A-4
Appendix A - ELMo 120 Multiplexer installation requirements
Revision 2.01 ELMo 120 Multiplexer Installation and Maintenance Guide 08-01023-01
CBN grounding environment
In most facilities using the CBN environment, the bay containing the ELMo
120 shelf should be grounded to a frame ground bar (FGB) as the common
ground point using a 6 A WG, stranded, ground conductor . In smaller facilities
where no FGB exists, the building principal ground (BPG) must be used.
If the facility has a ground collector , the bay must be grounded to the connector
using a 6 AWG (stranded) ground conductor to the collector. The collector
must then be grounded to the common ground point (FGB or BPG) using a 2
AWG (stranded) ground conductor.
If the distance from the FGB, BPG or ground collector is greater than
53 ft (16 m), a 2 A WG (stranded) ground conductor must be used to ground the
bay .
IBN grounding environment
In most facilities using the IBN environment, the bay containing the ELMo
120 shelf should be grounded using a 6 AWG, stranded, ground conductor to
the building single-point ground (SPG) as the common ground point. In
smaller facilities where no SPG exists, the building principal ground (BPG)
must be used.
If the facility has a ground collector , the bay must be grounded to the connector
using a 6 AWG (stranded) ground conductor to the collector. The collector
must then be grounded to the common ground point (SPG or BPG) using a 2
AWG (stranded) ground conductor.
If the distance from the SPG, BPG or ground collector is greater than
53 ft (16 m), a 2 A WG (stranded) ground conductor must be used to ground the
bay .
Network support equipment
The network support equipment that may need to be installed includes the
following:
• Ethernet 10Base-T hub port for ELMo 120 Hub card connection (one per
ELMo 120 shelf)
• Ethernet 10Base-T hub ports for NSS/InterProxy (two per NSS)
• LAN router connections
• WAN gateway connection
Network support requirements will vary according to the existing facility
resources. See the completed Elastic Networks
Site Survey Questionnaire
for
more information.