elco 6.170 L-E, 6.240 L-E, 6.300 L-E, 7.350 L-E, 7.450 L-E Operation Manual

...
Operation Manual
for the authorized specialist
Oil Burner EK 6../7../8../9.. L-E
03/2005 102.880.2006
Inhalt
Overview Contents ...........................................................................................................2
Overview Important Information Warranty Product Description .......................................3
Technical Data .................................................................................................4
Dimensioned Drawings ....................................................................................9
Operation Start-up Mode Oil Operating Mode General Safety Functions .......................12
Fuel-air Compound Control Hydraulic Diagram .............................................13
Hydraulic Diagram L-E / GL-E Burner EK 6 - EK 9 ........................................14
Operation Hydraulic Valves and Instruments Group .......................................................15
Start-up Burner Head Settings .....................................................................................16
Installation Mounting to Boiler Electrical Connection Presetting ......................................19
Installation Boiler lining for Burner L-R/E .........................................................................20
Oil Connection Oil Pressure Control (Feed) ...................................................21
Start-up Return Nozzle Rod Type RDN Burner Type EK 6 .........................................22
Start-up Nozzle Selection, Type W2-50° ........................................................... ...... ....23
Start-up Return Nozzle Rod RDG 1250 Burner EK 7... - EK 9... .................................24
Nozzle selection „Sonic“ ..................... ..... ...... ....................................... ...... ....25
Checking Procedure .......................................................................................26
Adjusting Instructions Elektronic Burner Control with Electronic Compound Controller ....................27
Flame Detecting System Type FLW 05 .........................................................28
Servomotor Type SAD 15.0 ...........................................................................29
Electrical Actuator STM 40 .............................................................................30
Starting the BCS, Etamatic, VMS/FMS Electronic Compound Controller .....31
Adjusting Instructions Oil Pressure Switch (Option) Air Pressure Switch .........................................32
Operation Automatic Furnace Controller LAL... / LOK... Regulator KS 92 ....................33
Adjusting Instructions Flame Monitor Sensor Current Measurement ...............................................34
Adjustment Fan Impeller ...................................................................................................35
Servicing Instructions Burner Maintenance .......................................................................................36
Exhaust Gas Test ...........................................................................................37
Trouble Shooting Instruction s ......................................................... ..... ...... ....38
Operating Trouble ............................................... ..... ......................................40
System Diagram .............................................................................................41
Overview
Contents
Overview Important Information
Warranty Product Description
Important information
The burners of type EK 6.../ 7.../ 8.../
9...L-E have been designed for the combustion of light fuel oil EL. The burners should be installed and taken into opera tion by qualifi ed pers on­nel only who will be responsible for the proper performance of this work in accordance with the applicable regulati­ons and guidelines.
Any repair work on monitors, limiters and automatic furnace controllers and on the other sa fety f aci lities are allowed to be done only by the manufacturers themselves or specialists authorized by them. Original parts should only be exchanged by a duly qualified specia­list.
Standards and regula tion s
The following standard s sho ul d be observed in the interest of a safe, easy­on-the-environment and energy-saving operation of the burner:
According to DIN 4755, the user must be instructed in the ope rati on o f the bur­ner.
For the installation of an oil furnace system, care should be taken to observe DIN 4755, TRbF (Technical Regulation on Combustib le Liquids) and the local furnace construction regulati­ons applicable in the country.
Place of installation
The burner must not be operated in rooms containing aggressive vapours (e.g. spray, perchloroethylene, hydro­carbon tetrachloride, solvent, etc.) or tending to heavy dust formation or high air humidity. Adequate ventilation must be prov id ed at the place of installation of the furnace system to ensure a reliable supply with combustion air.
Maintenance
The furnace system should be serviced at least once a year by an authorized specialist. It is recommended to con­clude a maintenance agreement to this effect.
Warranty
Manufacturer will not accept any war­ranty if the operating instructions have not been duly observed in the start-up and maintenance of the burner and damages have been caused by impro­per installation, incorrect adjustment, unauthorized interference or operating errors.
Product description
The burners of type EK 6.../EK 7.../EK
8.../EK9...L-E can be used for the com­bustion of light fuel oil EL according DIN 51603-1. The burners are equipped with combu­stion air fan and air pr essure swit ch with test key, windbox with actuator for the air control dampers, oil pressure atomi­zer with oil high-pressure pump, nozzle rod, return nozzle and oil hydraulics block (with pressure sw it ches, valves and control shaft), pressure hoses and electric ignition system. The burners are designed to operate with an electronic compound control system.
EN267/ DIN4787
Oil atomizer burners
VDE 0116 Electrical Equipment
of furnace
Technical Data Sheet Monoblock Oil Burner
EK 6.170 / 200 L-E
Technical Data
Burner output Fuel flow rate Operating mode Type of fuel Burner control box Flame sensor Fan motor
Pump unit
Gear output Pressure Nozzle rod Nozzle Oil hoses / External connection Actuator Ignition transformer Weight
Operating range EK 6.170 / 200 L-E
0
2
4
6
8
10
12
14
16
18
20
0 500 1000 1500 2000 2500
6.170 L 6.200 L
Q Burner output [kW]
F
Air temperature 20°C, test values according to EN 267 (DIN 4787) at 171 m above sea level
Pressure in
c
ombus
t
ion
c
hamb er [mb ar]
6.170 L-E
501 - 1800 kW 42 - 152 kg/h fully modulating Light oil EL BCS / LAL 2 / LOK 16 QRB 3 / RAR 7 400 / 690 V, 50Hz
3,0 kW, 6,4 A, 2800 min-¹
SMG 1945 - 0,75 kW
520 l/h 30 bar RDN Thread 7/8" DN 16 x 1500 / R 1/2" SAD 15 / STM 40 / MM1004
150 kg
ZA20 140 / ZM20-14
6.200 L-E
640 - 2300 kW 54 - 194 kg/h fully modulating Light oil EL BCS / LAL 2 / LOK 16 QRB 3 / RAR 7 400 / 690 V, 50Hz
3,0 kW, 6,4 A, 2800 min-¹
SMG 1945 - 0,75 kW
520 l/h 30 bar RDN Thread 7/8" DN 16 x 1500 / R 1/2" SAD 15 / STM 40 / MM1004
150 kg
ZA20 140 / ZM20-14
No.: 102.880.434203/05
Technical Data
EK 6.170 / 200 L-E
Technical Data Sheet Monoblock Oil Burner
EK 6.240 / 300 L-E
Technical Data
Burner output Fuel flow rate Operating mode Type of fuel Burner control box Flame sensor Fan motor
Pump unit
Gear output Pressure Nozzle rod Nozzle Oil hoses / External connection Actuator Ignition transformer Weight
Operating range EK 6.240 / 300 L-E
0
5
10
15
20
25
0 500 1000 1500 2000 2500 3000 3500
6.240 L 6.300 L
Q Burner output [kW]
F
Air temperature 20°C, test values according to EN 267 (DIN 4787) at 171 m above sea level
Pressure in
c
ombus
t
ion
c
hamb er [mb ar]
6.240 L-E
681 - 2500 kW 57 - 210 kg/h fully modulating Light oil EL BCS / LAL 2 / LOK 16 QRB 3 / RAR 7 400 / 690 V, 50Hz
4,0 kW, 8,5 A, 2800 min-¹
SMG 16026 - 1,1 kW
735 l/h 30 bar RDN Thread 7/8" DN 20 x 1500 / R 1/2" SAD 15 / STM 40 / MM1004
160 kg
ZA20 140 / ZM20-14
6.300 L-E
940 - 3250 kW 79 - 280 kg/h fully modulating Light oil EL BCS / LAL 2 / LOK 16 QRB 3 / RAR 7 400 / 690 V, 50Hz
4,0 kW, 8,5 A, 2800 min-¹
SMG 16026 - 1,1 kW
735 l/h 30 bar RDN Thread 7/8" DN 20 x 1500 / R 1/2" SAD 15 / STM 40 / MM1004
160 kg
ZA20 140 / ZM20-14
No.: 102.880.435303/05
Technical Data
EK 6.240 / 300 L-E
Technical Data Sheet Monoblock Oil Burner
EK 7... L-E
Technical Data
Burner output Fuel flow rate Operating mode Type of fuel Burner control box Flame sensor Fan motor
Pump unit
Gear output Pressure Nozzle rod Nozzle Oil hoses / External connection Actuator Ignition transformer Weight
Operating range EK 7... L-E
0
5
10
15
20
25
30
0 1000 2000 3000 4000 5000 6000
7.350 L 7.450 L
Q Burner output [kW]
F
Air temperature 20°C, test values according to EN 267 (DIN 4787) at 171 m above sea level
Pressure in
c
ombus
t
ion
c
hamb er [mb ar]
7.350 L-E
1115 - 4500 kW 94 - 380 kg/h fully modulating Light oil EL BCS / LAL 2.2 / LOK 16 QRB 3 / RAR 7 400 / 690 V, 50 Hz
5,5 kW, 11,7 A, 2800 min-¹
KL-TA 4C - 2,2 kW SMG 19065 - 1,5 kW
800 l/h / 900 l/h 30 bar RDG 1250 Thread M14 DN 20 x 1500 / R 3/4" SAD 15 / STM 40 / MM1004 / EA2
250 kg
ZA20 140 / ZM20-14
7.450 L-E
1300 - 5300 kW 110 - 447 kg/h fully modulating Light oil EL BCS / LAL 2.2 / LOK 16 QRB 3 / RAR 7 400 / 690 V, 50 Hz
7,5 kW, 15,5 A, 2800 min-¹
KL-TA 5C - 2,2 kW SMG 1629 - 2,2 kW
1200 l/h 30 bar RDG 1250 Thread M14 DN 20 x 1500 / R 3/4" SAD 15 / STM 40 / MM1004 / EA2
250 kg
ZA20 140 / ZM20-14
No.: 102.880.436403/05
Technical Data
EK 7... L-E
Technical Data Sheet Monoblock Oil Burner
EK 8... L-E
Technical Data
Burner output Fuel flow rate Operating mode Type of fuel Burner control box Flame sensor Fan motor
Pump unit
Gear output Pressure Nozzle rod Nozzle Oil hoses / External connection Actuator Ignition transformer Weight
Operating range EK 8... L-E
0
5
10
15
20
25
30
0 1000 2000 3000 4000 5000 6000 7000 8000 9000
8.550 L 8.700 L
Q Burner output [kW]
F
Air temperature 20°C, test values according to EN 267 (DIN 4787) at 171 m above sea level
Pressure in
c
ombus
t
ion
c
hamb er [mb ar]
8.550 L-E
2000 - 6049 kW 168 - 510 kg/h fully modulating Light oil EL BCS / LAL 2.2 / LOK 16 QRB 3 / RAR 7 400 / 690 V, 50 Hz
11 kW, 22,5 A, 2800 min-¹
KL-TA 5C - 2,2 kW SMG 1629 - 2,2 kW
1200 l/h 30 bar RDG 1250 Thread M14 DN 20 x 1500 / R 3/4" SAD 15 / STM 40 / MM1004 / EA2
320 kg
ZA20 140 / ZM20-14
8.700 L-E
2000 - 7672 kW 168 - 647 kg/h fully modulating Light oil EL BCS / LAL 2.2 / LOK 16 QRB 3 / RAR 7 400 / 690 V, 50 Hz
15 kW, 30 A, 2800 min-¹
KL-TA 3C - 3,0 kW SMG 1630 - 3,0 kW
1700 l/h 30 bar RDG 1250 Thread M14 DN 25 x 1500 / R 1" SAD 15 / STM 40 / MM1004 / EA2
350 kg
ZA20 140 / ZM20-14
No.: 102.880.437503/05
Technical Data
EK 8... L-E
Technical Data Sheet Monoblock Oil Burner
EK 9... L-E
Technical Data
Burner output Fuel flow rate Operating mode Type of fuel Burner control box Flame sensor Fan motor
Pump unit
Gear output Pressure Nozzle rod Nozzle Oil hoses / External connection Actuator Ignition transformer Weight
Operating range EK 9... L-E
0
5
10
15
20
25
30
0 2000 4000 6000 8000 10000 12000
9.850 L 9.1000 L
Q Burner output [kW]
F
Air temperature 20°C, test values according to EN 267 (DIN 4787) at 171 m above sea level
Pr
essure in c
ombustio
n cha
m
b
e
r [m
b
ar]
9. 850 L-E
2574 - 9596 kW
217 - 809 kg/h
fully modulating
Light oil EL
BCS / LAL 2.2 / LOK 16
QRB 3 / RAR 7
400 / 690 V, 50 Hz 18,5 kW, 35 A, 2800 min-¹
KL-T 4C SMG 1631 - 4,0 kW
2250 l/h / 2200 l/h
30 bar
RDG 1250
Thread M14
DN 25 x 1500 / R 1"
SAD 15 / STM 40 / MM1004 / EA2
450 kg
ZA20 140 / ZM20-14
9.1000 L-E
2490 - 11409 kW
210 - 962 kg/h
fully modulating
Light oil EL
BCS / LAL 2.2 / LOK 16
QRB 3 / RAR 7
400 / 690 V, 50 Hz 22 kW, 42,5 A, 2800 min-¹
KL-T 4C SMG 1631- 4,0 kW
2250 l/h / 2200 l/h
30 bar
RDG 1250
Thread M14
DN 25 x 1500 / R 1"
SAD 15 / STM 40 / MM1004 / EA2
490 kg
ZA20 140 / ZM20-14
No.: 102.880.438603/05
Technical Data
EK 9... L-E
Overview
Dimensioned Drawings EK 6... L-E
EK 6.170/200 L-E
Dimensions in boiler connection plate
EK 6.240/300 L-E
Dimensions in boiler connection plate
10
Overview
Dimensioned Drawings EK 7... / 8... L-E
EK 7.350/450 L-E
Dimensions in boiler connection plate
Type
EK 8.550/700 L-E
Dimensions in boiler connecti on plate
Type
11
Overview
Dimensioned Drawings EK 9... L-E
EK 9.850/1000 L-E
Dimensions in boiler connection plate
Type
12
Operation Start-up Mode
Oil Operating Mode General Safety Functions
Start-up mode
As soon as the furnace system is requi­red to supply heat the bur ner c ont rol c ir­cuit will clo se and the program be started. After the prog ram has ru n down the burner will start.
The air damper is closed when the
burner is out of operation.
The automatic furnace controller con­trols and monitors the starting function. The electric actuator opens the closed air damper to its full-load position so that the burner will sweep the furnace compartment and exhaust ports at t he required air flow rates. Shortly after the pre-ventilation pro cess has been star ted the lack-of-air cut-out must change ov er to operating position within a certain time, i.e. the minimum air pressure set­ting must be reached and maintained until the burner is turned off. At the end of the specified pre-ventilation time the air damper will be moved into its par tial­load position. This operation will be fol­lowed by the pre- igniti on proc edure and the oil feed start.
The solenoid valves will open and thus allow the pressurized oil to flow to the nozzle and to t he return line. The oil will be atomized, mixe d with the combus tion air and ignited. A safety period is provided to allow the flame to develop a proper and steady pattern. On the terminati on of the safety period, a flame signal must have been received by the automatic furnace con­troller via the flame monitor and remain on until the regular shut-of f. The start-up program of the burner has now been completed.
Oil operating mode
After the flame has developed the load regulator will be enabled which brings the burner into its operating position. The load regulator will now control the burner automatically between its partial­load and full-load stages.
Depending on the heat rate required the servomotor will via the controller be given an "open" or "close" signal and thus increase or decre ase the oil and air flow rates. This compound c ontrol conc ept will v ary the position of the oil control valve and
air damper and thus adjust the oil flow rate in relation to the air flow rate. The stepless control will allow the bur­ner to be operated at any desired stage between its partial-load and full-load positions. The burner will be turned off from its partial-load position. The air damper will be closed when the burner is out of operation and will thus prevent cold air flowing through the burner chamber, heat exchanger and chimney. The interior cooling losses will be grea­tly minimized.
General safety functions
In case a flame does not develop when starting the burner (fuel release) the burner will shut off at the end of the safety period (shut-off on trouble). A shut-off on trouble will also occur in the case of flame f ailure during oper ation, air flow failure during the pre - ven til ati on phase and pressure failure during the whole period of burner operation. Any failure of the flame signal at the end of the safety period and a flame signal during the pre-ventilation phase (exter­nal light control) will result in a shut-off
on trouble with the automatic furnace controller being locked. The trouble is indicated by the trouble signal lamp lighting up. The automatic furnace con­troller can be unlocked immediately after a shut-off on trouble by pressing the unlocking key. The program unit will return to its starting position and pro­ceed with the restart of the burner.
A voltage failure will result in a regular shut-off of the burner. Upon voltage recovery there may be an automatic restart unless another interlock is provi-
ded, e.g. by the safety system. In any case of trouble the fu el oil suppl y wi ll be shut off right away. The program unit will stop at the same time causing also the trouble location indicator to stop. The symbols will indicate the kind of trouble. When using the burner control system type BCS all operational and fault mes­sages may be indicated in plain text on an optionally available operating and display module.
Zündung/Ventile Pumpe
Teillast
EIN
Freigabe
Leistungsregulierung
Betriebsstellung
Vollast
AUS
Oil control
steepless
Full load
Operating position Load regulator Release
Partial load
Ignition/valves Pump
ON OFF
13
Operation
Fuel-air Compound Control Hydraulic Diagram
Fuel-air compound control
This compound pneumatic control system with precision-adjustment capa­bility has been designed to allow the fuel and air flow rates to be steadily varied in sliding mode for an adjust ment of the fuel-air ratio over the whole con­trol range. In the two-stage sliding control concept the partial-load and full-load positions are within the control range. Depending on the heat demand these two load points will be selected in sliding mode. A larger fuel feed will not be suddenly turned on or off. In the stepless control mode the load will be controlled at any point within the control rang e dependin g on the heat demand. The two-stage sli­ding and the stepless control concepts are different only in the contr ol systems used with the burners. The same mode of operation is used for both versions.
Electronic compound control:
The air box includes an actuator for operating the air dam per . Th e oil co ntrol valve incorporates an actuator for adju­sting the return oil flow rate and thus th e output of the burner. The actuators for the air and fuel flow control will be operated depending on output by the electronic compound con­trol which will move them into the pro­grammed positions.
Electronic compound control
Oil feed Oil return
Air
1a Oil control valve with actuator 1b Air dampers with actuators 2Burner 3Boiler 4 Combustion air fan
Loading...