elco ES08.2800 G/F-VT, ES08.3700 G/F-VT, ES08.4000 G/F-VT, ES08.5000 G/F-VT Operating Instructions Manual

04/2009 - Art. Nr. 4200 1018 1100A
ES08.2800 G/F-VT ES08.3700 G/F-VT ES08.4000 G/F-VT ES08.5000 G/F-VT
Operating instructions
For the authorized specialist
Gas burners ........................................... 2-19
Betriebsanleitung
Für die autorisierte Fachkraft
Инструкция по эксплуатации
Предназначено для квалифицированных специалистов по установке
Газовая горелка ................................. 38-55
fr, it, es ................................. 4200 1018 1000
............................................. 4200 1018 0900
en
de
ru
04/2009 - Art. Nr. 4200 1018 1100A2
General information
Table of contents Guarantee, safety Main statutory instruments
Contents
General information
Guarantee, safety .............................. 2
Main statutory instruments................. 2
Overview legend.................................3
Packaging...........................................4
Technical data
See technical data N° 420010180900
Installation
Assembly............................................5
Gas connection ..................................6
Electrical connection .......................... 6
Start-up
Preliminary check-up.......................... 7
Settings .....................................7 to 13
Program of the control
and safety unit.........................14 to 15
Control panel TC ..............................16
Settings, safety checks.....................17
Firing ................................................17
Maintenance....................................18
Troubleshooting ............................. 19
Guarantee
Installation and start up must be carried out in accordance with currently accepted practices by a qualified technician; current regulations as well as the instructions that follow must be complied with. The manufacturer will decline all responsibility in the event of failure to comply fully and in every respect with any of the relevant requirements. Refer also to:
- the certificate of guarantee attached to the burner;
- the general terms of sales.
Safety
The burner is designed to be installed on a generator connected to exhaust pipes used for products of combustion in serviceable condition. It should be used in areas where an adequate supply of fresh air is available for correct combustion and where any waste products can be properly evacuated. The size and design of the flue must be appropriate to the fuel in accordance with current regulations and standards. Power supply 230 VAC % 50Hz
±1%
the control and safety unit as well as to the cut-off devices used must include an earthed neutral wire. In addition, the neutral conductor
must have the same electrical potential as the earth conductor.
Failing that, power supply to the burner must include an isolating transformer and the appropriate protection (30 mA circuit breaker and fuse). In order that the burner operates
correctly, please respect the polarity of the conductors when connecting the 7P connector.
The burner must be able to be isolated from the system by means of a multi pole switch complying with the standards in force. Operating personnel should act with extreme caution in all cases and more especially avoid any direct contact with areas that are not heat-insulated and electrical circuits. Water should not be splashed on to the burner's electrical components. In the event of flooding, fire, fuel leakage or any other dangerous situation (smells, suspicious noises, etc.), stop the burner, cut off the main power supply and the fuel supply and call in an approved specialist. The use of chlorinated solvents to clean the burner is prohibited. It is compulsory for all furnaces and accessories, flues and connection pieces to be maintained, cleaned and swept at least once a year and prior to burner start up. Consult the applicable regulations in force.
Use a purpose-designed foam to test the external tightness of valve assembly connections, including the filter.
Main statutory instruments “FR”
Dwellings :
- French Order dated 2nd August 1977 and later modifying / supplementary orders: Technical and safety regulations governing combustible gas and liquified hydrocarbon installations located inside dwellings and their outbuildings.
- DTU Standard P 45-204 : Gas installations (formerly DTU n° 61-1
- Gas installations - April 1982 + later addendums).
- DTU Standard 65.4 - Boiler house technical provisions.
- French NF Standard C15-100 + Low voltage electrical installation regulations.
- French Departmental health regulations.
Public Buildings :
- Public building fire and panic prevention safety regulations.
General provisions :
- GZ sections (combustible gas and liquified hydrocarbons);
- CH sections (heating, ventilation, cooling, air conditioning and steam and domestic hot water production);
Provisions specific to each type of public building.
Outside “FR”
Refer to local regulations.
+
10
- 15
04/2009 - Art. Nr. 4200 1018 1100A 3
General information
Overwiew Legend
Legend
B Valve assembly connecting flange C Gas supply line nut/bolt E-F-D Mobile and fixed shafts and safety
screw F6 Air pressure switch M1 Fan motor T Nozzle line T2 Ignition transformer Y10 Servomotor 1 Blast-tube 2 Space flange 5 Combustion head identification
plate 8 Case (burner body) 9 Burner body ID plate 11 Control unit
Control panel TC 14 Boiler sight glass ventilation air
pressure take-off
119.2 pF combustion chamber take-off
119.3 pL Pressure take-off L
en
04/2009 - Art. Nr. 4200 1018 1100A4
General information
Packaging
Packaging
The burner is delivered on two pallets, in three parcels, weighing on average 305 to 370 kg, depending on the model. The burner of the body with :
- the built-in or detached electrical cabinet. In those circumstances, a connecting case is fitted on the burner with the following inside :
- the operating instructions,
- the wiring and hydraulic diagrams of
the burner,
- the boiler house plate,
- the guarantee document,
The combustion head with :
- the burner front face seal, one bag of bolts, two hinge pins.
The gas train with :
- a collector valve set,
- a bag o bolts, a PG21 support, rubber gaskets, two tubes pF, one pipe pL, a drawing, and a preassembled outside filter.
04/2009 - Art. Nr. 4200 1018 1100A 5
Installation
Assembly
Boiler face
• Prepare face following the enclosed space requirement diagram.
• If required, insert face counter-plate (optional)
• Fill in space 1 with recommended heat-resistant material or material supplied by the boiler manufacturer.
Chamber pressure take- off pF should
never be choked.
Combustion head
• Position combustion head, so that gas train is horizontally connected on the right.
• The other assembly positions are not allowed.
• Fix and secure combustion head with its gasket on boiler face.
• Check subsequently for leaks.
Gas train
• Check presence and position of gasket on the flange of gas train B.
• Install support PG 21 (drawing)
• When fitting gas train, valve coils must be in high vertical position.
Important
When using a left-mounted VGD gas train, the SKP75 regulator should pivot by 180°. To that end :
• Remove regulator SKP75.
• Remove connector (3P + T) on the side of the regulator, and put it back together on the opposite side.
Seal off the former position of the
connector.
• Reassemble the regulator after it has pivoted by a half turn (180°).
Burner Body
• Hook burner body to combustion head using fixed pin F located on the opposite side of the gas train.
• Connect the ignition cables on both transformers.
• Close the burner body with removable pin E.
• Fix safety screw D.
Connecting the gas pressure take-offs
• Connect coupling pF of the valve to the coupling labelled pF on the combustion head with two reversible preformed tubes (right - left) ,which are connected up by a coupling (see drawing).
• Crimp the rings on the tubes.
• Connect the coupling labelled pL to the coupling pL of the valve.
• Tighten nut by hand.
• Check subsequently for leaks.
Fitting the leaks controller VPS 504 S02
• Remove the two screws pa and pe on valve MBVEF, and the two screws 1 and 2 on valve VGD.
• Make sure the two O-rings are available on the VPS.
• Fasten the VPS with the 4 self-forming screws
• Connect the cord of plug 7P according to the electrical diagram.
• Connect plug 7P to the VPS.
• Check subsequently for leaks
Case of valve VGD20 : proceed as indicated at the beginning of the earlier paragraph, then :
• Fit the tubes and the terminal block supplied.
• Fasten the VPS on the terminal block using the 4 self-forming screws supplied.
• Proceed afterwards as in earlier paragraph.
en
04/2009 - Art. Nr. 4200 1018 1100A6
Installation
Gas and electrical connections
Gas connection
Connecting the gas distribution system to the gas train must be carried out by a skilled technician. The pipe section must be calculated, so that load losses do not exceed 5% of distribution pressure. The external filter (ES08.2800) must be fitted horizontally with a clean tube and the cover placed in a vertical position to allow for maintenance and to prevent dust being carried along downstream of the filter upon disassembly.
Any other type of assembly is prohibited.
The ball valve (not supplied) must be mounted upstream and as close as possible to the external filter or to the valve (pocket filter). Threaded couplings used should comply with current standards: tapered external thread, parallel internal thread, with tightness secured in the thread. Enough space should be provided for access to the setting of the gas pressure switch. Piping must be drained upstream of the valve. Connections carried out in sit must be tested for leaks using foam designed for that purpose.
No leakage should be detected.
Electrical connection
Electrical fittings and connections should comply with the current standards.
Earth must be connected and tested.
See electrical diagram when connecting the burner and the regulator. The burner is supplied for a three-phase electrical voltage 400V - 50Hz with neutral and earth. The ventilation motor starts up automatically. A variable frequency regulator can be fitted as an extra option. The three-phase operation 230V - 50Hz requires : changing the coupling of the motors and of the thermal relays of the contactors (ES08.4000 and 5000), and using a 630 VA insulation transformer on the control circuit (not supplied). For other voltages and frequencies, please contact us.
Electrical connections
1) burner
- Built-in electrical cabinet
• Use stuffing boxes in order to secure the required level of protection.
All the links, power and control, are connected to the terminal block of the cabinet. Provide cables in sufficient length to secure the gyration of the burner body according to the assembly.
• Check and adjust the calibre of the contractors and thermal relays and the wires section according to the characteristics of the motor and of the available voltage.
Wiring is not supplied.
- Detached electrical cabinet:
That cabinet can be installed:
- either against a wall
- or on a floor-mounted sub-frame.
All the links, power and control are connected between the cabinet terminal block and the terminal block of the coupling case on the burner body. The other assembly conditions are similar to those of the built-in cabinet
2) of the gas train
• Connect the plugs pending to the valve:
- either on the control cabinet,
- or on the coupling case on the
burner body.
04/2009 - Art. Nr. 4200 1018 1100A 7
Start up
Preliminary check-up and leakage tests Adjusting air pressure switch
Burner start up simultaneously involves starting up the installation by the fitter or his representative; only they can guarantee compliance of the boiler house with currently accepted practices and the regulations in force. The fitter must first be in possession of a "certificate of gas conformity" (fuel) issued by either the approved body or the distributor and also have leak-tested and drained the pipework upstream from the quarter-turn hand-operated valve.
Preliminary check-up
• Check the following:
- rated available voltage and electric frequency and compare them with the value showing on the identification plate,
- polarity between phase and neutral,
- connection of the previously tested earth wire,
- lack of potential between neutral and earth,
- motors direction of rotation,
- thermal relays only in manual (H) position with intensity adjustment.
• Cut off the power supply
• Make sure power is off
• Close fuel valves
• Read service instructions from boiler and regulator manufacturers
• Check that :
- boiler is full of pressurized water
- circulator(s) is (are) working
- mixing valve(s) is (are) open
- combustible air supply to the boiler
and combustion products exhaust pipe are actually operating and are compatible with the rated capacity of burner and fuels
- draught regulator is working properly
on the exhaust pipe
- protective fuses outside burner are
available, calibrated and adjusted
- boiler regulator circuit is adjusted.
Gas pressure switch setting
• Remove the transparent cover.
The unit includes a index and a graduated mobile disk.
• Provisionally set the pressure switch at the minimum value shown on the graduated disk.
Leakage test
• Connect a manometer on the pressure nipple upstream from the gas train.
• Open and close the ball valve
• Check supply pressure and its long­term stability
• Use a specially designed foam product to check tightness of gas train connections, including external filter.
No leakage should be detected.
• Drain when necessary pipework downstream from the ball valve
• Close drain valve, remove the manometer and close the pressure take-off.
en
04/2009 - Art. Nr. 4200 1018 1100A8
Start-up
Checking and adjustments Combustion implements and secondary air
Secondary air (dimension Y)
This is the amount of air flowing between the tubulators diameter and blast-tube. On delivery, dimension Y is set at 453 in KN and 753 in KL. However,
- this value can be adjusted according to the following :
- gas firing quality (shock, vibration, judder, time lag),
combustion quality for gas flows.
Setting It is performed when burner is shutdown, with removal of combustion implements, following the procedure outlined in the earlier section. By increasing dimension Y, secondary air reduces, the CO
2
increases and vice
versa.
• Loosen both screws from the turbulator support.
• Slide the turbulator support into the required direction.
• Measure dimension Y; tighten both screws.
• Adjust the diffuser according to the type of head and gas used following the enclosed plan.
• Reassemble the whole unit.
• Make sure the flat gasket is available and in position on the gas inlet line.
Natural gases -low NOx
Bold : factory settings
secondary air maxi
secondary air mini
KN Y=453 Y=478 KL Y=753 Y=778
Natural gases & propane
Bold : factory settings
secondary air maxi
secondary air mini
KN Y=453 Y=478 KL Y=753 Y=778
Checking and setting combustion
Burner is supplied already set for natural gas.
• Remove the safety screw D.
• Remove the movable pin E.
• Open the body of the burner.
• Disconnect the two ignition cables on the transformer and the ionization sensor cable.
• Unscrew the nut and the lateral screw C which immobilise the gas supply line.
• Withdraw the combustion components.
• Check the settings : of the ignition electrodes, the ionisation sensor, and of the diffusors according to the gas available and the accompanying diagrams.
• Check to ensure the presence and the correct positioning of the sheet gasket on the gas supply line.
• Re-assemble.
• Check :
- the tightness of the screw and the
nut C,
- subsequently for leaks.
04/2009 - Art. Nr. 4200 1018 1100A 9
Start-up
Adjustments Diffusors and injectors
"G-VT-type" head adjustment for Low NOx natural gas
Diffusors A:
- External slots fully closed
- Downstream injector pellet P1 with screw in position 4 for ES08.2800 and 5 for ES08.3700 to 5000.
Diffusors C:
- Upstream slot closed
- Downstream injector with screw in position G3 for ES08.2800 and G2 for ES08.3700 to 5000.
Ignition diffusor D:
- Upstream slot open
- Downstream injector with screw in position G2
Head F-VT adjustment for Low NOx propane gas
Diffusors A:
- Upstream slots open
- Downstream injector pellet P1 with screw in position 1
Diffusors C:
- Upstream slot closed
- Downstream injector with screw in position G2
Ignition diffusor D:
- Upstream slot open
- Downstream injector with screw in position G2
Natural gas Low NOx
G/F-VT
Propane gas Low NOx
G/F-VT
en
04/2009 - Art. Nr. 4200 1018 1100A10
Start up
Description, settings Combustion air
Servomotor Y10
1 Connection terminal board 2 Cam setting key 3 Seven adjustable graduated cams 4 Motor disengaging lever 5 No adjustable graduated cylinder
for servomotor position
6 Graduated cylinder index
SQM 10 16
Cam functions
Cam Function I Nominal flow-rate II Stop/0° III Firing air flow-rate IV Free 0° V Cam V gives minimum regulation
info; must be set between values
of cam I and VI VI Set minimum air flow-rate VII Simultaneous switch-on of
nominal flow indicator and hour
counter (only for operation hours
below nominal flow rate)
• Set a few degrees below the regulation flow-rate value of Cam I.
Cam VI controls minimum automatic flow-rate following ignition. If not requested, the flow remains unchanged. The time-delay unit K6 in the control cabinet must be set at 15s.
Setting
• Remove cover.
• Check cam drum reset.
• Preset the cams according to boiler capacity and the values shown in the table below.
To do this:
• Adjust the cam either by hand or with the key going along with the servomotor. The angular position is obtained in relation to each cam index.
Burner
power
kW
2100 33 2850 55 2250 50
3800 80 2400 55 4100 80 2800 55 4600 80
Air setting in °
i gnition nominal
cam III cam I
ES08.
2800
15
ES08.
3700
ES08.
4000
ES08.
5000
04/2009 - Art. Nr. 4200 1018 1100A 11
Start up
Description and adjustment MB-VEF gas valve
1 Pressure switch electrical
connection (DIN 43650)
2 Solenoid electrical connection
(DIN 43650) 3 Pressure switch 4 Intake flange 5 Pressure take-off G 1/8 before
possible filter on either side 6 Filter under the cover 7 Identification plate 8 Air pressure pL G 1/8 connection 9 V ratio adjusting screw 10 Pressure take-off pe G 1/8 both
sides 11 Gas pressure take-off pBr
M4 (V2) 12 Adjusting screw for correction of
zero point N 13 Connection G 1/8 for combustion
chamber pressure pF 14 Connection G 1/8 for gas pressure
pBr
15 Outlet flange 16 Pressure pa take-off after V1 both
side 17 On indicator V1, V2 (optional) 18 pBr - pL - pF pressure take-off
tubes
MB VEF valve
MB VEF valve…is a compact assembly including the following : A built-in or pocket filter, adjustable pressure switch, non-adjustable quick­acting safety valve, proportional regulator-controlled main valve which can be adjusted on opening (V and N). It ensures a constant gas flow/air flow ratio and is quick-acting. The regulator also takes into account combustion chamber pF pressure or atmospheric pressure. The valve is delivered preset according to table here below.
Air pressure switch setting
• Remove the transparent cover.
The unit includes a index and a graduated mobile disk.
• Provisionally set the pressure switch at
the minimum value shown on the graduated disk.
Regulator setting
All settings are carried out with the burner working:
• Use 2,5mm hex key to turn the 2
screws.
- Screw V gives the gas/air ratio, graduated 0,75 to 3,0.
- Screw N is used to adjust air excess, graduated - 2 to + 2.
ES08.2800 G/F-VT
Gas
P
VEF 412 42
0
V
3
N
0
V
3
N
0
V
3
N
0
ES08.3700 G/F-VT
Gas
P
VEF 412 42
0
V
3
N
0
V
3
N
0
V
3
N
0
ES08.4000/5000 G/F-VT
Gas
P
VEF 412 42
0
V
3
N
0
V
3
N
0
G20 1 50
G20 3 00
G25 3 00
G20 1 50
G20 3 00
G25 3 00
G20 3 00
G25 3 00
en
04/2009 - Art. Nr. 4200 1018 1100A12
Start-up
Description and settings VGD gas valve SKP75 regulator
1 Pressure switch electrical
connection (DIN 43650)
2 Solenoid electrical connection
(DIN 43650) 3 Pressure switch 4 Intake flange 5 Pressure take-off G 1/8 before the
filter 6 External filter DN65 7 Identification plate 8 Air pressure pL G 1/8 connection 9 Adjusting screw R of gas flow/air
flow ratio 12 Adjusting screw D for correcting
zero point 13 Connection G 1/8 for combustion
chamber pressure pF 14 Connection G 1/8 for gas
pressure pBr 15 Outlet flange 16 pBr - pL - pF pressure take-off
pipes
Setting gas pressure switch
• Remove transparent cover.
Unit includes a | index and a movable graduated disk.
• Provisionally set the pressure
switch at the minimum value shown on the graduated disk.
Gas valve opening indicator
R ratio indicator
D value indicator
The VGD valve associated with SKP75 regulator ensures a constant gas flow/air flow ratio and is quick­acting. The regulator also takes into account combustion chamber pF pressure. The valve is delivered preset according to table here below.
ES08.2800 G/F-VT
Gas P 40.06
5
40.08
0
(Scr. R)1 2 (Scr.
D
)2 1,4
ES08.3700 G/F-VT
Gas P 40.06
5
40.08
0
(Scr. R)2 (Scr.
D
)1,4
(Scr.
R
)1
(Scr.
D
)2
ES08.4000/5000 G/F-VT
Gas P 40.06
5
40.08
0
(Scr. R)1 (Scr.
D
)2
G20 150
G20
40
150
VGD
VGD
G20 20 - 40
VGD
04/2009 - Art. Nr. 4200 1018 1100A 13
Start-up
Description of adjustments Gas valve / leakage controller
Leakage controller VPS 504 S02
Optional for ES08.2800 Operating principle : Prior to each start-up of burner, the control unit shall check subsequently for leaks between safety and main valves by increasing the distribution pressure. Electrically, the leakage controller gets connected serially between the thermostatic circuit and the control and safety unit of the burner.
Installation : Directly on valve.
Program development : At shutdown, safety and main valves are closed. At thermostatic shutdown, the leakage controller is powered up and the booster increases distribution pressure by 20mbar. After no more than 30 seconds of operation :
- If leakage test is validated, the yellow
light comes on and power is released to feed the control and safety unit, which starts its cycle.
- If leakage test is not validated, the red
light comes on and the control and safety unit is not powered up.
- Control cycles need to be restarted
manually. If fault persists, valve should be changed.
Adjustment : The leakage controller requires no on­site adjustment. Operating test : While leakage controller is working :
• Open pressure take-off pa. The
leakage so generated prevents the super pressure from building up, and the safety unit locks on after 30 seconds.
• Close pressure take-off pa.
• Release controller safety by pressing
the red indicator light. The leakage controller restarts and, after 30 seconds, the yellow indicator lights up and powers up the control and safety unit, which begins its cycle.
1 Wieland 7P socket 3 Filter element 4 O-ring Ø 10.5 x 2.25 5 Fuse Y 6.3 250V Ø 5 x 20 6 Yellow indicator On :
Leakage test validated
7 Red indicator On :
Leakage test not validated,
manual release 8 Spare fuses magazine 9 pa (p2) pressure take- off Ø 9.
Test pressure : pe + 20mbar 10 Pressure take- off : pe (p1) Ø 9.
Inlet pressure (distribution)
en
04/2009 - Art. Nr. 4200 1018 1100A14
Start up
LFL 1.333 Control and safety unit
Required input signals
Output signals
Reset Trouble Pressure switch Limiter Burner motor Ignition transfo. Oil valve Regulator Servo motor Flame Reset
t1 Pre ventilation time with open air flap
t2 Safety time
t2’ Safety time or 1st safety time for burner with driver
t3 Short pre-ignition time (transformer terminal 16)
t3’ Long pre-ignition time (transformer terminal 15)
t4 Interval between voltage at terminal 18 (t2 start) and 19 (BV1-BV2)
t4’ Interval between t2’ start and 19 (BV2)
t5 Interval between voltage at terminal 19 and 20 (BV-Regul.)
t6 Post-ventilation time (with M2)
t7 Interval between start order and voltage in 7
t10 Interval between start and air pressure monitoring without flap movement time
t11 OPEN position air flap movement time
t12 MINI position air flap movement time
t13 Accepted post combustion time
t16 Interval until air flap opening order.
04/2009 - Art. Nr. 4200 1018 1100A 15
Start-up
LFL 1.333 control unit program
LFL 1.333 control unit program
t1 : Pre ventilation time 30s t2 : 1st safety time 3s t3 : Pre-ignition time 6s
- Safety time following
flame disappearance < 1s
Safety unit operation
The control and safety unit LAL 2.25 is designed for intermittent service, (limiting it to twenty-four hours of continued use). For convenience sake, the function diagram does not include all electrical components. It is assumed that :
- Power supply is compliant
- Pressure switches and servomotor
cams have been preset correctly.
Commands from control and safety unit Required input signals
Terminal numbers are those shown on the control and safety unit base. Each unit program sequence is shown by a visible symbol on the rotating disk, near reset button.
Program operating sequences :
Motor switched on (terminal 6)
when :
- main voltage is applied to terminal 1,
- air flap is closed : voltage at terminal 11 is applied to terminal 8,
- air pressure switch is off : voltage at terminal 12 is applied to terminal 4,
- limit and safety thermostats and min. gas pressure switch are off: voltage at terminal 4 is applied to terminal 5.
Servomotor control (cam I) is wide
open (terminal 9) and opening confirmed (terminal 8) : start of pre ventilation.
Start of permanent air pressure
monitoring by air pressure switch and confirmation at terminal 14. Circuit broken between terminals 4 and 13.
Servomotor control (cam III) in
ignition position (terminal 10) and position confirmed (terminal 8).
Start of pre-ignition (terminal 16)
Simultaneous opening of safety
valve and main valve (terminal 18) : start of safety time.
Start of continuous monitoring of flame presence.
Ignition transformer off, shortly
followed by end of safety time.
Power regulation enable
(terminal 20) :
Burner stoppage via limit
thermostat cutoff, then servomotor control off (cam II).
Important : in continual functioning, a thermostatic cut-out is obligatory after twenty-four hours.
en
04/2009 - Art. Nr. 4200 1018 1100A16
Start-up
Description of functions Control panel TC
TC
Description of TC functions (Control Panel)
A2 Standardized 48x48 or
48x96mm power regulator positions (option)
B10 Measuring bridge [µA DC],
ionization current
F10 Control panel fuse TC
Green indicators
H4 Ignition load H4.1 Safety valve H4.2 Main valve H5 Minimum control flow H5.1 Nominal flow H10 Control Panel (TC) energized H15 Transformer P4 Hourly totalizer counter P5 Nominal flow hourly counter
Three position switch :
S1 General switch of TC
0 Off 1& Local mode 1> Remote control mode
S2 Choice of power setting
' Manual mode with S3 Auto Automatic mode with
S1&
S3 Pulse with S2'
+/- Power increase/decrease
SA1 The control unit displays :
- the program
- faults : red indicator illuminated and reset button
10 Two screws to be removed for
access to the control unit and to option positions
11 On the underside of the control
panel (TC), remove two screws 10 and switch to DIN 35mm rail and terminals for options
21 Rating plate 23 Movable plate for the cable
glands
Electrical cabinet on burner
The electrical cabinet holds all the required components for the operation of the device. The access door, which can be locked, is fitted with a window displaying the control panel TC, signals and, inside, a magazine containing the literature. In the lower part, there is a removable plate with the various stuffing boxes. Thanks to such cabinet with easy access, it is possible to install various options :
- A built-in power regulator in a standardized space requirement of 48 x 48 or 48 x 96 mm.
- Relays for data transmission to be fitted on a 35 mm DIN rail ,in abeyance under the control panel (remove two screws 10 and tip out).
Coupling case on burner
Option for cabinet outside burner B10 Measuring bridge [µ A DC]
cell current
24 Link terminals between burner
and electrical control cabinet
04/2009 - Art. Nr. 4200 1018 1100A 17
Start up
Working cycle test Firing Safety unit settings and checks
Cycle functioning test
• Open and then shut the quarter-turn manual fuel valve.
• Charge the burner.
• In the TC of the electric control box select the manual operation mode
S1& - S2'.
• Close the thermostatic circuit.
The leak tightness test device VPS 504 S02 is charged. After 30s if the test is validated ; the yellow light will shine. The control and safety unit is supplied with a voltage; the red light of the unit will shine.
• Reset the control and safety unit and check that it is working correctly.
The program should function in the following way :
- air flap totally open,
- initial blower time 30s,
- return to ignition position,
- ignition of electrodes for 6s,
- opening of the valves,
- closing of the valves after a maximum of 3s after they were opened,
- the burner will stop functioning due to a lack of gas pressure or due to resetting of the control and safety unit due to the disappearance of the flame.
In case of doubt, perform the test previously described.
It is only after this very important program test phase that the burner can be fired.
Firing
Warning :
Firing should only take place when all the conditions set out in the previous chapters have been adhered to.
• Connect a microammeter scale (0­100µA DC), instead of the measuring bridge located on the TC.
• Open the quarter-turn manual valve of the fuel.
• Close the thermostatic circuit.
The leak tester is charged. At the end of the test (30s), the unit is charged.
• Reset the control and safety unit.
The burner will be working.
- Check :
- the combustion process once the
flame has appeared,
- the overall leak tightness of the gas
train.
There should not be any leakage.
• Read the current of ionization (a value between 20 and 80µA).
• Measure the gas flow shown on the counter.
• Raise the power to its nominal output by activating the switch intermittently S3+.
• Test the combustion.
Observe the waste gas temperature recommended by the boiler manufacturer to obtain the required useful output. According to the combustion tests, adjust the burner while in operation to the nominal output on the screw V of the MB VEF valve (R for the Skp regulator).
• To increase the CO
2
rate, increase the ratio (decreasing the ratio will have the opposite effect).
• Read the current of ionization (a value between 20 and 80µA).
• Measure the gas output on the counter.
• Increase or reduce the power by increasing or reducing the value read from the graduated vessel of the cam I.
• Stop and then start the burner up again.
• Check the combustion process once the flame has appeared.
According to the measured values, adjust the burner while in operation on the screw N of the MB VEF valve (D for the SKP regulator).
• If necessary, adjust the cam value III for ignition and the cam VI for minimum control. The adjusting procedure is identical to that of the cam adjustment I.
• Increase the power back up to the nominal output and check the combustion. If the value has been changed by the action performed on the screw N (D for the SKP regulator); adjust the ratio V (R for the SKP regulator) as required.
• Optimize combustion results by adjusting :
- the setting of the secondary air (Y
dimension) following the procedure described in the chapter : “Setting combustion components and secondary air ”;
• Increase the Y dimension, the CO
2
rate rises and this process can occur inversely.
A modification made to the Y dimension can necessitate a correction of the air flow rate.
• Test the combustion.
Assess burner operation : on ignition, and when power is increased and decreased.
• Check, while the burner is functioning, and by using a foaming liquid product that is specially designed for this purpose, the leak tightness of the gas train connections.
There should not be any leakage.
• Test the safety devices.
Setting safety test devices
Gas pressure
• Set at the minimum distribution pressure.
Burner is working with ignition flow.
• Close the quarter-turn manual valve of the fuel slowly.
The burner should stop functioning owing to a lack of gas pressure.
• Re-open the quarter-turn manual valve.
The burner will start up again automatically. The pressure switch is set.
• Fix and screw on the housing.
Air pressure switch. Burner is working with ignition flow.
• Locate the switch’s cut-off point (lock).
• Multiply the value by 0.8 to obtain the setting point.
• Restart the burner.
• Progressively obstruct the aspirating port on the motor-driven blower unit.
• Check that the CO rate is still inferior to 10, 000ppm before resetting the control unit. If not, increase the air pressure switch setting and repeat the test.
Leak testing device tester VPS :
• Open pa on the device.
• Restart the burner.
After 30s the device is safe (red light illuminated).
• Close pa.
• Reset the leak tightness tester’s safety device by pressing the red indicator.
The test cycle is relaunched. The burner is operational.
• Check for leaks.
• Disconnect the two cables of the microammeter simultaneously.
The unit should reset itself immediately.
• Replace the measuring bridge, the housings.
• Disconnect the measurement devices.
• Re-close the pressure connectors.
• Reset the unit.
The burner will be working.
• Check :
- the absence of leaks between the
flange and the boiler front,
- opening of regulator (limiter and
safety) circuit,
- intensity of thermal relays of the
motor-driven blower unit according to the manufacturer’s instructions.
• Check combustion under actual operating conditions (doors closed, etc) and absence of leaks in the different systems.
• Note the results on the appropriate documents and communicate them to the dealer.
• Start-up automatic operation.
• Distribute the information required to operate the boiler.
• Place the boiler-room plate where it can be easily seen.
en
Loading...
+ 39 hidden pages