Elacompil FPM+, FPM Plus Technical And Operational Documentation

technical and operational documentation
Doc. version: 3.0.100
Contents
1.
2.
3.
3.1.
3.2.
4.
4.1.
4.2.
4.3.
4.4.
5.
6.
6.1.
6.2.
6.3.
6.4.
6.5.
6.6.
6.7.
6.8.
FPM+ ARCHITECTURE AND TOPOLOGY ............................................................................................. 5
REQUIREMENTS FOR EXTERNAL COMPONENTS .............................................................................. 7
FPM+ power supply .......................................................................................................................................................................... 7
Electrical installation ......................................................................................................................................................................... 7
FPM+ LIMITATIONS ........................................................................................................................... 8
No. of items per bus .......................................................................................................................................................................... 8
Length of bus between modules .................................................................................................................................................... 8
Length of MP-Bus .............................................................................................................................................................................. 8
Number of zones ............................................................................................................................................................................... 8
FPM+ UNIT AND MODULE SPECIFICATIONS ..................................................................................... 9
FPM+ MODULES .............................................................................................................................. 15
FPM+ control unit - central (MASTER) module ......................................................................................................................... 15
LSK ..................................................................................................................................................................................................... 17
e.LSK .................................................................................................................................................................................................. 18
EPSCUS ............................................................................................................................................................................................. 19
e.USP..................................................................................................................................................................................................20
SKC .....................................................................................................................................................................................................20
SKC-A ................................................................................................................................................................................................. 21
FPM+ bus repeater module ........................................................................................................................................................... 22
7.
7.1.
7.2.
7.3.
7.4.
7.5.
7.6.
7.7.
8.
8.1.
8.2.
8.3.
8.4.
8.5.
8.6.
8.7.
8.8.
9.
9.1.
9.2.
9.3.
10.
10.1.
10.2.
10.3.
10.4.
10.5.
10.6.
10.7.
10.8.
10.9.
CONNECTING MODULES .................................................................................................................. 24
FPM-X-YY-ZZ housings .................................................................................................................................................................. 24
EPSCUS ............................................................................................................................................................................................. 25
e.UPS.................................................................................................................................................................................................. 25
LSK ..................................................................................................................................................................................................... 26
e.LSK .................................................................................................................................................................................................. 29
SKC-A ................................................................................................................................................................................................. 29
FPM+ bus repeater .......................................................................................................................................................................... 32
MAIN HOUSINGS FOR CONTROL UNIT MODULES ........................................................................... 33
EPSCUS ............................................................................................................................................................................................. 33
LSK ..................................................................................................................................................................................................... 33
SKC ..................................................................................................................................................................................................... 33
SKC-A ................................................................................................................................................................................................. 34
Main housing of the control unit, type FPM-M-YY-ZZ .............................................................................................................. 34
FPM-X-YY-ZZ .................................................................................................................................................................................... 35
FPM-U-x-x-x-x-x and FPM-L-x-x-x-x-x ........................................................................................................................................... 36
Plastic multiple-module housings ................................................................................................................................................ 36
ASSEMBLY INSTRUCTIONS ............................................................................................................. 40
Bus......................................................................................................................................................................................................40
Shielding ............................................................................................................................................................................................40
External power supplies .................................................................................................................................................................40
TYPES OF INPUTS IN THE UNIT ....................................................................................................... 40
Input type: unused ........................................................................................................................................................................... 41
Input type: digital NO ...................................................................................................................................................................... 41
Input type: digital NC....................................................................................................................................................................... 41
Input type: digital three-state ........................................................................................................................................................ 42
Input type: analog resistive ........................................................................................................................................................... 42
Input type: digital supervised NO ................................................................................................................................................. 42
Input type: digital supervised NC .................................................................................................................................................. 42
Input type: analog 0-5V .................................................................................................................................................................. 43
Input type: analog 4-20mA ............................................................................................................................................................ 43
11.
TYPES OF OUTPUTS IN THE UNIT ................................................................................................... 44
11.1.
Output type: relay ............................................................................................................................................................................ 44
11.2.
Output type: Open Collector .......................................................................................................................................................... 44
11.3.
Output type: actuators and appliances compatible with MP-Bus standard ........................................................................ 44
12.
INPUT FUNCTIONS .......................................................................................................................... 45
12.1.
Input function: disabled .................................................................................................................................................................. 45
12.2.
Input function: fire alarm ................................................................................................................................................................ 45
12.3.
Input function: smoke alarm in a duct ........................................................................................................................................ 45
12.4.
Input function: smoke alarm in air intake ................................................................................................................................... 45
12.5.
Input function: smoke warning in air intake ............................................................................................................................... 45
12.6.
Input function: smoke warning in a duct .................................................................................................................................... 45
12.7.
Input function: fire reset ................................................................................................................................................................. 45
12.8.
Input function: firefighting action ................................................................................................................................................. 45
12.9.
Input function: technical alarm ..................................................................................................................................................... 45
12.10. Input function: ventilation .............................................................................................................................................................. 45
12.11. Input function: forced air supply from downstairs ................................................................................................................... 45
12.12. Input function: forced air supply from upstairs ......................................................................................................................... 45
12.13. Input function: indicator light test ................................................................................................................................................ 45
12.14. Input function: measurement ....................................................................................................................................................... 45
12.15. Input function: venting open ......................................................................................................................................................... 45
12.16. Input function: venting close ......................................................................................................................................................... 46
12.17. Input function: drive start test....................................................................................................................................................... 46
12.18. Input function: power failure ......................................................................................................................................................... 46
12.19. Input function: limit switch ............................................................................................................................................................ 46
12.20. Input function: limit switch group ................................................................................................................................................ 46
12.21. Input function: manual control ..................................................................................................................................................... 46
12.22. Input function: manual fire alarm ................................................................................................................................................. 46
12.23. Input function: smoke detector alarm ......................................................................................................................................... 46
12.24. Input function: smoke detector warning ..................................................................................................................................... 46
12.25. Input function: evacuation with firefighting action ................................................................................................................... 46
12.26. Input function: general alarm ........................................................................................................................................................ 46
12.27. Input function: pressure control ................................................................................................................................................... 46
12.28. Input function: external temperature sensor ............................................................................................................................. 46
12.29. Input function: internal temperature sensor .............................................................................................................................. 47
12.30. Input function: upper pressure sensor ........................................................................................................................................ 47
12.31. Input function: bottom temperature sensor............................................................................................................................... 47
13.
OUTPUT FUNCTIONS ....................................................................................................................... 48
13.1.
Output function: normal fan switch on ....................................................................................................................................... 48
13.2.
Output function: reverse fan switch on ....................................................................................................................................... 48
13.3.
Output function: upper fan rotation direction ............................................................................................................................ 48
13.4.
Output function: lower fan rotation direction ............................................................................................................................. 48
13.5.
Output function: fan switch on with firefighting action ........................................................................................................... 48
13.6.
Output function: evacuation with firefighting action ................................................................................................................ 48
13.7.
Output function: sensor power supply reset .............................................................................................................................. 48
13.8.
Output function: indicator lights ................................................................................................................................................... 48
13.9.
Output function: fire alarm............................................................................................................................................................. 48
13.10. Output function: technical alarm .................................................................................................................................................. 48
13.11. Output function: line actuator plus .............................................................................................................................................. 48
13.12. Output function: line actuator minus ........................................................................................................................................... 48
13.13. Output function: failure ................................................................................................................................................................... 48
13.14. Output function: actuator .............................................................................................................................................................. 48
13.15. Output function: actuator disabled .............................................................................................................................................. 48
13.16. Output function: cut-off gate ......................................................................................................................................................... 49
13.17. Input function: pressure regulator ............................................................................................................................................... 49
13.18. Output function: exhaust bottom ................................................................................................................................................. 49
13.19. Output function: exhaust top ........................................................................................................................................................ 49
13.20. Output function: supply bottom ................................................................................................................................................... 49
13.21. Output function: supply top ........................................................................................................................................................... 49
14.
COMMISSIONING INSTRUCTIONS ................................................................................................... 50
15.
15.1.
15.2.
15.3.
16.
16.1.
16.2.
16.3.
17.
PRODUCT SAFETY PRECAUTIONS .................................................................................................. 51
Proper usage regulations ............................................................................................................................................................... 51
Periodical inspection and maintenance regulations ................................................................................................................ 51
Safety precautions .......................................................................................................................................................................... 51
PACKAGING, TRANSPORT AND STORAGE ....................................................................................... 53
Packaging ......................................................................................................................................................................................... 53
Transport regulations ..................................................................................................................................................................... 53
Storage regulations ......................................................................................................................................................................... 53
ENVIRONMENT IMPACT .................................................................................................................. 54
LIST OF DRAWINGS ....................................................................................................................................... 55
18.
APPENDIX A: FPM-X-YY-ZZ HOUSING SPECIFICATIONS ................................................................. 56
19.
APPENDIX B : - DRAWINGS OF FPM-X-YY-ZZ HOUSINGS ............................................................... 57
19.1.
FPM-2-YY-ZZ .................................................................................................................................................................................... 57
19.2.
FPM—4-YY-ZZ .................................................................................................................................................................................. 59
19.3.
FPM-6-YY-ZZ .................................................................................................................................................................................... 61
19.4.
FPM-8-YY-ZZ .................................................................................................................................................................................... 63
19.5.
FPM-10-YY-ZZ .................................................................................................................................................................................. 65
20.
APPENDIX C : FPM-U-X-X-X-X-X AND FPM-L-X-X-X-X HOUSING SPECIFICATIONS ......................... 67
21.
APPENDIX D : FPM-U-X-X-X-X-X AND FPM-L-X-X-X-X HOUSINGS - DRAWINGS .............................. 68
21.1.
FPM-U-4-6-0-A-D .............................................................................................................................................................................. 68
21.2.
FPM-U-4-6-18-A-G ........................................................................................................................................................................... 69
21.3.
FPM-U-4-6-0-B-D .............................................................................................................................................................................. 69
21.4.
FPM-U-4-6-18-B-G ...........................................................................................................................................................................70
21.5.
FPM-U-6-6-0-A-D ..............................................................................................................................................................................70
21.6.
FPM-U-6-6-26-A-G ........................................................................................................................................................................... 71
21.7.
FPM-U-6-6-0-B-D .............................................................................................................................................................................. 71
21.8.
FPM-U-6-6-26-B-G ........................................................................................................................................................................... 72
21.9.
FPM-L-8-6-0-A-D .............................................................................................................................................................................. 72
21.10. FPM-L-8-6-18-A-G ............................................................................................................................................................................ 73
21.11. FPM-L-8-6-0-B-D .............................................................................................................................................................................. 73
21.12. FPM-L-8-6-18-B-G ............................................................................................................................................................................ 74
22.
APPENDIX E: CUSTOM HOUSINGS .................................................................................................. 75
1. APPLICATION OF THE FPM+ UNIT
The FPM Plus fire alarm control panel is a modular device for monitoring the operating status and control of all the pieces of equipment triggered as a result or during a fire. These can be dedicated firefighting systems, such as:
Fire emergency ventilation system,
Fire shutdown systems,
Evacuation support system,
Other building systems triggered to do any action as a result of fire.
Other systems include:
Access control system,
Burglary and robbery alarm system,
Escalator,
Lifts,
Utilities control (shut-off) systems,
Heat pumps and HVAC systems.
The unit features integration of various types of systems (with different functions) and building a single control algorithm (control matrix).
9) (…) equipment (fixed or semi-fixed, actuated manually or automatically) having the function of prevention, detection and putting out or containment of fires, particularly fixed or semi-fixed fire extinguishing and fire protection systems,
Page 4 of 78
inerting systems, voice alarm system and fire alarm system equipment, including alerting/alarm devices, fire alarm receiving equipment, damage alert receiving system, evacuation lighting systems, internal standpipes and standpipe valves, external standpipes, pumps in fire water pumping stations, fire dampers, smoke extraction equipment, explosion prevention and containment equipment, smoke curtains and doors, fire doors and other fire rated closures if fitted with control systems, fire emergency power shutdown devices, and hoists for rescue teams;
The control unit is responsible for technical handling of fire controls in the building. In response to an alarm from the Fire Alarm System, the unit will control all the firefighting equipment according to the assumed fire scenario.
As a minimum, the link between the Fire Alarm System and the Control Unit can consist of:
Zone alarms (‘Fire in a zone’) - number of signals equals the number of zones - signal from FAS to the FPM+control unit,
Feedback alarms - these should be matched to the needs of the building. Feedback alarms may include notifications of the control unit operation in fire mode (trigger confirmation), notifications of damage to the FAS, indications of alarms and hazards discovered by the control unit (if needed)
Fig. 1 Location of the control unit within the overall fire safety system in the building
2. FPM+ ARCHITECTURE AND TOPOLOGY
Page 5 of 78
The FPM+ unit has a modular design and is composed of modules of various types with various functions. Specific modules may be enclosed in separate single-module housings or in group housings where more than one module can be placed in each.
All the modules are connected with a bus loop. Every module on the bus is addressable. Information is exchanged digitally between the modules.
The MASTER module is unique among all the unit modules. This is the main module of the unit, with the function of overseeing the exchange of information between the other
modules and the exchange of information between the control unit and the higher level system (BMS, firefighting equipment integration system). The MASTER module with additional control unit handling items (buttons and indicator lights) is always housed in a separate housing (main housing of the control unit). Together with the MASTER, this housing can accommodate the power supply and a maximum of two EPSCUS controllers.
Other modules can be housed in ABS housings or steel housings.
Page 6 of 78
Fig. 2 Control unit topology diagram
3. REQUIREMENTS FOR EXTERNAL COMPONENTS
3.1. FPM+ POWER SUPPLY
Page 7 of 78
The FPM+ modules, according to type, can be powered from:
The control unit internal power supply,
External power supply,
Mains power ~230V.
Mains power can only be used when the unit performs control and monitoring functions over systems which are not required to work during a fire. An example system of this type can be a fire damper control system. In this case, mains
3.2. ELECTRICAL INSTALLATION
Electrical installation should be built with flame retardant or non-flammable cables. The choice of cable depends on the use of the FPM+ unit in the building. If the FPM+ controls any equipment or systems which are required to operate during a fire, a non-flammable cable must be used. If the FPM+ controls any equipment or systems which are not required to operate during a fire, a flame retardant cable can be used.
The general rule is that if at least one system or one appliance connected to the FPM+ must be operating during a fire, FPM+ action at the time of fire must be assured. Therefore, the bus and controller power supply installations must be wired in non-flammable cables. Connections to appliances and systems should be wired with a cable adequate for the requirements prevailing in the building.
For fire safety applications, Certificates of Approval should be issued for the cables by CNBOP-PIB Scientific and Research Center for Fire Protection National Research Institute.
voltage or secure voltage from external power supply units can be used.
If the FPM+ is expected to monitor and control equipment and systems which are required to operate during a fire, all the FPM+ modules should be powered with a buffered power supply, certified for conformity with EN-PN 54-4 or EN-PN12101-10, with the supply voltage and output current appropriate for the specific application.
Cable ways for fire safety applications should be produced to appropriate rating, i.e. E30/E60/E90, etc. For a specific application. Conformity with the classification requirements should be verified by an appropriate certificate.
Example cables:
YnTKSYekw 1x2x0.8 – fire retardant cable for wiring installations not required to operate during a fire. Can be used for example to wire a bus linking the modules, or to wire an MP-Bus.
HTKSHekw PH90 1x2x1 – fire resistant cable for wiring installations required to operate during a fire. Can be used for example to connect bus lines.
HDGs 2x1 – fire resistant cable for power supply and control of systems which need to be powered with electricity during a fire.
The designer should always make sure that the cable they intend to use has the requisite approvals and certificates required by law.
4. FPM+ LIMITATIONS
Page 8 of 78
4.1. NO. OF ITEMS PER BUS
In terms of technical feasibility, a maximum of 254 controllers can be covered within a single bus. These modules are divided into two groups:
126 x LSK / e.LSK controllers
126 x EPSCUS/e.USP controllers
LSK/e.LSK modules have an address pool attributed on bus 1..126, while the pool attributed to EPSCUS/e.UPS modules is 129…254.
LSK controllers can be addressed on the basis of settings of controls on the front panel of the respective module, or on the basis of controller serial numbers.
EPSCUS, e.USP and e.LSK controllers are addressed on the basis of controller serial numbers.
4.2. LENGTH OF BUS BETWEEN
MODULES
The bus is divided into sections. Each module on the bus is the end and the start of the respective sections to which it is connected. The length of sections between specific modules should not exceed 1200 meters.
4.3. LENGTH OF MP-BUS
The overall length of a single MP-Bus (connecting 8 actuators with a single LSK module) should not exceed 600 meters.
4.4. NUMBER OF ZONES
Notwithstanding the number of all zones (fire, control, smoke extraction zones) that can be covered by the FPM+ unit, there is a limitation of the number of zones to which a specific output can be assigned. This number is limited to 70 in the software. Should outputs (EPSCUS and e.USP relay outputs and LSK and e.LSK actuators) need to be assigned to a higher number of zones, contact the FPM+ unit manufacturer.
5. FPM+ UNIT AND MODULE SPECIFICATIONS
Table 1 FPM+ unit and module specifications
GENERAL DESCRIPTION
Page 9 of 78
FPM+ architecture
Climate class
Loops
Minimum no. of modules
Maximum no. of modules
Max. bus voltage
Max. bus current
IP
Operating temperature range
Dimensions (L x W x H)
Firmware version
Manual/auto options
Systems and appliances integrated with the control unit
Modular, loop, addressable unit
2
1x
1x, as per 3.1.1 of this approval
1 MASTER
126 EPSCUS/e.USP
126 LSK or LSK/24 or e.LSK
2016 SKC, SKC-A (using 126 e.LSK), or 1008 SKC, SKC-A (using 126 LSK)
A MASTER module is required for more than 1 module
5VDC
Short-circuit current 50mA (limited with a polyfuse)
IP42 for external housing of the control unit and individual housings IP55 for SKC modules IP65 for LSK and LSK/24 modules
-50C to +550C (relative humidity 80% at 550C)
Min. 500x600x250 Other dimensions as per the control unit documentation
FPMplus
Automatic, through a signal from the fire alarm system control panel, smoke extraction system control panel, or automatic smoke detectors of the fire alarm system.
Manual trigger with the smoke extraction button Manual control from the integrating system
Fire alarm control panels Smoke and heat propagation control system components (shut-off dampers,
smoke vents, fire vents, smoke curtains, etc.) Conventional fire detectors (readings on parametric lines) Smoke extraction buttons and manual call points Pressure sensors Temperature sensors Wind direction and wind force detectors Voltage presence detectors Fire dampers Electromagnetic holders (releases) Voice alarm systems Fixed fire extinguishing equipment Emergency exit controls Other building control systems Intermediary devices, such as: contacts, inverters, switches
Other external appliances and systems that may or must be controlled during a fire, where the design and operating mode makes them integrable with the control unit
Other systems and appliances without firefighting functions where the design and operating mode makes them integrable with the control unit
POWER SUPPLY DESCRIPTION
Page 10 of 78
Power supply
Supply voltage
Max. power consumption
Internal operating voltage
Power supply type or other identification
Operating temperature range
Housing protection grade
Dimensions (L x W x H)
Main power supply: supply voltage
Max. power consumption from mains
Max. continuous load on power supply
Max. short-term load on power supply
Ripples
Uninterrupted power supply: battery type
Max. battery capacity
Battery charging voltage in buffer mode
Max. battery charging current
Battery cut-off voltage
Max. resistance of battery bank circuit
Output circuits: power supply output voltage range
Functional class
External power supply conforming to PN-EN12101-10 and PN-EN 54-4 Dedicated control unit power supply, type CAMELEON, series ZM24VxxA-
yyyPZ(C), specifically ZM24V6A-151PZ(C), ZM24V8A-200PZ(C) ZM24V12A-300PZ(C), ZM24V16A-
400PZ(C) and ZM24V24A-600PZ(C) ~230V mains for LSK module
24-48VDC from external power supply For LSK module powered from ~230VAC mains
2A @ 24VDC (excluding power supply to appliances, such as actuator, holders, etc.)
24-48VDC
CAMELEON
ZM24V24A-600PZ(C)
-25..70°C
n.a. (installed in multiple-module IP42 housing)
262x111x66mm With connections 279x111x66mm
184..230..253VAC 230 V AC (-20% / +10%)
2.1A
I
=18A
maxA
I
=24A
maxB
150mV
AGM type (VRLA) lead acid batteries
120Ah
26.4…..28.8V
6A
<21.0V
100mΩ
21.0…28.8V
A
Page 11 of 78
Environmental class
2 (when installed in the control unit in IP42 housing)
OUTPUTS DESCRIPTION
Potential-free relay outputs
Potential-free relay contacts Contact type: changeover Current capacity: 2A for 30VDC Resistance of contacts: < 50mΩ For loads with higher current or voltage, use additional high current relays Number of zones assignable to a single output: 70
OC outputs
OC type outputs Max. external voltage 48VDC Current capacity: 100mA per output at 25°C Induction load operation only with idling diode!
MP-Bus outputs
MP-Bus output No. of items on bus: 8 Operating voltage >20VDC Maximum current >10mA
Maximum outputs
MP-Bus: 126*8 = 1008 x MP-Bus devices for LSK, 2016 for e.LSK Relay outputs: 1008 O/C: 756
INPUTS DESCRIPTION
Digital inputs
Digital inputs, supervised, with the option of switching off supervision (NO, NC mode)
Typical line resistance values Supervision state 1kΩ Alarm state 3,3kΩ
Analog inputs
Analog inputs for signal acquisition:
4..20mA (with external resistor)
0..5V direct
0..10V with external resistor
Max. inputs
Digital, monitored: 504 Digital/analog (configurable): 1008 for EPSCUS, 2016 for e.LSK
Recommended cable types
For control unit bus: non-flammable cables (for fire ventilation systems and smoke extraction systems) or flame retardant cables (for fire damper control), single pair, shielded. Min. core section 0.5mm
Sample cables:
Flame retardant YnTKSYekw 1x2x0.8
Fire resistant HTKSHekw 1x2x1.0 PH90
If the control unit covers at least one appliance requiring uninterrupted power supply during a fire alarm, fire resistant cables should be used to produce the bus, in accordance with the applicable legal requirements, including § 187 of Regulation of the Minister of Infrastructure of 12 April 2002 concerning
Supply voltage
IP
No. of inputs
No. of outputs
FPM+ bus
Configuration/visualization bus
Page 12 of 78
technical requirements applicable to buildings and their locations (Journal of Laws No. 75, item 690, as amended).
For powering actuators - cables should be selected in accordance with the legal requirements, including § 187 of Regulation of the Minister of Infrastructure of 12 April 2002 concerning technical requirements applicable to buildings and their locations (Journal of Laws No. 75, item 690, as amended).
E.g. fire resistant cable HDGs 2x1 Use of a flame retardant cable, e.g. YnTKSYekw 3x2x0.8, is permitted for
powering and controlling appliances for which uninterrupted power supply is not required during a fire (e.g. fire cut-off dampers with springreturn actuator).
If the appliances connected to the control unit require the use of cabling with varying flammability classifications, use highest rated cables out of the applicable requirements to build the bus.
Cables must be provided with relevant approval documents for use in fire protection installations (Certificate of conformity, Certificate of Approval by CNBOP-PIB Scientific and Research Center for Fire Protection National Research Institute).
24-48VDC
n.a. (installed in multiple-module IP42 housing)
Digital/analog inputs: 8
Relay outputs: 8
2xRS485
Ethernet
EPSCUS module DESCRIPTION
Supply voltage
IP
24-48VDC
n.a. (installed in multiple-module IP42 housing) IP42 – for individual housing with ABS
No. of inputs
No. of outputs
Digital/analog inputs: 8
Relay outputs: 8 O/C outputs: 6
FPM+ bus
2xRS485
LSK and LSK/ MODULE DESCRIPTION
Supply voltage
24 - 48VDC for LSK/24 230VAC for LSK
IP
No. of inputs
No. of outputs
FPM+ bus
IP65
Digital inputs: 4
MP-Bus: 1
2xRS485
FPM+ BUS REPEATER MODULE DESCRIPTION
Page 13 of 78
Supply voltage
IP
No. of inputs
24VDC
n.a. (installed in multiple-module IP42 housing)
2x RS485
SKC module DESCRIPTION
Supply voltage
IP
No. of inputs
No. of outputs
230VAC
IP55
n/a (power supply module)
24VAC power supply output
SKC-A MODULE
Supply voltage
IP
No. of inputs
230VAC or 24VAC or 24VDC
IP42
MP-Bus: 1 Analog actuator limit switches: 1
No. of outputs
230VAC or 24VDC control output MP-Bus: 1
e.LSK MODULE DESCRIPTION
Supply voltage
IP
24-48VDC/VAC
IP 20 for the module itself IP 42 for steel housings (module installed in FPM+ multiple-module housing) IP 42 for ABS housings (module installed in same housing as SKC-A)
Maximum power consumption
In/out lines
2.4W @ 24VDC
System bus – 2x – EIA-485 (RS-485) standard, galvanically isolated MP-BUS – 2 x – MP-BUS standard
System bus voltage
Max. bus current in supervised state
Dimensions
+/-5VDC
50mA (typical 0.05mA)
88 x 108 x 62 mm In ABS housing: 172 x 132 x 78 mm
Weight
ca. 180 g In ABS housing: 450 g
e.USP MODULE DESCRIPTION
Supply voltage
24-48VDC/VAC
Page 14 of 78
IP
Maximum power consumption
In/out lines
System bus voltage
Max. bus current in supervised state
Dimensions
Weight
IP 20 for the module itself IP 42 for steel housings (module installed in FPM+ multiple-module housing) IP 42 for ABS housings (module installed in same housing as EPSCUS)
2.4W @ 24VDC
System bus – 2x – EIA-485 (RS-485) standard, galvanically isolated Inputs – 16 x Outputs – 8 x - relays
+/-5VDC
50mA (typical 0.05mA)
214 x 108 x 62 mm In ABS housing: 252 x 202 x 90 mm
ca. 400 g In ABS housing: 1100 g
6. FPM+ MODULES
Page 15 of 78
The FPM Plus system is composed of multiple units (the central module and local modules) with different functions. The central module monitors the service of local controllers
Modules are set up in FPM+ Configurator.
and facilitates communication between them.
6.1. FPM+ CONTROL UNIT - CENTRAL (MASTER) MODULE
The master module of FPM+ control unit has the following functions:
exchange of information between other modules
monitoring loop continuity
connection of FPM+ unit with a visualization system (BMS, SMS).
Fitted with Ethernet port, two RS485 ports, an RS232 port, eight relay outputs, and eight inputs.
The communication ports as well as two 5A@VDC relays are installed on the main board of the module, while the inputs
and the six additional 1A@30VDC outputs are located on the extension board.
Module inputs are used to monitor and control the unit (managing lights, buttons, access key).
The main unit housing consists of: the housing itself, a control & alert panel, a power supply with batteries (the power supply and batteries can be waived upon request and the unit can be powered from an external certified power supply), installation pieces (cable grommets, DIN bus bars, cable trays).
Fig. 3 FPM+ unit housing (MASTER housing)
A control & alert panel is located on the main housing of the FPM+ unit, fitted with the following controls:
Page 16 of 78
Fig. 4 Control panel
Confirm for shutting down voice alarms
Reset
button
button
for a fire reset triggered from access level 2
light
Power indicates that the unit is powered and working
Malfunction light
indicates that the unit has discovered a malfunction
light
Fire indicates that the unit is in the fire state
light
Locked indicates that the unit has certain components in locked state
6.2. LSK
Page 17 of 78
The LSK module is designed for controlling and monitoring actuators and other devices fitted with MP-Bus interface. Such actuators may include:
fire shut-off damper actuators (e.g. BF24-TL-T-ST),
line actuators of air dampers in HVAC systems, and slide valves (e.g. LH24A-MP, NM24A-MP, SM24A-MP, GM24A-MP)
SA actuators for dampers and louvres (e.g. LU24A-MP)
actuator valves for water installations (e.g. LV24A-MP-TPC, NVC24A-MP-TPC)
actuators for water installation valves (e.g. LR24A-MP)
VAV regulators (e.g. LMV-D3-MP)
air pressure regulators (e.g. VRP-M)
Apart from devices supporting the MP-BUS standard, the LSK module can also control and monitor analog equipment
items, e.g. fire damper actuators. In order to support such devices, the LSK must be connected to SKC-A module.
The LSK module is also fitted with four potential-free signal inputs. These inputs can operate in supervised, NO or NC modes. For the purpose of receiving alarm signals from the FAS, an input should be configured in line supervision mode.
The primary method of installation of an LSK module is to place it in a separate housing in the building, near the equipment it supervises.
Two versions of LSK modules are available: fitted for 230VAC or 24VAC/VDC power supply. The difference between these modules is the non-existence of a transformer in the power system. Besides, the modules are identical and have the same properties.
Fig. 5 LSK module
6.3. E.LSK
Page 18 of 78
The e.LSK is a more recent version of LSK, a module designed for controlling and monitoring actuators and other devices fitted with MP-Bus interface.
Fig. 6 e.LSK module
Below are the primary differences between e.LSK and LSK:
e.LSK is fitted with two MP-Bus items (1 bus in LSK), capable of accommodating up to 16 actuators (8 actuators can be connected to an LSK module);
no trip inputs in e.LSK (there are 4 trip inputs in an LSK module);
different installation method: by default, e.LSK should be installed in a multiple-module housing of the FPM+ unit on a DIN bus bar, while LSK is installed in a separate housing.
The primary method of installation of an LSK module is to place it in a multiple-module housing of the FPM+ unit, while an e.LSK can be installed in a separate housing in the building, near the equipment it supervises. Such additional housing for e.LSK is the same as that for SKC-A.
e.LSK modules are powered with 24- 40VDC/VAC voltage.
6.4. EPSCUS
Page 19 of 78
EPSCUS is the primary control and monitoring module of an FPM+ unit. It can receive potential-free signals from external equipment and systems, and is fitted with 8 relay outputs for controlling external hardware.
In addition, an EPSCUS module has 6 OC outputs which can be used for connecting indicator elements, such as lights.
A module adapted to measurement of analog values from different types of detectors is referenced as EPSCUS(A).
An EPSCUS module can be placed:
in the main housing, together with the MASTER module ­max. 2 items;
in one of the steel housing versions (OZ-FPMPLUS-xx or OBZ-FPMPLUS-xx);
in an ABS housing for a single module.
EPSCUS modules are installed in multiple-module housings on a DIN bus bar.
The choice of the specific housing and number of modules in a housing depends on the building design and the need to build a control system for fire safety equipment.
The EPSCUS model is designed for 12-48VDC.
Fig. 7 EPSCUS module
6.5. E.USP
Page 20 of 78
e.USP is the more recent version of the EPSCUS module. It can receive potential-free signals from external equipment and systems, analog signals (0 30V or 0-24mA, shared
Fig. 8 e.USP module
ground wire) and is fitted with 8 relay (toggle) outputs designed for external device control.
Differences between USP and EPSCUS modules:
no OC outputs in e.USP (there are 6 OC outputs in an EPSCUS module);
e.USP has 16 inputs (EPSCUS - 8 inputs);
higher current capacity of e.USP outputs (up to 5A);
additional indicator items (LEDs) for easier startup and servicing;
terminals supporting cables with core diameters up to 2.5mm2 (28-12AWG);
closed DIN bus bar enclosure.
6.6. SKC
SKC modules are designed for powering and monitoring the service of type BF24TL-T-ST actuators. These actuators are used to energize fire shut-off dampers.
EPSCUS modules are installed in FPM+ unit housings on a DIN bus bar. Installation in an additional ABS housing is also possible, such as the housing for EPSCUS module. The choice of the specific housing and number of modules in a housing depends on the building design and the need to build a control system for fire safety equipment.
The EPSCUS model is designed for 12-48VDC.
A single module supports the connection of a single damper with a single actuator. It converts ~230V mains voltage to the supply voltage for ~24V actuator.
Page 21 of 78
Fig. 9 SKC module
6.7. SKC-A
The function of SKC-A modules is to supervise the service of analog equipment controlled by 24VDC or 230VAC voltage input. Such equipment can include fire damper actuators. The modules are adapted for integration with LSK modules.
The modules are available in 2 versions, depending on equipment operating voltage:
230V version - for equipment powered from ~230VAC mains
24V version - for equipment powered with 24VDC
The module can be configured for transmission at 230VAC, 24VDC voltage relay output, or as a potential-free output only.
The module is configured in terms of output signal (230VAC voltage, 24VDC voltage, potential-free signal) by the manufacturer. Such setup can also be done by a trained service operative. In such case, the manufacturer is not responsible for service personnel errors.
Identification of SKC-A module. According to module configuration, additional power supply and output data is provided in the identification.
Identification of
SKC-A-XXX-YYY.
Where:
SKC-A – module type
-XXX – supply voltage
-
-
– 230VAC power supply
-230 – 24VDC power supply
-24
- output type
YYY
-
-
-
– 230VAC output
-230 – 24VDC output
-24
– relay output
-R
Example:
Example:
Page 22 of 78
Example:
SKC-A-230-230
– SKC-A module configured for 230VAC voltage supply and generating 230VAC voltage signal at output
SKC-A-230-24 configured for 230VAC voltage supply and generating 24VDC voltage signal at output
– SKC-A module
SKC-A-230-R
SKC-A module configured for 230VAC voltage supply and generating potential-free signal at output
NOTE: For technical reasons, the module cannot be configured according to the pattern SKC- A- 24- 230
Fig. 10 SKC-A module
6.8. FPM+ BUS REPEATER MODULE
The function of FPM+ bus repeater module is to provide bus signal gain. It is used in layouts with very large distances between modules, and in high-interference environments (primarily at industrial sites).
The FPM+ bus repeater module is manufactured by MOXA as TCC-120I module, but will be tuned by the control unit manufacturer to the operating parameters of the FPM+ control unit bus. The control unit manufacturer cannot warrant proper operation of the bus if a TCC-120I module is used without appropriate tuning.
The FPM+ bus repeater module is installed inside the housing of an FPM+ unit module and powered with the supply voltage dedicated to that module. The FPM+ bus repeater module will always be installed so that one of the FPM+ bus repeater module buses extends outside the housing in which the module is installed and the other bus connects to an EPSCUS or MASTER module installed locally.
Fig. 11 FPM+ bus repeater module
The FPM+ bus repeater module is not addressable and invisible for the FPM+ control unit. Any damage to that module can be diagnosed on the basis of broken bus continuity. If the control unit generates an alert of loss of bus continuity:
Check the power supply to FPM+ bus repeater module(s);
Check the connection between the FPM+ bus repeater module and other FPM+ unit modules;
Check the connections between other FPM+ unit modules.
Damage to the bus is indicated by a joint damage alert (DAMAGE indicator light on the unit’s control panel), in the visualization system and in FPM Configurator.
Page 23 of 78
Loading...
+ 55 hidden pages