elco EK 4.100 L-ZA, EK 4.160 L-ZA Operating Instructions Manual

Page 1
09/2005 - Art. Nr. 13 019 533A
Operating instructions
for authorized experts
Light oil burners EK4...L-ZA
Designs: Basis CEN DIN
Page 2
09/2005 - Art. Nr. 13 019 533A
2
Survey
Table of contents General information
Table of contents Page
Survey Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Performance charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Burner functions Functional description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Functional diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Functional sequence LAL 1 . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Installation Mounting the burner to the heat generator . . . . . . . . . . . . . . . . . . . 7
Zero point adjustment (flame cup) . . . . . . . . . . . . . . . . . . . . . . . 7
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Oil connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Oil pressure regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Start-up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Adjustments Burner head setting dimensions . . . . . . . . . . . . . . . . . . . . . . . . 9
Air regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Service instructions Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
General information
The EK4...L-ZA series of ELCO light oil burners, featuring monobloc design and fully automatic two-stage operation, are suitable for the combustion of extra­light fuel oil. Design and performance of the burners comply with currently appli
­cable guidelines and regulations. Burner installation and start-up must be performed by a qualified expert who is responsible for the proper execution of these tasks. The burner complies with the standards
EN 267 DIN 4787
Observe the following standards to ensure safe, environmentally friendly and energy-saving operation of the burner.
DIN 4755
Oil-burning installations in heating systems.
DIN 4789
Connection of atomizing oil burners and blower gas burners to heat generators.
EN 60335-1
Safety of electrical appliances for domestic use
Site of installation
The burner must not be operated in rooms with aggressive fumes (e.g. hairspray, tetrachloroethylene, carbon tetrachloride), dust-laden air or high atmospheric humidity (e.g. laundry rooms).
ELCO rejects all warranty claims for damage resulting from one of the following reasons:
Improper use
Inexpert installation or mainten
­ance by the purchaser or third persons, including the installation of parts other than genuine parts supplied by the manufacturer.
Start-up
Initial start-up of the oil burning installa
­tion must be performed by the installer, manufacturer, or by another expert designated by them.
Delivery and operating instructions
At the time of delivery at the latest, the company installing the oil burner must supply the user with a set of Operating and Service Instructions. These should be kept in the room where the heat generator is installed. The address and telephone number of the nearest service representative must be entered in the Instructions.
Note for the user
The system should be serviced by an expert at least once a year. To ensure maintenance at regular intervals, we recommend you to conclude a service contract.
Scope of delivery
Each burner is delivered in a separate packing case. The following compo
-
nents are included in delivery:
Burner with burner head
Movable mounting flange and insula
-
ting base
Two oil tubes
Automatic burner control unit with plug-in socket
Document folder
Page 3
09/2005 - Art. Nr. 13 019 533A
3
Survey
Technical data Performance charts
Burner type EK 4.100 L-ZA EK 4.160 L-ZA
Technical data
Thermal output . . . . . . . . . . . . min. 360 kW 580 kW
Thermal output . . . . . . . . . . . . max. 1070 kW 1660 kW
Oil flow . . . . . . . . . . . . . . . . min. 31 kg/h 49 kg/h
Oil flow . . . . . . . . . . . . . . . . max. 90 kg/h 140 kg/h
Fuel oil . . . . . . . . . . . . . . . . Extra Light, DIN 51603 Extra Light, DIN 51603
Hydraulic system/standard . . . . . . 2-stage, 2 nozzles/CEN 2-stage, 2 nozzles/DIN
Air regulation . . . . . . . . . . . . . suction side Air cut-off valve Air cut-off valve
Air regulation . . . . . . . . . . . . . pressure side in burner head in burner head
Control ratio . . . . . . . . . . . . . max. 60/100% 60/100%
Voltage . . . . . . . . . . . . . . . . 230/400 V, 50/60 Hz 230/400 V, 50/60 Hz
Power consumption . . . . . . . . . 2.5 kW 2.5 kW
Weight approx. . . . . . . . . . . . . 83 kg 98 kg
Burner equipment
Electric motor 2800 min.–1 2.2 kW 2.2 kW Automatic burner control unit LAL 1.25 LAL 1.25 Flame monitor QRB 1 QRB 1 Ignition transformer ZM 20/10 ZM 20/10 Solenoid valves Nozzle control 2-way on pump 2-way Solenoid values 3-way 3-way Air damper drive hydraulic hydraulic Oil pressure pump A2L95D, 110 l/h at 18 bar RSA 125
Performance charts
The performance charts reflect the values approved during official homologation.
Determining the required thermal output
Q
Q
K
F
N
=
h
Q
F
= Thermal output (kW)
Q
N
= Rated boiler capacity (kW)
h
K
= Boiler efficiency (%)
Thermal output Q
F
Oil throughput
Furnace pressure
EK4.100 L-ZA EK4.100 L-ZA
Page 4
09/2005 - Art. Nr. 13 019 533A
4
Survey
Dimensions
Key
EK = Manufacturer 4 = Size 160 = Performance rating L = Fuel oil Extra Light Z = Two-stage A = Automatic burner control unit
1 Return line connection 2 Suction line connection 3 Solenoid valve, nozzle 2 4 Solenoid valve, nozzle 1 5 Solenoid valve for hydraulic air
damper drive
6 Switch box with automatic burner
control unit, switch, protective motor switch and connecting
terminals 7 Connecting flange 8 Insulating base 9 Burner tube
10 Flame cup
11 Electric motor 12 Flame monitor 13 Burner housing 14 Air suction box 15 Oil pressure pump 16 Hydraulic air damper drive 17 Inspection glass 18 Ignition transformer
Burner type Thermal
output kW
A B C Eø* Type No.
EK 4.100 L-ZA 360–1070 455 176 179 159 190 240–300* BN19787/89
EK 4.160 L-ZA 580–1660 455 176 179 185 220 280 BN19787/89
Customized designs and voltages on request. * Long holes in burner connecting flange, graduated circle from … to …
Burner type F ø Fig. G H J K L M N O
EK 4.100 L-ZA 330 1 222 M12 200 430 520 120–406 382 307
EK 4.160 L-ZA 310 2 222 M12 230 430 535 125–380 382 332
Holes in the boiler connecting plate
Fig. 1 Fig. 2
Page 5
09/2005 - Art. Nr. 13 019 533A
5
Burner Functions
Functional Description Functional Diagram
Starting function
The automatic burner control unit auto
­matically starts the burner when heat is required by the system.
The motor starts, the ignition is switched on.
The air damper drive 6a switches the air damper 5 to the low-load position ( in ”Basis” design, the air damper is in the low-load position when the burner is idle)
Preventilation
The solenoid valve 2 opens nozzle 1
The flame is formed (low load is in operation).
Switching over to full load
If required by the system, the automatic burner control unit switches the burner to full load.
The solenoid valve 3 opens nozzle 2
At the same time, the solenoid valve
7 switches from passage b–c to a–b
The hydraulic air damper drive 6 switches the air damper 5 to full load (full load is in operation).
The ignition is switched off again upon activation of full load.
Functional diagram
A Supply oil connection B Return oil connection C Combustion air inlet D
1
Nozzle 1
D
2
Nozzle 2
1 Oil pressure pump with pressure
regulator 2 Solenoid valve for nozzle 1 3 Solenoid valve for nozzle 2 4 Nozzle rod with two nozzles 5 Air damper 6 Hydraulic air damper drive 6a Hydraulic air damper driver for air
cut-off 7 Solenoid valve for air damper drive 8 Combustion air blower 9 Safety solenoid valve (with design
”DIN”)
Safety functions
A fault shutdown is effected if:
a flame signal occurs during preventilation (extraneous light moni
-
toring)
no flame occurs within 5 secondsafter starting the burner (initial oil release)
the flame is extinguished during operation.
A fault shutdown is indicated by the flashing lamp in the reset button. The program timer stops and the location of the malfunction is indicated (see Service Instructions, Malfunctions). After eliminating the malfunction, press the reset button to start the burner again.
A controlled shutdown is effected if:
the medium temperature or pressure is reached
the power supply fails.
The burner starts again automatically as soon as the operating conditions have returned to normal.
Basis
CEN/ DIN
Page 6
09/2005 - Art. Nr. 13 019 533A
6
Burner functions
Functional sequence of burner control units LAL 1...
The burner control units LAL 1... are designed for controlling and monitoring burners with multi-stage or modulating control systems. For a detailed functio
­nal description of the burner control units, including technical data and planning information, refer to
Technical Documentation
LAL 1 L&G 7153 D
Functional diagram, 2-stage
A = Start command A–B = Interval for flame formation B = Burner in operating position B–C = Burner operation
(heat generation)
C = Controlled shutdown
t1 Pre-venting time t2 Safety time t3 Preignition time, short t30 Preignition time, long t3n Post-ignition time t4 Interval between voltage on
terminals 18 and 19 t6 Post-venting time t7 Interval between Start command
and voltage on terminal 7 t11 Opening time of air damper t12 Closing time of air damper t13 Admissible after-burning time t16 Interval until OPEN command
for air damper
G Blower motor R Temperature or pressure controller Z Ignition transformer BV Fuel valve(s) FS Flame signal LR Load controller LK Air damper
Page 7
09/2005 - Art. Nr. 13 019 533A
7
Installation
Mounting the burner to the heat generator Zero point adjustment Electrical connection
Mounting the burner to the heat generator
To mount the burner connecting flange to the heat generator, prepare the con
-
necting plate according to the dimen
­sions given on page 4. The connecting flange 4 with the insulating base 3 have been factory-mounted to the front of the burner tube.
·
Set the desired burner tube length in the furnace by moving the flange on the burner tube
·
Insert the burner into the opening of the heat generator and secure it.
Inspection glass cooling
To keep the boiler inspection glass cool and clean, a cooling line may be connected to connection 12 R
1/4”.
The cooling line can be either a hose or a copper pipe. A hose union is enclosed with the burner. To connect a copper pipe, a suitable clamping ring connection is required.
Zero point adjustment, flame cup
Before the burner is operated for the first time, the zero point must be checked and adjusted, if necessary, so that the zero mark on the scale corre
­sponds to the zero position in the burner head. Adjustment is made by displacing the flame cup after releasing the screw 1.
Electrical connection
Electric wiring must be carried out by an authorized electrician according to the enclosed wiring diagram. The connecting terminals are located in the built-in switch box.
For cable connection, ensure the following:
·
Connect to terminal strip 8.
·
Provide sufficient length of cable so that the burner and the boiler door can be opened.
·
Do not install the sensor lead in the multi-conductor cable.
The electric module can be removed for connection, replacement or adjustment of components.
5 Lock nut for electric module 6 Pushbutton, stage 1 - stage 2 7 Pushbutton On/Off 8 El. connecting terminals 9 Overload relay 10 Protective motor switch 11 Automatic burner control unit with
reset button
12 Connection for inspection glass
cooling
Disassembling the electric module
·
Set the main switch to off, remove the fuse
·
Release the lock nuts 5
·
Carefully remove the electric module.
Caution!
Never apply voltage to the electric module after disassembly. After making the connections, check all system components for correct wiring. Then start the motor for a short time to check its sense of rotation.
Page 8
09/2005 - Art. Nr. 13 019 533A
8
Installation
Oil connection Oil pressure regulation Start-up
Oil connection
Hoses are used for connecting the oil pipes and the valve system. The hoses must be properly installed (suspended if possible) to avoid kinking and the risk of fracture. For the dimen
­sions of the supply and return pipes from the valve system to the tank, please consult the relevant technical data sheets.
Mounting options
Direct single-pipe installation
Single pipe installation with vent filter
Two-pipe installation
Filters
To protect the burner pump and the hydraulic system, suitable filters must be installed upstream of the burner.
Conversion from two-pipe to single­pipe installation
The burners are delivered with the pumps fitted for two-pipe installation.
Conversion
·
Remove the bypass plug from the return line connection and close the return line R with the screw supplied with the burner.
Attaching the measuring instruments
·
Suction line vacuum gauge to con
-
nection 3
·
Oil pressure gauge to connection 4
Oil pressure regulation
The oil pressure is regulated by the pressure regulator incorporated in the pump. The correct setting is approx. 15–20 bar, depending on the burner capacity. The pressure regulator is actuated by turning the screw 6.
Vacuum test (suction line)
The maximum permissible vacuum is
0.4 bar. A higher vacuum will cause the heating oil to vaporize and may cause malfunctions.
Pump type for EK4.160 L-ZA
R Return line connection S Suction line connection
1 Solenoid valve, nozzle 2 (full load) 2 Connection, nozzle 2 3 Vacuum gauge connection
(suction line)
4 Pressure gauge connection
(oil pressure) 5 Screws for pump cover 6 Oil pressure regulator 7 Connection, nozzle 1 8 Connection, hydraulic air damper
drive 9 Solenoid valve, nozzle 1 (low load) 10 Pressure output
Start-up and ventilation
Switch on the burner for a short while and check whether the sense of rotation is correct. Loosen the oil pipe union at the pressure output (7 or 10), switch on the burner and run the burner until bubble-free oil emerges. Then reconnect the oil pipe.
Important!
The hydraulic system has been filled with test oil at the factory. This may cause ignition problems when starting the burner for the first time.
Adjustment sequence
·
Start the burner
·
Adjust the oil pressure (15–20 bar)
·
Provisionally adjust low load
·
Switch over to full load
·
Finally adjust full load
·
Switch back to low load
·
Finally adjust low load
Pump type for EK4.100 L-ZA
Page 9
09/2005 - Art. Nr. 13 019 533A
9
Start-up
Burner head setting dimensions
The setting dimensions are standard values which refer to 80% of the maximum burner capacity. They can be readjusted depending on operating con
-
ditions, flue gas analysis and combu
-
stion behaviour.
Important!
Check the settings by means of the table before starting the burner for the first time. Remove the nozzle connec
-
tion for this purpose.
Ignition electrodes
The ignition electrodes are directed to nozzle 1. Spare ignition electrodes must be bent for replacement (at an angle of approx. 30° to the nozzle).
Burner head
1 Oil connection, minimum low load 1a Oil connection, maximum full load 2 Ignition electrode 3 Flame cup 4 Nozzle rod 5 Baffle plate holder 6 Nozzle 7 Baffle plate
Burner type Standard settings
ACDEHKL
Baffle plate/
nozzle rod
Electrode/axis
Electrode/
nozzle rod
Electrode gap
Baffle plate/
flame cup
max. longitudi-
nal adjustment
Oil filler neck/
scale plate 0
EK 4.100 L-ZA
27 7 20 3 20 50
EK 4.160 L-ZA
27 7 20 3 20 50
View Z
Page 10
09/2005 - Art. Nr. 13 019 533A
10
Start-up
Air regulation
Design ”Basis”
Low load
·
Release the lock nut 1
·
Use the screw 2 to adjust the low-load air
·
Tighten the lock nut after adjustment.
Full load
·
Release the lock nut 3
·
Use the screw 4 to adjust the full-load air
·
Tighten the lock nut after adjustment.
Air regulation, suction side
The combustion air is adjusted on the hydraulic air damper drive.
Design ”CEN”/”DIN”
The closed air damper position is adjusted by means of the screw 6 (standard factory setting).
Low load
· Release the plug screw 5. The screw behind it is now accessible for adjusting the low-load air.
· Retighten the plug screw.
Full load
·
Release the lock nut 3
·
Use the screw 4 to adjust the full-load air
· Tighten the lock nut after adjustment.
Important!
Make sure that you do not turn the stops of the hydraulic drive forcefully towards each other, i.e. adjust the stop screws only as long as the air dampers move synchronously. Violent and excessive turning will destroy the pinion.
1 Lock nut 2 Air regulator, low load (Basis) 3 Lock nut 4 Air regulator, full load 5 Air regulator, low load (CEN) 6 Air regulator, air damper closed
(CEN)
7 Locking screws for longitudinal
nozzle rod adjustment
8 Fixing screw, nozzle rod
Air regulation, pressure side
Moving the nozzle rod changes the available sectional area F in the flame cup.
Adjusting the nozzle rod
·
Release the screws 7
·
Adjust the nozzle rod
·
Tighten the screws after adjustment.
The ideal position of the nozzle rod is determined by analyzing the combustion quality at low and full load. To disassemble the nozzle rod, release the screw 8.
Page 11
09/2005 - Art. Nr. 13 019 533A
11
Service instructions
Maintenance Troubleshooting
Maintenance
Burner installations should be serviced once a year. The combustion and emission values should be checked and readjusted, if necessary. All mechanical and hydraulic functions should also be checked and wearing parts should be replaced, if necessary.
Any maintenance and repair jobs may be carried out by authorized experts only.
Check for operating ability
If a malfunction occurs, check first whether all requirements for troublefree operation have been met.
1. Check fuel level
2. Check power supply
3. Check if all control and safety features, such as thermostat, safety limiter, low-water cutout, electric limit switches etc. are operative and properly adjusted
Burner malfunction, electric
Burner malfunctions are indicated by a malfunction lamp. The automatic burner control unit LAL 1 is equipped with a malfunction indicator that is very useful for locating the cause of a malfunction.
Malfunction control program and malfunction indicator
Automatic burner control unit LAL 1; for detailed information, see L and G 7153. Basically, the program timer and the malfunction indicator stop whenever a malfunction occurs. The symbol displayed above the reading mark indicates the type of malfunction:
w
No Start, e.g. because the CLOSED signal from limit reversing switch ”Z” (or from auxiliary switch ”M”) is missing on terminal 8, or because a contact is open between terminals 4 and
5.
x
Start aborted because the OPEN signal from limit reversing switch ”A” is missing on terminal 8. Terminals 6, 7 and 15 remain energized until the fault is eliminated!
Burner malfunction, general
In the event of any burner malfunction whose cause is not immediately identifi
­able, check the program sequence by means of the applicable wiring diagram and the hydraulic system description until you locate the fault.
z
Fault shutdown because the flame supervising circuit is defective.
v
Start aborted because the position signal from auxiliary switch ”M” for the small flame position is missing on terminal 8. Terminals 6, 7 and 15 remain energized until the fault is eliminated!
1 Fault shutdown because no flame
signal is present upon expiry of the safety time.
F
Fault shutdown because the flame signal has failed during burner operation.
w
Fault shutdown on or after completion of the control program because of extraneous
light (e.g. flame not extinguished, leaky fuel valves or shutoff elements in the nozzle rod, defective flame supervising circuit, etc.).
a–b Starting program b–b’ ”Blank spaces”
(no contacts actuated)
b(b’)–a Post-venting program
The automatic control unit can be reset immediately after a fault shutdown. After resetting (as well as after a power failure or after eliminating a malfunction which caused a fault shutdown), the program timer will always returns to its starting position, supplying voltage to terminals 7, 9, 10 and 11 only, as deter
­mined by the control program. Only then will the control unit initiate another starting sequence of the burner.
Note: Operate the reset button for 20 seconds at the most.
Page 12
09/2005 - Art. Nr. 13 019 533A
12
Fabriqué en EU. Made in EU. Hergestellt in der EU. Document non contractuel. Non contractual document. Angaben ohne Gewähr.
Adresse Service-Hotline
ELCO Austria GmbH
Aredstr.16-18 2544 Leobersdorf
0810-400010
ELCO Belgium n.v./s.a.
Pontbeeklaan-53 1731 Zellik
02-4631902
ELCOTHERM AG
Sarganserstrasse 100 7324 Vilters
0848 808 808
ELCO GmbH
Dreieichstr.10 64546 Mörfelden-Walldorf
0180-3526180
ELCO France
18 rue des Buchillons 74106 Annemasse
0450877624
ELCO-Rendamax B.V.
Amsterdamsestraatweg 27 1410 AB Naarden
035-6957350
NL
FR
DE
BE
AT
CH
Loading...