eks LCON-R User Manual

Version R2.0 Description and Manual
eks Ralph Engel Schützenstraße 2 DE-57482 Wenden
Tel: +49 (0) 2762 93136 Fax: +49 (0) 2762 3016 E-Mail: info@eks-engel.de Internet: www.eks-engel.de
VERSION: 06/04
ECHNISCHE ÄNDERUNGEN VORBEHALTEN
T
UBJECT TO TECHNICAL ALTERATIONS
S
Manual
System LCON-R
System Description
The interface module LCON operates as a coupler of RS485 two-wired busses with fiber optic busses. This system especially enables the connection of PROFIBUS-DP or PROFIBUS-FMS with fiber optics.
It shows that the connection of data processing applications is not easy. If too many units are connected or too long transmission paths are established, emg-distortion and potential differences may occur as great problems in a network. The solution is optical data transmission. Additionally, potential separation is often not achieved.
The LCON-R contains one RS485-channel and two fiber optic channels. Each channel is connected to the other channels by an electronic circuit. A message that is received on one channel will be prepared, amplified and overplugged on the two other channels.
The system LCON-R allows to create redundancy topologies with fiber optics. A failure between two LCON-Rs in an optical ring structure will be detected and signaled with LED’s and failure relays. The participants are always available as they are connected and addressed via a line structure. This also applies to a failure of the LCON-R system.
VERSION: 06/04
ECHNISCHE ÄNDERUNGEN VORBEHALTEN
T
UBJECT TO TECHNICAL ALTERATIONS
S
EITE : 1
S
Manual
t
y
f
t
System LCON-R
Safety Instructions
In case of non-observance of these warning instructions, personal injury and material damage may occur. Appropriate transport, professional storing, assembly and installation are necessary to ensure faultless and safe operation. In order to mark security relevant procedures in this manual, the following security notes apply, which are characterised by the shown pictograms:
This sign means: NOTE! NOTE
on the adequate operation. In case of non-observance consequential damage may occur.
This sign means: WARNING! WARNING refers to activities and procedures that may lead to safety
hazards for persons and goods, if they are not carried out adequately.
marks activities and procedures, which can have important influence
Advice for connections
Supply voltage 24V
Impress the supply voltage of 24DVC on the clamps 24VDC and 0V. During the operation of electrical equipment and facilities it is inevitable, tha certain parts are under dangerous voltage. Only electronic technicians ma work with electrical equipment and at electrical facilities. Instructed persons, who are guided and observed by an electric technician may also work in these surroundings. For both cases applies, that all work has to be done according to electronical rules and regulations.
Optical connection of fiber optics
Clamp the optical connector in a way, that in each case the right channel o one LCON-R is connected with the next right LCON-R and the left channel of the LCON-R is connected with the next adjoining LCON-R on the left. Please note, that it is important to connect always a sender and a receiver.
Pay attention to cleanness! Intruding dust can disable the optical components. Therefore, remove the protective dust cover imminent before the optical connection is established.
While in operation, bundled light opts out of the fiber optic senders. Don’ stare into the light of the sender!
VERSION: 06/04
ECHNISCHE ÄNDERUNGEN VORBEHALTEN
T
UBJECT TO TECHNICAL ALTERATIONS
S
EITE : 2
S
Manual
System LCON-R
Data D and D/
Data can be alternatively withdrawn from the 9pin SUB-D-connector or from the screw clamps D or D/ . Please note, that there is no conductive connection between GND and 0V.
Failure relay
A failure notice for the optical channel 1 (CH1) can be withdrawn at clamps K1, K2 and K3 over a potential free two-way contact (Kanalmeldung). For the optical channel 2 (CH2), the failure notice can be withdrawn at clamps K4, K5 and K6 over a potential free two-way contact (Kanalmeldung). An internal jumper facilitates the output of all failures as a collective declaration (Sammelmeldung).
Kanalmeldung
Sammelmeldung
Exception: With the type LCON-R/GST/K+P (Order-No. 0300931) it is possible to withdraw a collective failure declaration at clamps K1, K2 and K3 for optical channel 1 (CH1) or channel 2 (CH2) over a potential free two-way contact.
Green LED “ON“
means that LCON-R is supplied with voltage (24VDC) and that the internal operating voltage of 5VDC is available.
Yellow LED “R/T“
flickers, if data from the electrical channel (RS485) is transmitted to the optical channels.
Red LEDs “FAILURE CH1 CH2“
VERSION: 06/04
ECHNISCHE ÄNDERUNGEN VORBEHALTEN
T
UBJECT TO TECHNICAL ALTERATIONS
S
EITE : 3
S
Manual
System LCON-R
These LEDs shine, if there is no signal reception on the particular optical channel (fiber optic receiver). This display can be used to check fiber optic connections. If both receivers of the LCON-R receive signals from the adjoining LCON-Rs, the LED is not shining. The connection of a participant (master or slave) is not necessary for this. The clearing takes place approx. 2 seconds after the correct data reception.
Planning of optical rings with LCON-R
From the software-side a nonexistent participant has to be established with the maximum possible bus address.
Advice for laying the fiber optics
Please consider the following points:
Humidity and rodent protection while choosing the fiber optic.
Connections are sensitive against contamination. Therefore, protect non required fiber optic
connectors and terminals with the delivered dust protection covers.
Don’t bend, twist, stretch, overexpand, press or squeeze the fiber optic cable!
Take the allowed bending radius into account!
Think of the temperature range!
Observe the maximum tractive force!
Trouble Shooting
If there occur problems, while establishing the connection, please check the following settings:
Correct connection between LCON and end device?
Are the screw clamps tighten?
Are the fiber optic converters supplied with power?
Is the right interface chosen?
Are all optical and electrical parameters considered and adjusted?
Is the cable bend too strong?
Is the transmission path too long?
The value RETRY has to be raised to a minimum of 3.
The value SLOT TIME has to be adjusted to a minimum of 900.
VERSION: 06/04
ECHNISCHE ÄNDERUNGEN VORBEHALTEN
T
UBJECT TO TECHNICAL ALTERATIONS
S
EITE : 4
S
Manual
System LCON-R
The following diagramm helps with trouble-shooting:
VERSION: 06/04
ECHNISCHE ÄNDERUNGEN VORBEHALTEN
T
UBJECT TO TECHNICAL ALTERATIONS
S
EITE : 5
S
Manual
System LCON-R
Bases of calculation
Following parameters must be strictly adhered to
t
RING
= max. delay in the ring
t
RING
n
t
LCON-R
l
= number of LCON-R systems in the ring
= module delay: delay of the signals in the LCON-R
= length of fiber optics in the ring
t
RING
= (n-1)*t
= < ½ * Slot time
LCON-R
+ l * t
fiber optic
t
fiber optic
The following characteristics apply:
Data rate
in KBit/s
187,5
93,75
45,45
= delay per meter fiber optic
Delay per
1500
500
19,2
9,6
LCON-R
4,5 µs
4,5 µs
4,5 µs
4,5 µs
4,5 µs
4,5 µs
4,5 µs
meter fiber
Delay per
optic
5 ns 900 0,30 ms 0,7 km 120 km
5 ns 900 0,90 ms 2,2 km 360 km
5 ns 900 2,40 ms 5,8 km 960 km
5 ns 900 4,80 ms 11,7 km 1920 km
5 ns 900 9,90 ms 24,2 km 3960 km
5 ns 900 23,44 ms 57,2 km 9375 km
5 ns 900 46,88 ms 114,5 km 18750 km
Slot time
in bit times
Delay in
the ring
max. distance
between two
LCON-R
Expansion in
the ring
VERSION: 06/04
ECHNISCHE ÄNDERUNGEN VORBEHALTEN
T
UBJECT TO TECHNICAL ALTERATIONS
S
EITE : 6
S
Manual
System LCON-R
VIEW
Connection Technology
Optical connection
HP - Versatile Link
F - SMA
F - ST
Electrical connection
9 pol. SUB-D female
Screw clamps
VERSION: 06/04
ECHNISCHE ÄNDERUNGEN VORBEHALTEN
T
UBJECT TO TECHNICAL ALTERATIONS
S
EITE : 7
S
Manual
System LCON-R
TECHNICAL DATA
LCON-R/GST/K+P LCON-R/GST LCON-R/GSMA LCON-R /KST
Order No. 0 300 931 0 300 930 0 300 925 0 300 929
Fiber connector
Data rate max.
Fiber
Optical Budget
typical
Worst Case
Transmission path
F-ST F-ST F-SMA F-ST
100KBit/s 9,6kBit/s, 19,2KBit/s, 93,75KBit/s, 187,5KBit/s, 500KBit/s, 1,5
MBit/s
Glass Fiber
62,5 (50)/125 µm
8 (4,2) dB 12 dB
2600 (1400) m
(3 dB/km)
POF
980/1000 µm
70 m
(180 dB/km)
Wavelength
Transmission
Load
Cable length
Delay
Bit distortion max.
Connector
Control - LED’s
Failure relay
Current consumption
Operating voltage
Potential separation
Operating temperature
820 nm 650 nm
half duplex
switchable: pull-up and wave resistance (Rp) or (Rw)
50 m max.
4,5µs per module and 5ns per meter fiber optic
60 ns
9 pol. SUB-D female
Power (green), data (yellow), fiber optic failure (red)
potential free relay contact (two-way contact)
100mA at 24VDC
24 V (18...30 VDC), other voltages on request
500 VDC (24 VDC RS485)
0 °C / 70 °C
Weight
Dimensions H x T x B
Case
VERSION: 06/04
ECHNISCHE ÄNDERUNGEN VORBEHALTEN
T
UBJECT TO TECHNICAL ALTERATIONS
S
250 g
82 x 93 x 40 mm
Polyamide case, grey, for snap mounting
EITE : 8
S
Manual
System LCON-R
APPLICATION
Optical Ring Structure
IM FAULT BUS FAU L T
POWER ON
24 V
FFF
SUB-D9
IM FAULT BUS FAULT
POWER ON
24 V
SUB-D9
FFF
IM FAULT BUS FAU L T
POWER ON
24 V
SUB-D9
FFF
IM FAULT BUS FAULT
POWER ON
24 V
FFF
SUB-D9
VERSION: 06/04
ECHNISCHE ÄNDERUNGEN VORBEHALTEN
T
UBJECT TO TECHNICAL ALTERATIONS
S
EITE : 9
S