Function
After the electrical connection has been completed, the TK-101 is operational and provides the current
value in accordance with the input signal to the output loop.
When ordering, the TK-101 is aligned with the output current range (4...20 mA).
In case the connection to the transmitter chain is defective, the signal is displayed with a current
value of I > 22 mA (except 100% connection). The supply voltage in the electric circuit of the unit
depends on the burden resistance. For more information, refer to the supply voltage range specified in
the technical data.
The TK-101 transducer always saves the most current measured value.
Function diagram
No.Function/designation Device TK-101 Comments
1 0 % indication Float, bottom position (4 mA) Device provides an output current of approx. 4 mA
2 50 % indication Float, center position (12 mA) Device provides an output current of approx. 12 mA
3 100 % indication Float, top position (20 mA) Device provides an output current of approx. 20 mA
Errorlimit = ±1%; FSO= ±0,2 mA; burden resistance 500 ΩFor an inverse display
(100% indication = float, bottom position), the connection wires 0% and 100% have to be exchanged
For an inverse display (100% indication = float, bottom position),
the connection wires 0% (RED) and 100% (Yellow) have to be exchanged.
Functional check / adjustment
Potentiometer adjustment
If this setting is to be changed, the "cover" of the housing needs to be removed. A current measuring device with
a measuring range of 30 mA is required and must be connected to the current loop.
Zero offset „0 %“ Max offset „100%
For this purpose, the resistance sensor must provide a
signal, which shall be used as zero position. On the
"Zero" potentiometer, the output current can now be set
to the required value.
For this purpose, the resistance sensor must provide a
signal, which shall be used as the maximum signal
value. On the "Max" potentiometer, the output current
can now be set to the required value.