elco 6.170 L-E, 6.240 L-E, 6.300 L-E, 7.350 L-E, 7.450 L-E Operation Manual

...
Page 1
Operation Manual
for the authorized specialist
Oil Burner EK 6../7../8../9.. L-E
03/2005 102.880.2006
Page 2
Inhalt
Overview Contents ...........................................................................................................2
Overview Important Information Warranty Product Description .......................................3
Technical Data .................................................................................................4
Dimensioned Drawings ....................................................................................9
Operation Start-up Mode Oil Operating Mode General Safety Functions .......................12
Fuel-air Compound Control Hydraulic Diagram .............................................13
Hydraulic Diagram L-E / GL-E Burner EK 6 - EK 9 ........................................14
Operation Hydraulic Valves and Instruments Group .......................................................15
Start-up Burner Head Settings .....................................................................................16
Installation Mounting to Boiler Electrical Connection Presetting ......................................19
Installation Boiler lining for Burner L-R/E .........................................................................20
Oil Connection Oil Pressure Control (Feed) ...................................................21
Start-up Return Nozzle Rod Type RDN Burner Type EK 6 .........................................22
Start-up Nozzle Selection, Type W2-50° ........................................................... ...... ....23
Start-up Return Nozzle Rod RDG 1250 Burner EK 7... - EK 9... .................................24
Nozzle selection „Sonic“ ..................... ..... ...... ....................................... ...... ....25
Checking Procedure .......................................................................................26
Adjusting Instructions Elektronic Burner Control with Electronic Compound Controller ....................27
Flame Detecting System Type FLW 05 .........................................................28
Servomotor Type SAD 15.0 ...........................................................................29
Electrical Actuator STM 40 .............................................................................30
Starting the BCS, Etamatic, VMS/FMS Electronic Compound Controller .....31
Adjusting Instructions Oil Pressure Switch (Option) Air Pressure Switch .........................................32
Operation Automatic Furnace Controller LAL... / LOK... Regulator KS 92 ....................33
Adjusting Instructions Flame Monitor Sensor Current Measurement ...............................................34
Adjustment Fan Impeller ...................................................................................................35
Servicing Instructions Burner Maintenance .......................................................................................36
Exhaust Gas Test ...........................................................................................37
Trouble Shooting Instruction s ......................................................... ..... ...... ....38
Operating Trouble ............................................... ..... ......................................40
System Diagram .............................................................................................41
Overview
Contents
Page 3
Overview Important Information
Warranty Product Description
Important information
The burners of type EK 6.../ 7.../ 8.../
9...L-E have been designed for the combustion of light fuel oil EL. The burners should be installed and taken into opera tion by qualifi ed pers on­nel only who will be responsible for the proper performance of this work in accordance with the applicable regulati­ons and guidelines.
Any repair work on monitors, limiters and automatic furnace controllers and on the other sa fety f aci lities are allowed to be done only by the manufacturers themselves or specialists authorized by them. Original parts should only be exchanged by a duly qualified specia­list.
Standards and regula tion s
The following standard s sho ul d be observed in the interest of a safe, easy­on-the-environment and energy-saving operation of the burner:
According to DIN 4755, the user must be instructed in the ope rati on o f the bur­ner.
For the installation of an oil furnace system, care should be taken to observe DIN 4755, TRbF (Technical Regulation on Combustib le Liquids) and the local furnace construction regulati­ons applicable in the country.
Place of installation
The burner must not be operated in rooms containing aggressive vapours (e.g. spray, perchloroethylene, hydro­carbon tetrachloride, solvent, etc.) or tending to heavy dust formation or high air humidity. Adequate ventilation must be prov id ed at the place of installation of the furnace system to ensure a reliable supply with combustion air.
Maintenance
The furnace system should be serviced at least once a year by an authorized specialist. It is recommended to con­clude a maintenance agreement to this effect.
Warranty
Manufacturer will not accept any war­ranty if the operating instructions have not been duly observed in the start-up and maintenance of the burner and damages have been caused by impro­per installation, incorrect adjustment, unauthorized interference or operating errors.
Product description
The burners of type EK 6.../EK 7.../EK
8.../EK9...L-E can be used for the com­bustion of light fuel oil EL according DIN 51603-1. The burners are equipped with combu­stion air fan and air pr essure swit ch with test key, windbox with actuator for the air control dampers, oil pressure atomi­zer with oil high-pressure pump, nozzle rod, return nozzle and oil hydraulics block (with pressure sw it ches, valves and control shaft), pressure hoses and electric ignition system. The burners are designed to operate with an electronic compound control system.
EN267/ DIN4787
Oil atomizer burners
VDE 0116 Electrical Equipment
of furnace
Page 4
Technical Data Sheet Monoblock Oil Burner
EK 6.170 / 200 L-E
Technical Data
Burner output Fuel flow rate Operating mode Type of fuel Burner control box Flame sensor Fan motor
Pump unit
Gear output Pressure Nozzle rod Nozzle Oil hoses / External connection Actuator Ignition transformer Weight
Operating range EK 6.170 / 200 L-E
0
2
4
6
8
10
12
14
16
18
20
0 500 1000 1500 2000 2500
6.170 L 6.200 L
Q Burner output [kW]
F
Air temperature 20°C, test values according to EN 267 (DIN 4787) at 171 m above sea level
Pressure in
c
ombus
t
ion
c
hamb er [mb ar]
6.170 L-E
501 - 1800 kW 42 - 152 kg/h fully modulating Light oil EL BCS / LAL 2 / LOK 16 QRB 3 / RAR 7 400 / 690 V, 50Hz
3,0 kW, 6,4 A, 2800 min-¹
SMG 1945 - 0,75 kW
520 l/h 30 bar RDN Thread 7/8" DN 16 x 1500 / R 1/2" SAD 15 / STM 40 / MM1004
150 kg
ZA20 140 / ZM20-14
6.200 L-E
640 - 2300 kW 54 - 194 kg/h fully modulating Light oil EL BCS / LAL 2 / LOK 16 QRB 3 / RAR 7 400 / 690 V, 50Hz
3,0 kW, 6,4 A, 2800 min-¹
SMG 1945 - 0,75 kW
520 l/h 30 bar RDN Thread 7/8" DN 16 x 1500 / R 1/2" SAD 15 / STM 40 / MM1004
150 kg
ZA20 140 / ZM20-14
No.: 102.880.434203/05
Technical Data
EK 6.170 / 200 L-E
Page 5
Technical Data Sheet Monoblock Oil Burner
EK 6.240 / 300 L-E
Technical Data
Burner output Fuel flow rate Operating mode Type of fuel Burner control box Flame sensor Fan motor
Pump unit
Gear output Pressure Nozzle rod Nozzle Oil hoses / External connection Actuator Ignition transformer Weight
Operating range EK 6.240 / 300 L-E
0
5
10
15
20
25
0 500 1000 1500 2000 2500 3000 3500
6.240 L 6.300 L
Q Burner output [kW]
F
Air temperature 20°C, test values according to EN 267 (DIN 4787) at 171 m above sea level
Pressure in
c
ombus
t
ion
c
hamb er [mb ar]
6.240 L-E
681 - 2500 kW 57 - 210 kg/h fully modulating Light oil EL BCS / LAL 2 / LOK 16 QRB 3 / RAR 7 400 / 690 V, 50Hz
4,0 kW, 8,5 A, 2800 min-¹
SMG 16026 - 1,1 kW
735 l/h 30 bar RDN Thread 7/8" DN 20 x 1500 / R 1/2" SAD 15 / STM 40 / MM1004
160 kg
ZA20 140 / ZM20-14
6.300 L-E
940 - 3250 kW 79 - 280 kg/h fully modulating Light oil EL BCS / LAL 2 / LOK 16 QRB 3 / RAR 7 400 / 690 V, 50Hz
4,0 kW, 8,5 A, 2800 min-¹
SMG 16026 - 1,1 kW
735 l/h 30 bar RDN Thread 7/8" DN 20 x 1500 / R 1/2" SAD 15 / STM 40 / MM1004
160 kg
ZA20 140 / ZM20-14
No.: 102.880.435303/05
Technical Data
EK 6.240 / 300 L-E
Page 6
Technical Data Sheet Monoblock Oil Burner
EK 7... L-E
Technical Data
Burner output Fuel flow rate Operating mode Type of fuel Burner control box Flame sensor Fan motor
Pump unit
Gear output Pressure Nozzle rod Nozzle Oil hoses / External connection Actuator Ignition transformer Weight
Operating range EK 7... L-E
0
5
10
15
20
25
30
0 1000 2000 3000 4000 5000 6000
7.350 L 7.450 L
Q Burner output [kW]
F
Air temperature 20°C, test values according to EN 267 (DIN 4787) at 171 m above sea level
Pressure in
c
ombus
t
ion
c
hamb er [mb ar]
7.350 L-E
1115 - 4500 kW 94 - 380 kg/h fully modulating Light oil EL BCS / LAL 2.2 / LOK 16 QRB 3 / RAR 7 400 / 690 V, 50 Hz
5,5 kW, 11,7 A, 2800 min-¹
KL-TA 4C - 2,2 kW SMG 19065 - 1,5 kW
800 l/h / 900 l/h 30 bar RDG 1250 Thread M14 DN 20 x 1500 / R 3/4" SAD 15 / STM 40 / MM1004 / EA2
250 kg
ZA20 140 / ZM20-14
7.450 L-E
1300 - 5300 kW 110 - 447 kg/h fully modulating Light oil EL BCS / LAL 2.2 / LOK 16 QRB 3 / RAR 7 400 / 690 V, 50 Hz
7,5 kW, 15,5 A, 2800 min-¹
KL-TA 5C - 2,2 kW SMG 1629 - 2,2 kW
1200 l/h 30 bar RDG 1250 Thread M14 DN 20 x 1500 / R 3/4" SAD 15 / STM 40 / MM1004 / EA2
250 kg
ZA20 140 / ZM20-14
No.: 102.880.436403/05
Technical Data
EK 7... L-E
Page 7
Technical Data Sheet Monoblock Oil Burner
EK 8... L-E
Technical Data
Burner output Fuel flow rate Operating mode Type of fuel Burner control box Flame sensor Fan motor
Pump unit
Gear output Pressure Nozzle rod Nozzle Oil hoses / External connection Actuator Ignition transformer Weight
Operating range EK 8... L-E
0
5
10
15
20
25
30
0 1000 2000 3000 4000 5000 6000 7000 8000 9000
8.550 L 8.700 L
Q Burner output [kW]
F
Air temperature 20°C, test values according to EN 267 (DIN 4787) at 171 m above sea level
Pressure in
c
ombus
t
ion
c
hamb er [mb ar]
8.550 L-E
2000 - 6049 kW 168 - 510 kg/h fully modulating Light oil EL BCS / LAL 2.2 / LOK 16 QRB 3 / RAR 7 400 / 690 V, 50 Hz
11 kW, 22,5 A, 2800 min-¹
KL-TA 5C - 2,2 kW SMG 1629 - 2,2 kW
1200 l/h 30 bar RDG 1250 Thread M14 DN 20 x 1500 / R 3/4" SAD 15 / STM 40 / MM1004 / EA2
320 kg
ZA20 140 / ZM20-14
8.700 L-E
2000 - 7672 kW 168 - 647 kg/h fully modulating Light oil EL BCS / LAL 2.2 / LOK 16 QRB 3 / RAR 7 400 / 690 V, 50 Hz
15 kW, 30 A, 2800 min-¹
KL-TA 3C - 3,0 kW SMG 1630 - 3,0 kW
1700 l/h 30 bar RDG 1250 Thread M14 DN 25 x 1500 / R 1" SAD 15 / STM 40 / MM1004 / EA2
350 kg
ZA20 140 / ZM20-14
No.: 102.880.437503/05
Technical Data
EK 8... L-E
Page 8
Technical Data Sheet Monoblock Oil Burner
EK 9... L-E
Technical Data
Burner output Fuel flow rate Operating mode Type of fuel Burner control box Flame sensor Fan motor
Pump unit
Gear output Pressure Nozzle rod Nozzle Oil hoses / External connection Actuator Ignition transformer Weight
Operating range EK 9... L-E
0
5
10
15
20
25
30
0 2000 4000 6000 8000 10000 12000
9.850 L 9.1000 L
Q Burner output [kW]
F
Air temperature 20°C, test values according to EN 267 (DIN 4787) at 171 m above sea level
Pr
essure in c
ombustio
n cha
m
b
e
r [m
b
ar]
9. 850 L-E
2574 - 9596 kW
217 - 809 kg/h
fully modulating
Light oil EL
BCS / LAL 2.2 / LOK 16
QRB 3 / RAR 7
400 / 690 V, 50 Hz 18,5 kW, 35 A, 2800 min-¹
KL-T 4C SMG 1631 - 4,0 kW
2250 l/h / 2200 l/h
30 bar
RDG 1250
Thread M14
DN 25 x 1500 / R 1"
SAD 15 / STM 40 / MM1004 / EA2
450 kg
ZA20 140 / ZM20-14
9.1000 L-E
2490 - 11409 kW
210 - 962 kg/h
fully modulating
Light oil EL
BCS / LAL 2.2 / LOK 16
QRB 3 / RAR 7
400 / 690 V, 50 Hz 22 kW, 42,5 A, 2800 min-¹
KL-T 4C SMG 1631- 4,0 kW
2250 l/h / 2200 l/h
30 bar
RDG 1250
Thread M14
DN 25 x 1500 / R 1"
SAD 15 / STM 40 / MM1004 / EA2
490 kg
ZA20 140 / ZM20-14
No.: 102.880.438603/05
Technical Data
EK 9... L-E
Page 9
Overview
Dimensioned Drawings EK 6... L-E
EK 6.170/200 L-E
Dimensions in boiler connection plate
EK 6.240/300 L-E
Dimensions in boiler connection plate
Page 10
10
Overview
Dimensioned Drawings EK 7... / 8... L-E
EK 7.350/450 L-E
Dimensions in boiler connection plate
Type
EK 8.550/700 L-E
Dimensions in boiler connecti on plate
Type
Page 11
11
Overview
Dimensioned Drawings EK 9... L-E
EK 9.850/1000 L-E
Dimensions in boiler connection plate
Type
Page 12
12
Operation Start-up Mode
Oil Operating Mode General Safety Functions
Start-up mode
As soon as the furnace system is requi­red to supply heat the bur ner c ont rol c ir­cuit will clo se and the program be started. After the prog ram has ru n down the burner will start.
The air damper is closed when the
burner is out of operation.
The automatic furnace controller con­trols and monitors the starting function. The electric actuator opens the closed air damper to its full-load position so that the burner will sweep the furnace compartment and exhaust ports at t he required air flow rates. Shortly after the pre-ventilation pro cess has been star ted the lack-of-air cut-out must change ov er to operating position within a certain time, i.e. the minimum air pressure set­ting must be reached and maintained until the burner is turned off. At the end of the specified pre-ventilation time the air damper will be moved into its par tial­load position. This operation will be fol­lowed by the pre- igniti on proc edure and the oil feed start.
The solenoid valves will open and thus allow the pressurized oil to flow to the nozzle and to t he return line. The oil will be atomized, mixe d with the combus tion air and ignited. A safety period is provided to allow the flame to develop a proper and steady pattern. On the terminati on of the safety period, a flame signal must have been received by the automatic furnace con­troller via the flame monitor and remain on until the regular shut-of f. The start-up program of the burner has now been completed.
Oil operating mode
After the flame has developed the load regulator will be enabled which brings the burner into its operating position. The load regulator will now control the burner automatically between its partial­load and full-load stages.
Depending on the heat rate required the servomotor will via the controller be given an "open" or "close" signal and thus increase or decre ase the oil and air flow rates. This compound c ontrol conc ept will v ary the position of the oil control valve and
air damper and thus adjust the oil flow rate in relation to the air flow rate. The stepless control will allow the bur­ner to be operated at any desired stage between its partial-load and full-load positions. The burner will be turned off from its partial-load position. The air damper will be closed when the burner is out of operation and will thus prevent cold air flowing through the burner chamber, heat exchanger and chimney. The interior cooling losses will be grea­tly minimized.
General safety functions
In case a flame does not develop when starting the burner (fuel release) the burner will shut off at the end of the safety period (shut-off on trouble). A shut-off on trouble will also occur in the case of flame f ailure during oper ation, air flow failure during the pre - ven til ati on phase and pressure failure during the whole period of burner operation. Any failure of the flame signal at the end of the safety period and a flame signal during the pre-ventilation phase (exter­nal light control) will result in a shut-off
on trouble with the automatic furnace controller being locked. The trouble is indicated by the trouble signal lamp lighting up. The automatic furnace con­troller can be unlocked immediately after a shut-off on trouble by pressing the unlocking key. The program unit will return to its starting position and pro­ceed with the restart of the burner.
A voltage failure will result in a regular shut-off of the burner. Upon voltage recovery there may be an automatic restart unless another interlock is provi-
ded, e.g. by the safety system. In any case of trouble the fu el oil suppl y wi ll be shut off right away. The program unit will stop at the same time causing also the trouble location indicator to stop. The symbols will indicate the kind of trouble. When using the burner control system type BCS all operational and fault mes­sages may be indicated in plain text on an optionally available operating and display module.
Zündung/Ventile Pumpe
Teillast
EIN
Freigabe
Leistungsregulierung
Betriebsstellung
Vollast
AUS
Oil control
steepless
Full load
Operating position Load regulator Release
Partial load
Ignition/valves Pump
ON OFF
Page 13
13
Operation
Fuel-air Compound Control Hydraulic Diagram
Fuel-air compound control
This compound pneumatic control system with precision-adjustment capa­bility has been designed to allow the fuel and air flow rates to be steadily varied in sliding mode for an adjust ment of the fuel-air ratio over the whole con­trol range. In the two-stage sliding control concept the partial-load and full-load positions are within the control range. Depending on the heat demand these two load points will be selected in sliding mode. A larger fuel feed will not be suddenly turned on or off. In the stepless control mode the load will be controlled at any point within the control rang e dependin g on the heat demand. The two-stage sli­ding and the stepless control concepts are different only in the contr ol systems used with the burners. The same mode of operation is used for both versions.
Electronic compound control:
The air box includes an actuator for operating the air dam per . Th e oil co ntrol valve incorporates an actuator for adju­sting the return oil flow rate and thus th e output of the burner. The actuators for the air and fuel flow control will be operated depending on output by the electronic compound con­trol which will move them into the pro­grammed positions.
Electronic compound control
Oil feed Oil return
Air
1a Oil control valve with actuator 1b Air dampers with actuators 2Burner 3Boiler 4 Combustion air fan
Page 14
14
Operation
Hydraulic Diagram L-E / GL-E Burner EK 6 - EK 9
120 Air damper 175 Filter 176 Pump 178 Feed solenoid valve 180 Nozzle rod 181 Return solenoid valve 184 Output control valve 187a Pressure re gulating valve
(integrated in pump) 311 Return oil pressure switch 312 Feed oil pressure switch 349 Actuator
In case of TRD 604/72 hr control items (pos. 311, 312) need to be
tested according to „special construc­tion design“ or must be installed twice.
312
RL
181
175
187 a
VL
176
311
178
178
M M
120
184
349
349
180
181
Hydraulic diagram -DIN / EN
RL
175
187 a
VL
176
311
312
178
178
181
180
181
M
184
120
M
349349
Hydraulic diagram -TRD 604/72 h
Page 15
15
Operation
Hydraulic Valves and Instruments Group
The hydraulic valves and instruments group is an integrated concept that combines several functions of the hydraulic systems of burners. Its modu­lar construction makes it possible to meet a wide range of requirements and conditions of installation. The pump adapter module (1) allows the hydraulic valves and instruments group to be mounted directly to oil burner pumps of any size. It is fastened to the pump by means of hollow bolts which are provi-
ded with ¼" screw plugs (4) for venting the pump when taken into operation. The basic group module (2) is moun- ted to the pump adapter with the two modules being sealed against each other by O-rings in the supply and return pipes. Depending on the level of equipment of the hydraulic system, oil pressure switches and pr essure gauges may be installed in the supply and return pipes of the basic module. The solenoid valve in the supply pipe is of servo-assisted type while the return valve is directly controlled. The soleno­ids of the two valves are electrically connected i n series which will prevent one of the valves being opened alon e if any of the so lenoids is defective. For the replacement of the solenoid valves during maintenance work it should be ensured that the right valve type is installed in the correct direction of mounting. For mounting the solenoid valve in the supply pipe (type 321 H
2520) it must be ensured that the direc­tion of flow shown be a stamped arrow on the valve flange is the same as the direction of flow of the oil (from the pump to the nozzle rod). The solenoid valve in the return pipe (type 121 G
2520) is marked with a stamped arrow opposite to the direction of the oil flow from the nozzle rod back to the pump.
The volume flow control valve installed in the return pipe consists of a bush pressed into the hydraulic valves and instruments group and locked against torsion and a control shaft. As the con­trol shaft is turned, the contoured confi­guration of the bush and shaft will change the open cross section for the oil flowing back and thus vary the oil return flow rate. Control shafts with dif­ferent control contour parameters are available for adjustment to various oil nozzle sizes. This c onc ept ensures that an excellent control characteristic and a wide control range can be c overe d for a great variety of applicatio ns. The co ntrol contour parameter is affixed to the con­trol shaft by means of an electric mar­ker. The current position of the control shaft is indicated by the position display. From the "min." mark (low load of bur­ner) the control shaft will turn clockwise to the "max." mark (full load of burner). If the control shaft has been removed during maint enance work care shou ld be taken when reinstalling it to ensure the right mounting position o f the co ntrol contour by observing the centre punch mark on the shaft end face. In the low load position (min.) the centre punch mark will in any case point up (12 o'clock position - see figure). If the hydraulic valves and instr uments group is used in conju nctio n with nozzle rods not approved as safety shut-off valve according to EN 264, an exten- sion module (3) is available which incorporates an additional solenoid valve each in the supply and return pipes. The ex tension module is atta­ched directly to the basic module. The modules are sealed against each other by O-rings. Metal hoses are used for connection between the hydraulic valves and instruments group and the nozzle rod. The hose lines must be protected against exterior mechanical damage. The hoses must be positioned and mounted in accordance with the appli­cable technical standards. For the installation care must be taken not to introduce torsional or buckling stresses neither by the mounting procedure nor by movements at a later stage. Speci­fied bending radii of the h ose s m us t not be changed.
Pumpadapter
Basic module
Extension module
Control shaft installation
Complete hydraulic valves and
instruments group
Page 16
16
Start-up
Burner Head Settings EK 6... L-R/E
EK 6.170 L-R/E EK 6.200 L-R/E
EK 6.240 L-R/E EK 6.300 L-R/E
Page 17
17
Start-up
Burner Head Settings EK 7... / 8... L-R/E
EK 7.350 L-R/E EK 7.450 L-R/E
EK 8.550 L-R/EEK 8.550 L-R/E EK 8.700 L-R/E
Page 18
18
Start-up
Burner Head Settings EK 9... L-R/E
EK 9.850 L-R/E EK 9.1000 L-R/E
Page 19
19
Installation Mounting to Boiler
Electrical Connection Presetting
Burner mounting
For mounting the burner to the boiler make sure the connection plate has been prepared according to the dimen­sions given in the technical datas heets.
• Install the stud bol ts in the connection plate.
• Put the insulating backing and burner in place and fasten by bolts.
Check before burner installation
1. Select the nozzle according to
boiler output and combustion chamber geometry.
2. Set the mixing and ignition unit
according to the boiler output. For the standard factory setting refer to the burner head settings.
3. Set the ignition electrodes on the
nozzle.
4. Check the burner tub e ins t a lla tion
depth according to the data speci­fied by the burner and boiler manufacturers.
Electrical connection
The electrical connection work compri­sing all the installation materials, termi­nals and eart h connections must be carried out in accordance with the appli­cable regulations. For the electrical installation of the burner care must be taken to observe the circuit diagram made out for the furnace system. The electrical connection of the burner and gas valves a nd instrume nts shal l be entrusted to authorized specialists only.
NOTE: For the installation of the con­nection cables care must be taken to provide cable loops of sufficient length to allow for the swing-out of the boiler door and burner . Make sure after the completion of the electrical connection work to check the wiring of the electrical system of the burner. This should include a check of the direction of rotation of the burner motor (fan).
Boiler inspection glass cooling
For cooling and cleaning the boiler inspection glass a cooling line (e.g. hose) may be installed from the burner to the inspection glass. The burner is provided with a connection socket for this purpose.
approx. 6 mm
approx. 15 mm
approx. 10 mm
Page 20
20
Installation
Boiler lining for Burner L-R/E
Boiler lining
Example of boiler lining for three-pass boilers:
The space between the flame tube of the burner φD and the boiler lining φ D1 must be packed wi th heat-resistant material, e.g. Cerafelt.
This space is not allowed to be lined with brickwork.
Boiler lining
Example of boiler lining for reve rse-flo w boilers:
T1 according to the boiler or burner manufacturer’s instructions.
The space between the flame tube of the burner φD and the boiler lining φ D1 must be packed wi th heat-resistant material, e.g. Cerafelt.
This space is not allowed to be lined with brickwork.
Burner type Dimension A Dimension T φD φD1
Standard 100 ext. 200 ext. (Standard)
EK 6.170 230 330 430 230 227 290 EK 6.200 230 330 430 230 227 290 EK 6.240 250 350 450 250 263 290 EK 6.300 250 350 450 250 263 290 EK 7.350 282 382 482 282 306 360 EK 7.450 282 382 482 282 325 360 EK 8.550 362 462 562 362 346 400 EK 8.700 362 462 562 362 369 400 EK 9.850 395 495 595 395 431 475 EK 9.1000 395 495 595 395 431 475
Boiler lining
Page 21
21
Installation
Oil Connection Oil Pressure Control (Feed)
Oil connection
Hoses are used for connection to the oil lines and stop valves. The hoses must be installed according to the applicable standards (relieved of tensile load, free of distortion) to avoid kinking and exclude the danger of breakage. Take care when mounting the oil lines to bring their ends as close to the burners as possible and to arrange them in a way that the boiler door and the burner can be swung out without any obstruc-
tion. Refer to the techni cal docum entation f or the line dimensions for the feed and return lines from the stop valves to the tank.
Oil filter
A filter must be inst alled upstream of the pump to protect the oil pressure pump and the hydraulic system.
Installation options
• Two-line installation (separate feed and retu rn lines withou t delivery pump)
• Ring line system (with delivery pump and gas-air sepa­rator)
Instrument mounting
Prior to adjusting the burner make sure to mount the test pressure gauges for measuring the feed pressure ( Item 2) and return pressure (Item 1).
A vacuum gauge and pressure gauge are mounted to the oil pump for measu­ring the oil pressure.
NOTE: After the burner has been tak en into operation the gauges must be removed again and the connections sealed with suitable means. If the gau­ges are mounted to remain on the bur­ner they should be fitted with stop valves.
Oil pressure control (feed)
The feed pressure is controlled by means of the pressure regulator instal­led in the pump and should be set at approx. 25 to 30 bar depending on bur­ner output and nozzle make. The pres­sure regulator is operated by turning its screw. Make sure to fill the pump with oil prior to taking into operation.
Pump bleeding
Open the feed and return stop valves and ensure the ring line (if any) is in operation. Reduce the oil pressure at the pressure regulating valve. Turn on the pump by pressing the contactor. Check the pump for proper direction of rotation. Check for proper oil delivery and absence of leaks in the hy draulic oil system. For bleeding the pump open the pressure gauge connection, for example. When taking the burner into operation proceed by gradually increa­sing the pressure to operating level (25­30 bar).
Checking the pressure (oil suction pressure)
The maximum permissible vac uu m is
0.2 bar . At higher vac uum levels t he fuel
oil will tend to gas evolution which may lead to operating tro uble. In the ring line mode of operation the pump oil pres­sure is not allowed to exceed 5 bar.
Range of application of oil hoses
Burner type DN Lenght
[mm]
Connection
on both ends
Minimum bending
radius [mm] EK 6.170/200 16 1500 R 1/2" 230 EK 6.240 20 1500 R 1/2" 230 EK 6.300 20 1500 R 1/2" 240 EK 7 20 1500 R 3/4" 240 EK 8.550 20 1500 R 3/4" 240 EK 8.700 25 1500 R 1" 250 EK 9 25 1500 R 1" 250
Page 22
22
Start-up
Return Nozzle Rod Type RDN Burner Type EK 6
'HVFULSWLRQ
7KHUHWXUQQR]]OHURGW\SH5'1LVVXLWD EOHIRURSHUDWLRQZLWKWKHUHWXUQQR]]OH
W\SH)OXLGLFV:or Bergonzo CBM type B with 7/8 in. connection thread
7KLVQR]]OHVLQFRUSRUDWHVDVSULQJ ORDGHGVKXWRIIV\VWHPZLWKDFXWRII QHHGOHGLUHFWO\FORVLQJWKHQR]]OHKROH 7KHFXWRIIQHHGOHLVDFWXDWHGE\WKH FRQWUROQHHGOHWKDWLVFRQQHFWHGZLWK WKHK\GUDXOLFSLVWRQV\VWHPRIWKH QR]]OHURG
7KHVWURNHRIWKHFRQWUROQHHGOHPXVW EHGLPHQVLRQHGVRWKDWWKHQR]]OHZLWK WKHPD[LPXPSRVVLEOHQHHGOHVWURNHLQ RSHQHGQHHGOHSRVLWLRQKDVVWLOOVRPH FOHDUDQFHEHWZHHQVSULQJGLVNDQGFRQ WUROQHHGOHKHDG,ILQFDVHRIORZSXPS SUHVVXUHEDUWKHFRQWUROQHHGOHLV QRWSUHVVHGLQWRLWVIXOO\RSHQHGSRVLWLRQ WKLVPD\FDXVHWKHWKURXJKSXWUDWHWR YDU\EHFDXVHWKHQHHGOHSRVLWLRQKDV DQLPSDFWRQWKHRLOUHWXUQIORZ
5HW
XUQQR]]OHURGW\SH
5'1
6WURNHDGMXVWHUFRQWUROQHHGOH  +\GUDXOLFSLVWRQV\VWHP  2LOUHWXUQFRQQHFWLRQ  2LOVXSSO\FRQQHFWLRQ  5HWXUQQR]]OHW\SH)OXLGLFV:
127(7KHVWURNHDGMXVWHULVIDF WRU\VHWDQGPXVWQRWEHFKDQJHG GXULQJWKHRSHUDWLRQRIWKHV\VWHP
7KHVWURNH+LVPPDQGPD\EHVHW ZLWKWKHUHTXLUHGGHJUHHRIDFFXUDF\LQ DVXLWDEOHK\GUDXOLFWHVWULJRQO\
)XQFWLRQLQJRIQR]]OHW\SH:RU &%0%
2SHQLQJWKHQR]]OH
7KHVXSSO\RLOSUHVVXUHFDXVHVWKH SLVWRQLQWKHK\GUDXOLFV\VWHPDQGZLWK LWWKHFRQWUROQHHGOHWREHUHWUDFWHG 7KHVSULQJLQWKHQR]]OHRSHQVWKH FXWRIIQHHGOH
&ORVLQJWKHQR]]OH
7KHEXUQHUVWRSVDQGWKHK\GUDXOLF SLVWRQV\VWHPLVGHSUHVVXUL]HG 7KHFRQWUROQHHGOHEULQJVVSULQJ IRUFHWREHDURQWKHFXWRIIQHHGOHRIWKH QR]]OHFDXVLQJLWWRPRYHLQWRLWVFORVHG SRVLWLRQ
2SHQLQJSUHVVXUH EDUIXOO\RSHQ
DWEDU
&ORVLQJSUHVVXUH EDU
&RQWUROQHHGOH  2SHQLQJVSULQJRIQR]]OH  &XWRIIQHHGOH
1R]]OHFORVHG
1R]]OHRSHQ
Page 23
23
Start-up
Nozzle Selection, Type W2-50°
Return nozzle
The nozzle type Fluidics W is a return nozzle with i ntegrated spring-loaded cut-off needle. The throughput rate is controlled by varying the return pres­sure while keeping the supply pressure at a constant level. Prior to burner start, check the nozzle size against the required out put. It might be necessary to replace the nozzle (see nozzle selection diagram).
Nozzle selection diagram
The diagram shows the maximum throughput rates of th e return no zzles in dependence of the supply oil pressure.
Supply oil pressure: min. 20 bar
max. 30 bar Nominal supply oil pressure: 28 bar Return oil p ressure: min. 8 bar
Example
Required oil throughput rate 238 kg/h Nozzle size accord ing to diagram W2-225 Supply pressure according to diagram 28 bar
W 100
W 115
W 130
W 145
W 160
W 180
W 200
W 225
W 250
W 275
W 300
0
50
100
150
200
250
300
350
20 21 2 2 23 24 25 26 27 28 29 30
Vorlauf Öldruck [bar]
Öldurchsatz [kg/h]
Throughput rates shall apply to closed return Density: 840 kg/m
3
Viscosity: 5 mm2/s Nozzle type: W2-50°
Oil throughput rate [kg/h]
Supply oil pressure [bar]
Page 24
24
Start-up
Return Nozzle Rod RDG 1250
Function description
The return nozzle rod RDG 1250 is for return nozzle without integrated needle valve and comes with M14 screw con­nection (for example Sonic DZ 100 0, CBM M14).The locking mechanism consisted of a slider with se al ring (Pos. 2 and 6) in the forward flow section and a needle valve (Pos. 5) in the return flow section, using the sliding rod con­trol by a hydraulic con trol- piston syst em located at the back of the nozzle rod. The opening pressure of RDG 1250 is about 3 bar in forward flow section or 13 to 20 bar in return flow section. When the solenoid valves are open, the pres­sure from the oil would retract the con­trol-piston via the pressure channel (Pos. 7) and then push open the slider .
Both the control-piston and sliding rod with needle valve wou ld remain open as long as there is an exi sting oil pres sure. The same oil pressure would keep the slider open. Under normal circum­stances, both lock in g mec han isms would open at the same time. The oil in the forward flow section would exit through the nozzle head to be mixed with the air for combustion. The remai­ning oil would be red ire cte d t hrou gh th e return holes of the nozzle back into the return flow section of the nozzle rod assembly. When it is not in operation, the swirl plate in the nozzle head blocks the return flow.The return oil flow rate can be adjusted accordingly using a pressure control valve If the pump pres­sure is too low (<20 bar), thereby pre­venting the control needle from opening all the way, variations in throughput are to be expected as the needle position will affect the return oil fl ow.
Control-piston openi ng distanc e H is set in the factory at 9mm. Any adjustment at installation site is not necessary.
1
5
3
6
4
7
2
+
The Control piston opens at ca. 13 bar; Fully open at 20 bar. Close at 10 bar.
1 Return Nozzle 2 Slider 3 Spring (Forward) 4 Sliding rod 5 Needle valve 6 Seal ring (Forward) 7 Pressure channel Distance H = 9 mm
Forward
Valve
Page 25
25
Start up
Nozzle selection „Sonic“
160 kg/h
240 kg/h
300 kg/h
350 kg/h
400 kg/h
450 kg/h
500 kg/h
550 kg/h
650 kg/h
700 kg/h
750 kg/h
800 kg/h
850 kg/h
900 kg/h
950 kg/h
1000 kg/h
Diagram - of Sonic-Spray return nozzle DZ 1000-60° with controlled return Light fuel Oil Feed pressure 28bar
Return nozzles of the type Sonic­Spray are availa bl e in different ratin gs with an angle of spray of 45°, 60° or 80°.
The 45° nozzles are preferably used for reversed-flow furnaces while the 60° and 80° nozzles are operated in three-pass boilers and swirl-type mixing installations, respectively.
Quantity Oil Nozzle [kg/h]
Return Pressure at the Hydraulicblock [bar]
Page 26
26
Start-up
Checking Procedure
Check the following prior to the initial operation of the boiler system:
• Take care to observe the operating instructions supplied by the boiler manufacturer. The boiler must be mounted ready for operation.
• Ensure that the heating system is fi lled with water to capacity.
• Check the complete system for correct electrical wiring.
• Check the burner motor for correct direction of rotation.
• Check for the proper setting of the temperature and pressure controllers, limiters, safety switches and electrical limit switches.
• Bleed the fuel-carrying lines (make sure they are free of air).
• Check tank, lines and oil pump are fil­led with oil and correct oil nozzle is fit­ted.
• Check the oil hydraulic system is free of leaks.
• Check the exhaust gas ports are ope­ned and adequate fresh air intake is ensured.
• With burner in starting position check that air damper is in „CLOSED“ posi­tion.
• Check that automatic furnace control­ler is unlocked and in its original posi­tion.
Prior to the initial oil feed start make a functional test of the burner program flow:
Oil system:
• Open all shut-off valves of the oil sup­ply system.
• The oil solenoid valve in the feed line disconnect on the terminal strip (see Circuit Diagram).
• Start burner and check program flow for correct start-up sequence.
1. Fan starts.
2. Pre-ventilating damper.
3. Air pressure check.
4. Partial-load air damper.
5. Ignition.
6. Valves open (disconnec ted valve
remains closed) .
7. Shut-off upon trouble after expiry
of safety period (see automatic furnace controller).
• Reconnect the valve.
• Unlock the automatic furnace control­ler.
Oil start-up
Open all shut-off valves of oil su pply system.
• Set fuel selector switch to its „Oil“ position.
• Fill pump with oil.
• Mount pressure gauge in the feed line and return line.
• Mount the pressure gauge for checking the pump suction pressure.
Bleeding
Shortly start the burner and check for proper direction of rota tion. Bleed the oil line and oil pump.
CAUTION: The hydraulic system has been filled with test oil by the manufac­turer. This may cause ignition trouble when initially operating the system. To protect the pump, the oil pressure con­troller is factory-set at zero pressure. When starting the burner take care to increase the oil pressure slowly to the operating level.
Page 27
27
Adjusting Instructions
Elektronic Burner Control with Electronic Compound Controller
BCS
Refer to the documentation supplied with the electronic compound control system for the pre-operational work on the burner, the checking requirements (e.g. actuators, limit switches, potentio­meters etc.) and the instructions for the initial operation of the electronic com­pound control system.
Etamatic
Page 28
28
Adjusting Instructions
Start-up of Burner Control System Type BCS 300 Flame Detecting System Type FLW 05
Description
The electronic burner control system type BCS 300 is a programmable auto­matic firing controller of modular con­struction with integrated electronic compound controller. It is designed for the control and automatic control of oil, gas and dual-fuel burners of medium to larger outputs. The automatic firing controller may be used for intermittent or continuous mode of operation and for furnace systems built according to TRD. The controller consists of the following units that communicate via a safety-ori­ented bus system:
- burner controller module type BCS 300 (attached to burner)
- flame detector module type BCS­FLW 05 (attached to burner)
- fuel and air servomotors
- operating and display unit type BAM (not required for opera tion of furnace system)
The system also incorporates a PID firing rate controller with standard or servo-control parameterization capabi­lity and a valve leak tester.
Technical data:
Operating voltage: 230 V a.c. Frequency: 50-60 Hz Power input:
BCS incl. BAM:<15 VA
FLW 05: <1.5 VA Back-up fuse: max. 10 AF Equipment fuse: 6.3 A slow-blow
0.1 A slow-blow
Permissible ambient temperature:
in operation: 0-60 °C
during storage: -20-70 °C
Starting the burner control system NOTE: The burner control system is
allowed to be started by duly qualified specialists only. The personnel opera­ting the system should strictly observe the applicable instructions for start-up.
Before proceeding with the pro­gramming of the system make a check of its wiring (especially for compliance with the relevant DIN-VDE standards and the regulations of the local power supply company).
The parameterization of the automatic firing controller programs, the valve leak test and the firing rate adjustment will be handled from the operating and dis­play module.
NOTE: For selecting the automatic con­troller programs and adjusti ng the pre­ventilation times care should be taken to observe the applicable standards. The fixed safety time settings are not allowed to be ex ten ded by external s wit­ching operations.
The fuel-air compound curves may be programmed by means of the operat ing and control module or a laptop compu­ter. If the compound controller is adjusted by means of the operating and display module it will only be possible to correct the curve point settings. A completely new curve and the defini­tion of new curve points can be achie­ved with the aid of a laptop computer only.
After the automatic controller programs have been set it will be possible to check the inputs and outputs of the bur­ner control system for proper functioning via the operating and dis­play module.
NOTE: For the tests, all manual fuel shut-off valves must be kept in closed position in any case.
The compound modules are provided with a basic curve when delivered ex works. This may be changed by means of the operating and control module to adjust it to the local conditions. For this purpose, it is possible to correct the damper positions for the 10 index points in the range from 10, 20, 30, etc . to 100.
Flame detecting system
The flame detector m odule type FL W 05 is used in conjunction with the burner control system. The following flame sensors may be connected to the flame detector module:
-QRA 2
- QRA 53/55
- RAR 7/8
- ionization electrode
- any flame detector with contact output
The sensor to be used will be selected by appropriate programming i n the bur­ner control system. The type of sensor used will depend on the burner opera­ting mode (continuous or intermittent). The flame boosters integrated in the flame detector will be checked for pro­per operation at an interval of 90 seconds in continuous mode. Flame detectors with conta c t output must if run in c onti nu ous m od e b e intrin­sically safe because only the parts of the BCS flame detect or a r e ch ec ked fo r safe operation.
The intensity of the flame signals (UV sensor, light sensor, ionization elec­trode) is evaluated in the burner control system and indicated on the operating and display module. This allows an exact orientation of the flame sensors. It is not possible to measure the flame intensity by means of instruments.
The flame sensors must be ch ecked for accumulation of dirt at re gul ar intervals. Take care that the sensor window is kept free of dust all the time. The flame intensity display may be used as an indicator for the dirt ac cu mul ati on load. If the situation cannot be remedied by cleaning it will be necessary to replace the flame sensor.
Page 29
29
Adjusting Instructions Start-up of Burner Control System Type
BCS 300 Servomotor Type SAD 15.0
The electronic compound control system type BCS makes use of digitally activated servomotors type SAD 15.0. These consist of a stepping motor with electronic trigger and power pack. A driver with digital feedback via enco­der disk is provided for monitoring the function and direction of rotation. Take care to observe the instruction for operation for the burner control system type BCS 300.
Dimensions:
Connection:
P1 : N, L, PE P2, P3: 1 - EA SA
2 - EB SB 3 - OK WD 4 - GND 5 - AA MA 6 - AB MB
NOTE: Check the zero position of the servomotors prior to start-up.
Technical documentation:
BCS 300, Dungs
Technical data:
Maximum torque 15 Nm Gear reduction 745:1 Positioning times (at 200 Hz) 22.3s/90°
Positioning accuracy <±0.3° Direction of rotation from zero mark to 90°counterclockwise (looking on drive
shaft)
Angular re solution stepping mo tor 0.02°
rotation monitoring 1°
Unidirectional positioning by external load
initial stress at 0.6 Nm Supply voltage 230 V a.c. +10/-15%, 50 Hz Current decrease 20 ms ±30% (after last step) Protection classification IP 54 Shaft, flanged with cylindrical pin 12 dia.
h8
Ambient temperature in operation -20 to +60 °C
Cable gland with PG 11 conduit thread
and earthing
Through hole for M6 thread
P1
N L PE
P3 P2 zu
Page 30
30
Adjusting Instructions
Electrical Actuator STM 40
The actuator STM 40 is us ed i n co nne c­tion with the electronic burner control
systems of the firm „Lamtec“.
Technical data:
Voltage: 230V AC Frequency: 50 Hz Angle of rotation: 90° Running time: 40 sec. for 90° Torque: 15 Nm Static holding moment: 8 Nm Dimensiones (B x H x T): (93 mm x 144 mm x 149 mm) Potentiometer (integrated): 5 k
5 k
Page 31
31
Start-up
Starting the BCS, Etamatic, VMS/FMS Electronic Compound Controller
Starting the electronic compound controller
For starting the electronic ratio control­ler make sure to proceed as described in the operating instructions.
NOTE:
Only duly qualified personnel must be employed for starting the controller. For the initial operation make a check that the controller settings are in line with the furnace system requirements. The configuration of the compound con­troller is shown on the sticker attached to the housing side wall.
Functional test without burner start
After the electronic compound co ntroller has been connected electrically pro­ceed with adjusting the potentiometers of the actuators. Start the fan for checking the feedback of the fan speed (press the fan contactor). As soon as the potentiometer feedback data have been properly set proceed with programming the compound con­troller. An exact description of the pro­gramming procedure can be found in the operation manual supplied with the compound controller.
NOTE:
The start-up manual of the compound controller contains information on trouble signals, detailed instructions for start-up and for programming the con­troller.
Page 32
32
Adjusting Instructions
Oil Pressure Switch Air Pressure Switch
Oil pressure switch
Oil pressure switches are provided to burners for monitoring the oil pressure. Depending on the b urner design, the oil pressure switches can be installed eit­her in the return line only or in both the return line and feed line. The cut-out pressure will be selected depending on the burner system data (ring line pres­sure, oil nozz le, etc.).
Oil pressure damper
An oil pressure damper or a capillary pipe may be installed in the connection fitting (2) to make up for oil pressure variations.
Operating pressure adjustment
For adjusting the operating pressure, remove the setting know (1) b y pul ling i t upward and reinstall it again the other way round. After the adjustment has been completed mak e sure to instal l the setting know in its original position again.
Switching difference
The switching difference may be selec­ted on the pressure switches within the limits shown in the table. For the adjust­ment, turn the threaded pin in the set screw (3) for the switching point. One turn will change the switching difference by approx. 20 % of the total ra nge of the switching difference. The oil pressure switch has a facility for attaching a seal.
Type
Setting
range
Switching difference
Location
DSB 143 F... 0 - 6 bar 0,3 - 1,6 bar Return line acc. to DIN / EN
DSB(F) 170 F... 15 - 40 bar 1,2 - 4,5 bar Feed line acc. to DIN/EN in pumps
without quick-action stop valve
DSF 146 F... 0 - 10 bar 0,5 - 2,5 bar Return line acc. to TRD 604/ 72h
DSB 158 F... 3 - 25 bar 1,0 - 4,3 bar Feed line acc. to TRD 604/ 72h
Air pressure switch
The air pressure switch is provided for monitoring the pressure of the combu­stion air fan. The pressure switch DL 50A has been designed for switchi ng on, of f or ov er an electric circuit in the case of changes of the actual pressure levels from the set­point setting. The pressure switch DL 50A can be used as overpressure, vacuum or differential press ure mo nit or for air and non-aggressive gases but not for gases according to DVGW Worksheet G 260/l.
Determining the differential pre­flushing pressure and adjusting the differential pressure switch
• Burner in the pre-aeration phase.
• Measure pressure on test connection (2).
• Measure vacuum on test connection (3).
• Add the measured pressures.
• Set the scale to 90% of the calculated value.
Certification
The pressure switch has been tested in accordance with DIN 3398 Part 2 and is registered by CE/DIN-DVGW. It has been registered in other important gas consumption countries.
Switch function test
Test buttons are provided to check the switch functions for proper operation (with safety cut-out and interlock). The burner is normally run in partial-load condition when testing the safety functions. On pressing button (4) the vacuum will be removed which causes the different ial pressure to drop below the required level. If it is necessary to test the pressure switc h functio ns under full-load condition s this may be done by pressing button (1).
Page 33
33
Operation
Automatic Furnace Controller LAL... / LOK... Regulator KS 92
The automatic furnace controlle rs LAL... and LOK... are designed to control and monitor burners of stepless or modula­ting mode of operation. For a detailed functional description of the automatic furnace controllers with technical data and design information see the enclos­ure hereto and further descriptive mate­rial.
Technical documents
LAL 2.25 LOK 16 L & G 7785 June 1996
Funktional diagram LAL ... / LOK ...
A = Start command A-B = Flame formation interval B = Burner operating position
has been reac hed
B-C = Burner operation (heat
generation) C-D = Regular shut-off t1 Pre-flushing time t2 Safety period t3 Short pre-ignition time t4 Option: interval between voltage
on terminal 18 and terminal 19
(valve 1 and 2 will open at the
same time) t5 Interval between voltage on
terminal 19 and terminal 20
(interval between valve 2 and
controller enable) t6 After-flushing time t7 Interval between start command
and voltage on terminal 7 t11 Air damper operating time
(OPEN) t12 Air damper operating time (MIN) t13 Permissible after-burning time t16 Interval to OPEN co mmand fo r air
damper
R Temperature or pressure controller G Blower motor Z Ignition transformer BV Fuel va lve(s) LR Load controller LK Air damper RV Steadily adjustable fuel valve FS Flame signal
In steplessly variable burners use is made of the KS 92 industrial controller. This has specifically been designed for use with furnace s ystems, preferably for temperature and pres su re c ontrollers in conjunction with burners f eaturing steplessly variable fuel throughput rates. For adjusting the controller to the controlled condition, the desired set­point range and the way o f detecting the actual value, the software configuration is structured accordingly.
Technical documentation
KS 92 PMA
Page 34
34
Adjusting Instructions
Flame Monitor Sensor Current Measurement
Flame monitor with photoresistor
A photoresistor is used as the light-sen­sitive element of the QRB series. The resistance of this element will decrease with rising illumination intensity. In the dark condition the element will develop a high resist ance, i.e. a re sistanc e in the M range, whil e under the influence of light the element will develop a low resi­stance, i.e. in the K range. The after­glow of the f urnace lining will be detec­ted.
Flame monitor with photocell
A selenium cell is used as the light-sen­sitive element of the RAR series. In illu­minated condition this cell will generate a DC voltage and thus cause a current to flow to the input of the flame signal amplifier. Thus, the selenium photocell sensor is an active sensor. The cell is insensitive in the infrared r ange so that light glowing parts of the furnace refrac­tory lining will not be detect ed.
Application
The LAL 2... automatic furnace control­ler with its QRB1/3 flame sensor is mounted to burners with intermittent mode of operation which are shut down within 24 hours.
Application
Burners operated in continuous or inter­mittent mode for pe riods in excess of 24 hours (e.g. boiler sequential control) or burners operated in steam boilers must be equipped with the LOK 16... automa­tic furnace controller with its RAR flame sensor.
Cleaning the sensor
Check the sensor window for possible accumulation of dirt at regular intervals and clean if required. Take care the sensor window is kept free of dust at any time. If upon cleaning the sensor does not properly work it will be required to replace it by a new one.
Sensor currents
The sensor current is measured to check the intensity of the lig ht radiation at the place of installation of the sensor.
Automatic furnace controller
Photoresistor sensor QRB 1/3
QRB 1/3
LAL 2...
Automatic furnace controller
Photocell sensor RAR
LAL 2 / LOK 1 6
Recommended instrument range: 0 - 100 µ A * See technical data for automatic furnace controller LAL 2 / LOK 16
Automatic controller Minimum
required
Maximum
possible Monitor with sensor with sensor * LAL 2.25 (QRB 1/3) 8 µA35 µA * LAL 2.25 (Q RC 1) 3,9 µA0,8 µA (without flame) * LOK 16 (RAR...) 6,5 µA25 µA
Page 35
35
Adjustment
Fan Impeller
The fan impeller can be locked in any desired position on the motor shaft. To ensure a high slipping moment take care that all par t s to be joined are clean and free of grease.
Removing the fan impeller
NOTE: Apply a mark on the shaft prior to removing the fan impeller to ensure it can be remounted in the same position. An axial displacement of the impeller on the shaft can lead to a reduction of the fan efficiency with a resultant lower air flow rate.
For removing the fan impeller unscrew the bolts (Items 1 a nd 2) and install one of them in the hole with semi-tapped thread (Item 3) to act as a forcing screw. Tighten this bolt to force off of the bush. Remove the loosened disk unit by hand w ithout ham mer b lows and taking care not to damage it.
Mounting the fan impeller
- Clean all bright surfaces and ensure they are free of grease.
- Mount disk and bush and align the holes.
- Align the two opposing bolts (Items 1 and 2) and tighten evenly.
Apply the following tightening torques:
SM 16, bush no. 1615 hub bores 28 mm: tightening torque 20 Nm.
SM 20, bush no. 2012 hub bores 38 mm and 42 mm: tightening torque 30 Nm.
SM 25, bush no. 2517 hub bore 42 mm and 48 mm: tightening torque 50 Nm.
WM 30 bush no. 3030 hub bore48 mm: tightening torque 90 Nm
fan impeller
suction-funnel
Burner X [mm]
EK 6.170/200 5,5 EK 6.240/300 4 EK 7.350/450 4 EK 8.550 14 EK 8.700 8 EK 9.850/9.1000 15
Page 36
36
Servicing Instructions
Burner Maintenance
Furnaces should be inspected once a year. An extract from DIN 4755 reads as follows:
„To ensure a high operational readi­ness, functionality, safety and ec ono­mic efficiency, the user should have the boiler system inspected by an authorized person of the manufactu­rer or other specialist once a year. The whole system must be checked for proper operation and faults detected should be rectified without delay. It is advisable however to make another inspection of the system in addition to the one speci­fied herein.“ The inspection should comprise the following work:
1. Inspect the boiler internals and insulating packages and replace by new ones if required. Check boiler for possible ac cumulation of dirt.
2. Remove the nozzle, check it and replace it by new one if required.
3. Clean the ignition electrodes.
4. Check the ignition electrode and spark functions and readjust if required.
5. Clean the burn er interior and exte­rior.
6. Clean the fan impeller.
7. Check the fan impeller for possi­ble deformation and cracks.
8. Clean the flame sensor.
9. Clean the filters and screens.
10. Check the electrical connections.
1 1. Check the flame tube and ret arder
disk/swirl element (replace if required) and check the burner head setting after such replace­ment
12. Check the control equipment for proper operation, setting and safety period.
13. Check the pressure switch for pro­per setting and operation.
14. Check the oil pump by measuring its pressure and vacuum levels.
15. Check the hydraulic oil system for absence of leaks.
16. Check the oil hoses for possible damage and twisting.
17. Clean the air damper and check for smooth operation.
18. Check the combustion process and make exhaust gas tests:
• Fuel throughput rate adjustment
• Heating chamber temperature
(intake temperature)
• Exhaust gas temperature
• Pressure in combustion
chamber and exhaust gas pipe
•CO
2
and O2 contents of exhaust
gases
• CO test, soot test
• UV sensor current measurement
19. Enter measured data in test record.
Removing the mixing unit
For replacing and setting the retarder and ignition unit it will be necessary to remove the nozzle rod from the burner pipe as described below:
• Disconnect the system from it s volt age source. Set the master switch to „OFF“.
• Close all shut-off valves upstream of the burner.
• Remove the housing cover.
• Pull off the ignition cable.
• Remove the flame sensor .
• Loosen the Metal oil hoses on the hydraulic block connecting to the RDG 1250. Avoid using exces sive tor­sion on the hydraulic hoses.
• Remove left-hand or right-hand hinge bolt depending on direction of swivel (if swivelling unit is provided).
• Loosen locking bolts .
• Swing out burner.
• Demount the nozzle rod. NOTE: Retarder disk / swirl element and ignition electrodes are mo unted to nozzle rod.
Note on re-assembly:
• In the front part of the RDG 1250 is a forward flow slide that controls oil flow to the nozzle. To ensure a safe functioning in this area, no fixtures are allowed 100mm from th e fro nt e dge of the nozzle rod assembly. (such as electrode and baffle holders)
• If you tighten the nut at the hydraulic hoses, make sure that it is torsi on-free at the nut. A spanner will have to be used on the opposite side. Re-assembly must be done in reverse order.
• After assembly, both function and lea­kage test on the RDG 1250 must be conducted. Start the burner after all necessary components were connec­ted and check for leakage. When flame is establish, stop the bur­ner.Re mov e the burn er cov er an d us e a torch to check for oil leakage from the nozzle rod assembly.Leakage should not be more than a few drops of oil, as they are from the remaining oil in the no zzle head.
Page 37
37
Exhaust Gas Test
Exhaust gas test
T o ensure an economically efficient and trouble-free operation of the system it will be necessary to adjust the burner specifically in accordance with the furnace system. This is achieved by means of a fuel-combustion air compound control unit which adjusts the burner to ensure a proper combustion. Exhaust gas tests are required for this purpose. The percentage CO
2
and O2 and the exhaust gas
temperature will have to be measured to determine the efficiency and combustion quality. Prior to any measurement make sure to check the boiler and exhaust gas system for absence of leaks.
Secondary air will falsify the measured results
Check that the exhaust gases have a residual oxy­gen (O
2
) content as low as possible and a carbon
dioxide (CO
2
) content as high as possible.
The carbon monoxide content of the exhaust gases must be below the currently applicable specificati­ons in all load stages. In the fuel oil combustion mode the permissible soot number in the exhaust gas is not allowed to be exceeded.
Ratio between O2- and CO2- for light oil EL (CO
2
max =15,40%)
% O
2
% CO2 % O2 % CO2
0,00 15,40 3,00 13,19 0,10 15,33 3,10 13,12 0,20 15,25 3,20 13,04 0,30 15,18 3,30 12,97 0,40 15,11 3,40 12,89 0,50 15,03 3,50 12,82 0,60 14,96 3,60 12,75 0,70 14,88 3,70 12,67 0,80 14,81 3,80 12,60 0,90 14,74 3,90 12,53 1,00 14,66 4,00 12,45 1,10 14,59 4,10 12,38 1,20 14,52 4,20 12,31 1,30 14,44 4,30 12,23 1,40 14,37 4,40 12,16 1,50 14,29 4,50 12,08 1,60 14,22 4,60 12,01 1,70 14,15 4,70 11,94 1,80 14,07 4,80 11,86 1,90 14,00 4,90 11,79 2,00 13,93 5,00 11,72 2,10 13,85 5,10 11,64 2,20 13,78 5,20 11,57 2,30 13,71 5,30 11,49 2,40 13,63 5,40 11,42 2,50 13,56 5,50 11,35 2,60 13,48 5,60 11,27 2,70 13,41 5,70 11,20 2,80 13,34 5,80 11,13 2,90 13,26 5,90 11,05
O221
CO
2max
CO
2gem
CO
2max
-----------------------------------------------
× %=
=
O
2
21
CO
2max
CO
2gem
CO
2max
-----------------------------------------------
× %=
=
Ratio between O2- and CO2- for heavy oil (CO
2
max =15,90%)
% O
2
% CO2 % O2 % CO2
0,00 15,90 3,00 13,63 0,10 15,82 3,10 13,55 0,20 15,75 3,20 13,48 0,30 15,67 3,30 13,40 0,40 15,60 3,40 13,33 0,50 15,52 3,50 13,25 0,60 15,45 3,60 13,17 0,70 15,37 3,70 13,10 0,80 15,29 3,80 13,02 0,90 15,22 3,90 12,95 1,00 15,14 4,00 12,87 1,10 15,07 4,10 12,80 1,20 14,99 4,20 12,72 1,30 14,92 4,30 12,64 1,40 14,84 4,40 12,57 1,50 14,76 4,50 12,49 1,60 14,69 4,60 12,42 1,70 14,61 4,70 12,34 1,80 14,54 4,80 12,27 1,90 14,46 4,90 12,19 2,00 14,39 5,00 12,11 2,10 14,31 5,10 12,04 2,20 14,23 5,20 11,96 2,30 14,16 5,30 11,86 2,40 14,08 5,40 11,81 2,50 14,01 5,50 11,74 2,60 13,93 5,60 11,66 2,70 13,86 5,70 11,58 2,80 13,78 5,80 11,51 2,90 13,70 5,90 11,43
O221
2max
CO
2gem
CO
2max
---------------------------------------- -
× %=
=
Page 38
38
Exhaust Gas Test
Trouble Shooting Instructions
Exhaust gas loss
Exhaust gas loss by way of free heat will occur as a result of th e temperat ure difference between the fuel-air mixture entering the furnace chamber and the gases discharged. Any increase in the excess of air and the resultant higher exhaust gas v olume will cause the exhaust gas loss to rise. The exhaust gas loss can be calculated as follows:
Example: Data measured in fuel oil mode: CO
2
content of exhaust gases 12,8%
Exhaust gas temperature 195°C
Air intake temperature 22°C The exhaust gas loss can be calcul ated
as follows:
q
A
= exhaust gas loss in %
t
A
= exhaust gas temperature
in °C
t
L
= combustion air temperature
in °C
CO
2
= volumetric content of carbon
dioxide in %
q
A
tAtL–
()
A
1
CO
2
-----------
B
+
=
Light oilELHeavy oil
S
A
1
= 0,50 0,490
B = 0,007 0,007
In any case of trouble proceed with checking the basic conditions for a proper operation of the boiler system:
1.Is electric power available?
2.Is fuel oil contained in the tank?
3.Are the shut-off valves opened?
4.Are all control and safety inst ruments such as boiler thermostat, water supply failure cut-out, limit switches,
etc. properly set?
1. Ignition failure Cause Remedy
Ignition elec­trode short cir­cuit.
Adjust electrodes.
Wide ignition electrode spacing.
Adjust electrodes.
Dirty and wet electrodes.
Clean electrodes.
Cracked insulator.
Replace insulator.
Defective igni­tion transformer.
Replace transformer.
Defective auto­matic furnace controller.
Replace controller.
Burnt ignit ion cable.
Replace cable; search for cause and eliminate.
Pilot burner failure.
Adjust ignition gas pressure
Ignition gas valve does not open.
Search for cause and elimi­nate
Defective solenoid.
Replace
2. Motor running failure Cause Remedy
Motor protection relay and fuses.
Check and replace if required.
Air pressure switch not changed over or defective.
Check and replace if required.
Defective motor. Replace motor. Defective power
contactor.
Replace contactor.
Air fan motor starts but stops after 20-25 secs.
Check for solenoid leaks
Air fan motor starts, but stops after about 10 secs in pre-ve nti­lating mode.
Air pressure switch fails to change over; replace switch if defective; clean switch if dirt has accumulated; check electrical connections.
3. Pump oil delivery failure Cause Remedy
Shut-off valves closed.
Open valves.
Filter blocked by dirt.
Clean filter or
replace cartridge. Filter leaks. Replace filter Oil lines leak. Retighten scre-
wed unions; tigh-
ten oil lines. Suction valve
leaks.
Remove and
clean or replace. Direction of rota-
tion of pump.
Check irection of
rotation. Damaged gear-
box.
Replace pump.
Reduced pump output.
Replace pump.
-Strong mechanical noise. Pump takes in air Retighten scre-
wed unions. High vacuum in
oil pipe
Clean filter; fully
open valves. For heavy oil:
Incorrect oil tem­perature.
Check pre-hea-
ter:
thermostat set-
ting, dirt
Page 39
39
Trouble Shooting Instructions
8. Cleaning and lubricating instructions
Depending on the amount of dir t intro­duced by the combustion air it will be necessary to clean the fan impeller, ignition electrodes, flame sensors and air dampers as required.
For burner with mechanical compound controller: Lubricate the ball heads of the com­pound controller setting screws with grease.
The bearing point s of the burner mov ing parts require no maintenance. Damages of ball bearings should be detected and eliminated at an early stage to avoid greater subsequent trouble. Listen to the motor bearing noise to identify possible irregularities.
4. Unsteady atomization Cause Remedy
Loosened nozzle.
Tighten nozzle
Hole partly clog­ged.
Remove and clean or replace.
Worn by long­time use.
Replace by new
one. Oil flow blokkage Due to clogged
nozzle.
Remove and
clean. Nozzle leaking. Replace nozzle. Shut-off valve in
nozzle rod lea­king.
Replace valve.
5. No respon se to flame by automatic furnace controller with flame sensor
Cause Remedy
Dirty flame sen­sor.
Clean flame
sensor. Burner fails to
start.
Check
connection of
automatic fur-
nace controller. Trouble lamp
lights; flam e trouble.
Unlock and
search for cause
Weak flame sen­sor signals.
Check combus-
tion setting. Burner starts
without flame formation. Solenoid valve fails to open.
Defective coil or
rectifier.
Check connec-
tion.
6. Mixing unit gives poor com­bustion data due to heavy inside accumulation of oil or coke
Cause Remedy
Incorrect set­tings.
Correct settings.
Incorrect mix­ture ignition unit.
Replace unit.
Nozzle too large or too small .
Replace nozzle.
Incorrect angle of spray.
Replace nozzle.
High or low com­bustion air flow rate.
Readjust burner.
Furnace cham­ber not suf­ficiently ventilated.
Furnace cham­ber to be ventila­ted through a non-closed ope­ning with a cross section of min. 50 % of all chim­ney cross sec­tions of the furnace system. Take care to observe the application regu­lations.
7. Solenoid valve fails to open
Cause Remedy
Defective coil. Replace coil. Defective auto-
matic furnace controller.
Replace auto­matic furnace controller.
Valve does not close tightly; dirt accumulated on sealing surfaces.
Open valve; remove foreign matter; replace valve if required.
Page 40
40
Servicing Instructions
Operating Trouble
a - b starting program b - b’ „idle steps“
contact not actuated)
b(b') - a after-flushing program The automatic furnace controller may
be unlocked immediately after a shut­off on trouble. After it has been unlok­ked (and after a defect with resultant operating stop has be en elim inated and after a voltage f ail ure), the program unit will in any case return to its starting position with voltage being only supp­lied to terminals 7, 9, 10 and 11 as pre­set by the control program. It is only at this stage that the program of the auto­matic furnace controller will restart the burner.
NOTE: Do not operate the unlocking unit fo r more than 20 seconds.
General burner trouble
In the case of a burne r trou ble for which a cause is not immedi ately obvious, the program flow should be checked by reference to the applicable electric cir­cuit diagram and functional description of the hydraulic system until the source of trouble can be located.
Electrical burner trouble
Burner trouble situations will be indica­ted by the signal lamp lighting up. The LAL 1 automatic oil furnace con troller is provided with a trouble location indica­tor which is very useful in searching for the cause of the trouble.
Control program in the case of trouble and trouble signals
For information regarding the LAL 1 automatic oil furnace controller refer to L and G 7153.
Basically, any trouble w il l c aus e the pro­gram unit and the trouble location indi­cator to stop. The symbol shown above the reading of the indicator will identify the type of trouble:
No start, e.g. because the CLOSED signal from the limit change-over switch «Z» (or auxiliary switch «M») is not available in terminal 8 or a contact is not closed between termi­nals 4 and 5.
Operating stop because the O PEN signal from the limit change-over switch «A» is not available on termi­nal 8. Note that terminals 6, 7 and 15 will remain live un til the trouble is eliminated.
Shut-off on trouble because of a fault in the flame monitoring circuit.
Operating stop because the posi­tion signal of the auxiliary switch «M» for the low-flame po sitio n is n ot available on terminal 8. Note that terminals 6, 7 and 15 w ill remain live until the trouble is eliminated.
1 Shut-off on trouble because a
flame signal is not available on the expiry of the safety time.
Shut-off on trouble because the flame signal has faile d during burner operation.
Shut-off on trouble during or after the control program flow due to
external light (e.g. by flame not extinguished, leaking fuel valves or shut-off valves in the nozzle rod, fault in flame monitoring circuit, or similar).
IMPORTANT NOTE: In case of failure of an automatic furnace controller this should be replaced by a new one. Do not attempt any repair work on any parts of automatic furnace controllers.
Check for proper working order
In case an operating trouble make a check for proper working conditions.
1. Fuel oil availability.
2. Electric power availability.
3. Proper functional order and set­ting of all control and safety instru­ments such as temperature controller, safety limiter, water failure cut-out, electrical limit swit­ches, etc.
Page 41
41
System Diagram
1 Burner blower 2 Oil filter 3 Stop valve 4 Oil level indicator 5 Suction val ve 6 Tank 7 Leak indicator 8 Quick-acting valve 9 Filling li ne 10 Limit transmitter 1 1 Vent line 12 Pump unit 13 Pressure holding valvel
Stepless control, with supply pump and ring line system
Stepless control, direct intake
1 Burner blower 2 Oil filter 3Stop valve 4 Oil level indicator 5 Suction valve 6 Tank
7 Leak indicator 8 Quick-acting valve 9 Filling line 10 Limit transmitter 1 1 Vent line
Page 42
42
Page 43
43
Customer Service:
ELCO GmbH
D-64546 Mörfelden-Walldorf
ELCO Austria GmbH
A - 2544 Leobersdorf
ELCOTHERM AG
CH - 7324 Vilters
ELCO Rendamax B.V.
NL - 1410 AB Naarden
ELCO Belgium n.v./s.a.
B - 1731 Zellik
Loading...