elco N6.2400 G-R, N7.3600 G-R, N6.2900 G-R, N7.4500 G-R Operating Instructions Manual

10/2010 - Art. Nr. 4200 1030 6900A
N6.2400 G-R N6.2900 G-R N7.3600 G-R N7.4500 G-R
Operating instructions
For specialist installation engineers
Gas burners ........................................... 2-25
e
de, fr ..................................... 4200 1030 7000
it, nl ...................................... 4200 1031 9200
............................................. 4200 1028 8600
10/2010 - Art. Nr. 4200 1030 6900A2
Overview
Contents
We accept no responsibility for damage arising from:
- inappropriate use.
- incorrect installation and/or repair on the part of the buyer or any third party, including the fitting of non-original parts.
Final delivery and instructions for use
The firing system fitter must supply the operator of the system with operating and maintenance instructions on or before final delivery. These instructions should be displayed in a prominent location at the point of installation of the heat generator, They should include the address and telephone number of the nearest customer service centre.
Notes for the operator
The system should be inspected by a specialist at least once a year. Depending on the type of installation, shorter maintenance intervals may be necessary! It is advisable to take out a maintenance contract to guarantee regular servicing.
Overview Contents.................................................................... 2
Important information................................................2
Burner description..................................................... 3
Operation Gas start-up mode, gas operating mode ..................4
General safety functions........................................... 4
Fuel-air compound control........................................ 5
Gas valves and instruments group ...........................5
Automatic furnace controller LFL 1.../LGK... ............6
Gas valve VGD with SKP regulator .......................... 7
Gas valve MBC-SE...................................................7
Assembly Boiler lining for G-R burner, burner assembly...........8
Gas connection.........................................................9
Checking, assembling the combustion components10
Gas connection, electrical connection .................... 11
Checks before commissioning................................ 11
Commissioning Burner power adjusting sequence .......................... 12
Mechanical compound, electrical actuator.............. 13
Limit switch setting.................................................. 13
Monitoring of the flame by ionisation ...................... 14
Sensor current measurement ................................. 14
Gas pressure switch, air pressure switch ............... 15
Gas valves and instruments group
Description.............................................................. 16
Basic construction.............................................. 17-19
Gas valve leakage controller................................... 20
Servicing Maintenance ..................................................... 21-22
Exhaust gas test, trouble shooting instructions..23-24
Operating trouble .................................................... 25
Declaration of conformity
for gas burners
We,
Elco Burners GmbH, Herbert­Liebsch-Straße 4a, 01796 Pirna, Germany,
declare under our sole responsibility that the products
N6.2400 G-R N6.2900 G-R N7.3600 G-R N7.4500 G-R
conform to the following standards EN 50165 EN 12953-7 EN 12952-8 EN 61000-6-2 EN 61000-6-4 EN 676
These products bear the CE mark in accordance with the stipulations of the following directives 2006/42 /EC Machinery directive 2004/108/EC EMC directive 2006/95/EC Low voltage directive 2009/142/EC Gas appliances
Directive
97/23/EC Pressure Equipment
Directive
Pirna, 26th May 2010
D. HOFFMANN
Important information
N6 and N7 G-R burners are designed for the combustion of natural gas. The design and function of the burners meet standard EN 676. They are suitable for use with all heat generators complying with standard within their respective performance range. Any other type of application requires the approval of ELCO. Installation, start-up and maintenance must only be carried out by authorised specialists and all applicable guidelines and regulations must be complied with.
Burner description
N6 and N7 G-R burners are progressive mechanical fully automatic monoblock devices. Emissions values may differ, depending on combustion chamber dimensions, combustion chamber load and the firing system (three-pass boilers, boilers with reverse firing). For specifying warranty values, the conditions for the measuring equipment, tolerances and humidity must be observed.
Packaging
The burner is supplied packaged in three boxes on a pallet:
- Burner body with:
- integrated switch cabinet
- flange seal and securing screws
- operating instructions, circuit diagram and spare parts list
- Combustion head
- Compact gas train with integrated or external filter
The following standards should be observed in order to ensure safe, environmentally sound and energy­efficient operation:
EN 226
Connection of fuel oil and forced­draught gas burners to a heat generator
EN 60335-1, -2-102
Specification for safety of household and similar electrical appliances, particular requirements for gas burning appliances
Gas lines
When installing the gas lines and trains, the general directives and guidelines, as well as the following national regulations, must be observed: CH: - G1 instruction text from SSIGE
- EKAS form no. 1942, liquefied gas directive, part 2
- Cantonal authority guidelines
(e.g. directives for the pilot valve)
DE: - DVGW-TVR/TRGI
Installation location
The burner must not be used in rooms with aggressive vapours (e.g. hair spray, tetrachloroethylene, carbon tetrachloride), high levels of dust or high air humidity (e.g. laundry rooms). If no connection to an air exhaust system is provided for the air supply, there must be a supply air inlet measuring: DE: up to 50 kW: 150 cm
2
per additional kW: : + 2.0 cm
2
CH: QF [kW] x 6= ...cm2; but at least
200cm2. Variations may arise as a result of local regulations.
10/2010 - Art. Nr. 4200 1030 6900A 3
Overview
Burner description
2 Power controller (option) 5 Housing 6 Gas inlet flange 8 Burner flame tube 10 Integrated electrical cabinet 11 Burner fixing flange 13 Air intake box 14 Mechanical compound 19 Hoisting eyes F6 Air pressure switch M1 Blower motor Y10 Actuator for air and gas dampers
e
10/2010 - Art. Nr. 4200 1030 6900A4
Gas start-up mode
As soon as the furnace system is required to supply heat, the burner control circuit will close and the program flow started. When the program has come to its end, the burner will be turned on.
An automatic test is made for the tightness of the gas valves prior to each burner start.
The air damper is in its closed position when the burner is out of operation.
The electric actuator will open the closed air damper to its full-load position so that the burner will ventilate the furnace and the exhaust hoods with the specified air rate. Shortly after the pre-ventilation process has been started the lack-of-air cut-out must change over to operating position within a certain time, i.e. the minimum air pressure setting must be reached and maintained until the burner is turned off. At the end of the specified pre-ventilation time the air damper will be moved into its partial-load position in a linked control concept with the gas damper.
The ignition transformer is activated.
After the pre-ignition time, the main gas valves are open and the gas comes out from injectors where it is mixed in the combustion head with air coming from the fan. The ignition of the gas air mixture is done directly by a high voltage spark on a gas injector. During the safety time, a stable flame is formed and is monitored by an ionisation sensor. The ignition is stopped before the end of the safety time and the burner operates at its minimum power. The start-up programme is completed.
Gas operating mode
After the flame has developed the load regulator will be enabled which brings the burner into its operating position. The load regulator will now control the burner automatically between its partial­load and full-load stages. Depending on the heat demand, the electric actuator of the compound control system will be fed with the OPEN or CLOSE command via the regulator and thus increase or decrease the gas and air flow rates. This compound control system will vary the positions of the gas control valve and air damper and thus regulate the gas flow rate in a linked concept with the air flow rate. The burner can either be controlled by a 2-stage sliding or, if a respective controller is provided, a stepless control concept. The stepless control will allow
the burner to be operated at any desired stage between its partial-load and full­load positions. The burner will always be turned off out of its partial-load position. The air damper will be closed when the burner is out of operation and will thus prevent cold air flowing through the burner chamber, heat exchanger and chimney. The interior cooling losses will thus be greatly minimized.
Attention:
If there are shut-off dampers in the flue gas tract they must be complete open. Otherwise there will be a high danger of low-speed detonation or explosion! The open-position of the shut-off damper can be assured by the integration of the opening contact of the shut-off damper in the safety chain of the heat generator.
General safety functions
In case a flame does not develop when starting the burner (fuel release), the burner controller will shut off at the end of the safety period (shut-off on trouble). A shut-off on trouble will also occur in the case of flame failure during operation, air flow failure during the pre­ventilation phase and pressure failure during the whole period of burner operation. Any failure of the flame signal at the end of the safety period and a flame signal during the pre-ventilation phase (external light control) will result in a shut-off on trouble with the automatic furnace controller being locked.
The trouble is indicated by the trouble signal lamp lighting up. The automatic furnace controller can be unlocked immediately after a shut-off on trouble by pressing the unlocking key. The program unit will return to its starting position and proceed with the restart of the burner.
A voltage failure will result in a regular shut-off of the burner. After voltage recovery, the burner can be automatically restarted unless another interlock is active, e.g. one caused by the safety circuit. In any case, the fuel oil supply will be immediately stopped upon occurrence of a trouble.
The control unit will stop at the same time causing also the trouble location indicator to stop. The symbols will indicate the kind of trouble.
Operation
Gas start-up mode Gas operating mode General safety functions
Full load
Operating position
Load regulator
Release
Partial load
Ignition/Gas valves
Gas control: 2-stage sliding Stepless
ON OFF
ON OFF
Full load
Operating position
Load regulator
Release
Start load
Partial load
Ignition/Gas valves
10/2010 - Art. Nr. 4200 1030 6900A 5
Operation
Fuel-air compound control Gas valves and instruments group
e
Fuel-air compound control
This compound control system with precision-adjustment capability has been designed to allow the fuel and air flow rates to be steadily varied in sliding mode for an adjustment of the fuel-air ratio over the whole control range. In the two-stage sliding control concept the partial-load and full-load positions are within the control range. Depending on the heat demand these two load points will be selected in sliding mode. A larger fuel feed will not be suddenly turned on or off. In the stepless control mode the load will be controlled at any point within the control range depending on the heat demand. The two-stage sliding and the stepless control concepts are different only in the control systems used with the burners. The same mode of operation is used for both versions.
Mechanical compound control:
The compound control system will be operated by the steplessly reversible electric drive unit in dependence of the heat requirement. The air damper and the gas damper will be controlled by the same system.
To ensure an optimum air-to-fuel adjustment over the full control range, it will be possible to vary the position of the air damper by means of stud bolts incorporated in the compound controller.
Gas valves and instruments group
The gas valves and instruments group used with the furnace will be selected according to the specific requirements to be met by a burner system.
The following factors must be taken into account:
• burner output
• furnace back pressure
• gas pressure loss of the burner head
• gas pressure losses of the gas valves and instruments group
The total gas pressure loss must always be smaller than the available gas flow pressure. NOTE: Use should only be made of gas valves and instruments that have been approved in accordance with the burner test specifications.
100 Burner 120 Air damper 141 Ball valve 142 Gas filter
143 Pressure gauge with stop valve
147 Test burner with stop valve
(optional) 150 Gas damper 153 Main gas solenoid valve 154 Safety solenoid valve 310 Blower 311 Minimum air pressure switch 313 Minimum gas pressure switch 314 Leak test 349 Actuator
10/2010 - Art. Nr. 4200 1030 6900A6
O peration
Autom atic furnace contro ller LFL 1.../LG K ...
The LFL 1…/LGK... type controller is designed to control and monitor burners working according to a stepwise or modulating principle. A detailed functional description with technical data and project planning information with respect to the automatic combustion controllers can be found in the annex and in the documents:
LFL 1...-7451/LGK...
Functional diagram LFL 1.../LGK...
A = Starting type interval A-B= Flame development interval B = Burner has reached operating
position
B-C= Burner operation
(heat generation) C-D= regular shut-off t1 Pre-ventilating time t2 Safety time t3 Pre-ignition time t4 Fuel valve enable t5 Load regulator enable t11 „OPEN“ run time of air damper t12 „CLOSE“ run time of air damper
R = Temperature or pressure
controller M = Fan motor Z = Ignition transformer BV= Fuel valve(s)
LR= Load regulator LK= Air damper RV= Steadily adjustable fuel valve FS= Signal of flame
10/2010 - Art. Nr. 4200 1030 6900A 7
O peration
G as valve VG D with SKP actuator G as valve M BC-SE
Technical data
Input pressure 360 mbar max. Ambient temperature -15 to +50°C Voltage 230 V/ 50 Hz max. Protection rating IP 54
1 Gas ball valve (option) 2 Filter (under the cover) 3 Gas manometer with push button
(upstream) (option)
4 Test burner with push button
(option) 5 Actuator SKP 15 6 Actuator SKP 25 7 Gas main valve VGD.. 8 Gas manometer with push button
(downstream) (option) 9 Gas tightness control unit
e
Technical data
Input pressure 360 mbar max. Ambient temperature -15 to +50°C Voltage 230 V/ 50 Hz max. Absorbed output (in operation)
250 W max
Protection rating IP 54
1 Gas ball valve (option) 2 Filter (under the cover) 3 Gas manometer with push button
(upstream) (option)
4 Test burner with push button
(option)
5 Compact gas train (safety valve +
main valve)
8 Gas manometer with push button
(downstream) (option)
9 Gas tightness control unit
10/2010 - Art. Nr. 4200 1030 6900A8
Assembly
Boiler lining for G-R burner Burner assembly
Boiler lining
The burner lining must be installed right­angled to the burner tube. Possible trimming work (bevelling, rounding) as required for reverse boilers, for example, should be done at a diameter not below 70% of the combustion chamber diameter. The space between the flame pipe of the burner and the boiler lining should be lined with heat resistant material, such as Cerafelt.
This space is not allowed to be lined with brickwork
Note for reverse flow boilers!
For reverse flow boilers the dimension T1 is only a recommended value. Depending on type of boiler the burner head must stand at least 50 mm ahead the opening for flue gas turning back.
D = see dimensioned drawings D1 = see dimensioned drawings DF = combustion chamber diameter T1 > 80 mm T = depth of boiler lining (option: extensions: see technical data)
Burner assembly
• Take the burner tube (delivered in a
separate box).
• Fit it on burner body.
• Remove cover.
• Tighten the 2 fixing screws S1.
• Lift the burner, using the 2 hoisting
eyes 19 (see page 3) and fasten to the boiler.
• Tighten the 4 fixing screws S2.
• Place cover back on.
10/2010 - Art. Nr. 4200 1030 6900A 9
Assembly
Gas connection
Gas connection
The gas lines and valves and instruments group should be installed and taken into operation in accordance with the applicable engineering standards and regulations.
The connection between the gas distribution network and the gas ramp must be done by authorised persons.
The section of the pipings must be calculated so that the loss of load doesn’t exceed 5% of the distribution pressure.
A quarter turn manual valve (not supplied) must be provided for upstream of the gas ramp and the filter.
The filter must be installed on a horizontal nozzle with the cover in the vertical position to enable cleaning.
The threaded unions used must be in conformity with present standards (tapered male thread, straight female thread with sealing provided in the thread).
Provide for sufficient space to access the gas pressure switch adjustment.
Gas properties
Prior to any installation work make sure to obtain the following data from the gas supply company:
1. type of gas
2. calorific value H
un
=kW/m³ (kJ/m³)
3. maximum CO2 content of exhaust gas
4. gas connection pressure and rest pressure
Type of gas test
Prior to mounting the burner to the gas feed line check the available type of gas and burner type against the data given on the burner nameplate (attached to burner). Be sure the description of the burner and the type of gas are the same as indicated on the nameplate.
Gas connection pressure
A minimum connection pressure must be available upstream of the burner gas valve to ensure the proper functioning of the burner. For the installation of the valves and instruments group take care to observe the mounting instructions supplied by their manufacturers (these are packed with the equipment). The gas line installed to the burner must be dimensioned in accordance with the throughput rate and the available pressure.
For selecting the nominal bore „DN“ of the gas valves and instruments group
care should be taken to observe the flue resistance of the boiler and the gas pressure loss of the burner and valves and instruments group.
Caution!
The absence of impurities and foreign bodies must be checked before installation and commissioning of the gas ramp, the lever valves and unions.
Gas valves and instruments group
The gas valves and instruments group can be connected directly to the gas feed line. Take care to observe the
correct order of installation and direction of flow (arrow on housing).
Check the valves and instruments and connection pieces for absence of dirt particles and foreign matter before installation and initial operation. To
provide effective conditions for start­up make sure the distance between the burner and the gas stop valve is as short as possible.
Leak test
The gas line upstream of the burner gas valves and instruments group must be installed in accordance with the applicable regulations, checked for absence of leaks, vented and certified accordingly by the gas installation company. The screwed unions and flanged joints must be checked for proper tightness (by making a pressure test). The leak test must be made under pressure using approved foaming agents which do not cause corrosion. For steam boiler furnaces the result of the leak test must be duly certified.
Venting Caution! Prior to taking the burner into
operation or after any repair work make sure to vent the complete gas feed line and the gas valves and instruments group into the open atmosphere (e.g. by means of a hose) taking care to avoid any hazards.
In no case should the gas line be vented into the heating or furnace chambers. Make use of a test burner to
check the gas-carrying spaces are free from an inflammable gas mixture.
Support
The valves and instruments group must be supported with a telescopic jacking member or similar during and after installation (e.g. on filter and valve).
Joint
It is recommended to provide an easyto­disconnect joint (with planar sealing faces) to facilitate repair work on the boiler (furnace) and allow the boiler door to be swivelled out if required.
e
Loading...
+ 19 hidden pages