-21 www.elcon.se Go to INDEX.
6.3 Storing the SA10A. ................................................................................................................................................ 18
6.4 Every year or when necessary. ............................................................................................................................. 18
6.5 Battery Fuse ......................................................................................................................................................... 19
6.7 Upgrading SA10A internal software. ..................................................................................................................... 20
6.8 SA10A PROGRAM LOADER in display. ................................................................................................................... 21
7 Adjustments. ............................................................................................................................. 22
7.1 General. ................................................................................................................................................................ 22
7.1.1 Instrument needed. .............................................................................................................................................. 22
7.2 Calibration and functional test. ............................................................................................................................ 23
7.2.1 Check voltage measurement inputs Uc, Uk, Ul, Um. ......................................................................................... 23
7.2.2 Check current measurement inputs Ic, Im. .......................................................................................................... 24
7.2.3 Check transducer inputs T1, T2, T3. .................................................................................................................... 25
7.2.4 Check resistance measuring inputs Ur, Ir. ............................................................................................................. 26
7.2.5 Grounding. ............................................................................................................................................................ 27
7.2.6 Check main contact inputs. 1A,1B,1C,1D,2A,2B,2C,2D,3A,3B,3C,3D. ......................................................... 27
7.2.7 Check auxiliary contact inputs. 1a, 1b, 2a, 2b, 3a, 3b. ....................................................................................... 27
7.3 Recalibration procedure. ...................................................................................................................................... 28
7.3.2 Calibration wizard for current measurement inputs Ic, Im. ................................................................................. 31
7.3.3 Calibration wizard for analogue transducer inputs T1, T2, T3. ........................................................................... 33
7.3.4 Calibration of resistance measurement input Ur. ................................................................................................ 35
7.3.5 Calibration of resistance measurement input Ir. .................................................................................................. 37
7.3.6 Enter Password. .................................................................................................................................................... 38
8 Transportation/SCRAPPING/Recycling. ...................................................................................... 39
9 SA10A Accessories. .................................................................................................................... 39
10 CE-declaration. ........................................................................................................................ 40
Page 4 (40)
Rev 1 2018-03-21 www.elcon.se Go to INDEX.
1 G ENERA L DESC RIPTI O N.
The is a portable instrument, especially designed to analyze Circuit Breakers in the field. Even though is intended for use together with a computer, it can be used stand-alone for some simpler measurements. To be handy in field works, the is built into a small and robust metal carry case. On the cover section of the carry case, a notebook computer can be placed while testing.
The measurements that can be made without a Windows computer are: voltage and current for both motor and coils, time for three independent contacts in, open, close and close-open operations and static resistance of main contacts.
Contact time measurements.
There are three groups, each of four main and two auxiliary contact indication inputs. Main contact max output 30 mA during operations and can also indicate pre-insertion resistors simultaneously. Auxiliary contact inputs can handle both free and live contacts. All contact inputs are of type semi protected banana-jacks and are protected against faulty connections and high voltage discharges.
Travel transducers.
Up to three, digital or analogue, travel transducers, in any combination, can be used for simultaneous measurements.
Resistance measurement.
Main contact resistance measuring can directly be done with an internal 200 Amp current generator. Both static and dynamic measuring is possible. Pre-insertion resistor resistance can be measured with use of a reference resistance
Operating coil control.
With an external power supply connected through this section the operating coils can be fully controlled. The current flow through the coils and the supply voltage are measured.
Motor monitoring.
In the Auxiliary section there is provisions to monitor current and voltage from an external motor supply.
Internal sampling.
Sampling frequency for analogue and digital functions can be programmed for frequencies up to 50 kHz. Note! The PC­software sets the sampling frequency.
Power supply
The SA10A must powered with an external AC- or DC- power supply.
Environmental
SA10A is built in a small metal carry case designed for rough handling in tough outdoor environments. All connections are protected for any possible type of electrical discharges and disturbances. Some of the inputs are even protected against faulty connections up to 300V peak.
PC-Computer
In most cases a standard windows notebook computer can be used but for tougher environments an outdoor type is recommended. For recommended minimum requirements for the notebook computer. See BTS11 User manual
PC-software See separate manual BTS11 User manual for more information.
Page 5 (40)
Rev 1 2018-03-21 www.elcon.se Go to INDEX.
2 S AFETY REGU LATIO NS
IM P ORTAN T!
This instrument shall only be used by authorized and educated personnel. It is the operator’s responsibility to read and follow all operating and safety instructions for connecting and using this instrument. Always keep the below safety instructions in mind when using the instrument.
2. 1 GENERA L SAFE TY R E G U LATION S .
Local safety regulations.
Always follow local safety regulations for work on high-voltage circuit breakers.
Ground connection.
Always connect the separate ground terminal (green/yellow) on SA10A to protective ground before any other connections.
The SA10A unit can only be used in electrical system with a single ground. If there is a High voltage ground and Low voltage ground make sure that there is no potential voltages difference between these grounds. If a voltages difference exists between grounds, consult local safety regulations.
Check that the separate protective ground wire is in good condition before connection. Make sure that the power socket for mains is a grounded outlet and that the power cable is in good condition before connected the main power to the control unit SA10A.
Connections.
Before connecting the SA10A to a high-voltage circuit breaker, make sure that the breaker poles are in position CLOSE, and disconnected from the power line at both sides. The breaker must also be grounded on at least one side. Follow local safety regulations for work on high-voltage circuit breakers.
To avoid unintentional breaker operation! Never do any work on a circuit breaker unless the control circuits of the breaker are disconnected from the SA10A control outputs or from any other remote control device.
All cables shall first be connected to the SA10A before any connections to the test object.
Use of touch-protected connectors is required for personal safety.
Only use original cables for connection and make sure that the cables are in good conditions.
When the SA10A is connected to a wall socket, the socket must be a grounded power outlet. Note! The inputs for coils “Uc” and motor “Um” are not fused! Make sure that the output powers to these inputs are fused with maximum 32A.
Take care when working near bare connectors and bus bars. Contact with a conductor may cause an electrical shock. Take special care at wet conditions.
Page 6 (40)
Rev 1 2018-03-21 www.elcon.se Go to INDEX.
Testing the circuit breaker
Make sure that surrounding personal can’t touch the breaker during an operation.
If a test sequence shall be running in automatic mode it’s absolutely necessary to have a security circuit that prevent
surrounding personal to touch the test object during the sequence. The power supplies for coils and motor must be interlocked to a security circuit that cut the power if the security circuit is open.
Read also additional safety regulations presented in sections below.
3.1.1 Safety regulations. 3.2.1 Safety regulations.
3.3.1 Safety regulations. 3.4.1 Safety regulations.
Page 7 (40)
Rev 1 2018-03-21 www.elcon.se Go to INDEX.
2. 2 CONNEC T I ON OF S A10A TO MAINS P OWER.
The SA10A can be powered from any AC source 100-240V or DC source 100-240 VDC (with a ground connection).
When the SA10A is connected to a wall socket, the socket must be a grounded power outlet.
IMPORTANT!
The SA10A have a separate grounding terminal (green/yellow) that must be grounded to the nearest protective earth (ground) with a separate wire.
3.0 CONNECTIO NS
3. 1 CONNEC T I ONS F O R TIME M E ASURE M E N T .
3. 1 . 1 SAFE T Y REGU L A TIONS.
When only one side of the breaker is connected to earth (ground), special precautions must be observed. To protect service personnel and the measuring equipment from surges, two important rules must be followed closely.
The SA10A case must be grounded.
All circuit breaker connections and disconnection’s must be made while the breaker poles are closed and connected
to earth (ground) on least one side.
To avoid unintentional breaker operation! Never do any work on a circuit breaker unless the control circuits of the
breaker are disconnected from the SA10A control outputs.
Use of touch-protected connectors.
3. 1 . 2 PRI N C IPALS F OR CONNE C TIONS T O SA10A .
To get a useful protocol and to fit to the PC-software it is necessary to connect contacts in a certain way:
Use separate contact groups ("Contacts 1" - "Contacts 3") for separate phases.
Use contacts "A" - "D" for separate breaker elements in each phase.
Use contacts "a" and "b" for connection of auxiliary contacts (live or free)
Note! Do not exceed the input voltage limit of 250 V AC or 300 V DC.
3.1 .3 C ONNECT I ONS FO R ONE BRE A KING U N I T PE R P H ASE.
Figure 2.1 Connections for a one breaking unit per phase
Page 8 (40)
Rev 1 2018-03-21 www.elcon.se Go to INDEX.
3. 1 . 4 CON N E C TIONS FOR TWO O R MORE BREAKI N G UNITS P ER PH A S E .
Note!
Only one phase is shown
Figure. 2.2 Connections for four breaking units per phase
3.1 . 5 CON N E C TION F OR A BRE A KING U N IT WI T H A PRE-I N SERTIO N RESIS TOR.
The contact inputs "A" -"D" in each contact group have two levels of resistance sensitivity. There is no difference between connecting a breaker unit with a pre-insertion resistor and connecting a breaker unit without a pre-insertion resistor.
Note!
The value of the pre-insertion resistor must be in the range 50 - 5000 ohm
Figure. 2.3 Connections for a breaking unit with a pre-insertion resistor
Page 9 (40)
Rev 1 2018-03-21 www.elcon.se Go to INDEX.
3. 2 CONNEC T I ONS F O R A RESI S TANCE M E ASURE M E N T OF A B REAKI N G UNIT.
3.2 . 1 SAFE T Y REGU L A TIONS.
When only one side of the breaker is connected to earth (ground), special precautions must be observed. To protect service personnel and the measuring equipment from surges, the following important rules must be followed closely.
The SA10A case must be earthen (grounded).
All circuit breaker connections and disconnection’s must be made only while the breaker poles are closed and
connected to earth (ground) on least one side.
To avoid unintentional breaker operation! Never do any work on a circuit breaker unless the control circuits of the
breaker are disconnected from the SA10A control outputs.
Use of touch-protected connectors is required for personal safety.
200A Red Pole of SA10A is connected to chassis ground, and must be connected to the grounded side of the breaking
unit. See figure 2.4 below
3.2 . 2 CON N E C TION.
Use a connection cable with an area of 25mm² or more, to connect from the 200A current generator to the
breaking unit that is going to be measured.
Important!
200A Red Pole of is connected to chassis ground, and must be connected to the grounded side of the breaking
unit. See figure 2.4
Important!
Keep the two measuring wires connected to Ur+ and Ur- near together (twisted) as long as possible to reduce
interference and get a good measuring result.
Note! If there is a current transformer (CT) in the circuit, the 200A current from SA10A shall if possible be connected so that the 200A measuring current not go through the CT. If that not possible, the secondary windings of the CT must be short circuit and the CT must be demagnetized after done test.
Figure. 2.4 Connections for a resistance measurement of a breaking unit
Page 10 (40)
Rev 1 2018-03-21 www.elcon.se Go to INDEX.
3.3 CONNEC T I ONS F O R RESIS T A NCE M E A S UREME N T O F A P R E -INSE R T ION RESI S TOR.
3. 3 . 1 SAFE T Y REGU L A TIONS.
When only one side of the breaker is connected to earth (ground), special precautions must be observed. To protect service personnel and the measuring equipment from surges, the following important rules must be followed closely.
The SA10A case must be grounded.
All circuit breaker connections and disconnection’s must be made only while the breaker poles are closed and
connected to earth (ground) on least one side.
To avoid unintentional breaker operation! Never do any work on a circuit breaker unless the control circuits of the
breaker are disconnected from the SA10A control outputs.
The reference resistor itself and connections to the reference resistor must be well isolated.
Warning! Do not short-circuit or touch the auxiliary voltages to and from the SA10A.
Use of touch-protected connectors is required for personal safety.
3.3 . 2 PRI N C IPAL O F MEASUR E M E N T.
The auxiliary DC-voltage to the coils are used as a voltage source. The voltage division between the pre-insertion resistor and a reference resistor is used to calculate the resistance of the pre-insertion resistor.
Selection of reference resistor.
Select the reference resistor in the same range (or lower) as the pre-insertion resistor. Use a power resistor (>= 10W). Current will flow during a short time i.e. the pulse length set for coils.
The voltage across the reference resistor and the pre-insertion resistor are recommended to be greater than 20VDC and must be less than 300VDC. Try to get as high current as possibly to avoid influence from surrounded capacitive current.
3.3 . 3 CON N E C TION.
See figure 2.5. Make sure that the Resistor itself and connections to the reference resistor are well isolated.
Connect a wire between COILS:COM and AUX:COM Connect a wire between output COILS:CLOSE and measuring input AUX:Uk. Connect a reference resistor between output COILS:CLOSE and measuring input AUX:Ul. Connect the pre-insertion resistor between AUX:Ul” and AUX:COM.
Connect the breaker coils to the SA10A for a normal CO-operation (not shown in figure 2.5).
Note! Do not connect the motor to SA10A. See 3.4.2 Connection of operating coils. for connections.
Figure. 2.5 Connections for resistance measurement of a pre-insertion resistor
Page 11 (40)
Rev 1 2018-03-21 www.elcon.se Go to INDEX.
3.4 CONNEC T I ON OF THE BRE A K ER OP E R ATING M E C HANISM .
3.4 . 1 SAFE T Y REGU L A TIONS.
The case must be grounded.
Warning! Do not short-circuit or touch the auxiliary voltage.
Use of touch-protected connectors is required for personal safety.
The inputs for coils “Uc” and motor “Um” are not fused!
Make sure that the powers to these inputs are pre-fused with maximum 32A.
Never do any work on a circuit breaker unless the control circuits of the breaker are disconnected from the SA10A
control outputs. (avoiding unintentional breaker operations)
Note! The white 4 mm panel socket "ISOL" is an isolated connection that can be used to disconnect the control circuits of the breaker.
3.4 . 2 CON N E C TION O F OPERA T ING CO I L S.
See figure 2.6
Connect the input coil voltage to the inputs Uc and COM.
Connection to COM is optional and is only used for monitoring the voltage.
Connect the positive connection of the closing coil and the positive connection of the opening coil to the outputs
CLOSE and OPEN.
Connect the negative connections of the operating coils to the negative connection of the coil voltage.
3.4 . 3 CON N E C TION O F MOTOR.
See figure 2.6
Connect the auxiliary voltage to the inputs Um and COM
Connect the motor connections to the output MOTOR and to the negative connection of the auxiliary voltage.
Note!
The connection of the motor circuit is optional and is only necessary for monitoring the voltage and current
+ ~
-
+ ~
-
~
Coil Voltage <=32A
Motor Voltage <=32A
Motor
Close Coil
Open Coil
Coil interlocking
Figure. 2.6 Connection of the breaker operating mechanism
Page 12 (40)
Rev 1 2018-03-21 www.elcon.se Go to INDEX.
3.5 CONNEC T I ON OF TRANSDUCE R S.
Up to three pulse- or analog transducers can be connected to the inputs T1, T2, T3.
The connection must be done with a special cable connector: Connector: LEMO FGG.2K.308.CLCK90
Pin Description for a digital pulse transducer.
1 Pulse 1.
2 Pulse 1 inverted.
3 Pulse 2.
4 Pulse 2 inverted
5 +5 VDC
6 Ground.
Pin Description for an analog transducer
5 +5 VDC
6 Ground
7 Analogue measurement (Wipe)
8 Is not used.
Tip!
Use prefabricated cables for connection.
3.6 CONNEC T I ON TO W INDOWS PC
Any standard Windows PC with one free RS232, USB 2.0, USB 3.0 port can be connected.
The can be connected with 3 different methods.
USB Mini to USB cable. (Max 1 meters)
RS232 9 Pol Male to 9 Pol Female cable. (Max 2 Meters)
If computer is not equipped with RS232 port an USB to RS232 adapter can be used.
Bluetooth communication kit
Use a standard straight serial RS232 PC-cable with a 9 pole DSUB Male Female connectors, for connection to .
Loading...
+ 28 hidden pages