elco AEROTOP T Series, T07C, T12C, T12, T07 Planning Document

...
Page 1
Planning Document
AEROTOP T Air-Water Heat Pump
General information
Calculations, dimensioning, installations and commissioning
with regard to the products described in this document may only be executed by proven experts.
Locally valid regulations must be observed; they may deviate
from the information in this document.
Changes remain reserved.
10/2012 Art. 420010415801
Page 2
Table of Contents
Product overview AEROTOP T............................................................................ 3
Performance curves overview AEROTOP T at 35°C flow line................................................. 4
AEROTOP T at 45°C flow line................................................. 5
Product Description AEROTOP T............................................................................ 6
Planning hints Correct dimensioning................................................................ 8
Operational limits...................................................................... 9
Determination of the heating capacity...................................... 10
Dimensioning of pressure expansion vessels........................... 11
Dimensioning AEROTOP TC integrated expansion vessel...... 12
Cooling with the heat pump system.......................................... 13
Technical Data AEROTOP T............................................................................ 16
Fan rotational speed................................................................ 22
Loss of pressure water-heat exchanger................................... 23
Integrated pumps..................................................................... 24
Remaining pump pressure....................................................... 25
Noise level................................................................................ 26
Check list For correct setup of an air-water heat pump............................ 27
Performance data AEROTOP T07 T16.............................................................. 28
AEROTOP T20 T35.............................................................. 29
AEROTOP T07X T10X......................................................... 30
AEROTOP T07R T16R (Cooling)………............................. 31
AEROTOP T20R T35R (Cooling)………............................. 32
Setup and connection Safety, transport and installation.............................................. 33
Electrical connections, setup types.......................................... 34
Hydraulic connections, condensation water drain................... 34
Commissioning Conditions, parameterization, maintenance............................ 35
Indoor setup Unit dimensions....................................................................... 36
Air connections for indoor setup Air connections, type of setup.................................................. 38
Air inlet, corresponding unit dimensions................................... 38
Air outlet, corresponding unit dimensions................................ 39
Corner setup............................................................................ 40
Cut-out plans wall setup............................................................ 42
Accessories.............................................................................. 43
Variations corner setup with inflexible ducts............................. 47
Cut-out plans parallel setup....................................................... 49
Outdoor setup
Special regulations, setup location........................................... 51
Foundation plan....................................................................... 52
Performance diagrams AEROTOP T............................................................................ 54
Hydraulic plan Standard plans......................................................................... 74
Notes ................................................................................................. 82
Unit dimensions........................................................................ 50
2
Page 3
Product Overview
AEROTOP T
The high quality air-water heat pump AEROTOP T extracts geothermal heat from the environment and releases it to the heating system at a higher temperature. AEROTOP T heat pumps are suitable for indoor and outdoor installation when using the corres­ponding accessories (not T..C…).
The reversible model of the AEROTOP T heat pump series can also be used for active cooling. The broad range of AEROTOP T heat pumps is available in the following versions and models:
AEROTOP T
The standard version is used exclusively for heating, indoor or outdoor installation, 3x400 VAC.
AEROTOP T..C
Up to model AEROTOP T12C additionally available as compact heat pump with integrated buffer storage, electrical heater element, expansion vessel and circulation pump.
AEROTOP T..X
Up to model AEROTOP T10X and to AEROTOP T10CX also available in 1x230V (available in F / I / B).
AEROTOP T..R
Reversible heat pump in standard version, used to heat and cool, indoor or outdoor installation, 3x400 VAC.
AEROTOP T..RX
Up to model AEROTOP T10RX, also available in 1x230 V (available in F / I / B).
3
Page 4
Performance Curves Overview
AEROTOP T with 35°C Flow
Heating capacity AEROTOP T with 35°C Flow
Heating capacity (kW)
Air intake temperature (°C)
Also applies to same models in compact (C), in reversible (R), and mono-phase (M) designs.
4
Page 5
Performance Curves Overview
AEROTOP T with 45°C Flow
Heating capacity AEROTOP T with 45°C Flow
Heating capacity (kW)
Air intake temperature (°C)
Also applies to same models in compact (C), in reversible (R), and mono-phase (M) designs.
5
Page 6
Product Description
AEROTOP T
High Degree of Efficiency and Optimized Defrosting
Thanks to the correspondingly dimensioned air heat exchanger as well as the unique defrosting system, the AEROTOP T heat pump is especially efficient and a cost-saver. This heat pump always exceeds the required degree of efficiency (coefficient) of3.0 (COP at A2W35). Frost forms on the air exchanger, the evaporator, if the exterior temperature is less than 5°C. This results in ice formation and as a consequence reduces the heat exchange and with that the efficiency of the heat pump. The evaporator must be defrosted to remove this frost or ice. However, the defrosting process, carried out by the AEROTOP T by reversing the cooling circuit, is cumbersome since the heat pump does not yield any energy during the defrosting process but still uses electricity. This is frequently unnecessary since frost formation depends on the humidity in the air. Instead of the unnecessary defrosting at timed intervals, the AEROTOP T determines the correct time to defrost the unit using a progressive and well thought out logic with different per­formance parameters in the cooling circuit. Thanks to this procedure, the unit rarely requires any defrosting during the winter, if any at all, which is a great advantage.
Cooling with AEROTOP TR
The purpose of heat pumps is primarily to supply a building with heat. However, the technology can also be used to cool a building in the summer. This involves actively generating the cooling energy through a process reversal of the heat pump. In case of distributor systems specifically designed for cooling (fan coil or similar), the cooling capacity of the heat pump can be transferred optimally to the building. Cooling ceilings also have a good cooling capacity and comfort level. Floor heaters, however, are only partially suited and provide a limited cooling effect. Radiator heaters are unsuitable.
Cascade
Thanks to the new heat pump controller LOGON B WP61, it is possible to link and operate several heat generators of a system in a cascade arrangement. Cascades with up to 4 heat pumps, or a bivalent operation in combination with fossil heat generators are feasible. When using a cascade formation, the heat generators switch on or off depending on the current energy demand: If the currently running heat pump cannot satisfy the energy demand within a specific time, an additional heat pump/heat generator switches on.
Quiet Operation
Regardless whether installed indoors or outdoors, the air-water heat pump AEROTOP T is characterized by comparatively very low noise emissions. This is possible thanks to the high-performance fan, the very advantageous air routing, the noise--dampening insulation of the cladding, as well as the multi-dampened support of the cooling circuit. Additional noise insulation elements are available for most variants to reduce sound emissions further. AEROTOP T heat pumps are quiet and efficient. However, incorrectly integrating constructional components may result in undesired noise increases if the conditions are unfavorable.
Flexible and Space-Saving
Thanks to the clever utilization of the geometric properties of the radial fan, AEROTOP T heat pumps are among the most flexible, space saving air--water heat pumps. Especially noteworthy is the fact that the heat pump can be placed into the left or right corner of the utility room when not using the air ducts. The exhaust opening is easily moved on-site from the left to the right and even to the top without having to use any additional tools. The intake openi selected as desired without special accessories. AEROTOP T heat pumps are also suitable for outdoors installation when using the corresponding accessories.
ng can also be
6
Page 7
Product Description
AEROTOP T
Enclosure and Special Components
The enclosure consists of a frame that is completely free of thermal bridging, sound dampened, and specifically developed for use with heat pumps. The cladding and panels feature a high-grade insulation to sound-dampen and thermally insulate the unit. A pedestal or base is not required since the feet of the unit feature a vibration­dampening design. All panels can be detached for easy access to the internal elements of the unit and for control or configuration tasks.
The high-performance radial fan ensures the unit runs efficiently and quietly. The high performance cooling circuit is mounted on a vibration­dampened support and features a thermostatic expansion valve, filter dryer, inspection glass, high-pressure pressure controller with manual reset, and a low-pressure pressure controller with automatic reset function. The hermetic scroll compressor is mounted on a double vibration dampened s upport. The evaporator consists of a large-area finned tube heat exchanger made from aluminum and copper; the condenser consists of a welded chromium steel high performance plate heat exchanger. The environmentally friendly refrigerant R407C is used as the working medium. A flow monitor on the consumer side ensures trouble-free cooling for reversible heat pumps.
Brief Description of the LOGON B WP61 Controller
Plain text display unit, control and protection of the cooling circuit, defrost logic, malfunction display and dia­gnostics, control of a sliding or mixed heating circuit, service water heating, storage tank charging, control of the electrical auxiliary heater, expandable for several mixed heating circuits.
LPB system bus with up to 15 heating circuits per segment, bivalent operation with additional heat generator (oil/gas), cascade of several HPs. cooling function, improved solar function (heating support, pool, PWH), pool function, controlling the multi-phase electrical heating elements.
Selectable Connections
The connections for heater flow and return, condensate drain, and electrical connections can be placed on the left or right side during the on-site installation and even directed towards the bottom when installed outdoors.
7
Page 8
Planning Notes
Correct Dimensioning of the heating capacity
Heat demand of the building
Heating capacity of an air-water heat
Exterior temperature
Exterior design temperature
Exterior temperature
Heat Demand and Heat Capacity
The correct dimensioning of the air-water pump is a key task. The heat pump must meet the heat demand of the building. This demand increases as the exterior temperature drops but the heat capacity of the air-water heat pump decreases at the same time. The two charts illustrate this opposing trend.
Heating capacity
Heat demand of the building
Exterior temperature
Chart A
Heating capacity
Heat output Auxiliary heater
Heating capacity of
an air-water heat
pump dimensioned
for exterior design
temperature (output
Heating capacity of
an air-water heat
pump dimensioned
for bivalence
temperature
(correct output)
Exterior temperature
too high)
Correct Dimensioning and Bivalence Point
This makes it clear that a monovalent system with an air-water heat pump as the only heat generator has a clearly overdimensioned heat pump during most of the year and especially during the intermediate season. Not only does this result in higher investments costs, the more frequent switching (on, off) of the heat pump also has a negative effect on the pump's efficiency and thereby increases operating costs (see chart A).
A somewhat smaller heat pump is selected for a bivalent system. This pump is dimensioned not for the exterior design temperature of the system but a slightly higher exterior temperature instead, the so-called bivalence point. If the exterior tempera­ture drops below the bivalence point, an electrical auxiliary heater is switched on, this then covers the missing heat output. The heat pump continues to have priority and, together with the additionally activated electrical heater, delivers the required heat (see chart B).
With a bivalence point, the heat pump is dimensioned exactly to meet the heat demand of the building. With lower exterior temperatures, the electrical auxiliary heater is activated; with higher exterior temperatures, the heat pump is still overdimensioned but to a lesser degree. An optimal annual degree of efficiency (coefficient) is achieved if the bivalence point is set to be slightly below the temperature most frequently occurring at the building location.
Bivalence point
Chart B
8
Page 9
Planning Notes
Operating Limits
General Information
The rated throughput values for evaporator and condenser are minimum values. Set points and adjusted parameters may not fall below these values to ensure the indicated performance.
Pipes, tubes, and air ducts must be kept as short as possible and routed in such a way that pressure and heat loss are minimized. Incorrectly or badly installed or dimensioned pipes, tubes, or air ducts may damage the heat pump.
Area of Application
The following chart depicts the application area of the air-water heat pump AEROTOP T. Please consult the performance overview for more detailed operating specifications for various heat pump models. The temperature difference at the condenser must be between 7 and 10°C.
flow temperature [°C]
Operating the heat pump is prohibited if the following conditions exist:
Construction drying
System/unit used in unfinished
buildings
Windows or exterior doors
unfinished and locked These cases require the use of a specific construction heating system. Functional heating or surface-ready heating with the heat pump acc. to DIN EN 1264 is only permitted when complying with these conditions.
source inlet temperature [°C]
Furthermore, it must be noted that the design of the heat pump concerning its standard operation may not yield the full extent of the required heat output.
The following notes must be observed as well:
Comply with the corresponding
standards and rules of the floor/screed manufacturer!
Proper function is only ensured
with a correctly installed system (hydraulics, electrical, settings)!
Deviations may damage the
floor/screed!
9
Page 10
Planning Notes
Determining Heat Output and Allowances
Retrofitting an existing oil or gas heater with heat pump:
The heating capacity can be calculated based on the existing average fuel consumption.
Gas heater
Oil heater
Mid-level altitude
In excess of 800 m above
With hot water
Qh = Oil consumption (Ltr.)
Qh = Oil consumption (Ltr.)
Mid-level altitude Qh = Gas consumption (m3) x 0.93
300
In excess of 800 m above
Qh = Gas consumption (m
330
3
) x 0.93
Qh = Heat demand in kW
Hot water demand
Hot Water Allowances
The allowance for generating hot water
per person
and day (l)
can be taken into account as follows:
Example
Number of people 4
Hot water demand 50 liters per person and day.
Heat demand allowance:
Q˙WW = 4 x 0,085 kW = 0,34 kW
With hot water
Without hot water
Qh = Oil consumption (Ltr.)
300
265
Qh = Oil consumption (Ltr.)
330
Without hot water
295
Qh = Gas consumption (m3) x 0.93
265
Qh = Gas consumption (m3) x 0.93
295
Additional heating output
per person (kW)
Tw = 45°C
T = 35 K
30 0,051
40 0,068
50 0,085
60 0,102
Allowances to the Heat Pump Output Off Periods
Blocked Times
The off periods (blocked times) theoretically should be considered by
f = 24 h 24 h - off period per day (h)
the following formula and the heat demand should be multiplied with the factor f.
10
Page 11
Planning Notes
Configuration of Pressure Expansion Vessels
VN = VA x F x X
Key Vn = Expansion volume VA = System content acc. to
list below F = Temperature-dependent Factor
TZ = Average system temperature TZ = (TV + TR)/2
= F
X = Safety factor
Safety factor for boiler output
Important
Water contents of hot water tanks (buffer storage) are not considered in the table and must be added separately.
40°C 50°C 60°C 80°C
0,0079 0,0121 0,0171 0,029
Up to 30 kW X = 3,0
31 - 150 kW X = 2,0
above 150 kW X = 1,5
1 = Floor heating 2 = Radiators 3 = Heating panels
Select the expansion vessel based on the expansion volume and the system height Hp. The system height Hp is the height from the middle of the expansion vessel up to the upper point of the heating unit.
VA system capacity (liter)
Boiler output (kW)
Type
PND 18 10,3 8,7 7,7 6,6 5,1 3,5
PND 25 14,3 12,0 10,7 9,1 7,1 4,7
PND 35 20,2 17,0 15,0 13,0 10,0 7,0
PND 50 28,6 24,4 21,4 18,5 14,3 9,8
PND 80 45,7 38,6 34,3 29,7 22,9 16,5
max. height Hp 2 m 5 m 7 m 9 m 12 m 15 m
11
0,5 bar 0,8 bar 1,0 bar 1,2 bar 1,5 bar 1,8 bar
Initial Pressure in Empty Vessel (= Hp + 0,3 bar)
Page 12
Planning Notes
Configuration of the AEROTOP TC integrated 12 litre expansion vessel
General information for the correct configuration
The heat pumps AEROTOP T..C can be installed without an additional external expansion vessel if all of the following conditions are met:
Direct heating circuit: Standard 1
or standard 1-6
H (height of system) <= 7m
Heating capacity at outdoor
temperature (Ta) –10°C of maximum 10kW. (Note: AEROTOP T12C electric heater element with max. 2 kW)
Water volume of the system VA
must not exceed the values given in the table.
Installation example
AEROTOP T12C, electric heater element with maximum capacity of 2 kW, standard
TZ 35°C: Maximum averaged
temperature of the system during heating mode (corresponds to 40°C/30°C)
H (system height) <= 7m
Ta (dimensioning of outdoor
temperature): -10°C
AEROTOP T12Cmaximum capacity
at Ta of -10°C and 40°C Flow temperature: 7.4 kW + 2 kW Electric heater element = 9.4 kW < 10 kW, OK!
Requirement: VA <= 290 litres;
rough verification: Maximum heating capacity at Ta of 9.4 kW x 20 litres/kW for underfloor heating + 50 litres Integrated accumulation tank = 238 litres < 290 litres: OK! VA must be known for final dimensioning of the expansion vessel.
Permissible water volume VA of the system
The following table gives the maximum water volumes for the system depending on the TZ (max. averaged temperature of the system during heating mode) and the structural height of the system (H), whose expansions can be absorbed by the integrated 12 litre expansion vessel.
H (m) p
2 0.5 550 390 300 230 190 160 130
3 0.6 520 370 280 220 180 150 130
5 0.8 460 330 250 190 160 130 110
6 0.9 430 310 230 180 150 120 100
7 1 400 290 210 170 140 110 100
9 1.2 340 250 180 140 110 100 -
12 1.5 240 180 130 - - - -
15 1.8 - - - - - - -
H System height p
(bar) Minimum primary pressure of expansion vessel
o
TZ Maximum averaged operating temperature of the system (Tvl + Trl)/2 during heating mode PSV Switching-on point of the pressure relief valve = 3 bar
Permissible water volume of the system. Heating system water volume including 40 litres of the
V
A
integrated accumulation tank
(bar) TZ = 30°C TZ = 35°C TZ = 40°C TZ = 45°C TZ = 50°C TZ = 55°C TZ = 60°C
0
VA [Litres]
12
Page 13
Planning Notes
Cooling with Heat Pump Systems
Active Cooling
The cooling energy is produced actively using the heat pump to cool. The purpose of heat pumps is primarily to supply a building with heat. However, the technology can also be used to cool a building in the summer. This requires a process reversal during the cooling cycle. In this case, the heat emission side (condenser) becomes the heat absorption side (evaporator). During this phase, the heat pump functions like a refrigerator. The cooling and heating cycle cannot run at the same time. The use of a cool store is recommended in any case to prevent the heat pump from switching on and off and switching to water heating too often. Depending on the system concept, the heating storage can also be used as cooling storage. In case of distributor systems specifically designed for cooling (fan coil orsimilar), the cooling capacity of the heat pump can be transferred optimally to the building. Cooling ceilings also have a good cooling capacity and comfort level. Floor heaters, however, are only partially suited and provide a limited cooling effect. Radiator heaters are unsuitable.
Active Cooling Insulation
Water at a temperature less than 17°C is considered to be cold water. In the presence of cold water, the usual heating system insulations cannot be used. Suitable insulation, especially when using active cooling, is necessary. Insulation suitable for cold water is primarily used to avoid condensation but also to prevent cold water absorbing any of the heat, and also to protect against external mechanical stresses. Condensation must be avoided with a suitable insulation to prevent surface corrosions on the distributor system or mold in moist layers.
Insulation for cold water must be vapor-- proof and installed to all distributor system elements (pipes, tanks, pumps, cocks, valves, etc.) in a vapor-proof manner. Special insulating materials are commercially available in different designs (e.g. Armaflex, Tubolit). Standards SIA 380, DIN 4140 describe the insulation techniques. Please comply with the guidelines of relevant local professional associations (VSI, VDI, FESI).
General Cooling Information
1. The cooling cycle always must be monitored. If the room air is cooled unchecked, condensation water will emerge. This may damage the equipment or building components. The flow temperature in conjunction with the humidity (dew point contact temperature detector or room sensor for humidity and tempera ture) is best for monitoring.
2. A separate cooling circuit should be planned for the cooling mode. This circuit can be combined with a cooling ceiling or ventilation system, for example. Partial cooling via the floor heater or convectors is also possible if the need for cooling is limited.
3. Water flow must be ensured or cooling is not possible. When cooling via the heating surfaces, thermostatic individual controls must be used that can be switched to cooling mode. The valves are otherwise closed in summer and cooling is impossible.
Measures to Reduce the Building Cooling Capacity
The room cooling capacity is calculated based on the sum of the individual room demand. If the cooling demand exceeds the available cooling capacity, the following reduction measures may be used:
1. Direct sunlight through the window areas can be restricted through constructional measures (shutters, window shades, blinds).
2. The amount of sunlight received by each room frequently differs due to the different cardinal points.
is means that not the entire
Th cooling capacity must be available at the same time. This can reduce the max. simultaneous cooling demand.
3. Nighttime cooling of constructional elements can also lower the daytime cooling demand.
Calculating the Cooling Capacity
The cooling demand is calculated in accordance with national and local standards. E.G.: VDI 2078 : Real estate and buildings DIN 18599: Energetic assessment of nonresidential buildings (also includes air-conditioning or cooling) DIN EN ISO 13790 Energetic assessment of buildings (similar to DIN 18599) only across Europe DIN EN 255 SIA382/2: Room temperature requirements. SIA382/3: Determining the cooling requirement of building.
Cooling is differentiated by internal cooling capacity (e.g. thermal discharge of equipment, persons, lights) and external cooling capacity (sun exposure, heat from building components, and ventilation gains due to exterior air). The estimate acc. to HEA can be used for approximate calculations. However, the conditions listed below must be taken into account as well. The calculations of the implementation phase must be based on national and local standards.
Empirical Data for a Quick Calculation
Factors
Private residences 30 Watt/m3
Offices 40 Watt/m3
3
Sales rooms 50 Watt/m
Glass additions 200 Watt/m
3
13
Page 14
Planning Notes
Cooling with Heat Pump Systems
Comfortable Room Temperature
A room is considered to be thermally comfortable when the room tempera­ture in the summer is below 28°C. This does not apply to air-conditioned rooms. Other factors are affecting thermal comfort ranges as well. Thermal comfort requirements are defined in standard DIN EN 15251, which provides a general guideline when implementing construction projects.
Recommendations for Surface Temperatures of Cooled Floors
When using a floor area for cooling, the comfort requirements and the weather data can be used to estimate the condensation risk so that the surface temperatures should generally be in a range of 20°C to 29°C. Special attention must be paid to floor surfaces that are used when barefoot, for example, in bathrooms, since the surface temperatures perceived as being comfortable may be significantly higher depending on the floor covering. Rooms with high humidity loads, especially bathrooms and kitchens, should not be cooled or only by considering the dew point threshold.
28
27
26
25
24
23
Room temperature in °C
22
21
Range of comfortable Temperature
20 21 22 23 24 25 26 27 28 29 30 31 32
Outside temperature in °C
Comfortable floor surface temperatures
min max
Wearing shoes 19 °C 29°C
Carpet 21°C 28°C
Pine wood 23°C 28°C
Barefoot
Oak 24°C 28°C
Linoleum 24°C 28°C
Concrete/screed 26°C 28°C
14
Page 15
Planning Notes
Cooling with Heat Pump Systems
Monitoring Function to Prevent Condensate Precipitation
To avoid condensation, the integrated Logon B WP61 controller features different monitor functions.
1. Flow Temperature Monitor
The temperature is set at the factory to 18°C. This temperature value ensures in almost all cases that condensation does not occur. A dew point monitor should always be used in addition.
2. Dew Point Monitor
This device is attached to critical points such as the floor heating distribution box. As soon as the connected dew point monitor detects condensation, it closes the contact and thereby switches cooling off.
3. Hygrostat
To prevent condensate due to a room humidity that is too high, a hygrostat can be connected, which then realizes a fixed flow temperature increase. As soon as the value set at the hygrostat is exceeded, the hygrostat closes the contact and this triggers the flow temperature set point increase set here.
High-End Solutions
4. Humidistat
To prevent condensate due to a room humidity that is too high, a humidistat can be connected, which then realizes a continuous flow set point increase. If the relative room humidity exceeds an adjustable value, the flow set point is increased steadily.
5. Room Sensor for Humidity and Temperature
The dew point temperature is determined based on the relative room humidity and the associated room air temperature. To prevent water condensation on surfaces, the flow temperature is min. limited by an adjustable value that is above the dew point temperature.
Distributor Box
Return Flow
Flow
TP = Dew point temp. Monitor
Dehumidifier
An external dehumidification can be used in combination with the last two monitoring functions. An external de-humidifier can be switched on to reduce the humidity in the air.
15
Page 16
Technical Data
AEROTOP T07(C)-T16
Heat pump type AEROTOP T T07(C) T10(C) T12(C) T14 T16 Heating operation For A2/W35
Heating Capacity Qh kW Power input Pel kW Performance number EN14511 COP ­Heating operation For A7/W35 Heating Capacity Qh kW Power input Pel kW Performance number EN14511 COP ­Condenser Scroll hermetically Maximum current consumption lmax. A 6.3 10 11 13 13.5 Start-up current with smooth starter VSA A 15.75 25 27.5 32.5 33.75 Current intensity with blocked rotor LRA A 40 50 66 74 74 Current connection V-f-Hz 400-3-50 Fuse WP A/T 16 16 16 20 20 Fuse WP with electrical insert A/T 20 20 20 25 25 Condenser, heater side Material: Chrome steel AISI 304, 1.4301 Hydraulic connections IG Zoll 1” 1” 1” 1” 1” Water content incl. connection hoses AEROTOP TC l 53 53 53 - ­Water content incl. connection hoses AEROTOP T l 2.6 3 3.1 3.4 3.4 Volume stream heating operation nom/min Pressure loss heating operation AEROTOP TC kPa 8.4/2.1 16.4/4.1 22.8/5.7 AEROTOP T kPa 28.3/4.4 32.9/4.1 33/4.5 36.5/4.6 35.5/5.5 Residual pressure AEROTOP TC Expansion tank heating AEROTOP TC V l 12 12 12 - ­Primary pressure heating-circuit expansion tank p bar 1 1 1 - ­Maximum working pressure p bar 3 3 3 3 3 Evaporator/fan Volume stream m Available pressure Power consumption fan Maximum current consumption fan lmax. A 1.6 1.6 1.6 2.1 2.1 Coolant R407C Coolant filling AEROTOP TC kg 1.9 2.95 3.7 - ­Coolant filling AEROTOP T kg Coolant circuit oil - Ester oil Oil quantity l 1.1 1.36 1.85 1.65 1.89 Weight heat pump AEROTOP TC kg 239 274 299 - ­AEROTOP T kg 204 246 272 276 279 Indoor setup Sound power level
On exhaust
Inside Lwa dB(A) Outdoor setup Sound power level standard configuratuion Lwa dB(A) Sound pressure level standard configuratuion in 1 m Lpa dB(A) 51.0 54.0 50.0 55.0 59.0 LP pressure control OFF-switch off p bar 0.2 LP pressure control ON- switch on p bar 1.6 HP pressure control OFF-switch off p bar 29.0 HP pressure control ON- switch on p bar 24.0
1) Min: ∆t max= 10 K, with PHW-preparation ∆tmax = 5 K. (V' [l/h]= Qh[kW]/(4.18*∆t[K]*ρ[kg/l])*3600)
2) Residual pumping pressure is stated for maximum pumping stage.
3) At maximum fan rotational speed.
4) At fan rotational speed setting B (T07(C), T10(C), T12(C), T14, T16).
5) Data for star/V connection of the electric motor. The machines are factory-equipped with star connection.
6) Measuring according to DIN ISO 9614-2. Sound power level is a property of the source of noise and therefore dependent on the distance; it describes the totality of the sound power of the corresponding source radiating in all directions. Information to determine the noise level see planning documents.
7) Information without consideration of a light well or air duct, which reduce the noise level considerably. Screen noise absorbers reduce noise by 6-7 dB(A).
3)
Pa
4)
P kW
6)
On suction 7) Lwa dB(A)
2)
7)
Lwa dB(A)
1)
l/h
kPa 51.4 57.9 55.4
3
/h
16
6.4 9.1 11.8 13.7 14.8
2.0 2.8 3.4 3.9 4.1
3.3 3.3 3.5 3.5 3.6
8.1 11.5 13.6 15.8 17
2.0 2.9 3.4 3.9 4.2
4.0 4.0 4.0 4.0 4.1
1500/568 2100/835 2700/999 3070/1171 3100/1300
2'500 3‘300 5'300
150 92 146
0.035 0.100 0.100
2.5 3.1 3.7 4.1 4.1
53.0 56.0 54.0 59.0 61.0
48.0 53.0 50.0 53.0 55.0
50.0 54.0 55.0 60.0 60.0
62.0 65.0 61.0 66.0 70.0
6'300 6'800
112 82
0.170 0.210
Page 17
Technical Data
AEROTOP T20-T35
Heat pump type AEROTOP T T20 T26 T32 T35 Heating operation For A2/W35
Heating Capacity Qh kW Power input Pel kW Performance number EN255 COP ­Heating operation Heating Capacity Qh kW Power input Pel kW Performance number EN255 COP ­Condenser Scroll hermetically Maximum current consumption lmax A Start-up current with smooth starter VSA A Current intensity with blocked rotor LRA A Current connection V-f-Hz Fuse WP A/T Condenser, heater side Material: Chrome steel AISI 316, 1.4401 Hydraulic connections IG Zoll Water content incl. connection hoses AEROTOP T l Volume stream heating operation nom/min Pressure loss heating operation kPa Maximum working pressure p bar Evaporator/fan Volume stream m Available pressure Power consumption fan Maximum current consumption fan lmax. A Coolant ­Coolant filling AEROTOP T kg Coolant circuit oil - Ester oil Oil quantity l Weight heat pump AEROTOP T kg Indoor setup Sound power level On exhaust Inside
Outdoor setup
Sound power level with Sound pressure level with hoods in 1 m LP pressure control OFF-switch off p bar LP pressure control ON- switch on p bar HP pressure control OFF-switch off p bar HP pressure control ON- switch on p bar
3)
Pa
4)
P kW
6)
On suction 7)
6)
hoods
7)
1)
7)
l/h
3
/h
Lwa dB(A) Lwa dB(A) Lwa dB(A)
Lwa dB(A)
Lpa dB(A) 55.0 59.0 56.0 59.0
18.9 24.4 30.2 33.4
5.8 7.4 8.8 9.2
3.2 3.3 3.4 3.6 for A7/W35
22.4 30.8 37.9 39.6
6.0 7.6 8.9 9.6
3.7 4.1 4.3 4.1
16 22 27 25 40 55 67.5 62.5 99 123 127 167
400-3-50
25 32 40 40
1¼” 1¼” 1¼” 1¼”
4.9 4.9 5.7 5.7
3700/1714 5850/2259 6280/2803 7300/2964
14.9/4.5 32.9/7.7 36.1/6.4 46.7/7 10 10 10 10
7'300 8'300 10'000
155 75 255
0.530 0.700 0.500
1.8 1.8 2.8 2.8 R407C
6 7.4 9.2 9.2
4.1 4.1 4.1 4.1
375 392 460 468
65.0 67.0 66.0 70.0
59.0 61.0 64.0 67.0
59.0 59.0 63.0 68.0
66.0 70.0 67.0 70.0
0.2
1.6
29.0
24.0
11'000
180
0.650
1) Min: ∆t max= 10 K, with PHW-preparation ∆tmax = 5 K. (V' [l/h]= Qh[kW]/(4.18*∆t[K]*ρ[kg/l])*3600)
2) Residual pumping pressure is stated for maximum pumping stage.
3) At maximum fan rotational speed.
4) At fan rotational speed setting B (T07(C), T10(C), T12(C), T14, T16).
5) Data for star/delta connection of the electric motor. The machines are factory-equipped with star connection.
6) Measuring according to DIN ISO 9614-2. Sound power level is a property of the source of noise and therefore dependent on the distance; it describes the totality of the sound power of the corresponding source radiating in all directions. Information to determine the noise level see planning documents.
7) Information without consideration of a light well or air duct, which reduce the noise level considerably. Screen noise absorbers reduce noise by 6-7 dB(A).
17
Page 18
Technical Data
AEROTOP T07(C)X-T10(C)X (available in F /I / B)
Heat pump type AEROTOP T..X T07X (C) T10X (C) Heating operation For A2/W35
Heating Capacity Qh kW Power input Pel kW Performance number EN255 COP ­Heating operation for A7/W35 Heating Capacity Qh kW Power input Pel kW Performance number EN255 COP ­Condenser Scroll hermetically Maximum current consumption A 17.3 23.5 Start-up current with smooth starter A 40 40 Current intensity with blocked rotor LRA 76 114 Current connection V-f-Hz 230-1-50 Fuse WP A/T 25 32 Fuse WP with electrical insert: 2 kW A/T 32 40 Fuse WP with electrical insert: 4 kW A/T 40 50 Fuse WP with electrical insert: 6 kW A/T 50 63 Condenser, heater side Material: Chrome steel AISI 304, 1.4301 Hydraulic connections IG Zoll Water content incl. connection hoses AEROTOP TC l Water content incl. connection hoses AEROTOP T l Minimum volume stream heating operation Pressure loss heating operation AEROTOP TC kPa 8.4/2.1 16.4/4.1 AEROTOP T kPa 28.3/4.4 32.9/4.1 Residual pressure AEROTOP TC Expansion tank heating AEROTOP TC V l Primary pressure heating-circuit expansion tank p bar Maximum working pressure p bar Evaporator/fan Volume stream m Available pressure Power consumption fan Maximum current consumption fan A Coolant ­Coolant filling AEROTOP TCX kg Coolant filling AEROTOP TX kg Coolant circuit oil - Ester oil Oil quantity l 1.1 1.36 Weight heat pump AEROTOP TC kg 242 278 AEROTOP T kg 207 250 Indoor setup Sound power level On exhaust Inside Lwa dB(A) Outdoor setup Sound power level standard configuratuion Lwa dB(A) Sound pressure level standard configuratuion in 1 m LP pressure control OFF-switch off p bar 0.2 LP pressure control ON- switch on p bar 1.6 HP pressure control OFF-switch off p bar 29.0 HP pressure control ON- switch on p bar 24.0
1) t max= 10 K, with PHW-preparation tmax = 5 K. (V' [l/h]= Qh[kW]/(4.18*∆t[K]*ρ[kg/l])*3600)
2) Residual pumping pressure is stated for maximum pumping stage.
3) At maximum fan rotational speed.
4) At fan rotational speed setting B (T07(C), T10(C), T12(C), T14, T16).
5) Data for star/V connection of the electric motor. The machines are factory-equipped with star connection.
6) Measuring according to DIN ISO 9614-2. Sound power level is a property of the source of noise and therefore dependent on the distance; it describes the totality of the sound power of the corresponding source radiating in all directions. Information to determine the noise level see planning documents.
7) Measured 1m around the machine.
8) Information without consideration of a light well or air duct, which reduce the noise level considerably. Screen noise absorbers reduce noise by 6-7 dB(A).
18
3)
Pa
4)
kW
6)
On suction 8) Lwa dB(A)
2)
c
Lwa dB(A)
1)
kPa
7)
Lpa dB(A) 51.0 54.0
l/h
3
/h
6.4 9.1 2 2.8
3.3 3.3
8.1 11.5
2.0 2.9
4.0 4.0
1” 1”
53 53
2.6 3
1500/568 2100/835
51.4 57.9 12 12
1 1 3 3
2'500 3‘300
150 92
0.035 0.100
1.6 1.6 R407C
1.9 2.95
2.5 3.1
53.0 56.0
48.0 53.0
50.0 54.0
62.0 65.0
Page 19
Technical Data
AEROTOP T07R-T16R
Heat pump type AEROTOP TR T07R T10R T12R T14R T16R Heating operation For A2/W35
Heating Capacity Qh KW Power input Pel KW Performance number EN14511 COP ­Heating operation for A7/W35 Heating Capacity Qh kW Power input Pel kW Performance number EN14511 COP -
Cooling operation for A35/W18
Cooling Capacity Qc KW 6.7 9.7 11.9 15.3 15.6
Power input Pel KW 2.6 3.7 4.7 5.8 6.1 Condenser Scroll hermetically Maximum current consumption Imax A 6.3 10 11 13 13.5 Start-up current with smooth starter VSA A 15.75 25 27.5 32.5 33.75 Current intensity with blocked rotor LRA A 40 50 66 74 74 Current connection V-f-Hz 400-3-50 Fuse WP A/T 16 16 16 20 20 Fuse WP with electrical insert A/T 20 20 20 25 25 Condenser, heater side Material: Chrome steel AISI 304, 1.4301 Hydraulic connections IG R"
Water content incl. connection hoses AEROTOP T l
Volume stream heating operation nom/min
Pressure loss heating operation kPa 28.3/4.4 32.9/4.1 33/4.5 36.5/4.6 35.5/5.5
Minimum volume stream cooling operation (t= 5 K) l/h
Pressure loss cooling operation kPa
Maximum working pressure p bar
Evaporator/fan
Volume stream m
Available pressure
Power consumption fan
Maximum current consumption fan lmax A
Coolant -
Coolant filling AEROTOP TR kg
Coolant circuit oil - Ester Oil
Oil quantity l 1.1 1.36 1.85 1.65 1.89
Weight heat pump kg 204 246 272 276 279 Indoor setup Sound power level On exhaust Inside Lwa dB(A) Outdoor setup Sound power level standard configuratuion Lwa dB(A) Sound pressure level standard configuratuion in 1 m LP pressure control OFF-switch off p bar 0.2 LP pressure control ON- switch on p bar 1.6 HP pressure control OFF-switch off p bar 29.0 HP pressure control ON- switch on p bar 24.0
2)
Pa
3)
P kW
4)
On suction 6) Lwa dB(A)
6)
Lwa dB(A)
6.4 9.1 11.8 13.7 14.8
2.0 2.8 3.4 3.9 4.1
3.3 3.3 3.5 3.5 3.6
8.1 11.5 13.6 15.8 17
2.0 2.9 3.4 3.9 4.2
4.0 4.0 4.0 4.0 4.1
1” 1” 1” 1” 1”
1)
5)
Lpa dB(A) 51.0 54.0 50.0 55.0 59.0
l/h
3
/h
2.6 3 3.1 3.4 3.4
1500/568 2100/835 2700/999 3070/1171 3100/1300
1'150 1'670 2'050 3000 3050
17.4 16.1 18.3 19.4 20.4
3 3 3 3 3
2'500 3‘300 5'300
150 92 146
0.035 0.100 0.100
1.6 1.6 2.1 2.1 2.1
R407C
5 7.5 9 9 9
53.0 56.0 54.0 59.0 61.0
48.0 53.0 50.0 53.0 55.0
50.0 54.0 55.0 60.0 60.0
62.0 65.0 61.0 66.0 70.0
6'300 6'800
112 82
0.170 0.210
1) Min: ∆t max= 10 K, with PHW-preparation ∆tmax = 5 K. (V' [l/h]= Qh[kW]/(4.18*∆t[K]*ρ[kg/l])*3600)
2) At maximum fan rotational speed.
3) At fan rotational speed setting B.
4) Measuring according to DIN ISO 9614-2. Sound power level is a property of the source of noise and therefore dependent on the distance; it describes the totality of the sound power of the corresponding source radiating in all directions. Information to determine the noise level see planning documents.
5) Measured 1m around the machine.
6) Information without consideration of a light well or air duct, which reduce the noise level considerably. Screen noise absorbers reduce noise by 6-7 dB(A).
19
Page 20
Technical Data
AEROTOP T20R-T35R
Heat pump type AEROTOP TR T20R T26R T32R T35R Heating operation For A2/W35
Heating Capacity Qh KW Power input Pel KW Performance number EN14511 COP ­Heating operation for A7/W35 Heating Capacity Qh kW Power input Pel kW Performance number EN14511 COP ­Cooling operation for A35/W18 Cooling Capacity Qc KW Power input Pel KW Condenser Scroll hermetically Maximum current consumption Imax A Start-up current with smooth starter VSA A Current intensity with blocked rotor LRA A Current connection V-f-Hz Fuse WP A/T Condenser, heater side Material: Chrome steel AISI 304, 1.4301 Hydraulic connections IG R" Water content incl. connection hoses AEROTOP T l Volume stream heating operation nom/min Pressure loss heating operation kPa Minimum volume stream cooling operation (t= 5 K) l/h Pressure loss cooling operation kPa Maximum working pressure p bar Evaporator/fan Volume stream m Available pressure Power consumption fan Maximum current consumption fan lmax A Coolant ­Coolant filling AEROTOP TR kg Coolant circuit oil - Ester Oil Oil quantity l 4.1 4.1 4.1 4.1 Weight heat pump kg 375 392 460 468 Indoor setup
Sound power level
On exhaust Inside Lwa dB(A) Outdoor setup Sound power level with Sound pressure level with hoods in 1 m LP pressure control OFF-switch off p bar 0.2 LP pressure control ON- switch on p bar 1.6 HP pressure control OFF-switch off p bar 29.0 HP pressure control ON- switch on p bar 24.0
1) Min: ∆t max= 10 K, with PHW-preparation ∆tmax = 5 K. (V' [l/h]= Qh[kW]/(4.18*∆t[K]*ρ[kg/l])*3600)
2) At maximum fan rotational speed.
3) At fan rotational speed setting B.
4) Measuring according to DIN ISO 9614-2. Sound power level is a property of the source of noise and therefore dependent on the distance; it describes the totality of the sound power of the corresponding source radiating in all directions. Information to determine the noise level see planning documents.
5) Measured 1m around the machine.
6) Information without consideration of a light well or air duct, which reduce the noise level considerably. Screen noise absorbers reduce noise by 6-7 dB(A).
2)
Pa
3)
P kW
4)
On suction 6) Lwa dB(A)
4)
6)
Lwa dB(A)
hoods Lwa dB(A)
18.9 24.4 30.2 34.4
5.8 7.4 8.8 9.2
3.2 3.3 3.4 3.6
22.4 30.8 37.9 39.6
6.0 7.6 8.9 9.6
3.7 4.1 4.3 4.1
20.2 30.6 34.7 36.6
8.5 11.8 14 14.3
16 22 27 25 40 55 67.5 62.5 99 123 127 167
32 40 40 40
1¼” 1¼” 1¼” 1¼”
1)
l/h
3
/h
5)
Lpa dB(A)
4.9 4.9 5.7 5.7
3700/1714 5850/2259 6280/2803 7300/2964
14.9/4.5 32.9/7.7 36.1/6.4 46.7/7 3470 5260 5970 6300
14 20.6 14.8 21.8 10 10 10 10
7'300 8'200 10000
149 198 225
0.530 0.700 0.500
1.8 2.5 2.5 2.5
16 16 21 21
65.0 67.0 66.0 70.0
59.0 61.0 64.0 67.0
59.0 59.0 63.0 68.0
66.0 70.0 67.0 70.0
55.0 59.0 56.0 59.0
400-3-50
11000
313
0.650
R407C
20
Page 21
Technical Data
AEROTOP T07RX-T10RX (available in F /I / B)
Heat pump type AEROTOP T..RX T07RX T10RX Heating operation For A2/W35
Heating Capacity Qh kW Power input Pel kW Performance number COP ­Heating operation for A7/W35 Heating Capacity Qh kW 7.9 11.5 Power input Pel kW 2.0 2.9 Performance number COP - 3.9 4.0 Cooling operation for A35/W18 Cooling Capacity kW 6.7 9.7 Power input kW 2.6 3.7 Condenser Scroll hermetically Maximum current consumption Imax A Start-up current with smooth starter VSA A Current intensity with blocked rotor LRA A Current connection V-f-Hz Fuse WP A/T Fuse WP with electrical insert: 2 kW A/T Fuse WP with electrical insert: 4 kW A/T Fuse WP with electrical insert: 6 kW A/T Condenser, heater side Material: Chrome steel AISI 304, 1.4301 Hydraulic connections IG R" Water content incl. connection hoses AEROTOP T l Volume stream heating operation nom/min Pressure loss heating operation kPa 28.3/4.4 32.9/4.1 Minimum volume stream cooling operation (t= 5 K) l/h Pressure loss cooling operation kPa Maximum working pressure p bar Evaporator/fan Volume stream m Available pressure Power consumption fan Maximum current consumption fan Imax A Coolant ­Coolant filling AEROTOP TRX kg Coolant circuit oil - Ester Oil Oil quantity l 1.1 1.36 Weight heat pump kg 207 250 Indoor setup Sound power level On exhaust Inside Lwa dB(A) Outdoor setup Sound power level standard configuratuion Lwa dB(A) 60.0 57.0 Sound pressure level standard configuratuion in 1 m LP pressure control OFF-switch off p bar 0.2 LP pressure control ON- switch on p bar 1.6 HP pressure control OFF-switch off p bar 29.0 HP pressure control ON- switch on p bar 24.0
1) Min: ∆t max= 10 K, with PHW-preparation ∆tmax = 5 K. (V' [l/h]= Qh[kW]/(4.18*∆t[K]*ρ[kg/l])*3600)
2) At maximum fan rotational speed.
3) At fan rotational speed setting B.
4) Measuring according to DIN ISO 9614-2. Sound power level is a property of the source of noise and therefore dependent on the distance; it describes the totality of the sound power of the corresponding source radiating in all directions. Information to determine the noise level see planning documents.
5) Measured 1m around the machine.
6) Information without consideration of a light well or air duct, which reduce the noise level considerably. Screen noise absorbers reduce noise by 6-7 dB(A
2)
Pa
3)
P kW
4)
On suction 6) Lwa dB(A)
6)
Lwa dB(A)
1
) l/h
3
/h
5)
Lpa dB(A) 49.0 46.0
6.4 9.1 2 2.8
3.3 3.3
17.3 23.5 40 40 76 114
230-1-50 20 20 32 40 40 50 50 63
1” 1”
2.6 3
1500/568 2100/835
1'150 1'670
17.4 16.1 3 3
2'500 3‘300
150 92
0.035 0.100
1.6 1.6 R407C
5 7.5
53.0 56.0
48.0 53.0
50.0 54.0
21
Page 22
Technical Data
Fan Speed
Fan Speed Settings
The fan speed of the air-water AEROTOP T heat pumps can be directly adjusted on the LOGON B WP61 controller (parameter 3010). The following table serves as a reference for setting the fan speed of the air-water heat pump AEROTOP T based on the most important setup variants:
A values refer to outdoor and
corner setup.
B values refer to setups with air
duct on air intake and outlet KWI + KFS) or with rigid air ducts (KSL).
AEROTOP T A Value B Value
T35(R)
T32(R)
T26(R)
T20(R)
T16(R)
T14(R)
T12(R) / T12C
T10(X+R+RX) / T10C(X)
T07(X+R+RX) / T07C(X)
Notes: The setting must be increased by 5% if sound dampers are installed on the heat pump. Please contact the technical support if you have any additional questions.
64 % 69 %
56 % 61 %
72 % 77 %
60 % 65 %
55 % 60 %
50 % 55 %
42 % 47 %
70% 75 %
50 % 55 %
22
Page 23
Technical Data
Compact Heat Pump Water Heat Exchanger Pressure Loss
The thermal mixing valve integrated into the compact heat pump routes a part of the flow water back to the accumulation tank at flow temperatures below +30°C. This way the storage tank is heated immediately and the energy depot is available for the defrosting of the evaporator. This upholding function ensures a continuous defrosting process and the system can be operated even when the heating system is cold.
Settings of the Integrated Thermal Mixing Valve of the Compact Heat Pumps
Important: Already provided with factory settings and NORMALLY does not require readjustment.
- AEROTOP T07C (Manually adjustable valve with scale): The factory setting of this valve is set to the minimum (scale at 0) = crank completely closed! (Important: The mark for making adjustments is located on the rear of the valve; use handheld mirror)
- AEROTOP T10-12C (Not manually adjustable, must use key to change settings): Correct adjustment is as follows: Open completely and then turn back 3.5 turns.
Aerotop indoor installation
Heat circulation pump Grundfos UPS
Type/Specification T07C T10C T12C
25/60
UPS
25/70
UPS
25/70
Accumulator tank in Litre 43 43 43
Electric heating element
Expansion vessel Volume l/ primary
in kW
pressure bar
12/1 12/1 12/1
2/ 4 / 6
23
Page 24
Technical Data
Integrated pumps, compact heat pumps Heating pumps
AEROTOP T07C/T07CX: GRUNDFOS
Delivery height
Pumped Fluid = Water Fluid Temperature = 20 °C Density = 998.2 kg/m3
AEROTOP T10C/T10CX/T12C: GRUNDFOS
Delivery height
Pumped Fluid = Water Fluid Temperature = 20 °C Density = 998.2 kg/m3
977.8
70
24
Page 25
Technical Data
Remaining pump pressure circulation pump
Remaining pump pressure AEROTOP T07C
Pump pressure (kPa)
Pump pressure (kPa)
Flow rate (l/h)
Remaining pump pressure AEROTOP T10C
Flow rate (l/h)
Remaining pump pressure AEROTOP T12C
Pump pressure (kPa)
Flow rate (l/h)
25
Page 26
Technical Data
Noise Level
Sound AEROTOP T heat pumps
All ELCO-heat pumps are designed for low-noise operation. However, the setup location for the heat pumps should be selected in a way that noise pollution is avoided.
Inlet/outlet air shaft or heat pump is detached (min. 5 m distance to any wall)
Inlet/outlet air shaft or heat pump is situated on a wall
Inlet/outlet air shaft or heat pump is situated in a corner
-8 -14 -20 -24 -26 -28 -30 -32 -34 -38
-5 -11 -17 -21 -23 -25 -27 -28 -31 -35
-2 -8 -14 -18 -20 -22 -24 -25 -28 -32
Reduction table for sound: This table can be used to estimate the noise level at the measuring location on the basis of the noise level at the emission location (noise level according to page 16 and 17). Depending on the legal requirements, further correction factors have to be considered. In cases of doubt, the emission values should be calculated by an acoustic specialist.
Distance between emission location and measuring location [m]
1 2 4 6 8 10 12 15 20 30
dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A)
26
Page 27
Checklist
Correct Installation of an Air-Water Heat Pump
AEROTOP T heat pumps are quiet and efficient. However, incorrectly integrating constructional components may result in undesired noise increases if the conditions are unfavorable. A careful assessment of the noise emissions is required when planning the installation of heat pump systems.
To be considered when installing an air-water heat pump
Each reflecting surface doubles the noise (acoustic power). One wall increases this value by +3dB, one corner by +6dB.
Rooms with reverberant or sound-reflecting floor coverings and walls increase the noise level.
Be careful with dropping the washing
Adherence with the min. clearances reduces noise reflection and air short-circuits and improves airflow near the fan.
Construction measures can reduce noise, plants cannot.
Noise reduction measures considered early on in the development process result in the fewest additional costs. Subsequent measures usually are extremely expensive and cumbersome to implement. [Heat Pump Manual, Federal Energy Agency, Switzerland] The following points apply to the interior and exterior installation of air-water heat pumps.
one corner by +6dB. Avoid solid-borne noise transmission by avoiding reflecting surfaces. Never route air intake or outlet into closed or partially closed spaces such as a corner, foyer, entrance area, covered patio, etc.
Avoid rooms with reverberant or sound-reflecting floor coverings and walls. When installing the heat pump in a room with reverberant or sound-reflecting floor coverings and walls, reflections may increase the sound level. Cover one or two walls with noise-absorbing material if this is the case.
Dropping the washing from lived-in rooms to the place of installation of the heat pump can lead to noise transmission when unfavourably positioned.
Make sure the min. distances and clearances to the air intake and outlet as well as the min. size of the light wells are applied. Avoid walls or flow barriers around the circumference of the heat pump to ensure air can reach the fan evenly. Less pressure losses = low peripheral speed = reduction of the fan noise.
Use constructional measures to interrupt the flow of noise from the heat pump (direct noise propagation). Use solid walls, fences, palisades, etc. to reduce noise levels. Plants, however, do not reduce noise.
Consider different noise sensitivity levels.
Sound absorbing materials reduce noise.
Separation from the structure minimizes structure-borne sounds.
Correct installation of pedestal or base reduces structure-borne sounds.
Correct installation of the ducts reduces air and structure-borne noise transference.
Avoid air short-circuits and airflow barriers.
Always comply with all rules, regulations, and applicable laws.
Avoid placing the heat pump where it may cause problems due to its noise emission (bedrooms, living rooms, neighbors, etc.). Position heat pumps in areas where noise is less likely to be an annoyance. If installed indoors, do not install underneath or next to living or sleeping quarters.
Additional sound absorbing materials or measures must be planned for and used in cases where extreme noise reductions are desired or when installing model Forever GREEN 20C or later. Use only original accessories and spare parts. in extreme cases, it may be advisable to consult a noise expert.
Always use flexible connections throughout: Flexible hoses and tubes for heat distribution, flexible electrical connections, sound isolation of the air ducts by using elastic sleeves or Compriband products.
The base or ground must be level or made level and able to support the load of the equipment. Use the adjustable feet of the heat pump to level the equipment after installation.
All wall openings and ducts must be equipped with the corresponding noise-absorbing materials. Comply with the specified cross-sections and dimensions.
Air intakes and outlets cannot be installed next to each other without using a separating wall. Avoid any airflow obstacles that favor an air short-circuit.
Germany: Technical Instructions on Noise S
witzerland: Noise Protection Ordinance
27
Page 28
Performance Data
AEROTOP T07 – T16 (Information according to EN 14511)
Type Series
Ser i e
T
T
K
L
°C °C kW kW - kW kW - kW kW - kW kW kW kW
20
15
10
7
35
40
45
50
4
2
0
-4
-7
-10
-15
20
15
10
7
4
2
0
-4
-7
-10
-15
20
15
10
7
4
2
0
-4
-7
-10
-15
20
15
10
7
4
2
0
-4
-7
-10
AEROTOP T 07 AEROTOP T 10 AEROTOP T12 AEROTOP T14 AEROTOP T16
QPCOPQPCOPQPCOPQPCOPQPCOP
12.22.1 5.818.33.1 6.019.53.7 5.323.04.3 5.323.44.6 5.1
10.62.1 5.115.53.0 5.217.13.5 4.820.24.2 4.920.64.3 4.7
9.2 2.0 4.513.32.9 4.614.73.5 4.217.54.0 4.4 17.84.1 4.3
7.9 2.0 3.911.52.9 4.013.23.4 3.915.83.9 4.0 16.24.0 4.0
6.9 2.0 3.510.02.8 3.612.13.4 3.614.63.9 3.7 14.93.9 3.8
6.3 1.9 3.2 9.1 2.8 3.3 11.4 3.3 3.4 13.7 3.9 3.5 14.1 3.9 3.6
6.1 2.0 3.1 8.8 2.8 3.2 10.9 3.4 3.2 13.1 3.9 3.3 13.4 3.9 3.4
5.7 2. 0 2. 8 8. 3 2. 9 2.9 9. 7 3.4 2 .9 11. 7 4. 0 3. 0 12. 1 3. 9 3.1
5.4 2. 0 2. 6 7. 8 2. 9 2.7 8. 9 3.4 2 .6 10. 7 4. 0 2. 7 11. 1 3. 9 2.9
4.7 2. 0 2. 3 6. 9 2. 9 2.4 8. 3 3.4 2 .4 10. 1 4. 0 2. 5 10. 4 3. 9 2.7
3.52.01.85.22.81.87.33.52.19.04.12.2 9.33.92.4
11.62.4 4.917.33.4 5.119.04.1 4.622.54.8 4.722.95.0 4.6
10.22.3 4.415.03.4 4.516.84.0 4.219.94.7 4.320.34.8 4.2
9.1 2.3 3.913.13.3 4.014.53.9 3.717.34.5 3.8 17.74.6 3.8
8.1 2.3 3.511.83.3 3.613.33.8 3.515.94.4 3.6 16.34.4 3.7
7.1 2.3 3.110.33.2 3.212.23.8 3.214.64.5 3.3 15.04.5 3.3
6.5 2.3 2.9 9.4 3.2 2.9 11.5 3.8 3.0 13.8 4.5 3.1 14.2 4.5 3.2
6.2 2.3 2.7 9.1 3.2 2.8 10.9 3.8 2.8 13.1 4.5 2.9 13.5 4.5 3.0
5.7 2. 3 2. 5 8. 4 3. 3 2.6 9. 8 3.9 2 .5 11. 8 4. 5 2. 6 12. 1 4. 5 2.7
5.4 2. 3 2. 3 7. 8 3. 3 2.4 8. 9 3.9 2 .3 10. 8 4. 6 2. 4 11. 1 4. 5 2.5
4.7 2. 3 2. 0 6. 9 3. 3 2.1 8. 3 3.9 2 .1 10. 1 4. 6 2. 2 10. 4 4. 5 2.3
3.62.31.55.33.31.67.23.91.88.84.61.9 9.14.52.0
11.02.6 4.216.33.7 4.318.64.5 4.122.05.3 4.122.55.5 4.1
9.9 2.6 3.814.43.7 3.916.54.4 3.719.65.2 3.8 20.05.3 3.8
8.9 2.6 3.412.93.7 3.514.44.4 3.317.25.1 3.4 17.65.1 3.4
8.35 2 .62 3.2 12.0 3.7 3. 3 13.4 4.2 3 .2 15.9 4.9 3. 3 16. 4 4. 8 3.4
7.3 2.6 2.810.63.7 2.912.24.3 2.814.65.0 2.9 15.05.0 3.0
6.7 2.6 2.6 9.8 3.7 2.7 11.6 4.3 2.7 13.9 5.0 2.8 14.2 5.0 2.8
6.4 2.6 2.5 9.4 3.7 2.5 11.0 4.3 2.5 13.2 5.1 2.6 13.6 5.0 2.7
5.8 2. 6 2. 2 8. 5 3. 7 2.3 9. 9 4.4 2 .3 11. 9 5. 1 2. 3 12. 2 5. 1 2.4
5.4 2. 7 2. 0 7. 8 3. 7 2.1 9. 0 4.4 2 .1 10. 9 5. 2 2. 1 11. 2 5. 1 2.2
4.7 2. 7 1. 8 6. 9 3. 7 1.8 8. 3 4.4 1 .9 10. 1 5. 2 1. 9 10. 3 5. 2 2.0
3.62.71.45.43.71.47.14.41.68.75.21.7 8.95.21.7
10.42.9 3.615.34.1 3.718.15.0 3.621.55.8 3.722.06.0 3.7
9.6 2.9 3.313.94.1 3.416.24.9 3.319.35.7 3.4 19.85.8 3.4
8.8 2.9 3.012.74.1 3.114.34.8 3.017.15.6 3.0 17.55.6 3.1
8.3 2.9 2.812.04.1 2.913.34.7 2.815.85.5 2.9 16.35.4 3.0
7.5 2.9 2.510.84.1 2.612.24.8 2.614.75.6 2.6 15.05.6 2.7
7.0 2.9 2.410.14.1 2.511.64.8 2.414.05.6 2.5 14.35.6 2.6
6.6 2.9 2.2 9.6 4.1 2.3 11.1 4.8 2.3 13.3 5.6 2.4 13.6 5.6 2.4
5.9 3. 0 2. 0 8. 6 4. 1 2.1 9. 9 4.8 2 .0 12. 0 5. 7 2. 1 12. 3 5. 7 2.2
5.3 3. 0 1. 8 7. 8 4. 2 1.9 9. 1 4.9 1 .9 11. 0 5. 7 1. 9 11. 2 5. 7 2.0
4.7 3. 0 1. 6 6. 9 4. 2 1.7 8. 3 4.9 1 .7 10. 0 5. 8 1. 7 10. 3 5. 8 1.8
T
Water outlet temperature (flow)
K
in °C
TL Air intake temp. in °C Q Heat output in kW
The power consumption of the fan and the circulation pumps as well as the defrosting function must generally be considered as well.
Heating water flow and air flow are acc. to specifications listed on the Technical Data pages.
P Power consumption in kW COP Performance rating
28
Page 29
Performance Data
AEROTOP T20 – T35 (Information according to EN 14511)
Type Series
Seri e
T
K
°C °C kW kW - kW kW - kW kW - kW kW
35
40
45
50
-10
-15
-10
-15
-10
-15
-10
T
L
20
15
10
7
4
2
0
-4
-7
20
15
10
7
4
2
0
-4
-7
20
15
10
7
4
2
0
-4
-7
20
15
10
7
4
2
0
-4
-7
AEROTOP T20 AEROTOP T26 AEROTOP T32
Q P COP Q P COP Q P COP Q P COP
27.5 6 .6 4.2 37.1 7.7 4.8 45.8 9.4 4 .9 48.6 10.6 4.6
25.3 6 .4 4.0 34.7 7.7 4.5 42.9 9.3 4 .6 44.7 10.2 4.4
23.1 6 .1 3.8 32.4 7.7 4.2 40.0 9.2 4 .3 40.8 9. 8 4.1
21.7 6 .0 3.6 29.9 7.6 3.9 36.8 8.9 4 .2 38.4 9. 6 4.0
19.7 5 .9 3.3 27.0 7.5 3.6 32.3 8.8 3 .7 34.8 9. 3 3.7
18.3 5 .8 3.2 23.7 7.4 3.2 29.3 8.8 3 .3 32.4 9. 2 3.5
17.5 5 .8 3.0 22.7 7.4 3.1 28.0 8.8 3 .2 30.9 9. 1 3.4
15.7 5 .7 2.8 20.7 7.4 2.8 25.6 8.8 2 .9 27.8 8. 9 3.1
14.4 5 .6 2.6 19.2 7.4 2.6 23.7 8.7 2 .7 25.4 8. 7 2.9
13.5 5 .5 2.5 18.4 7.6 2.4 21.8 8.7 2 .5 23.8 8. 5 2.8
11.6 5 .3 2.2 16.6 7.4 2.2 18.7 8.7 2 .2 20.4 8. 1 2.5
27.3 7 .1 3.9 36.7 8.6 4.3 45.3 10.5 4 .3 48.0 11.4 4.2
25.0 6 .8 3.7 34.3 8.6 4.0 42.3 10.4 4 .1 44.2 11.1 4.0
22.9 6 .6 3.5 31.9 8.5 3.7 39.4 10.3 3 .8 40.4 10.7 3.8
21.1 6 .5 3.3 29.4 8.4 3.5 36.2 10.0 3 .6 37.4 10.3 3.6
19.7 6 .4 3.1 27.1 8.4 3.2 32.4 9.9 3 .3 34.7 10.1 3.4
18.4 6 .3 2.9 24.3 8.3 2.9 30.0 9.9 3 .0 32.5 10.0 3.3
17.5 6 .2 2.8 23.2 8.3 2.8 28.7 9.9 2 .9 30.9 9. 8 3.1
15.8 6 .1 2.6 21.1 8.3 2.5 26.0 9.9 2 .6 27.7 9. 6 2.9
14.4 6 .0 2.4 19.5 8.3 2.3 24.1 9.8 2 .4 25.3 9. 4 2.7
13.4 5 .9 2.3 18.5 8.5 2.2 22.0 9.7 2 .3 23.5 9. 1 2.6
11.5 5 .6 2.0 16.6 8.5 2.0 18.8 9.9 1 .9 20.2 8. 6 2.3
27.0 7 .6 3.6 36.2 9.5 3.8 44.7 11.6 3 .9 47.5 12.3 3.9
24.8 7 .3 3.4 33.8 9.5 3.6 41.8 11.5 3 .6 43.7 11.9 3.7
22.6 7 .1 3.2 31.5 9.4 3.3 38.9 11.4 3 .4 39.9 11.5 3.5
20.5 6 .9 3.0 28.8 9.2 3.1 35.5 11.2 3 .2 36.4 11.1 3.3
19.6 6 .8 2.9 27.2 9.3 2.9 32.5 11.0 2 .9 34.5 10.9 3.2
18.5 6 .7 2.7 24.9 9.3 2.7 30.8 11.0 2 .8 32.5 10.7 3.0
17.6 6 .7 2.6 23.8 9.3 2.6 29.4 11.0 2 .7 30.9 10.6 2.9
15.8 6 .5 2.4 21.5 9.3 2.3 26.5 11.0 2 .4 27.6 10.3 2.7
14.5 6 .4 2.3 19.8 9.2 2.1 24.4 10.9 2 .2 25.2 10.0 2.5
13.3 6 .2 2.1 18.6 9.3 2.0 22.1 10.7 2 .1 23.2 9.7 2.4
11.5 6 .0 1.9 16.6 9.5 1.7 18.8 11.2 1 .7 19.9 9.2 2.2
26.7 8 .0 3.3 35.8 10.4 3.4 44.1 12.7 3.5 47.0 13.2 3.6
24.6 7 .8 3.1 33.4 10.3 3.2 41.2 12.6 3.3 43.2 12.7 3.4
22.4 7 .6 3.0 31.1 10.3 3.0 38.4 12.6 3.1 39.5 12.3 3.2
20.8 7 .4 2.8 29.0 10.2 2.8 35.8 12.5 2.9 36.6 12.0 3.1
19.6 7 .3 2.7 27.3 10.3 2.7 33.1 12.4 2.7 34.4 11.7 2.9
18.6 7 .2 2.6 25.5 10.2 2.5 31.5 12.4 2.6 32.5 11.5 2.8
17.7 7 .1 2.5 24.3 10.2 2.4 30.0 12.3 2.4 30.9 11.3 2.7
15.8 6 .9 2.3 21.9 10.2 2.2 26.9 12.3 2.2 27.6 11.0 2.5
14.5 6 .8 2.1 20.1 10.2 2.0 24.9 12.3 2.0 25.1 10.7 2.4
13.2 6 .6 2.0 18.7 10.2 1.8 22.8 12.1 1.9 23.0 10.3 2.2
AEROTOP T35
T
Water outlet temperature (flow)
K
in °C
TL Air intake temp. in °C Q Heat output in kW
The power consumption of the fan and the circulation pumps as well as the defrosting function must generally be considered as well.
Heating water flow and air flow are acc. to specifications listed on the Technical Data pages.
P Power consumption in kW COP Performance rating
29
Page 30
Performance Data
AEROTOP T07X – T10X (Information according to EN 14511)
Serie
Type Series
T
K
°C °C kW kW - kW kW -
35
40
45
50
T
Water outlet temperature (flow)
K
T
20
15
10
-4
-7
-10
-15
20
15
10
-4
-7
-10
-15
20
15
10
-4
-7
-10
-15
20
15
10
-4
-7
-10
L
7
4
2
0
7
4
2
0
7
4
2
0
7
4
2
0
in °C
TL Air intake temp. in °C Q Heat output in kW P Power consumption in kW COP Performance rating
AER OTOP T07 X AEROTOP T10 X
QPCOPQPCOP
12.2 2 .1 5.8 18.3 3.1 6.0
10.6 2 .1 5.1 15.5 3.0 5.2
9.2 2 .0 4.5 13.3 2.9 4.6
7.9 2 .0 3.9 11.5 2.9 4.0
6.9 2 .0 3.5 10.0 2.8 3.6
6.3 1 .9 3.2 9.1 2.8 3.3
6.1 2 .0 3.1 8.8 2.8 3.2
5.7 2 .0 2.8 8.3 2.9 2.9
5.4 2 .0 2.6 7.8 2.9 2.7
4.7 2 .0 2.3 6.9 2.9 2.4
3.5 2 .0 1.8 5.2 2.8 1.8
11.6 2 .4 4.9 17.3 3.4 5.1
10.2 2 .3 4.4 15.0 3.4 4.5
9.1 2 .3 3.9 13.1 3.3 4.0
8.1 2 .3 3.5 11.8 3.3 3.6
7.1 2 .3 3.1 10.3 3.2 3.2
6.5 2 .3 2.9 9.4 3.2 2.9
6.2 2 .3 2.7 9.1 3.2 2.8
5.7 2 .3 2.5 8.4 3.3 2.6
5.4 2 .3 2.3 7.8 3.3 2.4
4.7 2 .3 2.0 6.9 3.3 2.1
3.6 2 .3 1.5 5.3 3.3 1.6
11.0 2 .6 4.2 16.3 3.7 4.3
9.9 2 .6 3.8 14.4 3.7 3.9
8.9 2 .6 3.4 12.9 3.7 3.5
8.35 2 .62 3.2 12.0 3.7 3.3
7.3 2 .6 2.8 10.6 3.7 2.9
6.7 2 .6 2.6 9.8 3.7 2.7
6.4 2 .6 2.5 9.4 3.7 2.5
5.8 2 .6 2.2 8.5 3.7 2.3
5.4 2 .7 2.0 7.8 3.7 2.1
4.7 2 .7 1.8 6.9 3.7 1.8
3.6 2 .7 1.4 5.4 3.7 1.4
10.4 2 .9 3.6 15.3 4.1 3.7
9.6 2 .9 3.3 13.9 4.1 3.4
8.8 2 .9 3.0 12.7 4.1 3.1
8.3 2 .9 2.8 12.0 4.1 2.9
7.5 2 .9 2.5 10.8 4.1 2.6
7.0 2 .9 2.4 10.1 4.1 2.5
6.6 2 .9 2.2 9.6 4.1 2.3
5.9 3 .0 2.0 8.6 4.1 2.1
5.3 3 .0 1.8 7.8 4.2 1.9
4.7 3 .0 1.6 6.9 4.2 1.7
The power consumption of the fan and the circulation pumps as well as the defrosting function must generally be considered as well.
Heating water flow and air flow are acc. to specifications listed on the Technical Data pages.
30
Page 31
Performance Data
AEROTOP T07R – T16R (according to EN 14511-Coolong)
The power consumption of the fan and
the circulation pumps as well as the
defrosting function must generally be
considered as well. Heating water flow and air flow are acc.
Water outlet temperature (flow)
Air intake temp. in °C
K
L
T
in °C
T
Q Heat output in kW
P Power consumption in kW
to specifications listed on the Technical
Data pages.
COP Performance rating
31
Page 32
Performance Data
AEROTOP T20R – T35R (according to EN 14511-Cooling)
32
The power consumption of the fan and
the circulation pumps as well as the
defrosting function must generally be
The power consumption of the fan and
considered as well. Heating water flow and air flow are acc.
the circulation pumps as well as the
defrosting function must generally be
considered as well. Heating water flow and air flow are acc.
Water outlet temperature (flow)
Water outlet temperature (flow)
Air intake temp. in °C
Air intake temp. in °C
K
L
K
L
T
in °C
T
in °C
T
Q Heat output in kW
T
P Power consumption in kW
Q Heat output in kW
P Power consumption in kW
to specifications listed on the Technical
Data pages.
to specifications listed on the Technical
Data pages.
COP Performance rating
COP Performance rating
Page 33
Setup and Connection Instructions
Safety, Transport and Installation
Safety Information
Compliance with all rules and
instructions of all documentation, labels, type plates, and associated documents of the unit is mandatory.
Transport
When receiving the shipment, the
heat pump must be checked for completeness as per order confirmation .In case of damaged or missing material, the carrier must be informed in writing immediately.
Care and due diligence are
required during transport, setup, preparation, or when handling heavy materials that may damage the heat pump.
Make sure that towing ropes, belts,
or chains used for transport or installation do not damage the heat pump. Do not allow the heat pump to swing back and forth when lifting it up. Never tilt the heat pump more than 15° from its vertical axis.
The heat pump is affixed to a pallet
at the factory for transport and covered with a protective film to protect the unit from scratches. Do not remove the packaging until the heat pump is positioned at its final location.
Setup
Setup must be carried out carefully
and accurately.
AEROTOP T heat pumps can be
installed on a level interior floor without pedestal or base. If installed outdoors, a pedestal or base is required unless the substrate is very firm and can support the load.
The installation room must have at
least one exterior wall. Rooms with high humidity are unsuitable as installation locations for AEROTOP T heat pumps. A condensate drain must be available.
The heat pump must be set up on
a level ground and aligned with the adjustable feet. Make sure there is sufficient space to access the control panel and at the sides for inspections and maintenance.
Make sure the ground is able to
support the load of the heat pump and all accessories. The floor or ground must be free of dust and other foreign particles. If installing in the basement, make sure the selected installation position cannot be flooded.
The heat pumps may not be placed
on floating floorings.
Once moved to its final location,
the heat pump must be carefully unpacked and removed from the pallet. Protect heat pump from impact and other damaging forces!
Installation
The safety regulations and
schemes/diagrams must be strictly observed.
The accessories and additional
equipment must be installed by a trained service technician (heating contractor) as per the enclosed assembly and installation instructions.
The noise emissions of the
AEROTOP T heat pump are very low thanks to the sound-absorbing materials used to mount the mobile parts and the insulating cladding. The effective noise value depends also on the size of the installation room, the noise-absorbance or reflection of the materials in the room, as well as the possibility of the noise to spread and transfer via solid bodies, among others.
Air ducts, pipes, and electrical lines
must be attached to the masonry and not the heat pump.
All of these connections must be
established using flexible connections so that they can swing freely, especially when the compressor or evaporator starts up. Only then is it possible to avoid transference of sound from solid bodies to the building structure as well as line breakages.
Observe the checklist notes when selecting the installation site for the correct setup of an air-water heat pump
33
Page 34
Setup and Connection Instructions
Electrical Connections, Installation Types, Hydraulic Connections, Condensate Drain
Electrical Connections and Control Information
The electrical connections must be established in compliance with local rules and regulations. The current feed may exhibit a max. tolerance of 2% with this power intensity when a voltage of 10% exists. Do not connect the heat pump if the phase difference exceeds more than 2%. Operating the equipment outside of the listed limit values will void the warranty. If necessary, please contact your local electricity company or utility. The internal wiring of the heat pump is carried out at the factory as listed on the electrical diagram included with the unit. The heat pump is equipped with an electrical supply box containing the components listed below.
Heat pumps and system controller
unit
Elements to feed the
corresponding components of the heat pump.
An automatic cutout switch or a 3 phase, slow-blow fuse with neutral conductor must be provided externally in compliance with the technical requirements of this documentation. The low voltage cables (control) may not be placed in the same cable c onduits or ducts as the supply cables. The exterior temperature sensor of the controller must be attached to the outside wall of the building in a location protected from the afternoon sun and other heat sources (open windows, chimneys, etc.). Northern and northeastern exposures are preferred. If the room impact is to be activated for a remote control, this control unit must be placed in a reference room (e.g. living room) where it cannot be influenced by an external heat source (e.g. stoves, heaters, air flow, etc.).
Indoor Installation
If installed indoors, AEROTOP T heat pumps do not require base or pedestal.
All heat pump models T20 – T35 must be equipped with noise dampers for air intake and air outlet.
Outdoor Installation
If the heat pump AEROTOP is installed outdoors, the heating pipes and ducts must be as short as possible and they must be well insulated. Place the heat pump on a level and solid surface with the necessary bearing capacity. The corresponding accessories needed for the outdoor installation must be ordered as well.
Heating System Hydraulic Connections
AEROTOP T heat pumps can be connected in any desired layout. The hydraulic connections require flexible ducts to avoid noise transference from pipe openings and solid bodies to the distributor network and from there to the heating elements such as radiators, etc. The ducts can be directed from the right or left and are connected to the inside of the heat pump.
The ductwork must be carried out in such a way that pressure drops at the nominal volume flow do not exceed the available pressure since this would result in a reduction of the heat pump output.
This means that ducts cannot have elbows that are too narrow.
Pipes and du insulated to prevent unnecessary heat loss and the formation of condensate, which could damage the pipe and duct system or the installation location.
cts must also be sufficient
For each heat pump we offer hydraulic standard schemes. The integration of these variants guarantee a safe and faultless operation.
The system must be thoroughly flushed before connecting to the heat pump.
Residues in the heat pipes lead to damages on the heat exchangers und to malfunction of the heat pump. Especially if there is no buffer storage it is recommended to a dirt trap in the heating return flow.
The water filled into the heating system must be handled in accordance with the rules and regulations of the relevant professional associations.
It is important to ventilate the heating system. If not the correct operation of the heat pump is affected. Therefore an exhauster must be provided. The compact heat pumps have an exhauster installed in the flow.
Condensate Drain
The condensate drain should be as close to the heat pump connection as possible. To prevent room air or c analization waste air from being sucked into the heat pump, the condensate drain must be connected airtight to the heat pump using a siphon with a min. height of 100 mm. The condensate drainage pipe cross-section may not be reduced and must be at a continuous 2% incline to ensure water can be ufficiently drained.
34
Page 35
Commissioning
Conditions, parameterization, maintenance
Requirements for Initial Startup (Commissioning)
The initial startup of the AEROTOP T heat pump must be carried out by our qualified technicians or the warranty will become void.
Operating the heat pump is prohibited if the following conditions exist::
Construction drying
System/unit used in unfinished
buildings
Windows or exterior doors
unfinished and locked.
These cases require the use of a specific construction heating system. Functional heating or surface-ready heating with the heat pump acc. To DIN EN 1264 is only permitted when complying with these conditions. Furthermore, it must be noted that the design of the heat pump concerning its standard operation may not yield the full extent of the required heat output. The following notes must be observed as well: The corresponding rules and regula­tions of the floor/screed manufacturer! Proper function is only ensured with a correctly installed system (hydraulics, electrical, settings)! Deviations may damage the floor/screed!
Ensure the following points are implemented and checked before the initial startup of the heat pump:
The control box is installed and
completely connected.
The heat pump is professionally
and completely installed (hydraulics and electrical).
All external system components
required for operating the heat pump (circulation pumps, three-way valves, sensors, etc.) are completely and professionally connected.
The hydraulic connections have
been established completely and professionally.
All sensors are professionally
installed, shielded, and positioned in the correct locations as outlined by the respective system scheme.
The heating system is pro-
fessionally installed and has been flushed, charged, vented, and checked for leaks as per rules and regulations.
The electrical voltage meets the
requirements listed on the type plate of the heat pump.
All fittings are in operational position.
The following persons must be present to carry out the initial startup process:
The planer; he or she must indicate
the operational parameters.
The installer; he or she is
responsible for the functionality and settings of the hydraulic system.
The system maintainer (customer
or representative); he or she will be instructed in the operation and functions of the system.
If an initial startup is requested without all of these conditions having been met, ELCO rejects any responsibility for system malfunctions or other operational problems. In this case, the system is operated at the risk and responsibility of the owner.
Parameterization
The heat pump and the entire system is controlled with the integrated LOGON B WP61 controller. Please consult the system documentation for the correct parameter settings.
After the Initial Startup
After the initial startup is finished, the AEROTOP T heat pump does not equire any additional interventions or adjustments to the controller. Any desired heating temperature adjustments can be made in accordance with the enclosed user manual for the LOGON B WP61 controller.
Controller Function
Different temperature sensors and ¨ measuring elements in the heat pump, at the exterior air, in the system, in the storage tank, in the hot water tank, and possibly also in the living quarters are used by the controller. If and as needed, the controller passes a heat demand signal to the heat pump. The input of a heating curve is used to control and adjust heating tempera­tures. The heat pump as well as the system is controlled automatically. The system-relevant parameters are entered when commissioning the climate-based controller.
Heat Pump Upkeep
The AEROTOP T heat pump does not require any special upkeep. However, it is important to keep the system clean and in good working order. The specified leak checks must be carried out as well. From an energetic viewpoint, it is also recommended, especially in case of a new construction, to have the heating parameters checked and optimized by a service technician during the second winter after the initial startup since the initial humidity has now evaporated from the building and the required heating output is less than initially.
Primary focus should be on keeping air intake and outlet free of dust and other foreign particles or objects. The air intake and outlet openings must be kept free of obstructions (e.g. leaves, vehicles, debris).
Only trained and authorized service technicians are permitted to service AEROTOP T heat pumps.
The warranty becomes null and void if the system or heat pump is serviced by other persons or companies that are not authorized to do so.
Error Messages
AEROTOP T heat pumps function without problems as long as the different parameters do not deviate from the intended or specified values. If one or several of these parameters exceed the limit values, the controller depicts the corresponding error in plain text and stops the heat pump if required to protect the different components. The different error messages are described in the LOGON B WP61 user manual. The heat pump is released again with some errors (automatic acknowledgement) once the intended status has been reached again. It is also usually possible to release the heat pump manually.
In order to ensure reliable functionality of your system, we recommend purchasing a mainte­nance/ service contract.
35
Page 36
Indoor Setup
Unit Dimensions, Indoor Setup (With optional noise dampers )
Legend
1 Heater flow 1” ( 11/4” from T20) flexible Hydraulic or electrical connections all left or right 2 Heater return flow 1” (11/4” from T20), flexible 3 Condensate drain ¾”, flexible 4 Air inlet (at the rear of the unit) 5 Air outlet (optional left, right or top) 6 Electrical connection 7 Vibration dampening rubber feet SI + SO noise damper (optional)
AEROTOP T
T07C, T07
Width
A A+SO B C C+SI d e i j k t q
995 1570 1525 650 1225 575 910 210 300 390 100 40
Heigh Depth
Height
at bottom
Height at Top
Hydraulic connections Feet
T10C, T10
T12C, T12, T14, T16
T20, T26
T32, T35
36
1095 1670 1575 750 1325 575 960 210 300 390 100 40
1195 1770 1675 750 1325 575 1060 210 300 390 100 40
1195 1770 1695 880 1455 670 975 230 385 545 110 50
1295 1870 1905 1000 1575 670 1185 230 385 545 110 50
Page 37
Indoor Installation
Unit Dimensions with Noise Dampers
With indoor installation all heat pump models can be equipped with noise dampeners. Additional measures must be planned for.
Width Width Heigh
AEROTOP T
a b c e A C
T07C, T07 995 1525 650 910 1570 1225
T10C, T10 1095 1575 750 960 1670 1325
T12C, T12, T14, T16
T20, T26 1195 1695 880 975 1770 1455
T32, T35 1295 1905 1000 1185 1870 1575
1195 1675 750 1060 1770 1325
Height at
Top
Dimensions with
Noise Damper
37
Page 38
Air Connections with Indoor Installation
Air Connections, Duct Lengths Air Intake, Associated Unit Dimensions
Air Connections
Air intake and air outlet systems must be protected with grating and kept clean.
It is recommended that light wells are insulated with a sound damping, weather resistant material to prevent dampness problems inside the house The light wells must be drained. The air intake and outlet openings must be kept free of obstructions. Make sure they are installed accordingly. Parking lots or leaves accumulating in fall and possibly suctioned into the system are a problem.
Select the air outlet in such a way that the emerging blast of air is not directly pointed at people, animals, or plants.
The air suction and discharge must not be oriented as the windflow. The correct functioning could be compro­mised by the wind action.
Duct Length
The possible duct lengths are derived from the available pressure and the pressure loss indicated for the respective accessories.
If the air ducts are more than 3 meters long each side, an accurate design is re­quired. In wind exposed places the uncontrolled airflow can be controlled by using shutters
Pressure Loss
Air duct, flexible Ø 500 0,5 - 1,4 Pa/m
flexible Ø 610 1,2 - 1,8 Pa/m
Rigid 750x750 0,5 Pa/m
Rigid 870x870 0,5 Pa/m
Elbow
Rigid750x750 4,2 - 6,9 Pa/m
Rigid 870x870 4,8 - 6 Pa/m
Light well ca 3,5 Pa
Mesh ca 1,5 Pa
Protective grating AIR IN
AIR OUT 11 - 45 Pa
Slienziatori SI+SO T20 6+8 Pa
Slienziatori SI+SO T26 9+14 Pa
Slienziatori SI+SO T32 4+10 Pa
Slienziatori SI+SO T35 5+10 Pa
Slienziatori SI+SO T07 1+2 Pa
Slienziatori SI+SO T10 1+3 Pa
Slienziatori SI+SO T12 2+5 Pa Slienziatori SI+SO T14-
T16
3 - 23 Pa
3+6 Pa
Due to the radial fan, the available pressure is more than sufficient and can be adjusted for all models T07 to T16, as weel as all T..R, with LOGON B WP61 heat pump controller to meet the needs of the respective system. Please comply with the fan speed setting values (page 18).
Air Intake
The air intake (A) is at the rear of the AEROTOP T. It is possible to place the heat pump against the exterior wall (use wall opening kit WAI). If this instal lation type is not possible, use the air intake box and a flexible duct to connect to the heat pump. The duct can then be directed to the left, right, or the top. Flexible ducts are not possible with AEROTOP T 20 to 35 models and rigid ducts must be used. These are to be connected to the heat pump with a flexible sleeve. Noise dampers for air intake and air outlet are recommended for AEROTOP T20 to T35 heat pumps according to page 35
AEROTOP
T07C, T07 995 1525 650 40 915 830 655 550 380 795 180 575
T10C, T10 1095 1575 750 40 1015 880 655 550 380 820 205 575
T12C, T12, T14, T16 1195 1675 750 40 1115 980 655 700 380 795 180 575
38
Width Width Heigh Profile
a b c f a1 e1 h l m r o u
Air Outlet With Wall
Installation
Air Intake with Intake
Box KWI
Page 39
Air Connections with Indoor Installation
Air Outlet, Associated Unit Dimensions
Air Outlet
If the heating or utility room has two exterior walls, a space-saving corner installation is ideal with the heat pump being placed into the left or right corner. This is possible since the air outlet (B) can be mounted on the left or right side (use wall opening kit).
If a corner installation is not possible (e.g. because the room has only one exterior wall or in case of an existing building), use the panel to connect a flexible duct. The alignment of the air outlet sleeve can be directed to the right (R), left, or top (T) as needed by simply replacing the panel
If air intake and air outlet are connected to the same building side (parallel installation), it must be prevented that emitted air is suctioned back into the system by the heat pump (no air short--circuit!). Flexible ducts are not possible with AEROTOP T 20 to 35 models and rigid ducts must be used. These are to be connected to the heat pump with a flexible sleeve.
Noise dampers for air intake and air outlet are recommended for Forever AEROTOP T20 to T35 heat pumps according to page 35.
AEROTOP T
T07C, T07 995 1525 650 40 570 830 655 550 380 795 180
T10C, T10 1095 1575 750 40 670 880 655 550 380 820 205
T12C, T12, T14, T16 1195 1675 750 40 670 980 655 700 380 795 180
T20, T26 1195 1695 880 40 800 895 760 - - - -
T32, T35 1295 1905 1000 40 920 1105 760 - - - -
39
Width Width Heigh Profile
a b c f c1 e1 h l m r o
Air Outlet With Wall
Installation
Air Outlet Via Flexible Duct
Page 40
Air Connections with Indoor Installation
AEROTOP T07 - T35 Corner Setup
AEROTOP T07 – T35 Corner Setup
If the heating or utility room has two exterior walls, a space-saving corner installation is ideal with the heat pump being placed into the left or right corner. Air ducts are not needed.
Left corner setup Right corner setup
Required Accessories:
- AIR IN wall setup kit
- AIR OUT wall setup kit
1) The compliance with acoustic limit values must be clarified by customer.
2) Necessary outside insulation by customer, minimal clearance of light well must not be gone below.
3) Possible air short-circuit to be prevented by customer.
4) Statistics to be checked by customer
AEROTOP T
T07C, T07 995 1525 650 950 600 640 860 60 1200 600 800 600
T10C, T10 1095 1575 750 1050 700 640 910 60 1200 600 1000 600
T12C, T12, T14, T16 1195 1675 750 1150 700 640 1010 60 1200 600 1000 600
T20, T26 1195 1695 880 1150 830 740 930 60 1400 800 1200 800
T32, T35 1295 1905 1000 1250 950 740 1140 60 1400 800 1200 800
The indicated cutouts apply only to the accessories AIR IN and OUTLET wall setup. The dimensions apply after all tasks have been completed and refer to
40
Width
Widt
a
Heigh
h
b
finished floors.
c
Statistics to be checked by
customer If necessary wall must be reinforced with PUR- insulation elements. This must be considered for the cutouts
Dimensions Of Both Cutouts,
Without Insulation
a2 c2 d2 e2
Recommended Dimensions,
Light Well
a3 c3 a4 c4
x
Possible air short-circuit to be
prevented by customer
Necessary outside insulation to be
installed by customer
Page 41
Air Connections with Indoor Installation
AEROTOP T07-T35 with Noise Dampers (SI + SO) Corner Setup
AEROTOP T07 - 35 Corner Setup
The dimensions of the noise dampers must be considered in addition when placing heat pumps into a corner. The heat pump can be placed in the right or left corner. Air ducts are not needed.
Required Accessories:
- AIR IN wall setup kit
- AIR OUT wall setup kit
- SI Noise damper
- SO Noise damper
1) The compliance with acoustic limit values must be clarified by customer.
2) Necessary outside insulation by customer, minimal clearance of light well must not be gone below.
3) Possible air short-circuit to be prevented by customer.
4) Statistics to be checked by customer
AEROTOP T
T07C, T07 995 1525 650 1570 1225 950 600 640 860 635 1200 600 800 600 T10C, T10 1095 1575 750 1670 1325 1050 700 640 910 635 1200 600 1000 600 T12, T14,
T16
T20, T26 1195 1675 880 1770 1455 1150 830 740 930 635 1400 800 1200 800
T32, T35 1295 1695 1000 1870 1575 1250 950 740 1140 635 1400 800 1200 800
The indicated cutouts apply only to the accessories AIR IN and OUTLET wall setup. The dimensions apply after all tasks have been completed and refer to finished floors.
41
Width Width Heigh
a b c A C a2 c2 d2 e2 x a3 c3 a4 c4
1195 1575 750 1770 1325 1150 700 640 1010 635 1200 600 1000 600
Dimensions With
Noise Dampers
Statistics to be checked by
customer If necessary wall must be reinforced with PUR- insulation elements. This must be considered for the cutouts
Dimensions Of Both Cutouts,
Without Insulation
Possible air short-circuit to be
prevented by customer
Necessary outside insulation to
be installed by customer
Minimal Dimensions,
Light Well
Page 42
Cutout Plans for Indoor Installation acc. to SIA Standard
Wall Installation
WP = heat pump, MD = wall opening w/o insulation, Uk = from finished floor = cutout lower edge from finished floor ab FFB = from finished floor *dimensions with noise damper SI and SO
AEROTOP T07 (C)
AEROTOP T10 (C)
AEROTOP T12 (C), 14, 16
AEROTOP T20, 26
AEROTOP T32, 35
42
Page 43
Air Connections with Indoor Installation
AIR IN and AIR OUT Wall Installation Accessories
AEROTOP T07-T35
AIR IN wall installation
AIR OUT wall installation
The wall opening can be made either on the left or on the right of the heat pump.
AEROTOP T07 – T35 with noise damper SI + SO
AIR IN wall installation AIR OUT wall installation
The wall opening can be made either on the left or on the right of the heat pump.
43
Page 44
Air Connections with Indoor Installation
Freely Selectable AIR IN AEROTOP T07 - T16
The use of flexible air ducts offers a variety of different air routing and airflow options. The flexible air out ducts are fastened suction-side and with the intake box for flexible air intake to the left or right side of the heat pump. The wall opening is insulated with the corresponding insulation kit.
Necessary outside insulation by customer
Flexible ducts are not possible with AEROTOP T 20 to 35 models and rigid ducts must be used. See also "Parallel Setup with Rigid Duct."
Required Accessories:
- Freely selectable AIR IN with air duct
- AIR OUT as needed, AIR OUT wall installation or freely selectable AIR OUT
  
The duct can also be mounted to the
left or at the top of the heat pump
1) The compliance with acoustic limit values must be clarified by customer.
2) Necessary outside insulation by customer, minimal clearance of light well must not be gone below.
3) Possible air short-circuit to be prevented by customer.
5) Noise level of AIR OUT and AIR IN must be considered separately
Cutouts Without Insulation
AEROTOP T
c2 e2 d2
T07C, T07 600 860 wählbar 620
T10C, T10 700 910 wählbar 620
T12C, T12, T14, T16 700 1010 wählbar 620
All dimensions refer to a finished floor and completed walls/masonry.
44
D2 with
rigid duct
Cutouts With
Insulation
e1 c1
800 540
850 640
950 640
Recommended Light
Well Dimensions
c3 e3
800 600
1000 600
1000 600
Page 45
Air Connections with Indoor Installation
Freely Selectable AIR OUT AEROTOP T07 - T16
The use of flexible air ducts offers a variety of different air routing and airflow options. The flexible air out ducts are fastened either to the left or right side of the air out panel at the heat pump. The wall opening is insulated with the corresponding insulation kit.
The duct can be
mounted on the left
or the top of the heat
pump as needed.
Flexible ducts are not possible AEROTOP T 20 to 35 models and rigid ducts must be used. See also "Parallel Setup with Rigid Duct."
Required Accessories:
- Freely Selectable AIR OUT
- AIR IN as needed, AIR IN wall installation or AIR IN freely selectable
1) The compliance with acoustic limit values must be clarified by customer.
2) Necessary outside insulation by customer, minimal clearance of light well must not be gone below.
3) Possible air short-circuit to be prevented by customer.
5) Noise level of AIR OUT and AIR IN must be considered separately
Light well
  
Cutouts Without Insulation
AEROTOP T
c2 e2 d2
T07C, T07 600 860 wählbar 620 800 540 800 600
T10C, T10 700 910 wählbar 620 850 640 1000 600
T12C, T12, T14, T16 700 1010 wählbar 620 950 640 1000 600
All dimensions refer to a finished floor and completed walls/masonry.
45
D2 with
rigid duct
Cutouts With
insulation
e1 c1
Recommended Light
Well Dimensions
E3 width C3 depth
Page 46
Air Connections with Indoor Installation
Freely Selectable AIR OUT and AIR IN Accessories (AEROTOP T07 to T16)
Corner installation option
All variants can also be installed mirror-inverted
Parallel installation option
All variants can also be installed mirror-inverted
46
Page 47
Air Connections with Indoor Installation
Parallel Setup with Rigid Duct (without Noise Damper)
Required Accessories:
AIR IN wall setup kit
AIR OUT parallel installation with
rigid duct.
1) The compliance with acoustic limit values must be clarified by customer.
2) Necessary outside insulation by customer, minimal clearance of light well must not be gone below.
3) Possible air short-circuit to be prevented by customer.
5) Noise level of AIR OUT and AIR IN must be considered separately
Partition wall Height k2 x Width k3
Light well
Light well dimension
a3 a4 c3 c4
T07C, T07 1200 800 600 600 T10C, T10 1200 1000 600 600 T12C, T12, T14, T16 1200 1000 600 600
Light well
or
or
All dimensions refer to a finished floor and completed walls/masonry.
Rigid Duct Dimension
AEROTOP T
e1 c1 a2 c2 d2 e2
T07C, T07 800 520 950 600 640 860 1500 630 1500 1000
T10C, T10 850 620 1050 700 640 910 1500 630 1500 1000
T12C, T12, T14, T16 950 620 1150 700 640 1010 1800 630 1700 1200
47
Cutouts without Insulation
Distance between
Cutouts
k1 without
partition
wall
partition
Partition Wall
k1 with
Height k2 Width k3
wall
Page 48
Air Connections with Indoor Installation
Parallel Setup with Rigid Duct (with Noise Damper)
Required Accessories:
Light well
AIR IN wall setup kit
AIR OUT parallel setup with rigid
duct
Partition wall Height k2 x Width k3
Light well
SI Noise damper
SO Noise Damper
1) The compliance with acoustic limit values must be clarified by customer.
2) Necessary outside insulation by customer, minimal clearance of light well must not be gone below.
3) Possible air short-circuit to be prevented by customer.
5) Noise level of AIR OUT and AIR IN must be considered separately
or
or
Light well dimension a3 a4 c3 c4 T07C, T07 1200 800 600 600 T10C, T10 1200 1000 600 600 T12C, T12, T14, T16 1200 1000 600 600 T20, T26 1400 1200 800 800 T32, T35 1400 1200 800 800
Rigid Duct Dimension
AEROTOP T
e1 c1 f1 a2 c2 d2 e2
T07C, T07 800 520 575 950 600 640 860 1500 630 1500 1000
T10C, T10 850 620 575 1050 700 640 910 1500 630 1500 1000
T12C, T12, T14, T16 950 620 575 1150 700 640 1010 1800 630 1700 1200
T20, T26 870 750 575 1150 830 740 930 2000 630 1700 1200
T32, T35 1080 870 575 1250 950 740 1140 2200 630 1700 1500
All dimensions refer to a finished floor and completed walls/masonry.
48
Cutouts without Insulation
Distance between
Cutouts
k1 without
partition
wall
partition
k1 with
wall
Partition Wall
Height
k2
Width
k3
Page 49
Cutout Plans for Indoor Installation acc. to SIA Standard
Parallel Setup With Rigid Duct With / Without Noise Damper
WP = heat pump, MD = wall opening w/o insulation, Uk = from finished floor = cutout lower edge from finished floor ab FFB = from finished floor
AEROTOP T07 (C)
AEROTOP T10 (C)
AEROTOP T12 (C), 14, 16
AEROTOP T20, 26
AEROTOP T32, 35
49
Page 50
Outdoor Setup
Unit Dimensions AEROTOP T.. Outdoor Setup
AEROTOP T20-T35
AEROTOP T..
Min. 1200 mm
AEROTOP T07-T16
Min. 800mm
4
AEROTOP T..
5
AEROTOP T..Outdoor setup : Incl. Hoods for Air In / Air Out, protective roof and regulating wall housing.
1 Flow line heater ø 1” (ø 11/4” from T20) Hydraulic and electrical connections all at the bottom 2 Return line heater ø 1” (ø 11/4” from T20) 3 Condensation water drain ø 3/4” 4 Air inlet 5 Air outlet 6 Electrical connections a Electric line low voltage b Electric line safety low voltage 7 Vibration dampening rubber feet 8 Protective roof with distance spacer 9 Setup foundation, minimum height 300 mm, account for local snow heights.
AEROTOP T
T07 995 1513 650 1450 575 910 1095 750 28 T10 1095 1563 750 1650 575 960 1195 850 28
T12, T14, T16 1195 1663 750 1750 575 1060 1295 850 28
T20, T26 1195 1690 880 1980 670 975 1295 980 45
T32, T35 1295 1900 1000 2200 670 1185 1395 1100
Width
A B C C+ d e AS CS q
Height without protective roof
Depth
Depth for
Minimum clearances for service works Prevent air short circuits Attention: a setup in the frontage corner leads to a higher noise emission and should be avoided, if possible!
The air discharge can’t be set directly on a wall. In this case a minimum distance of 2 meters must be respected. The air suction and discharge must not be oriented as the windflow. The correct functioning could be compromised by the wind action.
Height without protective roof
on top
foundation
ASS
Height
at bottom
Setup
Feet
45
AEROTOP T für Aussenaufstellung
50
50
Page 51
Outdoor Installation
Special Conditions, Installation Location
Special Rules for Outdoor Installa­tions
Please observe the general setup, in­stallation, and connection instructions. Place the heat pump on a level and solid surface with the necessary bearing capacity. If not available, provide a cement base, acc. to the snow height, so that the feet of the outdoor unit cannot be covered with snow. The heat pump must be aligned with the ad­justable feet.
Heater flow and return must be as short as possible and well insulated to prevent heat losses. The condensate drain must be insulated and protected from frost and have a siphon with a min. height of 100 mm routed into a closed drain. The drain line must not have any cross­section reductions and must be suffi­ciently suitable to ensure problem-free drainage.
The controller unit must be installed inside of the building (temperature range of +5°C to +40°C). The wall openings for heater flow and return as well as the electrical cables must be carried out according to the rules and regulations. Especially the flexible electrical cables as well as the low voltage (230 or 400V) and the extra-low voltage (sensor and controller cable) must be shielded from one another.
Information about Cables in Conduits (Min. Ø 70 mm)
1 EC block 2-pin Ø 5 mm
1 x malfunction 2-pin Ø 5 mm 1 x controller unit 3-pin Ø 7 mm
1 x room sensor 2-pin Ø 5 mm 7 x sensor 2-pin Ø 35 mm
1 x electr. feed 3 x 400 V 3-pin Ø 12 mm 1 x condenser pump 3-pin Ø 7 mm 1 x heating circuit pump 3-pin Ø 7 mm 1 x mixing valve 3-pin Ø 7 mm 1 x storage charge pump 3-pin Ø 7 mm Heating Circuit 2 1 x heating circuit pump 3-pin Ø 7 mm 1 x mixing valve 4-pin Ø 10 mm
51
Selecting the Installation Site
Air intake and outlet must be kept clean, unobstructed, and free of snow, leaves, plants, machinery, etc. Comply with min. clearances as specified for air intake, outlet, misc. ducts, and maintenance (see previous page). Avoid an air short-circuit at all costs. Use both sides for the air outlet if strong winds, for example, may cause an air short-circuit. The air intake must be protected from aggressive or corro­sive substances such as ammonia, chlorinated substances, etc.
The AEROTOP T heat pump is very quiet. However, since noise is per­ceived differently by different people, the heat pump should not be installed near windows, sleeping or living quarters (porch, edge of pool, etc.). The distance to neighboring houses should be sufficient as well. It is not advised to install the heat pump in recesses (possible echo or air short-­circuit). Local rules and regulations apply.
Observe the checklist notes when selecting the installation site for the correct setup of an air-water heat pump.
= Ø 57 mm (conduit min. 70 mm)
= Ø 57 mm (conduit min. 70 mm)
1
2
a
b
7
7
3
1 Heater flow Hydraulic and electrical connections are at the bottom side of the heat pump. 2 Heater return 3 Condensate drain Ø 25/31 mm 4 Air intake 5 Air outlet 6 Internal electrical panel 7 Hydraulic and electrical connections, electr. low voltage cable shielded from 380V and 230V 8 Adjustable, noise-dampened feet 9 Protective cover 10 Base or pedestal, recommended height of 200 mm, consider local snow levels. 12 Wall opening slanted towards inside with seal (in PE, inner diameter of 300 mm) 13 Controller unit for wall mounting (included in delivery)
.
Ø 300mm
13
1
12
Page 52
Outdoor Installation
Base/Pedestal Plan
Cutouts in Base/Pedestal for AEROTOP T07-T35
The base or pedestal should project beyond each side of the heat pump for about 50 mm and be approx. 300 mm high (adjust to local snow conditions as needed). A conduit (NW 250) must be installed between building and heat pump for the installation lines (electrical, hydraulic, and condensate).
Setup Base/Pedestal
AEROTOP T a1 c1 h1
AEROTO T07-T16
Min. 800mm
T07
T10
T12, T14, T16
T20, T26
T32, T35
1095 750 300
1195 850 300
1295 850 300
1295 980 300
1395 1100 300
min. 50 mm
Ø 175
AEROTO T20 - T35
min. 500
Min. 800mm
242 mm
52
242 mm
c1
Ø 175 mm
a1
min. 500 mm
Page 53
Installation
Duct and Cable Bushing
1
Upper edge of base to upper edge of conduit min. 3 cm
Prepunched Opening for Outdoor Installation of an Air-Water Heat Pump
A prepunched opening (1) for the lines routed from the rear of the enclosure into the ground is provided in the unit bottom behind the electrical panel. We recommend routing the lines this way for the heat pump installed outdoors. This involves pulling the heating lines, condensate connection, and the electrical cables through the opening.
Push conduit against HP insulation to protect from insects
Please take note of the base/pedestal plan with the required cutout. The prepunched cover can be lifted with a screwdriver or detached with sheet metal nippers.
Condensate drain also possible via seepage pit.
Drain pipe insulation min. 3 cm
Upper edge of ground to upper edge of base min. 30 cm
Water-proof conduit (plastic pipe) installed 800 to 1000 mm on-site under­ground with 2% tilt towards building. Use only 45° elbows.
Seepage pit size min. H = 50 cm W = 50 cm D = 50 cm
53
Page 54
Performance Charts
AEROTOP T07 (information according to EN 14511)
Conditions:
Hot water throughput 1500 l/h Air throughput 2500 m3/h
Water out temperature (flow) at 35°C and 45°C
Flow 35°C Flow 45°C
Power consumption and heat output in kW Performance rating while heating
54
Air intake temperature (°C)
Air intake temperature (°C)
Page 55
Performance Charts
AEROTOP T10 (information according to EN 14511)
Conditions:
Hot water throughput 2100 l/h Air throughput 3‘300 m3/h
Water out temperature (flow) at 35°C and 45°C
Flow 35°C Flow 45°C
Power consumption and heat output in kW
Performance rating while heating
Air intake temperature (°C)
55
Page 56
Performance Charts
AEROTOP T12 (information according to EN 14511)
Conditions:
Hot water throughput 2’700 l/h Air throughput 5‘300 m
3
/h
Water out temperature (flow) at 35°C and 45°C
Flow 35°C Flow 45°C
Power consumption and heat output in kW Performance rating while heating
56
Air intake temperature (°C)
Page 57
Performance Charts
AEROTOP T14 (information according to EN 14511)
Conditions:
Hot water throughput 3'070 l/h Air throughput 6‘300 m
3
/h
Water out temperature (flow) at 35°C and 45°C
Flow 35°C Flow 45°C
Power consumption and heat output in kW
Performance rating while heating
Air intake temperature (°C)
57
Page 58
Performance Charts
AEROTOP T16 (information according to EN 14511)
Conditions:
Hot water throughput 3'100 l/h Air throughput 6‘800 m
3
/h
Water out temperature (flow) at 35°C and 45°C
Flow 35°C Flow 45°C
Power consumption and heat output in kW
Performance rating while heating
58
Air intake temperature (°C)
Page 59
Performance Charts
AEROTOP T20 (information according to EN 14511)
Conditions:
Hot water throughput 3‘700 l/h Air throughput 7‘300 m
3
/h
Water out temperature (flow) at 35°C and 45°C
Flow 35°C Flow 45°C
Power consumption and heat output in kW
Performance rating while heating
Air intake temperature (°C)
59
Page 60
Performance Charts
AEROTOP T26 (information according to EN 14511)
Conditions:
Hot water throughput 5’850 l/h Air throughput 8’300 m
3
/h
Water out temperature (flow) at 35°C and 45°C
Flow 35°C Flow 45°C
Power consumption and heat output in kW Performance rating while heating
60
Air intake temperature (°C)
Page 61
Performance Charts
AEROTOP T32 (information according to EN 14511)
Conditions:
Hot water throughput 6’280 l/h Air throughput 10‘000 m
3
/h
Water out temperature (flow) at 35°C and 45°C
Flow 35°C Flow 45°C
Power consumption and heat output in kW
Performance rating while heating
Air intake temperature (°C)
61
Page 62
Performance Charts
AEROTOP T35 (information according to EN 14511)
Conditions:
Hot water throughput 7‘300 l/h Air throughput 11’000
Water out temperature (flow) at 35°C and 45°C
Flow 35°C Flow 45°C
Power consumption and heat output in kW
Performance rating while heating
62
Air intake temperature (°C)
Page 63
Performance Charts
AEROTOP T07X (information according to EN 14511) (available in F / I / B)
Conditions:
Hot water throughput 568 l/h Air throughput 2500m
3
/h
Water out temperature (flow) at 35°C and 45°C
Flow 35°C Flow 45°C
Power consumption and heat output in kW
Performance rating while heating
Air intake temperature (°C)
63
Page 64
Performance Charts
AEROTOP T10X (information according to EN 14511) (available in F / I / B)
Conditions:
Hot water throughput 835 l/h Air throughput 3300m
3
/h
Water out temperature (flow) at 35°C and 45°C
Flow 35°C Flow 45°C
Power consumption and heat output in kW
Performance rating while heating
64
Air intake temperature (°C)
Page 65
Performance Charts
AEROTOP T07R (according to EN 14511– Cooling)
Flow 7°C Flow 18°C
Power consumption and Cooling Capacity (kW)
EER
Flow 7°C Flow 18°C
Air intake temperature (°C)
65
Page 66
Performance Charts
AEROTOP T10R (according to EN 14511– Cooling)
Flow 7°C Flow 18°C
Power consumption and Cooling Capacity (kW)
EER
Flow 7°C Flow 18°C
66
Air intake temperature (°C)
Page 67
Performance Charts
AEROTOP T12R (according to EN 14511– Cooling)
Flow 7°C Flow 18°C
Power consumption and Cooling Capacity (kW)
EER
Flow 7°C Flow 18°C
Air intake temperature (°C)
67
Page 68
Performance Charts
AEROTOP T14R (according to EN 14511– Cooling)
Flow 7°C Flow 18°C
Power consumption and Cooling Capacity (kW)
EER
Flow 7°C Flow 18°C
68
Air intake temperature (°C)
Page 69
Performance Charts
AEROTOP T16R (according to EN 14511– Cooling)
Flow 7°C Flow 18°C
Power consumption and Cooling Capacity (kW)
EER
Air intake temperature (°C)
69
Page 70
Performance Charts
AEROTOP T20R (according to EN 14511– Cooling)
Flow 7°C Flow 18°C
Power consumption and Cooling Capacity (kW)
EER
Flow 7°C Flow 18°C
70
Air intake temperature (°C)
Page 71
Performance Charts
AEROTOP T26R (according to EN 14511– Cooling)
Flow 7°C Flow 18°C
Power consumption and Cooling Capacity (kW)
EER
Flow 7°C Flow 18°C
Air intake temperature (°C)
71
Page 72
Performance Charts
AEROTOP T32R (according to EN 14511– Cooling)
Flow 7°C Flow 18°C
Power consumption and Cooling Capacity (kW)
EER
Flow 7°C Flow 18°C
72
Air intake temperature (°C)
Page 73
Performance Charts
AEROTOP T35R (according to EN 14511– Cooling)
Flow 7°C Flow 18°C
Power consumption and Cooling Capacity (kW)
EER
Air intake temperature (°C)
73
Page 74
Hydraulic Plan
Overview Standard Plans (not concluding)
Plan Component Optional
Standard-Nr.
Floor heating direct
Buffer storage in returning line
Buffer storage un-coupled
AEROTOP TC 1
AEROTOP TC 1-6
Combined storage
Mixer circuit
Unmixed circuit
Warm water with register boiler
Warm water with Magro-storage
Solar connection 1-circuit
Heater support
Solar connection 1-circuit
Warm water processing
Additional mixer group
(extension N)
AEROTOP TC 1-6-7
AEROTOP T 1-I
AEROTOP T 2-6-H
AEROTOP T 2-6-7-H
AEROTOP T 2-I
AEROTOP T 2-6-I
AEROTOP T 2-5-B-I
Additional hydraulic suggestions
Special planning required!
AEROTOP T cascade with PHW separation switch
AEROTOP TR
General information
In systems with buffer storage, the flow volume over the heater distributor must not be larger than that of the load circuit (heat pump – storage); otherwise, a back-flow effect may be caused by the buffer storage. This would have a negative effect on the efficiency of the system and on the good functionality of the heat pump.
74
Page 75
Hydraulic System
AEROTOP TC 1
Application / Description:
Heat pump directly on heater without buffer storage. Optimal with floor heating with min. 60% constant hot water flow.
Function Description: Heating Cycle
The heat pump is activated via the internal return sensor and exterior sensor B9 when requesting heat. The circulating pump is active during the heating season.
Hot Water
Optionally, water heating can be carried out by the Multiaqua - service water heat pump
B9 Exterior sensor A6 Remote control (option) Multiaqua - service water treatment
optional Multiaqua
* option
75
Page 76
Hydraulic System
AEROTOP TC 1-6
B9 Exterior sensor B3 Service water sensor B31 Service water sensor A6 Remote control (optional) R6 Electrical heater element Q3 Switchover valve
Application / Description:
Heat pump directly on heater without buffer storage. Hot water is heated by a coil water heater. Optimal with floor heating with min. 60% constant hot water flow.
Function Description: Heating Cycle
The heat pump is activated via the internal return sensor and exterior sensor B9 when requesting heat. The circulating pump is active during the heating season. The switchover valve Q3 is at position B.
Hot Water
Sensor B3 activates the water heating. The switchover valve Q3 is switched to position A. Charging continues until the nominal value has been reached at sensor B31. Protection from Legionella pneumophila bacteria and auxiliary heating to a higher temperature level is carried out via electrical heater element R6.
76
Page 77
Hydraulic System
AEROTOP TC 1-6-7
B9 Exterior sensor B3 Service water sensor B6 Collector sensor B31 Service water sensor
Standard 1-6-7 Application / Description:
Heat pump directly on heater without buffer storage. Optimal with floor heating with min. 60% constant hot water flow. Hot water heating with coil hot water heater and solar integration.
Function Description: Heating Cycle
The heat pump is activated via the internal return sensor and exterior sensor B9 when requesting heat. The circulating pump is active during the heating season. The switchover valve Q3 is at position B.
Hot Water
Sensor B3 activates the water heating The switchover valve Q3 is switched to position A. Charging continues until the nominal value has been reached at sensor B3. Protection from Legionella pneumophila bacteria and auxiliary heating to a higher temperature level is carried out via electrical heater element R6.
A6 Remote control (option) R6 Electrical heater element Q3 Switchover valve Q5 Collector pump
Solar
If a difference exists between collector sensor B6 and storage sensor B31, the solar pump Q5 is activated and storage is charged. In case of excessive storage temperatures, the collectors are cooled at nighttime.
77
Page 78
Hydraulic System
AEROTOP TC 1I
B9 Exterior sensor B4 Storage sensor, top B41 Storage sensor, bottom A6 Remote control (option) R16 Electrical heater element (optional)
Standard 1-I Application / Description:
Heat pump uncoupled with buffer storage and adjustable heating circuit. Optimal with floor heating or radiator heating with variable flow.
Function Description: Heating Cycle
The heat pump is activated via sensor B4 and exterior sensor B9 when requesting heat. The storage charge pump Q9 starts running simultaneously. Storage is charged. Charging continues until the set point has been reached at sensor B4.
Hot Water
Optionally, water heating can be carried out by the Multiaqua - service water heat pump.
optional Multiaqua
Q2 Heating circuit pump, controlled Q9 Circulation pump R25 Electr. heater element (T07-T16) Multiaqua - service water heating
78
Page 79
Hydraulic System
AEROTOP T 2-6-H
B9 Exterior sensor B3 Service water sensor B4 Storage sensor B41 Storage sensor
Standard 2-6-H Application / Description:
Heat pump uncoupled with buffer storage and mixed heating circuit. Hot water heating with coil hot water heater. Optimal with floor heating or radiator heating with variable flow and limited hot water demand.
Function Description: Heating Cycle
The heat pump is activated via sensor B4 and exterior sensor B9 when requesting heat. The storage charge pump Q9 starts running simultaneously. The switchover valve is at position B. Storage is charged. Charging continues until the set point has been reached at lower sensor B41. The heating circuit mixer Y1 is controlled via the flow sensor B1.
B1 Flow sensor A6 Remote control (optional) Q3 Switchover valve Q9 Circulation pump Q2 Heating pump circuit, controlled
R6 Electrical heater element (option) R25 Electrical heater element /T07-T16) Y1 Mixing valve gear TS Safety thermostat for floor heating
Hot Water
Sensor B3 activates the water heating. The switchover valve Q3 is switched to position A. Charging continues until the nominal value has been reached at sensor B31. Protection from Legionella pneumophila bacteria and auxiliary heating to a higher temperature level is carried out via electrical heater element R6.
NOTE: To avoid damages to the internal storage, the PHW-storage must be pressurized first before filling of the heating circuit (i.e. fill the PHW-storage first)
79
Page 80
Hydraulic System
AEROTOP T 2-6-7-H
B9 Exterior sensor B3 Service water sensor B4 Service water sensor B41 Service water sensor B6 Solar collector sensor
Standard 2-6-7-H Application / Description:
Heat pump uncoupled with buffer storage with solar integration and mixed heating circuit. Optimal with floor heating or radiator heating with variable flow and limited hot water demand
Function Description: Heating Cycle
The heat pump is activated via sensor B4 and exterior sensor B9 when requesting heat. The storage charge pump Q9 starts running simultaneously. The switchover valve is at position B. Storage is charged. Charging continues until the set point has been reached at lower sensor B41. The heating circuit mixer Y1 is controlled via the flow sensor B1
Hot Water
Sensor B3 activates the water heating The switchover valve Q3 is switched to position A. Charging continues until the nominal value has been reached at sensor B3.
B1 Flow sensor A6 Remote control (option) R6 Electrical heater element Q2 Heating circuit pump, controlled Q3 Switchover valve
Q5 Solar collector pump Q9 Circulation pump R25 Electrical heater element (T07-T16) TS Safety thermostat for floor heating Y1 Mixing valve gear
Solar
If a difference exists between collector sensor B6 and storage sensor B41, the solar pump Q5 is activated and storage is charged. In case of excessive storage temperatures, the collectors are cooled at nighttime.
NOTE: To avoid damages to the internal storage, the PHW-storage must be pressurized first before filling of the heating circuit (i.e. fill the PHW-storage first)
80
Page 81
Hydraulic System
AEROTOP T 2-I
optional Multiaqua
B9 Exterior sensor B4 Storage sensor B41 Storage sensor B1 Flow sensor
Standard 2-I Application / Description:
Heat pump uncoupled with buffer storage and mixed heating circuit. Optimal with floor heating or radiator heating with variable flow and to optimize run times.
Function Description: Heating Cycle
The heat pump is activated via sensor B4 and exterior sensor B9 when requesting heat. The storage charge pump Q9 starts running simultaneously. Storage is charged. Charging continues until the set point has been reached at lower sensor B41. The heating circuit mixer Y1 is controlled via the flow sensor B1.
Hot Water
Optionally, water heating can be carried out by the Multiaqua - service water heat pump.
A6 Remote control (option) R16 Electrical heater element (optional) R25 Electr. heater element (T07-T16) Q2 Heating circuit pump, controlled
Q9 Circulation pump Y1 Mixing valve gear Multiaqua - service water heating
81
Page 82
Hydraulic System
AEROTOP T 2-6-I
A6 Remote control (option) B1 Flow sensor B3 Service water sensor B4 storage sensor, top B9 Exterior sensor
Application / Description:
Heat pump uncoupled with buffer storage and mixed heating circuit. Water heating with water heater with external exchanger. Optimal with floor heating or radiator heating with variable flow to optimize run times.
Function Description: Heating Cycle
The heat pump is activated via sensor B4 and exterior sensor B9 when requesting heat. The storage charge pump Q9 starts running simultaneously. The switchover valve is at position B. Storage is charged. Charging continues until the set point has been reached at lower sensor B41. The heating circuit mixing valve Y1 is controlled via the flow sensor B1.
B31 Service water sensor B41 Storage sensor, bottom Q2 Heating circuit pump Q3 Switchover valve Q9 Circulation pump
Hot Water
Sensor B3 activates the water heating. Both charge pumps Q3 are activated. The switchover valve Q3 is switched to position A. Charging continues until the set point at sensor B31 has been reached. Protection from Legionella pneumophila bacteria and auxiliary heating to a higher temperature level is carried out via electrical heater element R6.
R6 Electrical heater element N1 Heat pump controller (built-in)
R6
Y1 Mixing valve gear
82
Page 83
Hydraulic System
AEROTOP T 2-5-B-I
B1 Flow sensor B3 Hot water sensor B4 Storage sensor, top B9 Exterior sensor B31 Hot water sensor B41 Storage sensor, bottom
Application / Description:
Heat pump uncoupled,with buffer storage and mixed heating circuit. Water heating with water heater with external exchanger (Magro charge). Optimal with floor heating or radiator heating with variable flow to optimize run times and satisfy higher service water demands.
Function Description: Heating Cycle
The heat pump is activated via sensor B4 and exterior sensor B9 when requesting heat. The storage charge pump Q9 starts running simultaneously. The switchover valve is at position B. Storage is charged. Charging continues until the set point has been reached at lower sensor B41. The heating circuit mixing valve Y1 is controlled via the flow sensor B1.
N1 Heat pump controller (built-in) Q2 Heating circuit pump Q3 Service water pump Q9 Storage pump Y1 Mixing valve gear R6 Electrical heater element Q33 PHW-loading pump
Hot Water
Sensor B3 activates the water heating. Both charge pumps Q3 and Q9 are activated. The thermal mixing valve ensures that the charge is not released to the storage tank until the min. charge temperature has been reached. Charging continues until the set point at sensor B31 has been reached. Protection from Legionella pneumophila bacteria and auxiliary heating to a higher temperature levels is carried out via electrical heater element R6.
Option:
A6 Remote control
83
Page 84
Hydraulic System
Standard Expansion N Standard-Expansion 2
Multiaqua feed 1x230V /13A/T
Standard Expansion N
Electr. heater feed
Reduced rate 1x230 V 16 A
Note:
To ensure the Multiaqua service water heat pump is functioning properly, the min. flow of 500l/h must be available in the system in the winter as well as the summer. This means several circuits must be equipped without automatically closing valves. The selected rooms must be those to be cooled during the summer.
Hot Water
Cold water
Standard Expansion 2
N21 Additional module X30 Remote controll BX21 Flow sensor QX23 Mixed circuit pump QX21 Mixing drive
A second mixed circuit can be controlled with an expansion module of the heat pump controller. The second mixed circuit can be combined with the following schemes: 2-I, 2-6-I, 2-6-H, 2-5-B-I, 2-6-7-H.
84
Page 85
Hydraulic System
AEROTOP T Cascade with PWH Isolating Circuit
A6 Remote control (option) B1 Flow sensor B3 Service water sensor B4 Storage sensor top B9 Exterior sensor
Application / Description:
Several heat pumps, uncoupled, with buffer storage and mixed heating circuit. A heat pump is specifically assigned the task of heating potable water. Water heating with water heater with external exchanger (Magro charge). Optimal with floor heating or radiator heating with variable flow to optimize run times and satisfy higher service water demands.
B10 Bar flow temperature sensor B31 Service water sensor B41 Storage sensor bottom N1 Heat pump controller (built-in)
Function Description: Heating Cycle
The heat pump is activated via sensor B4 and exterior sensor B9 when requesting heat. The storage charge pump Q9 starts running simultaneously. If the currently running heat pump cannot satisfy the energy demand within a specific time, an additional heat pump/heat generator switches on (additional activation controlled by sensor B10 and assigned set point). Charging continues until the set point has been reached at lower sensor B41. The heating circuit mixing valve Y1 is controlled via the flow sensor B1.
Q2 Heating circuit pump Q9 Circulating pump Q33 PWH charge pump Y1 Mixing valve gear
Hot Water
Sensor B3 activates the water heating. Both charge pumps Q3 and Q33 are activated. The thermal mixing valve ensures that the charge is not released to the storage tank until the min. charge temperature has been reached.
Charging continues until the set point at sensor B31 has been reached. Protection from Legionella pneumophila bacteria and auxiliary heating to a higher temperature levels is carried out via electrical heater element R6.
Thanks to the PWH isolating circuit, a HP can be dimensioned and selected specifically for producing potable water. For example, a heat pump can be combined with different outputs. This makes it possible to heat potable water more efficiently and allows to run the system more efficiently as well since the heat pump is only specifically assigned to heat potable water in the summer. While in heating mode, the outputs of the two heat pumps are added to cover the required energy demand.
85
Page 86
Hydraulic System
AEROTOP T R with Active Cooling
A6 Remote control (option) B1 Flow sensor B4 Storage sensor, top B9 Exterior sensor
Application / Description:
Reversible heat pump (AEROTOP T), uncoupled, with buffer storage and mixed heating circuit, in combination with a distribution system suitable for heating and cooling (e.g.fain coil).
Function Description: Heating Cycle
The heat pump is activated via sensor B4 and exterior sensor B9 when requesting heat. The storage charge pump Q9 starts running simultaneously. Valves K28 remain in position AB-B. Storage is charged. Charging continues until the set point has been reached at lower sensor B41. The heating circuit mixing valve Y1 is controlled via the flow sensor B1.
B41 Storage sensor, bottom N1 Heat pump controller (built-in) Q2 Heating circuit pump Q9 Circulation pump
K6 Electrical heater element SW Y1 Mixing valve gear K28 Cooling demand
Cooling Cycle
The heat pump is activated via sensor B4 and exterior sensor B9 when requesting cooling. The four-way valve Y22 of the heat pump is also actuated, which results in a process reversal of the heat pump: The heat out side (condenser) becomes the heat absorption side (evaporator), i.e. the heating system is now cooled and the source is heated. Valves K28 are activated simultaneously (position AB-A) and the buffer storage is reversed or discharged. The storage charge pump Q9 starts running simultaneously. Storage is charged. Charging continues until the set point in the buffer has been reached. The cooling circuit mixing valve Y1 is controlled via the flow sensor B1.
Hot Water
Optionally, water heating can be carried out by the Multiaqua - service water heat pump.
Important:
- When used in applications with active cooling, a vapor-diffusion cold insulation is mandatory for all system components (lines, pumps, cocks, charging, storage)!
- In case of floor heaters, only a partial cooling is possible with flow temperatures above 18°C! A condensate monitoring system must be provided!
- Use only in combination with a distribution system suitable for heating and cooling (e.g. fan coil)
- Process reversal valves K28 are recommended with active cooling using a system temperature of 7/12°C and large buffer storage volumes. In case of partial cooling applications (system temperature > 18°C, floor heating) can be omitted.
86
Page 87
Notes
87
Page 88
Service:
ELCO GmbH D - 64546 Mörfelden-Walldorf
ELCO Austria GmbH
A - 2544 Leobersdorf
ELCOTHERM AG
CH - 7324 Vilters
ELCO-Rendamax B.V.
NL - 1410 AB Naarden
ELCO Belgium n.v./s.a.
B - 1070 Anderlecht
ELCO Italia S.p.A.
I - 31023 Resana
Loading...