Table of Contents:
General 1.0
Actuator Mounting 2.0
External Construction 3.0
Wiring Diagrams 4.0
Power Requirements 5.0
Duty Cycle
Manual Override
6.0
7.0
Mechanical Travel Stops 8.0
Electrical Connection 9.0
Limit Switch Setting Instructions 10.0
Torque Switch Adjustment 11.0
Reverse Acting (Counter Clockwise to close) 12.0
Lubrication 13.0
MDPI (Mechanical Dial Position Indicator) 14.0
Maintenance 15.0
Storage 16.0
Mounting Base Details 18.0
Drive Bushing Details
19.0
Trouble Shooting 20.0
Standard Specifications
EIM Office Locations
HQ Series I&M Manual HQ-400-1005 2
21.0
22.0
1.0 General
HQ series electric actuators are design to provide reliable and efficient operation of 90 degree quarter turn valves, dampers, etc
Pre-Installation Inspection
.
Warning: Use caution when working in, with, or around valves and actuators. High pressures, forces, voltages and flammable media can be present
Warning: Failure to follow instructions for proper electrical wiring, storage, set-up and maintenance may cause serious injury, damage equipment, or void warranty.
Verify the actuator nameplate to insure correct model number, torque, operating speed, voltage and enclosure type before installation or use.
It is important to verify that the output torque of the actuator is appropriate for the torque requirements of the valve and that the actuator duty cycle is appropriate of the intended application
2.0 Actuator Mounting
Do not lift the actuator by the handwheel
The actuator may be mounted in any position
The HQ- Series actuators are supplied with a female drive output. ISO5211. Bolt patterns are provided for actuator mounting. The actuator drive bush is removable for ease of machining.
It is mandatory that the actuator be firmly secured to a sturdy mounting bracket or directly mounted to the valve’s ISO mounting pad. High tensile bolts or studs with spring locking washers must be used.
The valve output shaft must be in line with the actuator output drive to avoid side-loading the shaft.
To prevent backlash, no flexibility in the mounting bracket or mounting should be allowed.
HQ Series I&M Manual HQ-400-1005 3
3.0 External Construction HQ-008 ~ HQ-120
HQ-200 ~ HQ-300
HQ Series I&M Manual HQ-400-1005 4
4.0 Wiring Diagrams
HQ Series I&M Manual HQ-400-1005 5
5.0 Power Requirements
Consult the nameplate of the actuator for duty cycle and current draw information
6.0 Duty Cycle
Duty cycle rated IEC34 – S2 (30%) Exceeding the actuator’s rated duty cycle may cause thermal overload.
7.0 Handwheel Declutch
HQ actuators are provided with a declutchable manual override system. To manually operate the actuator, pull the manual declutch lever towards the handwheel until it remains in
position.
Turn the handwheel until the valve reaches the required position  Turn clockwise to close and counter -clockwise to open
The manual declutch lever has motor preference, meaning that when the motor is energized, the lever will automatically shift to auto position.
7.0 Mechanical Travel Stop Adjustment
Built-in mechanical stops are provided to prevent handwheel operation beyond total valve travel
Loosen both locknuts and back out the stopbolts  Run actuator electrically to fully closed position  Screw close stopbolt in until it it seats, then back
Off ½ turn, Install washer and tighten locknut
Run actuator electrically to fully open position  Screw open stopbolt in until it it seats, then back
Off ½ turn, Install washer and tighten locknut
Do not set the Actuator position limit switches to drive into the mechanical stops. Damage can occur of electric unit is allowed to repeatedly stall into the end stops.
HQ Series I&M Manual HQ-400-1005 6
9.0 Electrical Connection
Move valve to mid-position by handwheel. This will allow sufficient time to stop actuator in case of
improper hook-up or reversed power phases
Identify means of removing power during hookup  Be sure no erroneous remote control signals can be received causing actuator to energize  Electrically operate the valve in the open direction. If the valve closes, actuator must be stopped and
the power leads reversed to correct voltage phasing or improper field wiring.
Set all field conduit entries in accordance with National Electric Code Requirements
Improper power voltage phasing eliminates protection of both the position limit switch and torque switches, risking valve damage.
10.0 Limit Switch Setting Instructions
HQ Series I&M Manual HQ-400-1005 7
10.0 Limit Switch Setting Instructions (cont)
Operate the actuator manually to closed position  Using a hex wrench, loosen the cam adjustment screw in the CLOSE limit switch cam  Rotate the CLS cam towards CW limit switch lever until the switch ‘clicks’  Tighten set screw with hex wrench  Operated the actuator manually to open position  Using a hex wrench, loosen the cam adjustment screw in the OPEN limit switch cam  Rotate the OLS can towards CCW limit switch lever until the switch ‘clicks’  Tighten set screw with hex wrench
11.0 Torque Switch Adjustment
The torque switches are adjusted at factory to protect actuator and valve against over torque. Should adjustment be necessary, please contact the factory, or your local EIM distributor for assi stance.
12.0 Reverse Acting (Counter Clockwise to Close)
Standard factory actuators are normally set to clockwise rotation to close. However the rotation can be reverse to counter-clockwise to close by simply reconfiguring the wiring as follows:
Exchange 9 and 10 in main actuator terminal block Exchange 11 and 12 in main actuator terminal block
If a PCU card is installed:
Exchange Potentiometer input wires P1(Orange wire) and P3 (Grey wire) on PCU Change the direction of the indicator (HQ-200 and 300 only) Re Calibrate by using Auto Calibrate feature
14.0 Lubrication
The HQ series actuators are totally enclosed units with a permanently lubricated gear trains (Moly EP Grease). Once installed lubrication should not be required. However, periodic preventative maintenance will extend the operating life of the actuator.
HQ Series I&M Manual HQ-400-1005 8
15.0 MDPI Settings
Manually rotate actuator to fully closed position  Remove actuator cover  Loosen indicator screw  Adjust indicator to correct orientation  Tighten indicator screw  Replace cover  Check indicator alignment
16.0 Maintenance
At least once a year a check should be make of your EIM HQ Series Actuator
Disconnect all power to actuator.  Open Electrical Enclosure. Inspect and tighten all electrical connections  Visually inspect for any electrical or mechanical damage. Replace worn or damaged components.
Check lubrication consistency and levels. Fill or replace if required.
17.0 Storage
Actuators must be stored in a clean, cool and dry area. The unit shall be stored with the cover installed and the conduit openings sealed. Storage must be off the floor, covered with a sealed dust protector.
HQ Series I&M Manual HQ-400-1005 9
21.0 Trouble Shooting
The following instructions are offered for the most common difficulties encounter during installation and start-up
Motor will not Run Open in control circuit Refer to appropriate wiring diagram and check for continuity Insulation resistance breakdown in motor Perform Megger Test No power available to actuator Tripped circuit breaker Reset circuit breaker Handwheel hard to turn Valve stem improperly lubricated Lubricate with grease Actuator lubrication has broken down Clean out old grease and replace with recommended lubricant Valve packing gland too tight Loosen packing gland nuts as necessary Jammed valve Refer to valve maintenance Valve only opens or closes Torque switch setting too low Check setting and reset if necessary partially with motor Limit switch improperly set Check setting and reset if necessary Torque switch is properly set, but Damaged or bent valve stem Refer to valve maintenance actuator torques out in mid-travel, Valve packing too tight Refer to valve maintenance open or closed direction Jammed valve (obstruction in line) Refer to valve maintenance Handwheel will not operate valve Stripped gearing Replace as necessary Clutch shifter position or malfunction Move shifter, or replace as necessary Broken handwheel shaft Replace as necessary Broken valve stem Repair or replace as necessary Motor runs but will not operate Stripped gearing Replace as necessary valve Clutch shifter position or malfunction Move shifter, or replace as necessary Broken handwheel shaft Replace as necessary
.
SYMPTOM PROBABLE CAUSE CORRECTIVE ACTION
HQ Series I&M Manual HQ-400-1005 10
HQ Standard Features
Enclosure Rated Weatherproof IP67, NEMA 4 & 6 Enclosure High grade aluminum alloy, corrosion coated Power Supply 110/220VAC 1 PH 50/60Hz, 440VAC 3PH 50/60Hz Duty Cycle EC 34 S2 (25~30%) Motor Squirrel caged induction motor Limit Switches 2 x open/close SPDT, 250VAC 10A rating Auxiliary Limit Switches 2 x open/close SPDT, 250VAC 10A rating (except HQ008) Torque Switches Open/close SPDT, 250VAC 10A Rating (except HQ008) Stall Protection Built –in thermal protection Travel Angle 90 degree +/- 10% Indicator Continuous position indicator Manual Override Declutchable manual override Self Locking By means of worm gear Mechanical Travel Stops 2 x external adjustable mechanical travel stops Space Heater 7~10W ceramic housed Conduit Entries 2 x PF3/4” Lubrication Grease moly EP Ambient Temperature -20 deg C ~ + 70 dec C (except on CPT & PCU board ) External Coating Dry powder polyester, Munsell No. 5R 3.5/12
HQ Series I&M Manual HQ-400-1005 11
Head Office and Factory
EIM Controls, Inc. 13840 Pike Road Missouri City, Texas 77489 USA (800) 679-1561 toll-free, US Only (281) 499-1561 phone (281) 499-8445 fax
sales.usa@eim-co.com
EIM NorthEastern Regional Office
sales.northeast@eim-co.com
EIM SouthWestern Regional Office
sales.southwest@eim-co.com
EIM SouthEastern Regional Office
sales.southeast@eim-co.com
EIM MidWestern Regional Office
sales.midwest@eim-co.com
EIM Western Regional Office
sales.western@eim-co.com
Eastern Hemisphere Sales
EIM Controls UK Ltd. 6-7 Galaxy House New Greenham Park, Newbury, Berkshire RG19 6HW, England +44 (0) 1635-817-315 phone +44 (0) 1635-817-460 fax